You are on page 1of 44

CHAPTER 7

FIRE RESISTANT
MATERIALS AND CONSTRUCTION
SECTION 701 subjected to afiretest from both sides provided that satis-
GENERAL factory evidence is furnished to show that the wall was
tested with the least fire resistant side exposed to the fur-
701.1 Scope. Provisions of this chapter shall govern the fire nace.
resistant materials and assemblies used for structural fire
resistance and fire resistant separation of adjacent spaces, Exception: Exterior walls with a horizontal separation
including construction, opening protectives, penetrations, greater than 5 ft shall be tested based upon interior fire
fireblocking and draftstopping. exposure only. (See Note i to Table 600.)

701.2 Tests 701.2.5 Where materials, systems or devices incorporated


701.2.1 Fire resistance requirements of this code are based into a fire resistant assembly have not been tested as part
on fire resistance ratings. Materials, thicknesses and of the assembly, sufficient data shall be made available to
assemblies which have successfully performed under tests the building official to show that the required fire resis-
tance rating is not reduced. Materials and methods of con-
made by a recognized laboratory in accordance with the struction used to protect joints and penetrations in fire
requirements of ASTM E 119 or based on calculations and resistant building assemblies shall not reduce the required
accepted engineering practice as set forth in 709 shall be fire resistance rating.
accepted by the building official for specific ratings.
701.3 Determining conditions of restraint
Exception: In determining the fire resistance rating of 701.3.1 For the purpose of determining the required fire
exterior bearing walls, compliance with the ASTM E resistance rating of floor and roof assemblies, including
119 criteria for unexposed surface temperature rise and individual beams, used in steel and concrete construction,
ignition of cotton waste caused by passage of flame or
gases is required only for a period of time correspond- such structural elements shall be classified as restrained or
ing to the required fire resistance rating of an exterior, unrestrained in accordance with 701.3.
nonbearing wall with the same horizontal separation
distance, and in a building of the same type of con- 701.3.2 Floor and roof assemblies and individual beams in
struction. When the fire resistance rating determined in buildings shall be considered restrained when their sur-
accordance with this exception exceeds the fire resis- rounding or supporting structure is capable of resisting
tance rating determined in accordance with ASTM E substantial thermal expansion throughout the range of
119, the fire exposure time period, water pressure and anticipated elevated temperatures. Construction not com-
application duration criteria for the hose stream test of plying with this definition is assumed to be free to rotate
ASTM E 119 shall be based on the fire resistance rat- and expand and shall therefore be considered as unre-
ing determined in accordance with this exception. strained. (See Table 701.3 for guidance in determining
restrained and unrestrained assemblies.)
701.2.2 When insulation or other materials which may 701.4 Column fire resistance. Where columns require a fire
change the capacity for heat dissipation are added to or resistance rating, the entire column, including its connections
subtracted from fire resistant roof or ceiling assemblies to beams or girders, shall be protected. Where the column
whose fire ratings are listed in this code or listed in refer- extends through a ceiling, fire resistance of the column shall
ence documents, fire test results or other substantiating be continuous from the top of the floor through the ceiling
data shall be submitted to the building official to show that space to the underside of the floor or roof deck above.
the required fire resistance time period is not reduced.
701.5 Fire resistance references
701.2.3 Thicknesses established by fire tests shall be con- 701.5.1 To meet the fire resistance requirements of this
strued as establishing minimum requirements for fire code, it shall be determined that materials, constructions
resistance only, and shall not preclude the application of and assemblies of construction materials have successful-
other requirements of this code where consideration of ly performed under accepted tests as prescribed in 701.2.
strength, durability or stability require greater thicknesses.
701.5.2 Appropriate fire resistant materials, constructions
701.2.4 Walls and partitions of nonsymmetrical construc- and assemblies of constructions as listed in 709.7 and the
tion shall be tested with both faces independently exposed following publications may be accepted as if herein listed:
to the furnace and the assigned fire resistance rating shall FM Specification Tested Products Guide
be the shortest duration obtained from the two tests con- GA Fire Resistance Design Manual
ducted in conformance with ASTM E 119. When SBCCI PST & ESI Evaluation Report Listing
approved by the building official, the wall need not be UL Fire Resistance Directory

FLORIDA BUILDING CODE BUILDING 7.1


TABLE 701.3-701.6.3

TABLE 701.3
CONDITIONS OF RESTRAINT
CONSTRUCTION CLASSIFICATION
1. Wall Bearing:
Single Span and simply supported end spans of
multiple bays:1
(1) Open-web steel joists or beams, supporting
concrete slab, precast units, or metal decking unrestrained
(2) Concrete slabs, precast units, or metal decking unrestrained
Interior spans of multiple bays:
(1) Open-web steel joists or steel beams, supporting
precast units or metal decking unrestrained
(2) Open-web steel joists, steel beams or metal
decking, supporting continuous concrete slab restrained
(3) Cast-in-place concrete slab systems restrained
(4) Precast concrete where the potential thermal
expansion is resisted by adjacent construction2 restrained

II. Steel Framing:


(1) Steel beams welded, riveted, or bolted to the
framing members restrained
(2) All types of cast-in-place floor and roof systems
(such as beam-and-slabs, flat slabs, pan joists,
and waffle slabs) where the floor or roof system is
secured to the framing members restrained
(3) All types of prefabricated floor or roof systems where
the structural members are secured to the framing
members and the potential thermal expansion of the
floor or roof system is resisted by the framing system
or the adjoining floor or roof construction2 restrained

III. Concrete Framing:


(1) Beams securely fastened to the framing members restrained
(2) All types of cast-in-place floor or roof systems (such
as beam-and-slabs, flat slabs, pan joists, and waffle
slabs) where the floor or roof system is cast with the
framing members restrained
(3) Interior and exterior spans of precast systems with
cast-in-place joints resulting in restraint equivalent
to that which would exist in condition III (1) restrained
(4) All types of prefabricated floor or roof systems where
the structural members are secured to such systems
and the potential thermal expansion of the floor or
roof systems is resisted by the framing system or the
adjoining floor or roof construction2 restrained
Notes:
1. Floor and roof systems shall be considered restrained when they are tied into walls with or without tie beams, the walls being designed and detailed to
resist thermal thrust from the floor or roof system.
2. Resistance to potential thermal expansion is considered to be achieved when:
(1) Continuous structural concrete topping is used,
(2) The space between the ends of precast units or between the ends of units and the vertical face of supports is filled with concrete or mortar, or
(3) The space between the ends of precast units and the vertical faces of supports, or between the ends of solid or hollow core slab units does not exceed
0.25% of the length for normal weight concrete members or 0.1 % of the length for structural lightweight concrete members.

701.5.3 Other fire resistance ratings may be accepted by equal to that required for beams, except thatfireresistance
the building official on evidence of compliance with may be omitted from the bottom flange of lintels, shelf
701.2. angles and plates not a part of the structural frame or with
a span of 6 ft (1829 mm) or less.
701.6 Exceptions tofireresistance
701.6.1 Elevator frames. Structural members of frames 701.6.3 Unusable space. The following shall be permitted
for elevators will not be required to have thefireresistance in 1-hour fire resistant floor/ceiling or roof/ceiling con-
required for structural steel, provided such members are struction:
erected within an enclosure of the prescribed fire resis- 1. Omission of the ceiling over unusable crawl space.
tance rating. (See 705.2.) 2. Omission of the flooring if unusable attic space
occurs above, and the ceiling has been shown to
701.6.2 Lintel protection. Lintels over openings in walls provide a 1-hourfireresistance.
shall be protected to provide afireresistance rating at least

7.2 FLORIDA BUILDING CODE BUILDING


702-703.10

SECTION 702 703.5.5 Gypsum veneer base shall comply with the provi-
DEFINITIONS sions of ASTM C 588.

For definitions, see Chapter 2. 703.5.6 Gypsum veneer plaster shall comply with the pro-
visions of ASTM C 587.
SECTION 703
MATERIALS FOR FIRE RESISTANCE 703.5.7 Exterior gypsum soffit board shall comply with
the provisions of ASTM C 931.
703.1 Scope. Materials prescribed herein for fire resistance
shall conform with the requirements of this chapter. 703.5.8 Water resistant gypsum backing board shall com-
ply with the provisions of ASTM C 630.
703.2 Brick. Brick shall be laid in Type M, S, N or O mortar.
Solid clay and shale brick shall conform to ASTM C 216 or 703.6 Metal or wire lath
ASTM C 62. Hollow clay and shale brick shall conform to 703.6.1 Metal lath shall comply with the provisions of
ASTM C 652. Concrete brick shall conform to ASTM C 55. ASTM C 847. Wherever metal lath or wire lath and plas-
Sand-lime brick shall conform to ASTM C 73. Ceramic ter are used as required protection against the spread of
glazed structural facing tile and facing brick shall conform to fire, the weight of lath shall be not less than 2.5 lb per sq
ASTM C 126. yd (1.4 kg/m2) when used in vertical position, and not less
than 2.75 lb per sq yd (1.5 kg/m2) when used in horizon-
703.3 Clay or shale tile. Hollow clay or shale tile shall be tal position. Wire lath shall not be lighter than 21/2 mesh-
laid in Type M, S, N, O or gypsum mortar. Clay or shale tile es per inch, or equivalent.
used in nonbearing partitions and for fire resistance shall
meet the requirements of ASTM C 56. Clay or shale tile used 703.6.2 Weight tags shall be left on all metal lath or wire
in exterior walls and in all loadbearing walls shall comply lath until inspected and approved by the building official.
with the requirements of ASTM C 34 and ASTM C 212.
703.6.3 Metal lath for ceilings below wood joists in con-
703.4 Gypsum struction which is required to be fire resistant shall be
703.4.1 Poured gypsum used for fire resistance and floor attached with l1/2 inch (38 mm), 11 ga, 7/16 inch (11.1
and roof construction shall contain not more than 121/2 mm) head barbed roofing nails spaced at intervals not to
percent of wood chips, shavings or fiber, measured in a exceed 6 inches (152 mm) on centers, or equivalent
dry condition, as a percentage by weight of the dry mix. attachment.
Gypsum mortar shall be composed of one part gypsum
and not more than three parts clean, sharp, well-graded 703.6.4 Welded wire lath shall comply with the provisions
sand, by weight. ofASTMC933.

703.4.2 Fibered plaster may be used where unsanded or 703.6.5 Woven wire lath shall comply with ASTM C
neat gypsum plaster is prescribed. 1032.

703.4.3 All plaster mixes for sanded gypsum plasters shall 703.7 Concrete block. Concrete masonry units used in exte-
be measured by dry weight. rior walls and in all walls or partitions shall comply with
ASTM C 90 and C 129.
703.4.4 When gypsum plaster is used with an aggregate,
the proportions shall be as required in 2504. 703.8 Vermiculite. Vermiculite, when used as an aggregate
with plaster, shall conform in particle size to ASTM C 35.
703.5 Gypsum lath, wallboard and sheathing board The weight of vermiculite shall be not less than 6 pcf (96
703.5.1 Gypsum lath shall comply with the provisions of kg/m3) nor more than 10 pcf (160 kg/m3) as determined by
ASTM C 37. measurement in a cubic-foot box, using the shoveling proce-
dure as outlined in ASTM C 29.
703.5.2 Gypsum lath shall be nailed to wood studs or
joists in all constructions required to be fire resistant, with 703.9 Perlite. Perlite, when used as an aggregate with plas-
l1/8 inch (29 mm), 13 ga, 19/64 inch (7.5 mm) flat head ter, shall conform in particle size to ASTM C 35. The weight
blued nails at intervals not exceeding 4 inches (102 mm) of perlite shall be not less than 71/2 pcf (120 kg/m3) nor more
on centers 5 nails per lath for support of 16 inch (406 mm) than 15 pcf (240 kg/m3), as determined by measurement in a
lath) or equivalent attachment. cubic-foot box, using the shoveling procedure as outlined in
ASTM C 29.
703.5.3 Gypsum wallboard shall comply with the provi-
sions of ASTM C 36. 703.10 Glass block. Glass block shall be labeled to conform
to NFPA 257 or UL 9.
703.5.4 Gypsum sheathing board shall comply with the
provisions of ASTM C 79.

FLORIDA BUILDING CODE BUILDING 7.3


704-704.1.3.3.2

SECTION 704 Exception: Accessory uses in Group F and S


FIRE RESISTANT SEPARATIONS occupancies conforming to 704.1.2.1.
704.1 Occupancy separation requirements 4. Rooms or spaces used for customary storage of
704.1.1 The minimum fire resistance of construction sep-
nonhazardous materials in Group A, Group B,
arating any two occupancies in a building of mixed occu-
pancy shall be the higher rating required for the occupan- Group E, Group F, Group M, and Group R,
cies being separated, as specified in Table 704.1. which in aggregate do not exceed 1/3 of the major
occupancy floor area in which they are located.
TABLE 704.1 5. Portions of buildings which are less than 3,000
OCCUPANCY SEPARATION REQUIREMENTS
sq ft used as accessory small businesses to and
Large or Small Assembly 2 hour open for business simultaneously with the princi-
Business 1 hour pal retail sales occupant, only in a Group M
Day-care Occupancy2-3'4 1 hour occupancy.
Educational 2 hour
Factory-Industrial 2 hour
Exception: Item 5 shall not apply to separa-
Hazardous See 704.1.4
Institutional 2 hour tion walls between tenants and malls in cov-
Mercantile 1 hour ered mall buildings.
Residential 1 hour
Storage, Moderate Hazard S1 3 hour 704.1.2.3 A 1-hour occupancy separation shall be per-
Storage, Low Hazard S2 2 hour mitted in assembly rooms greater than 750 sq ft (70
Automobile Parking Garages1 1 hour m2) but less than 2,000 sq ft (186 m2) in area when all
Automobile Repair Garages 2 hour of the following are met:
1. The occupant content does not exceed 300 per-
Note: sons calculated in accordance with Table 1003.1.
1. See 411.2.6 for exceptions. 2. The assembly room does not constitute the major
2. Rated separation is not required for day-care occupancies in assem- occupancy classification of the building.
bly occupancies used primarily for worship.
3. The assembly room is not associated with a haz-
3. In apartment occupancies containing a day -care occupancy, where
the two exit accesses from the day-care occupancy enter the same
ardous or Group S1 occupancy.
corridor as the apartment occupancy, the exit accesses shall be sepa- 4. The assembly room is not associated with a
rated in the corridor by a smoke barrier having a fire resistance rat- kitchen.
ing of not less than 1 hour. The fire rated smoke barrier shall be locat- 5. The assembly room is not a theater or restaurant.
ed so that there is an exit on each side.
4. Fire rated separation is not required for day-care homes in assembly 704.1.3 Special occupancy separations
occupancies used primarily for worship. 704.1.3.1 Assembly and educational. Fire resistance
separation shall not be required between Sunday school
704.1.2 Accessory occupancies rooms and a church auditorium of Group A - Small
704.1.2.1 Portions of buildings used as accessory Assembly occupancy, and between classrooms in day
offices or for customary nonhazardous uses necessary schools and auditoriums, gymnasiums, cafeterias, and
for transacting the principal business in Group S and libraries of small assembly occupancy, which are used
Group F occupancies need not be separated from the only as accessory uses to the education occupancy.
principal use. Group F occupancies producing, using or
storing low hazard contents as listed in 312.2.2 or as 704.1.3.2 Automobile parking garages. A separation
approved by the building official need not be consid- between an automobile parking garage used exclusive-
ered mixed occupancies. Height and area will be gov- ly for the storage of passenger vehicles that will
erned by the principal intended use. accommodate not more than 9 passengers and any
other occupancy having a rating of 2 hours or more in
704.1.2.2 The following occupancies need not be sepa- Table 704.1 shall be 2 hours.
rated from the uses to which they are accessory:
1. A kitchen in a Group A occupancy does not con- 704.1.3.3 Boiler and machinery rooms
stitute a mixed occupancy. A fire resistant sepa- 704.1.3.3.1 Every central heating boiler as defined
ration is not required. in the Florida Building Code, Mechanical installed
2. Assembly rooms having a floor area of not over in any building other than a one- or two-family
750 sq ft (70 m 2 ), are incidental to another occu- dwelling or Group F, shall be separated from the rest
pancy, and have an occupant load less than 50 of the building by not less than 1-hour fire resistant
shall be classified as part of the other occupancy. construction.
3. Administrative and clerical offices and similar
rooms which, in area per story, do not exceed 25 704.1.3.3.2 A central heating boiler installed in a
percent of the story area of the major use when Group A or H occupancy shall be separated from the
not related to Group H occupancies. rest of the building by construction having a fire
resistance rating of not less than 2 hours.

7.4 FLORIDA BUILDING CODE BUILDING


704.1.3.3.3-704.2.1.5

704.1.3.3.3 Steam boilers. Every steam boiler car- 704.1.4.4 Accessory areas, other than assembly occu-
rying more than 15 psi (103 kPa) pressure with a pancies, that do not exceed 10 percent of the allowable
rating in excess of 10 boiler horsepower (98 kW) area for the hazardous occupancy subclassification in
installed in a building other than one of Group F Table 500 and that do not exceed 1,500 sq ft (139 m2)
occupancy, shall be located in a separate room or shall not be required to comply with 704.1. Where
compartment, shall not be located under a means accessory areas are separated from hazardous occupan-
of egress and shall be separated from the rest of cies by partitions, the partitions shall be not less than 1
the building by construction having at least 2- hour fire resistant construction with an opening protec-
hour fire resistance. This rating may be reduced tion rating not less than 3/4 hour. Opening protection
in accordance with the hazard existing when in shall be either self-closing or automatic-closing in
the opinion of the building official it is desirable accordance with 705.1.3.2.3.
to provide for explosion venting upward.
704.2 Interior wall and partition fire separation require-
704.1.3.3.4 Refrigerant system machinery rooms. ments
Where required by the Florida Building Code, 704.2.1 General
Mechanical because of refrigerant type, amount, 704.2.1.1 This section shall apply to the fire separation
system classification and occupancy, a Level 2
machinery room shall be of noncombustible con- requirements of interior walls and partitions for the
struction. A minimum of 1-hour construction shall various occupancies and types of construction.
separate the machinery room from other occupied Partitions of higher fire resistance rating required by
spaces. A minimum of 3/4-hour C-labeled doors other sections of this code may also serve to meet the
shall be used when separating from other occupan- requirements of this section.
cies.
704.2.1.2 All partitions enclosing vertical openings
704.1.4 Hazardous occupancies such as stairways, utility shafts and elevator shafts
704.1.4.1 The separation of a hazardous occupancy which are required to have a fire resistance rating shall
from other occupancies shall be in accordance with extend from floor to floor or floor to roof. These walls
Table 704.1.4. shall be continuous through all concealed spaces such
as the space above a suspended ceiling. The supporting
TABLE 704.1.4 structure shall have a fire resistance rating equal to or
HAZARDOUS OCCUPANCY SEPARATION REQUIREMENTS greater than the fire resistance rating required for the
vertical enclosure. Where the openings are offset at
OCCUPANCY H1 H2 H3 H4 intermediate floors, the offset and floor construction
shall be of construction having a fire resistance of not
A NP 4 4 4 less than that required for the enclosing partitions.
B NP 2 2 1
D NP 4 4 4
E NP 4 4 4 704.2.1.3 All other partitions required to have a fire
F NP 2 1 1 resistance rating shall extend from the top of the floor
H1 NP NP NP below to the ceiling above and shall be securely
H2 NP 1 2 attached thereto. Where said ceiling is not a part of an
H3 NP 1 1 assembly having a fire resistance rating at least equal to
H4 NP 2 1 that required for the partition, the partition shall be
I NP 4 4 4 constructed tight against the floor or roof deck above.
M NP 2 2 2
R 1,2,3, and 4 NP 4 4 4 704.2.1.4 Corridor partitions, smokestop partitions,
Sl,2 NP 2 2 2
horizontal exit partitions, exit enclosures, and fire rated
Note:
walls required to have protected openings shall be
NP = H1 occupancies not permitted to be attached to other occupancies
effectively and permanently identified with signs or
or other H subclassifications.
stenciling in a manner acceptable to the authority hav-
ing jurisdiction. Such identification shall be above any
704.1.4.2 The separation of a hazardous occupancy decorative ceiling and in concealed spaces. Suggested
subclassification shall apply only to storage areas. wording: FIRE AND SMOKE BARRIER PROTECT
ALL OPENINGS.
704.1.4.3 Building areas intended for the use, process-
ing, manufacture or generation of materials having dif- 704.2.1.5 Any required smoke barrier shall be continu-
ferent hazard classifications, all of them being Group ous from outside wall to outside wall, from floor slab
H, need not be separated further within the confines of to floor slab or roof deck, from smoke barrier to smoke
the Group H occupancy provided the requirements for barrier, or a combination thereof, including continuity
each hazard are met. through all concealed spaces such as those found above
suspended ceilings however, smoke barriers are not
required in interstitial spaces designed and constructed

FLORIDA BUILDING CODE BUILDING 7.5


704.2.2 - 704.4.1

with ceilings equivalent to smoke barriers. Smoke bar- TABLE 704.2.4

riers shall be of 1-hour fire resistant construction. FIRE RESISTANCE RATING OF EXIT ACCESS CORRIDORS4-7
Fixed wired glass vision panels shall be permitted in
OCCUPANCY OCCUPANT FIRE RESISTANCE
such barriers provided the panels do not individually
LOAD RATING (hours)
exceed an area of 1,296 square inches (0.84 m2) and
are mounted in steel frames. There is no restriction on Sprinklered Unsprinklered
the total number of such panels in any barrier.
A,B,F,M,S less than 30 0 0
Exception: Smoke barriers in Group I Restrained A 30 or more 1 1
occupancies shall be permitted to be constructed of B,F,M,S 30 or more 0 1
minimum 0.10-inch (2.5 mm) thick steel. D6 All, 0 1
R1,R2,R3 less than 10, 0 0
Note 1
704.2.2 Partition requirements by occupancy R1.R2 10 or more, 1
/2 1
704.2.2.1 Group I Restrained Note 1
704.2.2.1.1 Smoke barriers shall be constructed in R4 16 or less 0 0
accordance with 704.2.1.5. R4 more than 16, 0 1
Note 1
704.2.2.1.2 All interior partitions in Type I and Type E Note 2, 5 1 1
II construction shall be of noncombustible construc- I Unrestrained All 0 N/A
I Restrained All 0 0, Note 3
tion.
H All 1 1

704.2.2.2 Group I Unrestrained. Smoke barriers shall


Notes:
have a minimum 1-hour fire-resistance rating and be 1. Corridors within guest rooms or dwelling units need not be rated.
constructed in accordance with 704.2.1.5. 2. Corridors need not be rated in Group E occupancies with rooms used either for
instruction with at least one exit door directly to the exterior at ground level or
for assembly purposes with at least one-half of the required exits directly to the
704.2.2.3 Group R Residential. Nonfire rated parti- exterior at ground level.
tions may be constructed within small residential 3. Unsprinklered use condition 5 shall have exit access corridors of 1-hour fire
resistance.
care/assisted living facilities (Group R4 Small 4. In buildings protected throughout with an approved automatic sprinkler sys-
Facility), one- and two-family dwellings and within tem, exit access corridor walls not required to be rated shall, in conjunction
individual dwelling units unless required by Table 600. with openings therein and ceilings at which they terminate, resist the passage
of smoke.
The tenant separation in a two-family dwelling shall 5. Exterior corridors or balconies in accordance with section 1021 shall be per-
comply with 704.3. mitted.
6. Corridors need not be rated where all spaces normally subject to client occu-
pancy have not less than one door opening directly to the outside or to an exte-
Exception: Shaft enclosures in Group R4 occupan- rior balcony complying with 1006.2.2.
cies shall be enclosed and protected in accordance 7. See Table 705.1.2 for separation requirements for bathrooms opening onto fire
rated exit access corridors.
with the requirements of Table 705.1.2.
704.3 Tenant fire separation
704.2.3 Partitions within tenant space 704.3.1 In a building or portion of a building of a single
704.2.3.1 Partitions dividing portions of stores, offices occupancy classification, when enclosed spaces are pro-
or similar places occupied by one tenant only, which do vided for separate tenants, such spaces shall be separated
not establish an exit access corridor serving an occu- by not less than 1-hour fire resistance.
pant load of 30 persons or more, and partial partitions,
may be temporary or permanent and constructed in Exception: In Group B and Group S occupancies, parti-
accordance with 609 without fire resistance, provided tions not rated for fire resistance may be used to separate
that: tenants provided no area between partitions rated at 1
1. Their location is restricted by their method of hour or more exceeds 3,000 sq ft (278.7 m 2 ).
construction or by means of permanent tracks,
guides or other approved methods. 7043.2 In buildings with usable crawl spaces, tenant sepa-
2. Flammability shall be limited to materials having ration walls required to have a fire resistance rating shall
an interior finish classification as set forth in extend from the underside of the floor to the ground below.
Table 803.3 for rooms or areas. A suitable foundation shall be provided at grade level.

704.2.4 Exit access corridors. Fire resistance rating of Exception: The wall need not be extended when the
exit access corridors shall be in accordance with Table floor above the crawl space has a minimum 1-hour fire
704.2.4. resistance rating.

704.4 Townhouse fire separation


704.4.1 Each townhouse shall be considered a separate
building and shall be separated from adjoining townhous-
es by a party wall complying with 704.4.2 or by the use of

7.6 FLORIDA BUILDING CODE BUILDING


704.4.2-705.1.2.1

separate exterior walls meeting the requirements of Table es (457 mm) past any combustible projection or veneer.
600 for zero clearance from property lines as required for Party walls or fire walls shall extend to the inside fac-
the type of construction. Separate exterior walls shall ing of the exterior surface of noncombustible construc-
include one of the following: tion.
1. A parapet not less than 18 inches (457 mm) abose
the roof line. 704.5.1.3 Fire walls shall be in accordance with the
2. Roof sheathing of noncombustible material orfireretar- requirements of NCMA-TEK 5-8 or equivalence in
dant treated wood, for not less than a 4 ft (1219 mm) brick or poured concrete or other nationally recognized
width on each side of the exterior dividing wall. tested systems.
3. One layer of 5/8 inch (15.9 mm) Type X gypsum
board attached to the underside of roof decking, for 704.5.2 Parapet Walls
not less than a 4 ft (1219 mm) width on each side of In Type III and Type V Construction. exterior walls shall
the exterior dividing wall. extend not less than 18 inches (457 mm) above the roof.

704.4.2 When not more than 3 stories in height, town- Exceptions:


houses may be separated by a single wall meeting the fol- 1. Walls located more than 15 ft (4.57 m) from a
lowing requirements: common property line or centerline of a public
1. Such wall shall provide not less than a 2-hour fire way.
resistance rating. Plumbing, piping, ducts, electrical 2. Where the roof slopes more than 4:12 from the
or other building services shall not be installed with- back of the exterior wall.
in or through the 2 hour wall, unless such materials
SECTION 705
and methods of penetration have been tested in
PROTECTION OF OPENINGS
accordance with 701.2.
2. Such wall shall be continuous from the foundation 705.1 Protection of wall openings
to the underside of the roof sheathing or shall have 705.1.1 Protection of openings in exterior walls
a parapet extending not less than 18 inches (457 705.1.1.1 The provisions of 705.1.1 do not apply to
mm) above the roof line. When such wall terminates Group R3 occupancies.
at the underside of the roof sheathing, the roof
sheathing for not less than a 4 ft (1219 mm) width 705.1.1.2 Every exterior wall within 15 ft (4572 mm)
on each side of the wall shall be of noncombustible of a property line shall be equipped with approved
material, or fire retardant treated wood, or one layer opening protectives.
of 5/8 inch (15.9 mm) Type X gypsum wallboard
attached to the underside of the roof decking. Exceptions:
3. Each dwelling unit sharing such wall shall be 1. Exterior walls not required by Table 600 to
designed and constructed to maintain its structural have a fire resistance rating.
integrity independent of the unit on the opposite 2. Show windows fronting on a street or public
side of the wall. space.
3. Open parking structures meeting the require-
Exception: Said wall may be penetrated by roof ments of 411.3.
and floor structural members provided that the
fire resistance rating and the structural integrity 705.1.1.3 Where openings in an exterior wall are above
of the wall is maintained. and within 5 ft (1524 mm) laterally of an opening of the
story below, such openings shall be separated by an
704.5 Fire wall extensions and parapets approved noncombustible flame barrier extending 30
704.5.1 Fire wall extensions inches (762 mm) beyond the exterior wall in the plane of
704.5.1.1 Party walls and fire walls shall extend not the floor or by approved vertical flame barriers not less
less than 3 ft (914 mm) above the roof. than 3 ft (914 mm) high measured vertically above the
top of the lower opening. Such flame barriers are not
Exception: Fire walls shall not be required to required when a complete approved automatic sprinkler
extend above the roof where the roof is: system is installed.
1. Noncombustible in Types I, II and IV con-
struction, or 705.1.1.4 Fresh air intakes shall be protected against
2. Noncombustible or fire retardant treated wood exterior fire exposure by means of approved fire doors,
for an area within 40 ft (12.2 m) of each side dampers or other suitable protection in accordance with
of the wall in Types III, V and VI construction. the degree of exposure hazard.
704.5.1.2 Party walls and fire walls shall extend not 705.1.2 Protection of openings in interior walls
less than 18 inches (457 mm) past exterior intersecting 705.1.2.1 General. Openings in interior walls and par-
walls of combustible construction or exterior noncom- titions shall be protected in accordance with 705.1.2
bustible walls with combustible projections or veneers. and Table 705.1.2.
The party or fire wall shall extend not less than 18 inch-

FLORIDA BUILDING CODE BUILDING 7.7


TABLE 705.1.2 -705.1.2.3.1

Exceptions: c. the walls, partitions, floor and ceiling of the bathroom/restroom


1. Where fire resistance is required because of have a fire rating at least equal to the rating of the hall, corridor or
type of construction only. exit access, and
d. the bathroom/restroom is not used for any other purpose than it is
2. Ducts in accordance with 705.1.2.2.
designed.
3. One- and two-family dwellings.
7. See 704.1.
8. See Table 600, 705.1.1 and 503.4.8.
TABLE 705.1.2
9. See 704.2.2.3 for walls and partitions in Group R4 occupancies.
MINIMUM FIRE RESISTANCE OF WALLS, PARTITIONS
10. In Group R4 Large Facility occupancies, sleeping room doors shall
AND OPENING PROTECTIVES1 (hr)
resist the passage of smoke but closers are not required.
WALLS AND OPENING 11. See 705.1.3.1.
COMPONENT PARTITIONS9 PROTECTIVES
705.1.2.2 Fire dampers
SHAFT ENCLOSURES (including 705.1.2.2.1 Fire dampers, installed in accordance
stairways, exits & elevators) with manufacturer's installation instructions, shall
be provided in ducts penetrating walls or partitions
4 or more stories 2 l1/2 having a fire resistance rating of 1 hour or more.
less than 4 stories 1 2
12
1 Exceptions:
all refuse chutes 2 l /2
1. Where branch ducts connect to return risers in
WALLS AND PARTITIONS which the air flow is upward and subducts at
fire walls3 4 3 least 22 inches (559 mm) long are carried up
within tenant space See 704.2.3
inside the riser at each inlet.
tenant space (see also 704.3) 1 3/4
2. In duct systems of any duct materials or combi-
nations thereof allowed by Chapter 6 of the
horizontal exit 2 l1/ 2
exit access corridors See Note 4,5 20min. 10,11 Florida Building Code, Mechanical penetrating
1-hour walls or partitions, where the duct pene-
smoke barriers See 409.1.2 trating the rated wall or partition meets all of the
refuse and laundry chute access 1 3/4 following minimum requirements:
rooms 1. the duct shall not exceed one 100 square
incinerator rooms 2 l1/ 2 inches (0.06 m2),
refuse and laundry chute termination 1 3/4
2. the duct shall be of 0.0217 inch (0.55 mm)
rooms
minimum steel,
hazardous occupancy control areas 1 3
/4 3. the duct shall continue with no duct open-
high rise buildings See 412 ings for not less than 5 ft (1.5 m) from the
covered mall buildings See 413 rated wall,
4. the duct shall be installed above a ceiling,
assembly buildings See Note 2 and,
bathrooms & restrooms See Note 6
5. the duct does not terminate at a wall regis-
OCCUPANCY SEPARATIONS7 ter in the rated wall.
Required Fire
Resistance 705.1.2.2.2 Fire dampers shall comply with the
4 3 requirements of UL 555 and shall bear the label of
3 3 an approved testing agency. Closure shall interrupt
2 l1/ 2 any migratory air flow and restrict the passage of
3
1 /4 flame. Fire dampers shall be classified and identi-
fied for use in either.
EXTERIOR WALLS8 All 3
/4 1. Static systems that automatically shut down in
the event of fire.
Notes:
1. Table 600 may require greater fire resistance of walls to insure struc- 2. Dynamic systems that operate in the event of fire.
tural stability.
2. All exits and stairways in Group A and H occupancies shall be 2 705.1.2.3 Smoke barriers
hours with 1 1/2-hour door assemblies. 705.1.2.3.1 An approved damper designed to resist
3. See also 503.1.2.
4. See 704.2.3 and 704.2.4. the passage of smoke shall be installed in accor-
5. See 409 for sprinklered Group 1 - buildings. dance with the manufacturer's installation instruc-
6. Fire rated bathroom/restroom doors are not required when opening tions at each air transfer opening or duct penetration
onto fire rated halls, corridors, exit access provided: of a required smoke barrier. The required smoke
a. no other rooms open off of the bathroom/restroom, and damper shall be arranged to operate automatically,
b. no gas or electric appliances are located in the bathroom/restroom,
controlled by a smoke detection system and manual
and

7.8 FLORIDA BUILDING CODE BUILDING


705.1.2.3.2-705.1.3.4

positioning shall be permitted from a remote com- 705.1.3.2.2 Unless otherwise specified, doors and
mand station. view panels within doors in walls required to have a
fire resistance rating of 1 hour or less shall have a
705.1.2.3.2 Smoke dampers located in ducts that fire protection rating of at least 20 minutes when
penetrate smoke barriers shall close upon detection tested in accordance with NFPA 252 without the
of smoke by smoke detectors that are: hose stream.
1. Installed in accordance with NFPA 72.
2. Located on either side of a smoke barrier door Exception: For Group I Unrestrained, corridor
opening where ducts penetrate smoke barriers doors shall be in accordance with 409.1.4.
above the door opening.
3. Located within the ductwork in existing 705.1.3.2.3 All doors in smoke barriers, horizontal
installations. exits, stairway enclosures and other doors opening
between rooms and fire-rated exit access corridors
705.1.2.3.3 Required smoke dampers in air transfer shall be self-closing and shall be maintained closed
openings shall close upon detection of smoke by or, in buildings of low or ordinary hazard contents
smoke detectors that are installed in accordance when approved by the building official, shall be
with NFPA 72. permitted to be automatic-closing doors provided
with approved door holding devices of the fail-safe
705.1.2.3.4 Smoke dampers are not required under type which will release the door causing it to
the following conditions: become automatic-closing and to close when acti-
1. Ducts or air-transfer openings that are part of vated by approved listed smoke detectors in accor-
an engineered smoke control system. dance with the following:
2. Ducts where the air continues to move and the 1. Upon release of the hold-open mechanism, the
air-handling system is arranged to prevent door becomes self-closing; and,
recirculation of exhaust or return air under a 2. The release device is designed so that the door
fire emergency condition. instantly releases manually and upon release
3. Air inlet or outlet openings in ducts that are becomes self-closing, or the door closes by some
limited to a single smoke compartment. simple or readily obvious operation; and,
4. Ducts that penetrate floors that serve as smoke 3. The automatic releasing mechanism or medium is
barriers. activated by the operation of an approved, auto-
matic smoke detection system installed in accor-
705.1.3 Approved types of fire windows, doors and dance with NFPA 72 to protect the entire build-
shutters ing, designed and installed to provide for actua-
705.1.3.1 Wall openings required to be protected shall tion of the system promptly so as to preclude the
be protected by approved listed and labeled fire doors, generation of heat or smoke sufficient to interfere
windows and shutters and their accompanying hard- with egress before the system operates; or, the
ware, including all frames, closing devices, anchorage operation of approved smoke detectors installed
and sills, in accordance with the requirements of NFPA in such a way as to detect smoke on either side of
80, except as otherwise specified in this code. the door opening, as detailed in NFPA 72. Either
Exception: Unprotected openings shall be permit- system shall be permitted to be zoned where
ted for corridors in multi-theater complexes where approved by the building official; and,
each motion picture auditorium has at least 1/2 of its 4. Any fire detection system or smoke detector is
required exit or exit access doorways opening provided with such supervision and safeguards as
directly to the exterior or into an exit passageway are necessary to insure reliability of operation in
and the complex is protected throughout with an case offire;and,
approved automatic sprinkler system. 5. Upon loss of power to the hold-open device, the
hold-open mechanism is released and the door
705.1.3.2 Openings are classified in accordance with the becomes self-closing; and,
character and location of the wall in which they are situ- 6. The release by means of smoke detection of one
ated. Fire protection ratings for products intended to com- door in a stair enclosure results in closing all
ply with this section shall be as determined and reported doors serving that stair.
by a nationally recognized testing agency in accordance
705.1.3.3 The maximum size of fire doors shall not
with NFPA 252 or NFPA 257. All such products shall bear
an approved label. In each of the following classes, the exceed that specified in Appendix E, NFPA 80.
minimum fire protection ratings are shown. 705.13.4 For 11/2hour and 1 hour doors used in stairway
enclosures the average temperature rise developed on the
705.1.3.2.1 Fire doors are classified as 3 hour, 1 1/2 unexposed side shall not exceed 450F (232C) at the end
hour, 1 hour, 3/4 hour or 20 minute. of 30 minutes of standard fire test exposure.

FLORIDA BUILDING CODE BUILDING 7.9


705.1.3.5-705.2.2

705.1.3.5 Fire doors shall be equipped with an approved 705.1.4 Fire shutters
closer. (See 1009.2.2 for doors in horizontal exits.) 705.1.4.1 When equipped with fire shutters of the
swinging type, at least one in every three openings fac-
Exception: Doors located in common walls separat- ing a street in each story shall have such shutters
ing guest rooms in Group Rl hotels and motels may arranged to be readily opened from the outside.
be installed without automatic or self-closing devices. Distinguishing marks shall be provided on such shutters.
705.1.3.6 View panels 705.1.4.2 Fire shutters of the rolling type shall include
705.1.3.6.1 One-fourth inch (6.4 mm) thick wired approved automatic closing devices.
glass labeled for fire protection purposes may be
used in approved opening protectives with the max- 705.1.5 Opening protection in stairway enclosures.
imum sizes shown in Table 705.1.3.6. Other glazing Opening protectives in stairway shafts are limited to self-
materials which have been tested and labeled to closing or smoke actuated, automatic-closing fire door
indicate the type of opening to be protected for fire assemblies. If smoke-actuated closures close one door, all
protection purposes may be used in approved open- doors serving that stairway shall close.
ing protectives in accordance with their listing with
the maximum sizes tested. For requirements for 705.2 Protection of floor openings
safety glazing, (See 2405.) 705.2.1 General requirements
705.2.1.1 Protection of floor openings shall be provid-
TABLE 705.1.3.6 ed in accordance with these provisions to prevent the
LIMITING SIZE OF WIRED GLASS PANELS1,2,3 spread of fire from story to story.
MAXIMUM MAXIMUM MAXIMUM 705.2.1.2 For protection of stairways, see 1006. For
RATING, OPENING AREA HEIGHT WIDTH protection of elevators, see 3003.1.
(sq In) (In) (in)
705.2.1.3 For protection of pipe, conduit, cable, wire,
3-hour door 0 0 0 tube, duct and vent penetrations of fire resistance rated
1 & 1 1/2-hour doors 100 33 12 floors, roofs, ceilings and shaft enclosures, see 705.4.
3
/4-hour door 1,296 54 54
705.2.1.4 Duct penetrations
For S1: 1 in = 25.4 mm, 1 in2: = 645.16 mm2. 705.2.1.4.1 Fire dampers shall be installed in accor-
dance with the manufacturer's installation instruc-
Notes: tions in ducts penetrating only one floor of a building
1. The glass shall be well-embedded in putty, and all exposed joints
between the metal and glass shall be struck and pointed. requiring the protection of vertical openings when the
2. Devices used to view through fire doors rated at 1 1/2 hours or less duct is not protected by a shaft enclosure described in
shall be labeled. the Florida Building Code, Mechanical.
3. Wired glass in 20-minute doors shall be limited to the amount of
glass tested in a door. 705.2.1.4.2 Fire dampers shall comply with the
requirements of UL 555 and shall bear the label of
705.1.3.6.2 Fire windows, side lights and transoms an approved testing agency. Closure shall interrupt
in 1-hour fire resistant partitions shall be 45-minute any migratory air flow and restrict the passage of
fire protection rated. Such fire protection rated glaz- flame. Fire dampers shall be classified and identi-
ing shall consist of labeled glazing installed in fied for use in either:
labeled frames in accordance with their individual 1. Static systems that automatically shut down
listings. in the event of fire.
2. Dynamic systems that operate in the event of
705.1.3.6.3 View panels shall achieve a minimum fire.
fire protection rating of 45 minutes, including fire
endurance and hose stream tests in accordance with 705.2.1.5 Floor fire doors. Floor fire door assemblies,
NFPA 257 under positive pressure. Within the first used to protect openings in fire rated floors, shall be
10 minutes of a test, the pressure in the furnace shall tested in the horizontal position in accordance with
be adjusted so at least 2/3 of the test specimen is ASTM E 119 and shall achieve a fire resistance rating
not less than that of the assembly being penetrated.
above the neutral pressure plane, and the neutral
Floor fire doors shall bear an approved label.
pressure plane shall be maintained at that height for
the balance of the test. 705.2.2 Shaft enclosures. All openings through a floor
and penetrations through a floor shall be protected by a
705.1.3.7 The aggregate area of glazing in fire doors, fire
shaft enclosure in accordance with 705.2.3.
windows, side lights and transoms in 1-hourfireresistant
partitions shall not exceed 25 percent of the area of a Exceptions:
wall separating a room or space from a corridor. 1. A shaft enclosure is not required for openings
totally within a dwelling unit and connecting
four stories or less.

7.10 FLORIDA BUILDING CODE BUILDING


705.2.3 - 705.2.3.4.2

2. A shaft enclosure is not required for a floor open- 705.2.3 Shaft enclosure construction
ing which: 705.2.3.1 Fire resistance. The fire resistance rating of
1. is not part of the required means of egress, and shaft enclosures shall be in accordance with Table
2. is not concealed within the building construc-
tion, and 705.1.2 and not less than the floor assembly penetrat-
3. does not connect more than two stories, and ed, but the rating need not exceed 2 hours.
4. does not connect with a stairway or escalator
serving other floors, and
5. is not open to any corridors in Group I and R 705.2.3.2 Construction type. Shaft enclosures shall be
Occupancies or to corridors on nonsprin- of noncombustible materials in Types I, II and IV con-
klered floors in other occupancies, and struction and may be of combustible materials in Types
6. is separated from floor openings serving other
floors by construction conforming with III, V and VI construction.
required shaft enclosures.
3. A shaft enclosure is not required for penetrations 705.2.3.3 Enclosure at bottom. Shafts which do not
by pipe, tube, conduit, wire, cable, duct and vents extend to the bottom of the building or structure shall
protected in accordance with 705.4. be enclosed at the lowest level with construction of the
4. A shaft enclosure is not required for floor open- same fire resistance as the lowest floor through which
ings complying with the special provisions for the shaft passes, but not less than the rating required for
covered malls or atriums. the shaft enclosure, or shall terminate in a room having
5. A shaft enclosure is not required for approved a use related to the purpose of the shaft. The room shall
masonry chimneys where annular space protec- be separated from the remainder of the building by
tion is provided at each floor level in accordance construction having a fire resistance rating and opening
with 705.4. protectives at least equal to the protection required for
6. A shaft enclosure is not required for floor open- the shaft enclosure. For shafts containing refuse or
ings in an open parking garage. laundry chutes, see 705.2.4.
7. A shaft enclosure is not required for floor open-
ings between a mezzanine and the floor below. Exceptions:
8. A shaft enclosure is not required in fully sprin- 1. Fire resistant separation of the room is not
klered buildings for an escalator opening protect- required, provided there are no openings in or
ed in accordance with one of the following alter- penetrations through the shaft enclosure to the
natives: interior of the building except at the bottom of
the shaft. The bottom of the shaft shall be
Alternative A - (1) The area of the floor opening closed off around the penetrating items with
between stories shall not exceed twice the hori- materials permitted by the code for draftstops,
zontal projected area of the escalator, and (2) or the room shall be provided with an
Draft curtains and special sprinkler head loca- approved automatic sprinkler system.
tions shall meet the requirements of NFPA 13, 2. Fire resistance separation of the room is not
and (3) In other than Group B and M occupancies required and the bottom of the shaft may be
the escalator openings shall not connect more open provided there are no combustibles in
than four stories, or the shaft and there are no other openings or
penetrations through the shaft enclosure to the
Alternative B - The opening is protected by interior of the building.
approved power-operated automatic shutters at
every floor opening. The shutters shall be of non- 705.2.3.4 Enclosure at top
combustible construction and have a fire resis- 705.2.3.4.1 A shaft that does not extend to or
tance rating of not less than 11/2hours. The shut- through the underside of the roof deck of the build-
ter shall close immediately upon the automatic ing shall be enclosed at the top with construction of
detection of smoke by an approved device and the same fire resistance as the topmost floor pene-
shall completely shut off the floor opening. The trated by the shaft, but not less than the rating
escalator shall stop when the shutter begins to required for the shaft enclosure.
close. The shutter shall operate at a speed of not
more than 30 ft per minute (0.152 m/s) and shall 705.2.3.4.2 When a shaft extends through a roof, the
be equipped with a sensitive leading edge to shaft enclosure shall extend at least 36 inches (914
arrest its progress when in contact with any mm) above the highest part of the roof that is with-
obstacle, and to continue its progress after in 5 ft (1524 mm) of the opening. The enclosure
release. wall or combination of enclosure wall and guardrail
shall be at least 42 inches (1066 mm) high.

FLORIDA BUILDING CODE BUILDING 7.11


705.2.3.5 - 705.5.1

Exception: When a shaft extends through a non- 705.2.4.6 Automatic sprinklers. An approved auto-
combustible roof, a noncombustible guardrail at matic sprinkler system shall be installed at the top and
least 42 inches (1066 mm) high may be used at alternate floor levels in refuse and laundry chutes
around the opening instead of a wall. and in the termination and incinerator rooms.

705.2.3.5 Openings in shaft enclosures. Openings in 705.3 Fireblocking and draftstopping


shaft enclosures shall be permitted when limited to 705.3.1 Fireblocking
those necessary for the purposes of the shaft. Permitted 705.3.1.1 Fireblocking shall be provided in all walls
openings in shaft enclosures shall be protected with and partitions to cut off all concealed draft openings
opening protectives having a fire resistance in accor- both horizontal and vertical and to form a fire barrier
dance with Table 705.1.2. between floors and between the upper floor and the
roof space. See also 2305.1.
705.2.4 Special provisions for refuse and laundry
chutes
705.3.1.2 Fireblocking shall not be covered or con-
705.2.4.1 General. Refuse and laundry chutes, access
cealed until inspected by the building official.
and termination rooms and incinerator rooms shall be
constructed in accordance with 705.2.4.2 through
705.3.1.3 Walls and stud partitions shall be fireblocked
705.2.4.6.
at floors, ceilings and roofs. Fireblocking in noncom-
bustible partitions shall not be required at the ceiling
Exception: Group R3 occupancies.
for suspended ceiling systems. Fireblocking shall con-
sist of approved noncombustible materials unless oth-
705.2.4.2 Refuse and laundry chute enclosures. A
erwise specified in this code. Material shall be secure-
shaft containing a refuse or laundry chute shall be used
ly fastened in place.
for no other purpose and shall be protected by a shaft
enclosure in accordance with 705.2.3. Refuse chute
705.3.1.4 Chimneys shall be fireblocked in accordance
material shall be noncombustible meeting Part 1 of the
with 2113, 2305, and 2804.
definition for noncombustible. All openings into the
shaft enclosure, including those from access rooms and
705.3.2 Draftstopping. Enclosed attic and floor spaces
termination rooms, shall be protected in accordance
formed of combustible construction shall be divided in
with Table 705.1.2. Such opening protectives shall be
accordance with 2305.2.
self-closing or automatic-closing upon detection of
smoke, except that the opening protective between the
705.4 Protection of penetrations
shaft and the termination room may be closed by a
705.4.1 General. Protection of penetrations through fire
heat-activated device.
rated and nonfire rated assemblies shall comply with
705.5 and 705.6.
705.2.4.3 Refuse and laundry chute access rooms.
Access openings for refuse and laundry chutes shall be
705.4.2 Sleeves. Where sleeves are used, the sleeves shall
located in rooms or compartments completely enclosed
be securely fastened to the assembly penetrated. All space
by construction and opening protectives in accordance
between the item contained in the sleeve and the sleeve
with Table 705.1.2. Access openings to refuse and
itself and any space between the sleeve and the assembly
laundry chutes shall not be located in exit access corri-
penetrated shall be protected in accordance with 705.5 or
dors or exit enclosures.
705.6.
705.2.4.4 Termination room. Refuse and laundry
705.4.3 Insulation. Insulation and coverings on the pene-
chutes shall discharge into an enclosed termination
trating item shall not penetrate the assembly unless the
room completely separated from the remainder of the
specific material used has been tested as part of the assem-
building by construction and opening protectives in
bly in accordance with 705.5 or 705.6.
accordance with Table 705.1.2. Refuse chutes shall not
terminate in an incinerator room.
705.5 Penetrations of fire rated walls. Penetrations into or
through fire resistant walls required to have opening protec-
705.2.4.5 Incinerator room. Incinerators shall be
tives shall comply with 705.5.1 through 705.5.3.
enclosed within a room separated from the remainder
of the building by construction and opening protectives
705.5.1 Through-penetrations. Through-penetrations of
in accordance with Table 705.1.2.
fire rated walls shall comply with 705.5.1.1 or 705.5.1.2.

7.12 FLORIDA BUILDING CODE BUILDING


705.5.1.1 - 705.6.1.1

Exception: Where the penetrating items are steel, fer- Where combustible members frame into hollow walls or
rous or copper pipes or steel conduits, the annular walls of hollow units, all hollow spaces shall be solidly
space shall be permitted to be protected as follows: filled for the full thickness of the wall and for a distance
1. In concrete or masonry walls where the penetrat- not less than 4 inches above, below and between the struc-
ing item is a maximum 6 inch nominal diameter tural members, with noncombustible materials approved
and the opening is a maximum 144 square inch- for fireblocking.
es, concrete, grout, or mortar shall be permitted
when installed the full thickness of the wall or 705.6 Penetrations of horizontal assemblies. All penetra-
the thickness required to maintain the fire rating, tions of a floor, floor/ceiling assembly, or the ceiling mem-
or brane of a roof/ceiling assembly shall be protected by a shaft
2. The material used to fill the annular space shall enclosure in accordance with 705.2 or shall comply with
prevent the passage of flame and hot gases suffi- 705.6.1 through 705.6.4.
cient to ignite cotton waste when subjected to
ASTM E 119 time/temperature fire conditions 705.6.1 Through-Penetrations. Through-penetrations of
under a minimum positive pressure differential fire rated horizontal assemblies shall comply with
of 0.01 inch of water column (2.5 Pa) at the loca- 705.6.1.1 or 705.6.1.2.
tion of the penetration for the time period equiv-
alent to the fire rating of the construction pene- Exceptions:
trated. 1. Steel, ferrous or copper conduits, pipes, tubes,
vents, concrete or masonry penetrating items that
705.5.1.1 Fire rated assembly. Penetrations shall be penetrate a single fire rated floor or floor/ceiling
installed as tested in the approved ASTM E 119 rated assembly where the annular space is protected
assembly. with materials that prevent the passage of flame
and hot gases sufficient to ignite cotton waste
705.5.1.2 Penetration firestop system. Penetrations when subjected to ASTM E 119 time/tempera-
shall be protected by an approved penetration firestop ture fire conditions under a minimum positive
system installed as tested in accordance with ASTM E pressure differential of 0.01 inch of water column
814, with a minimum positive pressure differential of (2.5 Pa) at the location of the penetration for the
0.01 inch of water column (2.5 Pa) and shall have an F time period equivalent to the fire rating of the
rating of not less than the required rating of the wall construction penetrated. Penetrating items with a
penetrated. maximum 6-inch nominal diameter shall not be
limited to the penetration of a single fire rated
705.5.2 Membrane penetrations. Membrane penetra- floor or floor/ceiling assembly provided that the
tions shall comply with 705.5.1 through 705.5.1.2. area of the penetration does not exceed 144
square inches in any 100 sq ft of floor area.
Exceptions: 2. Penetrations in a single concrete floor by steel,
1. Steel electrical boxes that do not exceed 16 ferrous or copper conduits, pipes, tubes and vents
square inches in area provided that the area of with a maximum 6 inch nominal diameter pro-
such openings does not exceed 100 square inch- vided concrete, grout or mortar is installed the
es for any 100 sq ft of wall area. Outlet boxes on full thickness of the floor or the thickness
opposite sides of the wall shall be separated by a required to maintain the fire rating. Penetrating
horizontal distance of not less than 24 inches. items with a maximum 6 inch nominal diameter
Membrane penetrations for electrical outlet shall not be limited to the penetration of a single
boxes of any other material are permitted provid- concrete floor provided the area of the penetra-
ed that such boxes are tested for use in fire rated tion does not exceed 144 square inches.
assemblies and installed in accordance with the 3. Electrical outlet boxes of any material are per-
tested assembly. mitted provided that such boxes are tested for use
2. The annular space created by the penetration of a in fire rated assemblies and installed in accor-
fire sprinkler provided it is covered by a metal dance with the tested assembly.
escutcheon plate.
705.6.1.1 Fire rated assemblies. Penetrations shall be
705.5.3 Combustible framing into masonry fire resis- installed as tested in the approved ASTM E 119 rated
tant walls. Adjacent combustible members entering into a assembly.
masonry fire resistant wall from opposite sides shall not
have less than a 4 inch distance between embedded ends.

FLORIDA BUILDING CODE BUILDING 7.13


705.6.1.2-705.7.2

705.6.1.2 Penetration firestop system. Penetrations 705.6.4.1 Through-Penetrations. Penetrations by an


shall be protected by an approved penetration firestop air duct through a fire rated floor/ceiling assembly
system installed as tested in accordance with ASTM E which connects not more than two stories are permitted
814, with a minimum positive pressure differential of where a fire damper is installed at the floor line.
0.01 inch of water column (2.5 Pa). The system shall
have an F rating and a T rating of not less than 1 hour 705.6.4.2 Membrane penetration. Where a noncom-
but not less than the required rating of the floor pene- bustible air duct penetrates a ceiling which is an inte-
trated. gral component of a fire rated floor/ceiling or roof/ceil-
ing assembly, an approved ceiling damper shall be
Exception: Floor penetrations contained and located installed at the ceiling line except where fire tests show
within the cavity of a wall do not require a T rating. that the integrity of the fire rated assembly is main-
tained without a ceiling damper. Ceiling dampers shall
705.6.2 Membrane penetrations. Penetrations of mem- be constructed in accordance with the details listed in a
branes which are part of a fire rated horizontal assembly fire rated design or shall be labeled to function as a heat
shall comply with 705.6.1 through 705.6.1.2. barrier for air-handling outlet/inlet penetrations in the
ceiling of a fire rated assembly.
Exceptions:
1. Membrane penetrations of steel, ferrous or cop- 705.6.43 Nonfire rated assemblies. Noncombustible air
per conduits, electrical outlet boxes, pipes, tubes, ducts through floor assemblies not rated for fire resis-
vents, concrete or masonry penetrating items tance which connect not more than three stories are per-
where the annular space is protected in accor- mitted provided that a fire damper is installed at each
dance with 705.6.1, 705.6.2 or is protected to floor line.
prevent the passage of flame and hot gases. Such
penetrations shall not exceed an aggregate area Exception: Fire dampers are not required in air
of 100 square inches in any 100 sq ft of ceiling ducts within individual residential dwelling units.
area in assemblies tested without penetrations.
2. Membrane penetrations for electrical outlet 705.7 Fire Resistant joint systems
boxes of any material are permitted provided that 705.7.1 General. Joints installed in or between fire resis-
such boxes are tested for use in fire rated assem- tant walls, fire resistant floor or floor/ceiling assemblies
blies and installed in accordance with the tested and fire resistant roof or roof/ceiling assemblies shall be
assembly. protected by an approved fire resistant joint system
3. The annular space created by the penetration of a designed to resist the passage of fire for a time period not
fire sprinkler provided it is covered by a metal less than the required fire resistance rating of the wall,
escutcheon plate. floor or roof in or between which it is installed. Fire resis-
tant joint systems shall be installed and tested in accor-
705.6.3 Nonfire rated assemblies. Penetrations of hori- dance with 705.7. The void created at the intersection of a
zontal assemblies without a required fire rating shall com- floor or floor/ceiling assembly and an exterior curtain wall
ply with 705.6.3.1 through 705.6.3.2. assembly shall be protected in accordance with 705.7.6.

705.6.3.1 Noncombustible penetrating items. Exception: Fire resistant joint systems shall not be
Noncombustible penetrating items which connect required for joints in the following locations:
not more than three stories are permitted provided 1. Floors within a single dwelling unit.
that the annular space is filled with an approved 2. Floors where the joint is protected by a shaft
material to resist the passage of flame and hot gases. enclosure in accordance with 705.2.
3. Floors within atriums where the space adjacent
705.6.3.2 Combustible penetrating items. Combustible to the atrium is included in the volume of the atri-
penetrating items which connect not more than two sto- um for smoke-control purposes.
ries are permitted provided that the annular space is filled 4. Floors within malls.
with an approved material to resist the passage of flame 5. Floors within open parking structures.
6. Mezzanine floors.
and hot gases. 7. Walls which are permitted to have unprotected
openings.
705.6.4 Air ducts. Penetrations of horizontal assemblies
by air ducts shall comply with 705.6.4.1 through 705.7.2 Fire test Fire resistant joint systems shall be test-
705.6.4.3. ed in accordance with ASTM E 119 under the following
conditions:

7.14 FLORIDA BUILDINGS CODE BUILDING


TABLE 705.7 - 708.1

1. Joint systems shall be installed full height in wall SECTION 706


assemblies and full length in floor and roof assemblies. COMBUSTIBLES IN FIRE RATED ASSEMBLIES
2. Floor and roof assemblies shall be tested with a
minimum positive pressure differential of 0.01 inch 706.1 Plumbing, electrical and air handling systems in
of water column (2.5 Pa). fire rated assemblies. In Type I and Type II construction,
3. Wall assemblies shall be tested with a minimum materials used for piping, conduit, raceways or duct systems
positive pressure differential of 0.01 inch of water which do not qualify as noncombustible in accordance with
column (2.5 Pa) measured at the mid-height of the the requirements of Part 1 of the definition of noncom-
wall assembly. bustible material contained in 202 shall neither
4. Joint systems shall contain a splice. For wall assem- 1. penetrate any assembly which is required to have a fire
blies the splice shall be located above the mid- resistance rating unless such materials and methods of
height of the wall assembly. penetration have been tested in accordance with 705.4,
5. Joint systems shall be tested at the maximum joint nor
width for which they are designed. Joint systems 2. be concealed within any assembly which is required to
designed to accommodate movement shall be have a fire resistance rating unless enclosed by or total-
expanded to the maximum joint opening width for ly embedded within noncombustible materials or
which they are intended to function. unless such materials and methods have been tested in
6. Joint systems designed to be loadbearing shall be accordance with 701.2.
loaded to the maximum design load in accordance
with their intended application. SECTION 707
7. Joint systems designed to accommodate movement COMBUSTIBLES IN CONCEALED SPACES
shall be preconditioned by cycling between the min-
imum and the maximum joint opening width for 707.1 Concealed spaces in Types I, II and IV construction.
which they are intended to function for the number Combustibles shall not be permitted in concealed spaces of
of cycles specified in Table 705.7 in accordance Types I, II or IV construction.
with ASTM E 1399.
8. Asymmetrical wall joint systems shall be tested in Exceptions:
accordance with 701.2.4 and 705.7.2. 1. Materials complying with 602 of the Florida
Building Code, Mechanical.
TABLE 705.7 2. Class A interior finish materials.
PRECONDITIONING CYCLES FOR FIRE RESISTANT 3. Fire retardant treated wood used in accordance with
JOINT SYSTEMS
Table 600 and wood used in accordance with 609.
TYPE OF JOINT SYSTEM NUMBER OF CYCLES 4. Floor finish complying with 803.7.
5. Conduit or raceway systems complying with 706.
Expansion/Contraction 500 6. Foam plastic insulation complying with 2603.
Seismic 100 7. Thermal insulation materials complying with 708.
Wind sway 500 8. Combustible piping within partitions or enclosed
shafts installed in accordance with the provision of
this code. Combustible piping may also be used
705.7.3 Installation. Fire resistant joint systems shall be within concealed ceiling spaces when approved.
securely installed in or on the joint for its entire length so
as not to dislodge, loosen or otherwise impair its ability to 707.2 Combustibles in plenums. The use of combustible
accommodate expected building movements and to resist materials in plenums shall be restricted in accordance with
the passage of fire and hot gases. the Florida Building Code, Mechanical.

705.7.4 Walls. The protection of joints in fire resistant SECTION 708


walls shall comply with the requirements of 705.7. THERMAL INSULATING MATERIALS
705.7.5 Floors and roofs. The protection of joints in fire 708.1 General. Insulating materials, including facings such
resistant floors and roofs shall comply with the require- as vapor retarders and breather papers, similar coverings and
ments of 705.7. all layers of single and multilayer reflective foil insulations,
shall comply with the requirements of this section. Where a
705.7.6 The void created at the intersection of a fire resis- flamespread rating or a smoke developed rating is specified
tant floor or a floor/ceiling assembly and an exterior cur- in this section, such rating shall be determined in accordance
tain wall shall be sealed using an approved material or with the ASTM E 84. Any material which is subject to an
assembly of materials designed and tested for this pur- increase in flamespread rating or smoke developed rating
pose. The material shall remain in place, sealing the open- beyond the limits herein established through the effects of
ing, for a time period at least equal to the required fire age, moisture, or other atmospheric conditions, shall not be
resistance rating of the floor deck. permitted.

FLORIDA BUILDING CODE BUILDING 7.15


708.2-709.2.1.1.4

708.2 Concealed installation SECTION 709


708.2.1 Insulating materials, when concealed as installed, CALCULATED FIRE RESISTANCE
in buildings of any type construction, shall have a flame-
spread rating of not more than 75 and a smoke developed 709.1 General
rating of not more than 450. 709.1.1 Scope. These provisions contain procedures by
which the fire resistance of specific materials or combina-
Exception: Cellulose loose-fill insulation, which is not tions of materials can be established by calculations.
spray applied, complying with the requirements of These procedures apply only to the information contained
708.8 shall be required to meet only the smoke devel- in this section and shall not be otherwise used. The calcu-
oped rating of not more than 450. lated fire resistance of concrete, concrete masonry, and
clay masonry assemblies shall be in accordance with this
708.2.2 When such materials are installed in concealed section or in accordance with ACI 216.1/TMS 0216.1.
spaces in buildings of Type III, Type V or Type VI con-
struction, the flamespread and smoke developed limita- 709.1.2 Definitions. For definitions, see Chapter 2.
tions do not apply to facings, coverings and layers of
reflective foil insulation that are installed behind and in 709.2 Concrete assemblies
substantial contact with the unexposed surface of the ceil- 709.2.1 Concrete walls
ing, wall or floor finish. 709.2.1.1 Cast-In-Place or precast walls
708.3 Exposed installation
709.2.1.1.1 The minimum equivalent thicknesses of
708.3.1 Insulating materials when exposed as installed in
cast-in-place or precast concrete walls for fire resis-
buildings of any type construction shall have a flame-
tance ratings of 1 hour to 4 hours are shown in Table
spread rating of not more than 25 and a smoke developed
709.2.1.1. For solid walls with flat vertical surfaces,
rating of not more than 450.
the equivalent thickness is the same as the thickness.
Exception: Cellulose loose-fill insulation, which is not The values in Table 709.2.1.1 apply to plain, rein-
spray applied, complying with the requirements of forced, or prestressed concrete walls.
708.8 shall be required to meet only the smoke devel- TABLE 709.2.1.1
oped rating of not more than 450. MINIMUM EQUIVALENT THICKNESS (in) OF CAST-IN-PLACE
OR PRECAST CONCRETE WALLS, LOADBEARING
708.3.2 Attic floors. Exposed insulation materials OR NONLOADBEARING
installed on attic floors shall have a critical radiant flux of MINIMUM SLAB THICKNESS (In)
not less than 0.12 watt per square centimeter when tested FOR FIRE RESISTANCE RATING OF
in accordance with ASTM E 970. Concrete
Typo 1-hr 1-1/2 hr 2-hr 3-hr 4-hr
708.4 Loose-Fill insulation. Loose-fill insulation materials, Siliceous 3.5 4.3 5.0 6.2 7.0
which cannot be mounted in the ASTM E 84 apparatus with- Carbonate 3.2 4.0 4.6 5.7 6.6
out a screen or artificial supports, shall comply with the Sand-Lightweight 2.7 3.3 3.8 4.6 5.4
flamespread and smoke developed limits of 708.2 and 708.3 Lightweight 2.5 3.1 3.6 4.4 5.1
when tested in accordance with CAN 4-S102.2-M83. For SI: 1 in = 25.4 mm.

Exception: Cellulose loose-fill insulation shall not be 709.2.1.1.2 For hollow-core precast concrete wall
required to comply with this test method, provided such panels in which the cores are of constant cross sec-
insulation complies with the requirements of 708.8. tion throughout the length, the equivalent thickness
may be calculated by dividing the net cross-section-
708.5 Roof insulation. The use of combustible roof insula- al area (the gross cross section minus the area of the
tion not complying with 708.2 or 708.3 shall be permitted in cores) of the panel by its width.
any type construction provided it is covered with approved
roof coverings directly applied thereto. 709.2.1.1.3 Where all of the core spaces of hollow-
core wall panels are filled with loose-fill material,
708.6 Duct insulation. Duct linings and coverings shall con- such as expanded shale, clay, or slag, or vermiculite
form to the appropriate requirements of the Florida Building or perlite, the fire resistance rating of the wall is the
Code, Mechanical. same as that of a solid wall of the same concrete
type and of the same overall thickness.
708.7 Foam plastics. Foam plastics shall comply with 2603.
709.2.1.1.4 The thickness of panels with tapered
708.8 Cellulose loose fill insulation. Cellulose loose-fill cross sections shall be that determined at a distance
insulation shall comply with CPSC 16 CFR, Parts 1209 and 2t or 6 inches (152 mm), whichever is less, from the
1404. Each package of such insulating material shall be point of minimum thickness, where t is the mini-
clearly labeled as meeting the requirements of CPSC 16 mum thickness.
CFR, Parts 1209 and 1404.

7.16 FLORIDA BUILDING CODE BUILDING


709.2.1.1.5-709.2.1.2.2

709.2.1.2 Multi-Wythe walls


709.2.1.2.1 For walls which consist of two (2) wythes
of different types of concrete the fire resistance ratings
may be determined from Figure 709.2.1.2.

709.2.1.1.5 The equivalent thickness of panels with


ribbed or undulating surfaces shall be determined by
one of the following expressions:
for s 4t, the thickness to be used shall be t;
for s < 2t, the thickness to be used shall be te;
for 4t > s > 2t, the thickness to be used shall be

t + (4t / s - I ) ( t , - t )

where
s = spacing of ribs or undulations
t = minimum thickness
te = equivalent thickness of the panel calculated as
the net cross-sectional area of the panel divided
by the width, in which the maximum thickness
used in the calculation shall not exceed 2t.
THICKNESS OF INSIDE WYTHE OF SANCM.IGHTWEIGHT CONCRETE INCHES

FIGURE 709.2.1.2
FIRE RESISTANCE RATINGS
TWO-WYTHE CONCRETE WALLS

For SI: 1 in. = 25.4 mm.

709.2.1.2.2 The fire resistance rating for wall panels


consisting of two or more wythes may be determined
by the formula:

R = (R10.59 + R20.59 + ... + Rn0.59)1.7 (Eq. 709.2.1.2)


NEGLECT SHADED AREA IN CALCULATION OF EQUIVALENT THICKNESS
where
R= the fire endurance of the
assembly, minutes
R1, R2, and R n = t h e fire endurances of the individ-
ual wythes, minutes.
Values of Rn0.59 for use in Equation 709.2.1.2 are given
in Table 709.2.1.2.

For SI: 1 in. = 25.4 mm

FLORIDA BUILDING CODE BUILDING 7.17


TABLE 709.2.1.2 - FIGURE 709.2.1.3

TABLE 709.2.1.2
0.59
VALUES OF R FOR USE IN EQUATION 709.2.1.2

TYPE OF MATERIAL THICKNESS OF MATERIAL


1
1 /22In 2 In 1
2 /2 In 3 in 3V2 In 4 in 4V2 in 5 In 5 In 6 in 6 1 / 2 ln 7 In
Siliceous aggregate
concrete 5.3 6.5 8.1 9.5 11.3 13.0 14.9 16.9 18.8 20.7 22.8 25.1

Carbonate aggregate
concrete 5.5 7.1 8.9 10.4 12.0 14.0 16.2 18.1 20.3 21.9 24.7 27.2'

Sand-lightweight concrete 6.5 8.2 10.5 12.8 15.5 18.1 20.7 23.3 26.03 Note 3 Note 3 Note 3

Lightweight concrete 6.6 8.8 11.2 13.7 16.5 19.1 21.9 24.7 27.8' Note 3 Note 3 Note 3

Insulating concrete1 9.3 13.3 16.6 18.3 23.1 26.53 Note 3 Note 3 Note 3 Note 3 Note 3 Note 3

Air Space2
For SI: 1 in = 25.4 mm.
Notes:
1. Dry unit weight of 35 pcf (560.6 kg/m3) or less and consisting of cellular, perlile. or vermiculite concrete.
2. The Rn0.59 value for one 1/2" to 31/2" air space is 3.3. The Rn0.59 value for two 1/2" to 31/2" air spaces is 6.7.
3. The fire resistance rating for this thickness exceeds 4 hours.

R, MINUTES R0.59

60 11.20
120 16.85
180 21.41
240 25.37

709.2.1.2.3 The fire resistance ratings of precast con- 709.2.1.3.2 Figure 709.2.1.3 shows thicknesses of
crete wall panels consisting of a layer of foam plastic ceramic fiber blankets to be used to insulate joints
insulation sandwiched between two wythes of con- between precast concrete wall panels for various
crete may be determined by use of Equation panel thicknesses and for joint widths of 3/8 inch
709.2.1.2. Foam plastic insulation with a total thick- (9.5 mm) and 1 inch (25.4 mm) for fire resistance
ness of less than 1 inch (25 mm) shall be disregard- rating of 1 hour to 4 hours. For joint widths between
3
ed. The Rn value for thickness of foam plastic insula- /8 inch (9.5 mm) and 1 inch (25.4 mm), the thick-
tion of 1 inch or greater, for use in the calculation, is ness of ceramicfiberblanket may be determined by
5 minutes; therefore Rn0.59 = 2.5. direct interpolation. Other tested and labeled mate-
rials may be used in place of ceramicfiberblankets.
709.2.1.3 Joints between precast wall panels
709.2.1.3.1 Joints between precast concrete wall
panels which are not insulated as required by this
section shall be considered as openings in walls.
Uninsulated joints shall be included in determining
the percentage of openings permitted by Table 600.
Where openings are not permitted or are required by
this code to be protected, the provisions of this sec-
tion shall be used to determine the amount of joint
insulation required. Insulated joints shall not be
considered openings for purposes of determining
compliance with allowable percentage of openings
in Table 600.

For SI: 1 in. = 25.4 mm.


FIGURE 709.2.1.3
CERAMIC FIBER JOINT PROTECTION

7.18 FLORIDA BUILDING CODE BUILDING


709.2.1.4 - TABLE 709.2.1.4A

709.2.1.4 Walls with gypsum wallboard or plaster 709.2.1.4.4 For a wall having no finish on one side
finishes or having different types or thicknesses of finish on
709.2.1.4.1 The fire resistance rating of cast-in- each side, the calculation procedures of 709.2.1.4.2
place or precast concrete walls with finishes of gyp- and 709.2.1.4.3 shall be performed twice, i.e.,
sum wallboard or plaster applied to one or both assume that either side of the wall may be the fire-
sides may be calculated in accordance with the pro- exposed side. The fire resistance rating of the wall
visions of this section. shall not exceed the lower of the two values.
709.2.1.4.2 Where the finish of gypsum wallboard Exception: For exterior wall with more then 5 ft
or plaster is applied to the side of the wall not (1524 mm) of horizontal separation, the fire shall
exposed to fire, the contribution of the finish to the be assumed to occur on the interior side only.
totalfireresistance rating shall be determined as fol-
lows: The thickness of the finish shall first be cor- 709.2.1.4.5 When the finish applied to a concrete
rected by multiplying the actual thickness of the fin- wall contributes to thefireresistance rating, the con-
ish by the applicable factor determined from Table crete alone shall provide not less than one-half the
709.2.1.4A based on the type of aggregate in the total required fire resistance rating.
concrete. The corrected thickness of finish shall
then be added to the actual thickness or equivalent 709.2.1.4.6 Finishes on concrete walls which are
thickness of concrete andfireresistance rating of the assumed to contribute to the total fire resistance rat-
concrete and finish determined from Table ing of the wall shall comply with the installation
709.2.1.1, Figure 709.2.1.2, or Table 709.2.1.2. requirements of 709.3.1.6.

709.2.1.4.3 Where gypsum wallboard or plaster is


applied to thefire-exposedside of the wall, the con-
tribution of the finish to the total fire resistance rat-
ing shall be determined as follows: The time
assigned to the finish as established by Table
709.2.1.4B shall be added to the fire resistance rat-
ing determined from Table 709.2.1.1 or Figure
709.2.1.2, or Table 709.2.1.2 for the concrete alone,
or to the rating determined in 709.2.1.4.2 for the
concrete and finish on the nonfire-exposed side.

TABLE 709.2.1.4A
MULTIPLYING FACTOR FOR FINISHES ON NONFIRE-EXPOSED SIDE OF WALL

TYPE OF AGGREGATE USED IN CONCRETE OR CONCRETE MASONRY

Concrete: Concrete: Concrete:


Siliceous or Sand-Light- Lightweight
Carbonate Weight
TYPE OF FINISH Concrete Masonry: Concrete Masonry: Concrete Masonry: Concrete Masonry:
APPLIED TO WALL Siliceous or Limestone, Expanded Shale, Pumice, or
Calcareous Cinders or Clay or Slate Expanded
Gravel Unexpanded Slag
Slag

Portland Cement-
Sand Plaster 1.00 0.751 0.751 0.501

Gypsum-Sand Plaster
or Gypsum Wallboard 1.25 1.00 1.00 1.00

Gypsum- Vermiculite
or Perlite Plaster 1.75 1.50 1.25 1.25

Note:
1. For portland cement-sand plaster 5/8 inch (15.9 mm) or less in thickness and applied directly to the concrete masonry on the nonflre-exposed side of the
wall, the multiplying factor shall be 1.00.

FLORIDA BUILDING CODE BUILDING 7.19


TABLE 709.2.1.4.B - 709.2.2.2.1

TABLE 709.2.1.4B 709.2.2.1.2 For hollow-core prestressed concrete


TIME ASSIGNED TO FINISH MATERIALS ON slabs in which the cores are of constant cross sec-
FIRE-EXPOSED SIDE OF WALL
tion throughout the length, the equivalent thickness
FINISH DESCRIPTION TIME (min) may be obtained by dividing the net cross-sectional
area of the slab including grout in the joints, by its
Gypsum
3
Wallboard width.
/8 in 10
1 15
5
/2in 709.2.2.1.3 The thickness of slabs with sloping sof-
/8in 30
2 layers of 3 / 8 in 25 fits shall be determined at a distance 2t or 6 inches
1 layer 3 / 8 in, 1 layer 1/2 in 35 (152 mm), whichever is less, from the point of min-
2 layers 1/2 in 40 imum thickness, where t is the minimum thickness.
Type X Gypsum Wallboard
1 25
5 /2in
/8in 40

Portland Cement-sand plaster


applied directly to concrete See
masonry Note 1

Portland cement-sand plaster


on metal lath
3
/4in 20 709.2.2.1.4 The thickness of slabs with ribbed or
7
/8in 25
1 in 30 undulating soffits shall be determined by one of the
following expressions, whichever is applicable.
Gypsum sand plaster on 3 / 8 in
gypsum lath
1
for s > 4t, the thickness to be used shall be t;
5
/2in 35 for s < 2t, the thickness to be used shall be te;
/8in 40
3
/ 4 in 50
for 4t > s > 2t, the thickness to be used shall be

Gypsum sand plaster on metal lath


3 50 t + (4t/s-1) (te - t)where
7 /4 in 60
/8 in
1 in 80 s = spacing of ribs or undulations
For SI: 1 in = 25.4 mm. t = minimum thickness
te = equivalent thickness of the slab calculated as
Note: the net area of the slab divided by the width,
1. The actual thickness of Portland cement-sand plaster, provided it is in which the maximum thickness used in the
5
/8 inch (15.9 mm) or less in thickness, may be included in deter-
mining the equivalent thickness of the masonry for use in Table calculation shall not exceed 2t.
709.3.1.

709.2.2 Concrete floor and roof slabs


709.2.2.1 Reinforced and prestressed floors and roofs
709.2.2.1.1 The minimum thicknesses of reinforced
and prestressed concrete floor or roof slabs for fire
resistance ratings of 1 hour to 4 hours are shown in NEGLECT SHADED AREA IN CALCULATION OF EQUIVALENT THICKNESS

Table 709.2.2.1.

TABLE 709.2.2.1
MINIMUM SLAB THICKNESS (in)

709.2.2.2 Multicourse floors and roofs


709.2.2.2.1 Figure 709.2.2A gives information on
the fire resistance ratings of floors which consist of
a base slab of concrete with a topping (overlap) of a
For S1: 1 in = 25.4 mm.
different type of concrete.

7.20 FLORIDA BUILDING CODE BUILDING


709.2.2.2.2 - FIGURE 709.2.2A

709.2.2.2.2 Figure 709.2.2B gives information on


thefireresistance ratings of roofs which consist of a
base slab of concrete with a topping (overlay) of an
insulating concrete or with an insulating board and
built-up roofing.
1. For the transfer of heat, three-ply built-up
roofing contributes 10 minutes to the fire
resistance rating; thus, 10 minutes can be
added to concrete assemblies such as those
shown in Figure 709.2.2B(a), (b) and (c), but
not to those shown in Figure 709.2.2B (d) and
(e).

709.2.2.3 Joints in precast slabs. Joints between adja-


cent precast concrete slabs may be ignored in calculat-
ing the slab thickness provided that a concrete topping
at least 1 inch (25.4 mm) thick is used. Where no con-
crete topping is used, joints must be grouted to a depth
of at least1/2the slab thickness at the joint, but not less
than 1 inch (25.4 mm), or the joints must be made fire
resistant by other approved methods.

FIGURE 709.2.2A
FIRE RESISTANCE FOR TWO-COURSE
CONCRETE FLOORS

For SI: 1 in. = 25.4 mm.

FLORIDA BUILDING CODE BUILDING 7.21


FIGURE 709.2.2B

FIGURE 709.2.2B
FIRE RESISTANCE RATINGS FOR CONCRETE ROOF ASSEMBLIES

For SI: 1 in. = 25.4 mm.

7.22 FLORIDA BUILDING CODE BUILDING


FIGURE 709.2.2B (continued)

FIGURE 709.2.2B (continued)


FIRE RESISTANCE RATINGS FOR CONCRETE ROOF ASSEMBLIES

For SI: 1 in. = 25.4 mm.

FLORIDA BUILDING CODE BUILDING 7.23


709.2.3 TABLE 709.2.3B

709.2.3 Concrete cover over reinforcement 709.2.3.2 Reinforced beam cover. The minimum
709.2.3.1 Slab cover. The minimum thickness of con- thickness of concrete cover to the positive moment
crete cover to the positive moment reinforcement is reinforcement (bottom steel) for reinforced concrete
given in Table 709.2.3A for reinforced concrete and beams is shown in Table 709.2.3C for fire resistance
Table 709.2.3B for prestressed concrete. These tables ratings of 1 hour to 4 hours.
are applicable for solid or hollow-core one-way or two-
way slabs with flat undersurfaces. Slabs may be cast- 709.2.3.3 Prestressed beam cover. The minimum
in-place or precast. For precast prestressed concrete not thickness of concrete cover in the positive moment pre-
covered elsewhere, the procedures contained in PCI stressing tendons (bottom steel) for prestressed con-
Design for Fire Resistance of Precast Prestressed crete beams is shown in Table 709.2.3D for fire resis-
Concrete shall be acceptable. tance ratings of 1 hour to 4 hours.

TABLE 709.2.3A
COVER THICKNESS FOR REINFORCED CONCRETE FLOOR
OR ROOF SLABS (in)

CONCRETE FIRE RESISTANCE RATING


AGGREGATE
TYPE RESTRAINED1 UNRESTRAINED1

1 hr 11/2 hr 2hr 3hr 4hr 1 hr 1 1 / 2 hr 2hr 3hr 4hr

3
Siliceous /4 3/4 3/4 3/4 3/4 3/4 3/4 l l1/4 l5/8

Carbonate 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 l1/4 l1/4

Sand-Light- 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 l1/4 l1/4
weight or
Lightweight

For SI: 1 in. = 25.4 mm.


Note:
1. See Table 701.3 for guidance on restrained and unrestrained assemblies.

TABLE 709.2.3B
COVER THICKNESS FOR PRESTRESSED CONCRETE FLOOR OR ROOF SLABS (In)

CONCRETE FIRE RESISTANCE RATING


AGGREGATE
TYPE RESTRAINED1 UNRESTRAINED1

1 hr 1 1 / 2 hr 2hr 3hr 4hr 1 hr 11/2hr 2hr 3hr 4hr

Siliceous 3/4 3/4 3/4 3/4 3/4 l1/8 11/2 13/4 23/8 23/4

Carbonate 3/4 3/4 3/4 3/4 3/4 1 13/8 15/8 21/8 21/4

Sand-Light- 3/4 3/4 3/4 3/4 3/4 1


13
/8 l'/2 2 21/4
weight or
Lightweight

For SI: 1 in = 25.4 mm.


Note:
I. See Table 701.3 for guidance on restrained and unrestrained assemblies.

7.24 FLORIDA BUILDING CODE BUILDING


TABLE 709.2.3C - TABLE 709.2.3D

TABLE 709.2.3C
MINIMUM COVER FOR MAIN REINFORCING BARS OF REINFORCED CONCRETE BEAMS:
(APPLICABLE TO ALL TYPES OF STRUCTURAL CONCRETE)

FIRE RESISTANCE RATING


R E S T R A I N E D OR BEAM
UNRESTRAINED1 WIDTH 2 (in.) 1 hr 11 1 / 2 hr 2hr 3hr 4hr

Restrained 5 -V4 3/4 3/4 1' 11/4


3
7 /4 3/4 3/4 3/4 3/4
>10 3/4 3/4 3/4 3/4 3/4

Unrestrained 5 3/4 1 11/4


7 3/4 3/4 3/4 13/4 3
2 10 3/4 3/4 3/4 1 13/4
For SI: 1 in = 25.4 mm.
Notes:
1. See Table 701.3 for guidance on restrained and unrestrained assemblies. Tabulated values for restrained assemblies apply to beams spaced more than
ft on centers. For restrained beams spaced 4 ft or less on centers, minimum cover of 3/4 inch is adequate for ratings of 4 hr or less.
2. For beam widths between the tabulated values, the minimum cover thickness can be determined by direct interpolation.
3. The cover for an individual reinforcing bar is the minimum thickness of concrete between the surface of the bar and the fire-exposed surface of the bean
For beams in which several bars are used, the cover for corner bars used in the calculation shall be reduced to one-half of the actual value. The covi
for an individual bar must be not less than one-half of the value given in Table 709.2.3C nor less than 3/4 inch.

TABLE 709.2.3D
MINIMUM COVER FOR PRESTRESSED CONCRETE BEAMS*6 . 7

RESTRAINED CONCRETE BEAM


OR AGGREGATE WIDTH3 FIRE RESISTANCE RATING
UNRESTRAINED 1 TYPE* (In.)
1 hr 11/2hr 2hr 3hr 4hr

1 1
Restrained Carb or Sil 8 1 /2 1 /2 1V2 1/3/41 2V2'
Carb or Sil 2 12 11/2 11/2 1
1 /2 P/2 17/8
Sand LW 8 11/2 1V2 1
1 /2 1V2 21
Sand LW >12 11/2 1V2 1
1 /2 1 /21 15/81

Unrestrained Carb or Sil 8 P/2 13/4 2V2 55


7
Carb or Sil > 12 P/2 l'/2 1 /8 2V2 3
Sand LW 8 11/2 1V2 2 31/2
Sand LW >12 1V2 11/2 15/8 2 2V2

For SI: I in = 25.4 mm.


Notes:
1. See Table 701.3 for guidance on restrained and unrestrained assemblies. Tabulated values for restrained assemblies apply to beams spaced more than 4
ft (1219 mm) on centers. For restrained beams spaced 4 ft () 219 mm) or less on centers, minimum cover of 3/4 inch (19 mm) is adequate for 4-hour rat-
ings or less.
2. Carb = carbonate aggregate concrete; Sil = siliceous aggregate concrete: Sand LW = sand-lightweight concrete.
3. For beam widths between 8 inches (203 mm) and 12 inches (305 mm), minimum cover thickness can be determined by direct interpolation.
4. The cover for an individual tendon is the minimum thickness of concrete between the surface of the tendon and the fire-exposed surface of the beam,
except that for ungrouted ducts the assumed cover thickness is the minimum thickness of concrete between the surface of the duct and the surface of the
beam. For beams in which several tendons are used, the cover is assumed to be the average of the minimum cover of individual tendons, where the min-
imum cover for corner tendons used in the calculation shall be reduced to one-half of the actual value. The cover for an individual tendon must be not
less than one-half of the value given in Table 709.2.3D nor less than 1 inch (25.4 mm).
5. Not practical for 8-inch (203 mm) wide beam but shown for purposes of interpolation.
6. For precast prestressed concrete not covered elsewhere, the procedures contained in PCI Design for Fire Resistance of Precast Prestressed Concrete shall
be acceptable.
7. The minimum cover for nonprestressed reinforcing in prestressed concrete beams shall be determined in accordance with the provisions of Table
709.2.3C.

FLORIDA BUILDING CODE BUILDING 7.25


709.2.4 - TABLE 709.3.1

709.2.4 Concrete columns 1. The fire resistance rating for the wall is equal to
709.2.4.1 Minimum size. Table 709.2.4 shows the or greater than the required rating of the column,
minimum overall dimensions of reinforced concrete and
columns for fire resistance ratings of 1 hour to 4 hours. 2. Openings in the wall are protected in accordance
with Table 705.1.2. and
TABLE 709.2.4
3. The main longitudinal reinforcing in the column
MINIMUM DIMENSION OF CONCRETE COLUMNS (in)
has cover not less than that required by
709.2.4.2.
FIRE RESISTANCE RATING
TYPES OF 709.2.4.4 Precast cover units for steel columns. See
CONCRETE 1 hr 11/2hr 2hr1 3hr1 4hr 2 709.5.1.4.
Siliceous 8 8 10 12 14 709.3 Concrete masonry
709.3.1 Concrete masonry walls
Carbonate 8 8 10 11 12
709.3.1.1 The fire resistance rating of walls and parti-
tions constructed of concrete masonry units shall be
Sand-Lightweight 8 8 9 10.5 12
determined from Table 709.3.1. The rating shall be
based on the equivalent thickness of the masonry and
For SI: 1 in. = 25.4 mm.
type of aggregate used.
Notes:
1. The minimum dimension is permitted to be reduced to 8 inches for rec- 709.3.1.2 Where plaster or gypsum wallboard is
tangular columns with two parallel sides at least 36 inches in length. applied to the side of the wall not exposed to fire, the
2. The minimum dimension is permitted to be reduced to 10 inches for contribution of the finish to the total fire resistance rat-
rectangular columns with two parallel sides at least 36 inches in length. ing shall be determined as follows: The thickness of
709.2.4.2 Minimum cover for R/C columns. The gypsum wallboard or plaster shall be corrected by mul-
minimum cover to the main longitudinal reinforcement tiplying the actual thickness of the finish by an applic-
in columns for fire resistance ratings of 1 hour, 11/2 able factor determined from Table 709.2.1.4A. This
hours, 2 hours and 3 hours shall be1 1 / 2 inches (38 corrected thickness of finish shall be added to the
mm); for 4 hours the minimum cover to the main lon- equivalent thickness of masonry and the fire resistance
gitudinal reinforcement shall be 2 inches (51 mm) for rating of the masonry and finish determined from Table
siliceous aggregate concrete and 11/2 inches (38 mm) 709.3.1.
for carbonate aggregate concrete or sand-lightweight
concrete. 709.3.1.3 Where plaster or gypsum wallboard is
applied to the fire-exposed side of the wall, the contri-
709.2.4.3 Columns built into walls. The minimum bution of the finish to the total fire resistance rating
dimensions of Table 709.2.4 do not apply to a rein- shall be determined as follows: The time assigned to
forced concrete column that is built into a concrete or the finish as established by Table 709.2.1.4B shall be
masonry wall provided all of the following are met: added to the fire resistance rating determined in
709.3.1.1 for the masonry alone, or in 709.3.1.2 for the
masonry and finish on the nonfire-exposed side.

TABLE 709.3.1
MINIMUM EQUIVALENT THICKNESS1 (in) OF BEARING
OR NONBEARING CONCRETE MASONRY WALLS2,3,4

FIRE RESISTANCE RATING (hours)

TYPE OF AGGREGATE 0.50 0.75 1 1.25 1.50 1.75 2 2.25 2.50 2.75 3 3.25 3.50 3.75 4

Pumice or Expanded Slag 1.5 1.9 2.1 2.5 2.7 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.5 4.7

Expanded Shale. Clay or Slate 1.8 2.2 2.6 2.9 3.3 3.4 3.6 3.8 4.0 4.2 4.4 4.6 4.8 4.9 5.1

Limestone, Cinders, or
Unexpanded Slag 1.9 2.3 2.7 3.1 3.4 3.7 4.0 4.3 4.5 4.8 5.0 5.2 5.5 5.7 5.9

Calcareous Gravel 2.0 2.4 2.8 3.2 3.6 3.9 4.2 4.5 4.8 5.0 5.3 5.5 5.8 6.0 6.2

Siliceous Gravel 2.1 2.6 3.0 3.5 3.9 4.2 4.5 4.8 5.1 5.4 5.7 6.0 6.2 6.5 6.7

For SI: 1 in. = 25.4 mm


Notes:
1. Equivalent thickness is the average thickness of the solid material in the unit. Determine the equivalent thickness in accordance with ASTM C 140.
2. Values between those shown in the table can be determined by direct interpolation.
3. Where combustible members are framed into the wall, the thickness of solid material between the end of each member and the opposite face of the wall,
or between members set in from opposite sides, shall not be less than 93% of the thickness shown in the table.
4. Requirements of ASTM C 55, ASTM C 73 or ASTM C 90 shall apply.

7.26 FLORIDA BUILDING CODE BUILDING


709.3.1.4-709.4.1.1

709.3.1.4 For a wall having no finish on one side or thickness of concrete masonry or concrete, or any combi-
having different types or thicknesses of finish on each nation thereof, covering the main reinforcing bars, as
side, the calculation procedures of this section shall be determined according to Table 709.3.4, or by approved
performed twice, i.e., assume that either side may be alternate methods.
the fire-exposed side of the wall. The fire resistance
rating of the wall shall not exceed the lower of the two TABLE 709.3.4
values calculated. MINIMUM COVER OF LONGITUDINAL
REINFORCEMENT IN FIRE RESISTANCE RATED
Exception: For exterior walls with more than 5 ft REINFORCED CONCRETE MASONRY LINTELS (in)
(1524 mm) of horizontal separation, the fire shall be
assumed to occur on the interior side only. NOMINAL WIDTH OF FIRE RESISTANCE RATING
LINTEL (inches)
1 hr 2hr 3hr 4hr
709.3.1.5 When the finish applied to a concrete mason-
1
ry wall contributes to the fire resistance rating, the 6 1 /2 l'/2
masonry alone shall provide not less than 1/2 the total 8 11/2 |l/2 13/4 3
required fire resistance rating. 10 or greater 11/2 l'/2 11/2 13/4
709.3.1.6 Installation of finishes shall be as follows: For S1: 1 in. = 25.4 mm.
1. Gypsum wallboard and gypsum lath applied to
concrete masonry or concrete walls shall be 709.3.5 Concrete masonry columns. Concrete masonry
secured to wood or steel furring members spaced columns shall be designed (and reinforced) in accordance
not more than 16 inches (406 mm) o.c. with applicable requirements of this code. The fire resis-
2. Gypsum wallboard shall be installed with the tance rating shall be determined based on the least plan
long dimension parallel to the furring members dimension of the column in accordance with Table
and shall have all joints finished. 709.3.5 or by approved alternate methods.
3. Other aspects of the installation of finishes shall
comply with the applicable provisions of TABLE 709.3.5
Chapter 7 and Chapter 25. MINIMUM DIMENSION (in) OF
CONCRETE MASONRY COLUMNS

709.3.2 Filled core spaces. The equivalent thickness of FIRE RESISTANCE RATING
filled hollow concrete masonry is the actual thickness of
the unit when loose fill materials are: sand, pea gravel, 1 hr 2hr 3hr 4hr
crushed stone or slag that meet ASTM C 33 requirements;
8 10 12 14
pumice, scoria, expanded shale, expanded clay, expanded
slate, expanded slag, expanded fly ash or cinders in com- For SI: 1 in. = 25.4 mm.
pliance with ASTM C 331; perlite or vermiculite that
complies with ASTM C 332 requirements. 709.4 Clay brick and tile masonry
709.4.1 Masonry walls
709.3.3 Multiwythe masonry walls. The fire resistance 709.4.1.1 The fire resistance ratings of single or multi-
rating of wall assemblies constructed of multiple wythes wythe walls or partitions constructed of solid or hollow
of masonry materials may be based upon the fire resis- clay masonry units shall be determined from Table
tance rating period of each wythe and the continuous air 709.4.1 A or Table 709.4.1B. The equivalent thickness
space between each wythe in accordance with the follow- of the clay masonry unit shall be determined by
ing formula: Equation 709.4.1.1 when using Table 709.4.1 A. The
RA = (R 1 0 . 5 9 + R20.59 + ... +Rn
0.59 fire resistance rating determined from Table 709.4.1 A
+ A 1 + A 2 + ... +A n ) 1 . 7 (EQ. 709.3.3) shall be permitted to be used in the calculated fire
resistance rating procedure in 709.4.2.
where
RA = Fire endurance rating of the TE =V n /LH (Eq. 709.4.1.1)
assembly, hours
R1, R 2 ,..., Rn = Fire endurance rating of wythes where:
for 1, 2, ...n (hours), respectively T E = the equivalent thickness of the clay masonry
A1 A2, ..... An = 0.30, factor for each continuous
air space for 1, 2, ...n, respective- unit, inches;
ly, having a depth of 1/2 inch Vn = the net volume of the clay masonry unit, in3;
(12.7 mm) or more between L = the specified length of the clay masonry unit,
wythes. inches;
709.3.4 Concrete masonry lintels. Fire resistance ratings H = the specified height of the clay masonry unit,
for concrete masonry lintels shall be determined based on inches.
the nominal thickness of the lintel and the minimum

FLORIDA BUILDING CODE BUILDING 7.27


TABLE 709.4.1 A - 709.4.1.2

TABLE 709.4.1 A
FIRE RESISTANCE PERIODS OF CLAY BRICK AND TILE MASONRY WALLS

MINIMUM REQUIRED EQUIVALENT THICKNESS FOR FIRE RESISTANCE1,2,3


MATERIAL TYPE (in.)

1 hr 2hr 3hr 4hr

Solid brick of clay or shale4 2.7 3.8 4.9 6.0

Hollow brick or tile of clay or shale,


unfilled 2.3 3.4 4.3 5.0

Hollow brick or tile of clay or shale,


grouted or filled with materials
specified in 709.4.1.1.3 3.0 4.4 5.5 6.6

Notes:
l. Equivalent thickness as determined from 709.4.1.1.
2 Calculated fire resistance between the hourly increments listed shall be determined by linear interpolation.
3 Where combustible members are framed in the wall, the thickness of solid material between the end of each member and the opposite face of the wall.
or between members set in from opposite sides, shall not be less than 93 percent of the thickness shown.
4. For units in which the net cross-sectional area of cored brick in any plane parallel to the surface containing the cores is at least 75 percent of the gross
cross-sectional area measured in the same place.

709.4.1.1.1 The equivalent thickness, T E , shall be the Values for R n 0.59 for use in Equation 709.4.1.2 are
value obtained for hollow clay units as determined in given in Table 709.4.1C. Coefficients for thickness of
accordance with ASTM C 67. plaster shall be selected from Table 709.4.1D based on
the actual thickness of plaster applied to the wall or
709.4.1.1.2 The equivalent thickness of solid grouted partition and whether one or two sides of the wall are
clay masonry units shall be taken as the actual thick- plastered.
ness of the units.

709.4.1.1.3 The equivalent thickness of hollow clay


masonry units is the actual thickness of the unit when
completely filled with loose fill materials of: sand, pea
gravel, crushed stone or slag that meets ASTM C 33
requirements; pumice, scoria, expanded shale, expand-
ed clay, expanded slate, expanded slag, expanded fly
ash or cinders in compliance with ASTM C 331; or per-
lite or vermiculite meeting the requirements of ASTM
C 549 and ASTM C 516, respectively.

709.4.1.2 Where plaster is applied to the wall, the total


fire resistive rating shall be determined by the formula:
R= (Rn0.59 + p1) 1.7 (Eq. 709.4.1.2)

where
R= the fire endurance of the assembly, hours;
R n = t h e fire endurance of the individual wall,
hours;
p1 = coefficient for thickness of plaster.

7.28 FLORIDA BUILDING CODE BUILDING


TABLE 709.4.1 B - TABLE 709.4.1 C

TABLE 709.4.1 B
FIRE RESISTANCE RATINGS FOR BEARING STEEL FRAMED
BRICK VENEER WALLS OR PARTITIONS

WALL OR PARTITION ASSEMBLY PLASTER SIDE BRICK FACED


EXPOSED SIDE EXPOSED
(hr) (hr)

Outside facing of steel studs:


1
/2-in wood fiberboard sheathing next
to studs, 3/4-in air space formed with
3
EXPOSED
/ 4 x l5/8-in wood strips placed over (hr) SIDE EXPOSED
the fiberboard and secured to the (hr)
studs; metal or wire lath nailed to
such strips, 33/4-in brick veneer 11/2 4
held in place by filling 3/4-in air
space between the brick and lath with
mortar.
Inside facing of studs: 3/4-in
unsanded gypsum plaster on metal or
wire lath attached to 5 / i6 -in wood
strips secured to edges of the studs.

Outside facing of steel studs: 1-in


insulation board sheathing attached to
studs, 1-in air space, and 33/4-in brick
veneer attached to steel frame with
metal ties every 5th course.
Inside facing of studs: 7/8-in sanded gypsum 11/2 4
plaster (1:2 mix) applied on metal
or wire lath attached directly to
the studs.

Same as above except use 7/8-in


vermiculitegypsum plaster or
1-in sanded gypsum plaster (1:2 mix) 2 4
applied to metal or wire.

Outside facing of steel studs:


1
/2-in gypsum sheathing board, attached
to studs, and 33/4-in brick veneer
attached to steel frame with metal
ties every 5th course.
Inside facing of studs: 1/2-in sanded gypsum
plaster (1:2 mix) applied to 1/2-in perforated 2 4
gypsum lath securely attached to studs
and having strips of metal lath 3-in
wide applied to all horizontal joints
of gypsum lath

For S1: 1 inch = 25.4 mm.

TABLE 709.4.1 C
VALUES OF Rn0.59
(FOR USE IN EQUATION 709.4.1.2, 709.4.1.3 OR 709.4.2)
0.59
R, HOURS Rn

1 1.0
2 1.50
3 1.91
4 2.27

FLORIDA BUILDING CODE BUILDING 7.29


TABLE 709.4.1 D - 709.5.1.1.1

TABLE 709.4.1 D 709.4.2.2 For walls which consist of 2 or more wythes


COEFFICIENTS FOR PLASTER1 of different materials (concrete or concrete masonry
units) in combination with clay masonry units, the fire
THICKNESS OF PLASTER, (In) ONE SIDE TWO SIDE resistance rating of the different materials shall be per-
mitted to be determined from Table 709.2.1.1 for con-
>/2 (12.7 mm) 0.3 0.6 crete; Table 709.3.1 for concrete masonry units or
5/8 (15.9 mm) 0.37 0.75 Table 709.4.1 A, or 709.4. IB for clay, brick and tile
3
/ 4 (19.1 mm) 0.45 0.90 masonry units.
Note:
1. Values listed in table are for 1:3 sanded gypsum plaster.
709.4.3 Reinforced clay masonry lintels. Fire resistance
ratings for clay masonry lintels shall be determined based
709.4.1.3 Where a continuous air space separates mul- on the nominal width of the lintel and the minimum cov-
tiple wythes of the wall or partition, the total fire resis- ering for the longitudinal reinforcement in accordance
tance rating shall be determined by the formula: with Table 709.4.3.

R = (R10.59 + R20.59 + ...+Rn0.59 + as) 1.7 (Eq. 709.4.1.3) TABLE 709.4.3


REINFORCED CLAY MASONRY LINTELS
where
MINIMUM LONGITUDINAL
R = the fire endurance of the assembly, REINFORCEMENT COVER FOR
hours; FIRE RESISTANCE (In)
R 1 , R 2 and Rn = the fire endurance of the
individual wythes, hours; NOMINAL LINTEL WIDTH, (In) 1 hr 2hr 3hr 4hr
as = coefficient for continuous air
space. 6 11/2 2 NP NP

Values forRn0.59 for use in Equation 709.4.1.3 are 8 11/2 11/2 13/4 3
given in Table 709.4.1C. The coefficient for each con- 11/2
tinuous air space of 1/2 inch to 3 1/2 inch (12.7 to 89 10 or more 11/2 1V2 13/4
mm) separating two individual wythes shall be 0.3.
For SI: 1 inch = 25.4 mm.
NP = Not permitted.
709.4.1.4 For a wall having no finish on one side or
having different types or thicknesses of finish on each
side, the calculation procedures of this section shall be 709.4.4 Reinforced clay masonry columns. The fire
performed twice, i.e., assume that either side may be resistance ratings shall be determined based on the least
the fire-exposed side of the wall. The fire resistance of plan dimension of the column in accordance with Table
the wall shall not exceed the lower of the two values 709.4.4. The minimum cover for longitudinal reinforce-
determined. ment shall be 2 inches (51 mm).

Exception: For exterior walls with more than 5 ft TABLE 709.4.4


(1524 mm) of horizontal separation, the fire shall be REINFORCED CLAY MASONRY COLUMNS
assumed to occur on the interior side only.
FIRE RESISTANCE RATING
709.4.2 Multiwythe walls.
1 hr 2 hr 3 hr 4 hr
709.4.2.1 The fire resistance rating for walls or parti-
tions consisting of two or more dissimilar wythes shall Minimum Column 8 10 12 14
be permitted to be determined by the formula: Dimension, in

R = (R10.59 + R20.59 + ...+Rn0.59 + as) 1.7 (Eq 709.4.2) For SI: 1 inch = 25.4 mm

where
709.5 Steel assemblies
R = the fire endurance of the assembly, 709.5.1 Structural steel columns
hours; 709.5.1.1 General
R 1 , R 2 and Rn = the fire endurance of the individ- 709.5.1.1.1 These procedures establish a basis foi
ual wythes, hours. determining the fire resistance of column assem-
blies as a function of the thickness of fire resistanl
Values for Rn0.59 for use in Equation 709.4.2 are material and, the weight, W, and heated perimeter.
given in Table 709.4.1C. D, of steel columns. As used in these sections, W is
the average weight of a structural steel column ir
pounds per linear foot. The heated perimeter, D, is

7.30 FLORIDA BUILDING CODE BUILDING


709.5.1.1.2-709.5.1.2.1

the inside perimeter of the fire resistant material in D = heated perimeter of the structural
inches as illustrated in Figure 709.5.1 A. steel column (inches), and
W = total weight of the structural steel col-
umn and gypsum wallboard protection
709.5.1.1.2 The application of these procedures
shall be limited to column assemblies in which the (pounds per linear foot).
fire resistant material is not designed to carry any of or, W = W+ 50hD/144
the load acting on the column.

709.5.1.1.3 In the absence of substantiating fire


endurance test results, ducts, conduit, piping and
similar mechanical, electrical and plumbing instal-
lations shall not be embedded in any required fire
resistant materials.

FIGURE 709.5.1 A
DETERMINATION OF THE HEATED PERIMETER
OF STRUCTURAL STEEL COLUMNS

For SI: I in. = 25.4 mm.

709.5.1.1.4 Table 709.5.1 A contains weight to


heated perimeter ratios (W/D) for both contour and
box fire resistant profiles, for the wide flange
shapes most often used as columns. For different
fire resistant protection profiles or column cross
sections, the weight to heated perimeter ratios
(W/D) shall be determined in accordance with the
definitions given in this section.

709.5.1.2 Gypsum wallboard protection.


709.5.1.2.1 The fire resistance of structural steel
columns with weight to heated perimeter ratios
(W/D) less than or equal to 3.65 and which are pro-
tected with Type X gypsum wallboard may be
determined from the following expression:

where
R = fire resistance (minutes),
h = total thickness of gypsum wallboard
(inches),

FLORIDA BUILDING CODE BUILDING 7.31


TABLE 709.5.1A

TABLE 709.5.1A
W/D RATIOS FOR STEEL COLUMNS

STRUCTURAL CONTOUR BOX STRUCTURAL CONTOUR BOX


SHAPE PROFILE PROFILE SHAPE PROFILE PROFILE

W14x233 2.49 3.65 W10xll2 1.78 2.57


x 211 2.28 3.35 x 100 1.61 2.33
xl93 2.10 3.09 x 88 1.43 2.08
x 176 1.93 2.85 x 77 1.26 1.85
xl59 1.75 2.60 x 68 1.13 166
xl45 1.61 2.39 x 60 1.00 1.48
xl32 1.52 2.25 x 54 0.91 1.34
xl20 1.39 2.06 x 49 0.83 1.23
x 109 1.27 1.88 x 45 0.87 1.24
x 99 1.16 1.72 x 39 0.76 1.09
x 90 1.06 1.58 x 33 0.65 0.93
x 82 1.20 1.68
x 74 1.09 1.53 W8x67 1.34 1.94
x 68 1.01 1.41 x58 1.18 1.71
x 61 0.91 1.28 x48 0.99 1.44
x 53 0.89 1.21 x40 0.83 1.23
x 48 0.81 1.10 x35 0.73 1.08
x 43 0.73 0.99 x 31 0.65 0.97
x 28 0.67 0.96
WI2x 190 2.46 3.51 x 24 0.58 0.83
xl70 2.22 3.20 x 21 0.57 0.77
x 152 2.01 2.90 x 18 0.49 0.67
x 136 1.82 2.63
x 120 1.62 2.36 W6 x 25 0.69 1.00
x 106 1.44 2.11 x20 0.56 0.82
x 96 1.32 1.93 x 16 0.57 0.78
x 87 1.20 1.76 x 15 0.42 0.63
x 79 1.10 1.61 xl2 0.43 0.60
x 72 1.00 1.48 x 9 0.33 0.46
x 65 0.91 1.35
x 58 0.91 1.31 W5 x 19 0.64 0.93
x 53 0.84 1.20 xl6 0.54 0.80
x 50 0.89 1.23
x 45 0.81 1.12 W4x 13 0.54 0.79
x 40 0.72 1.00

For SI: I plf/in = 0.059 kg/m/mm.

7.32 FLORIDA BUILDING CODE BUILDING


709.5.1.2.2-709.5.1.2.3

709.5.1.2.2 The gypsum wallboard shall be support-


ed as illustrated in either Figure 709.5.1B for fire
resistance ratings of four (4) hours or less, or Figure
709.5.1C for fire resistance ratings of three (3)
hours or less.

FIGURE 709.5.1 C
GYPSUM WALLBOARD PROTECTED STRUCTURAL STEEL
COLUMNS WITH STEEL STUD/SCREW ATTACHMENT SYSTEM

FIGURE 709.5.1 B For SI: 1 in. = 25.4 mm.


GYPSUM WALLBOARD PROTECTED STRUCTURAL STEEL
COLUMNS WITH SHEET STEEL COLUMN COVERS Notes:
1. Structural steel column, either wide flange or tubular shapes.
For SI: 1 in. = 25.4 mm. 2. l 5 / 8 inch (41.3 mm) deep studs fabricated from 0.0179 inch (0.46
mm) minimum thickness galvanized steel with l5/16-or l7/16-inch
Notes: (33.3 or 36.5 mm) legs. The length of the steel studs shall be 1/2 inch
1. Structural steel column, either wide flange or tubular shapes. (12.7 mm) less than the height of the assembly.
2. Type X gypsum wallboard in accordance with ASTM C 36. For sin- 3. Type X gypsum wallboard in accordance with ASTM C 36. For sin-
gle layer applications the wallboard shall be applied vertically with gle layer applications the wallboard shall be applied vertically with
no horizontal joints. For multiple layer application, horizontal joints no horizontal joints. For multiple layer applications, horizontal joints
are permitted at a minimum spacing of 8 ft (2438 mm) provided that are permitted at a minimum spacing of 8 ft (2438 mm) provided that
the joints in successive layers are staggered at least 12 inches (305 the joints in successive layers are staggered at least 12 inches (305
mm). The total required thickness of wallboard shall be determined mm). The total required thickness of wallboard shall be determined
on the basis of the specified fire resistance rating and the weight to on the basis of the specified fire resistance rating and the weight-to-
heated perimeter ratio (W/D) of the column. For fire resistance rat- heated-perimeter ratio (W/D) of the column.
ings of 2 hours or less, one of the required layers of gypsum wall- 4. Galvanized 0.0149 inch (0.378 mm) minimum thickness steel corner
board may be applied to the exterior of the sheet steel column covers beads with 1 1/2inch (38.1 mm) legs attached to the wallboard with 1
with 1 inch (25.4 mm) long Type S screws spaced 1 inch (25.4 mm) inch (25.4 mm) long, Type S screws spaced 12 inches (305 mm) on
from the wallboard edge and 8 inches (203 mm) on center. For such center.
installations, 0.0149 inch (0.378 mm) minimum thickness galvanized 5. No. 18 SWG steel tie wires spaced 24 inches (610 mm) on center.
steel corner beads with 1 1/2-inch (38 mm) legs shall be attached to 6. Sheet metal angles with 2-inch legs fabricated from 0.0209 inch
the wallboard with Type S screws spaced 12 inches (305 mm) on (0.531 mm) minimum thickness galvanized steel.
center. 7. Type S screws 1 inch (25.4 mm) long shall be used for attaching the
3. For the resistance ratings of 3 hours or less, the column covers shall first layer of wallboard to the steel studs and the third layer to the
be fabricated from 0.0239 inch (0.607 mm) minimum thickness gal- sheet metal angles at 24 inches (610 mm) on center. Type S screws 1
3
vanized or stainless steel. For 4 hour fire resistance ratings, the col- / 4 inches (44.5 mm) long shall be used for attaching the second layer
umn covers shall be fabricated from 0.0239 inch (0.607 mm) mini- of wallboard to the steel studs and the fourth layer to the sheet metal
mum thickness stainless steel. The column covers shall be erected angles at 12 inches (305 mm) on center. Type S screws 21/4 inches
with the snap lock or Pittsburgh joint details. (57.2 mm) long shall be used for attaching the third layer of wall-
For fire resistance ratings of 2 hours or less, column covers fabricat- board to the steel studs at 12 inches (305 mm) on center.
ed from 0.0269 inch minimum thickness galvanized or stainless steel
may be erected with lap joints. The lap joints may be located any- 709.5.1.2.3 The fire resistance of structural steel
where around the perimeter of the column cover. The lap joints shall columns can be determined from Figure 709.5.ID
be secured with 1/2 inch (12.7 mm) long No. 8 sheet metal screws
spaced 12 inches (305 mm) on center. for various thicknesses of gypsum wallboard as a
The column covers shall be provided with a minimum expansion function of the weight to heated perimeter ratio
clearance of 1/8 inch per linear foot (10.4 mm/m) between the ends (W/D) of the column. For structural steel columns
of the cover and any restraining construction. with weight to heated perimeter ratios (W/D)
greater than 3.65, the thickness of gypsum wall-
board required for specified fire resistance ratings
shall be the same as the thickness determined for a
W14 x 233 wide flange shape.

FLORIDA BUILDING CODE BUILDING 7.33


FIGURE 709.5.1 D 709.5.1.4.1

709.5.1.3.3 Spray-applied fire resistant materials shall


be identified by density and thickness required for a
given fire resistance rating.

FIGURE 709.5.1 E
WIDE FLANGE STRUCTURAL STEEL COLUMNS WITH
SPRAY-APPLIED FIRE RESISTANT MATERIALS

709.5.1.4 Concrete protected columns


709.5.1.4.1 The fire resistance of structural steel
FIGURE 709.5.1 D columns protected with concrete, as illustrated in
FIRE RESISTANCE OF STRUCTURAL STEEL COLUMNS' Figure 709.5.1IF (a) and (b), may be determined from
PROTECTED WITH VARIOUS THICKNESSES OF TYPE X the following expression:
GYPSUM WALLBOARO

For SI: 1 in. = 25.4 mm, 1 plf/in. = 0.059 kg/m/mm.


Note:
I. The W/D ratios for typical wide flange columns are listed in Table
709.5 1 A. For other column shapes, the W/D ratios shall be deter-
mined in accordance with 709.5.1.1.

709.5.1.3 Spray-Applied Are resistant materials As used in these expressions:


709.5.1.3.1 The fire resistance of wide flange structur- R = fire endurance at equilibrium moisture
al steel columns protected with spray-applied fire conditions (minutes)
resistant materials, as illustrated in Figure 709.5. IE, R0 = fire endurance at zero moisture content
may be determined from the following expression: (minutes)
m = equilibrium moisture content of the con-
R= [C, (W/D) + C2] h
crete by volume (percent)
where W = average weight of the steel column (pounds
R = fire resistance (minutes), per linear foot)
h = thickness of spray-applied fire resis D = heated perimeter of the steel column
tant material (inches), (inches)
D = heated perimeter of the structural h = thickness of the concrete cover (inches)
steel column (inches), kc = ambient temperature thermal conductivity
C1 and C2 = material-dependent constants, and of the concrete (Btu/hr ft F)
W = weight of structural steel column H = ambient temperature thermal capacity of
(pounds per linear foot)
the steel column = 0.11 W (Btu/ ft F)
709.5.1.3.2 The material-dependent constants, C1 and pc = concrete density (pounds per cubic foot)
C2, shall be determined for specific fire resistant mate- cf = ambient temperature specific heat of
rials on the basis of standard fire endurance tests in concrete (Btu/lb F)
accordance with 701. Unless evidence is submitted to L = interior dimension of one side of a square
the building official substantiating a broader applica- concrete box protection (inches)
tion, this expression shall be limited to determining the
fire resistance of structural steel columns with weight
to heated perimeter ratios (W/D) between the largest
and smallest columns for which standard fire
endurance test results are available.

7.34 FLORIDA BUILDING CODE BUILDING


709.5.1.4.2 TABLE 709.5.1 B

709.5.1.4.2 For wide flange steel columns completely


encased in concrete with all re-entrant spaces filled
(Figure 709.5. lF(c)), the thermal capacity of the con-
crete within the re-entrant spaces may be added to the
thermal capacity of the steel column, as follows:

where
bf = flange width of the steel column
(inches),
d = depth of the steel column (inches),
and
As = cross-sectional area of the steel column FIGURE 709.5.1 F
(square inches). CONCRETE PROTECTED STRUCTURAL STEEL COLUMNS 1
709.5.1.4.3 If specific data on the properties of con- Notes:
crete is not available, the values given in Table 1. When the inside perimeter of the concrete protection is not square, L
shall be taken as the average of L1 and L2. When the thickness of
709.5.IB may be used. concrete cover is not constant, h shall be taken as the average of h1
and h2.
709.5.1.4.4 For structural steel columns encased in 2. Joints shall be protected with a minimum 1 inch (25.4 mm) thickness
concrete with all re-entrant spaces filled (Figure of ceramic fiber blanket but in no case less than one-half the thick-
709.5.1F(c)), Tables 709.5.1C and 709.5.1D give the ness of the column cover (See 709.2.1.3).
thickness of concrete cover required for various fire
resistance ratings for typical wide flange sections. The 709.5.1.4.5 For structural steel columns protected with
thicknesses of concrete given in these tables also apply precast concrete column covers as shown in Figure
to structural steel columns larger than those listed. 709.5. lF(a), Table 709.5.1E gives the thickness of the
column covers required for various fire resistance rat-
ings for typical wide flange shapes. The thicknesses of
concrete given in these tables also apply to structural
steel columns larger than those listed.

TABLE 709.5.1 B
PROPERTIES OF CONCRETE

FLORIDA BUILDING CODE BUILDING 7.35


TABLE 709.5.1 C - TABLE 709.5.1 D

TABLE 709.5.1C TABLE 709.5.1D


MINIMUM COVER (in.) FOR STEEL COLUMNS MINIMUM COVER (in.) FOR STEEL COLUMNS
ENCASED IN NORMAL WEIGHT CONCRETE1 ENCASED IN STRUCTURAL LIGHTWEIGHT CONCRETE1
(FIGURE 709.5.1F(C)) (FIGURE 709.5.1F(C))

Fire Resistance Rating (hr) FIRE RESISTANCE RATING (hr)


Structural STRUCTURAL
Shape 1 11/2 2 3 4 SHAPE 1 11/2 2 3 4

2 1
W14 x 233 1 11/2 W14 x 233 11/2
x 176 x 193
x 132 1 21/2 x 74 1 1 1 2
x 90 1 2 x 61
x 61 11/2 x 43 11/2 2 2'/2
x 48 3
x 43 11/2 21/2 W12 x 65 11/2 2
x 53 1 1 1
W12 x 152 1 21/2 x 40 11/2 2 21/2
x 96 1 2
x 65 1 \V10 x 112 2
x 50 11/2 3 x 88 1 1 11/2
x 40 11/2 21/2 x 60 1
x 33 11/2 2 21/2
W10 x 88 1 2
x 49 3 W8 x 35 21/2
x 45 1 11/2 11/2 x 28 1 1 2
x 39 31/2 x 24 11/2 3
1
x 33 2 x 18 1 /2 21/2

\V8 x 67 1 3
x 58 l1/2 For SI: 1 in. = 25.4 mm.
x 48 1 21/2 Note:
x 31 11/2 31/2 1. The tabulated thicknesses are based on the assumed properties of
x 21 2 structural lightweight concrete given in Table 709.5.1B.
x 18 3 4

31/2
1
W6 x 25 1 /2 2
x 20 3
x 16 1 2 4
x 15
x 9 11/2 21/2 31/2

For SI: I in. = 25.4 ram.


Note:
1. The tabulated thicknesses are based on the assumed properties of
normal weight concrete given in Table 709.5.1B.

2'/2

7.36 FLORIDA BUILDING CODE BUILDING


TABLE 709.5.1E - TABLE 709.5.1F

TABLE 709.5.1E TABLE 709.5.1F


MINIMUM COVER (in.) FOR STEEL COLUMNS MINIMUM COVER (in.) FOR STEEL COLUMNS
IN NORMAL WEIGHT PRECAST COVERS1 IN STRUCTURAL LIGHTWEIGHT PRECAST COVERS1
(FIGURE 709.5.1F(A))
(FIGURE 709.5.1F(A))
FIRE RESISTANCE RATING (hr)
FIRE RESISTANCE RATING (hr)
STRUCTURAL
1 Structural
SHAPE 1 1 /2 2 3 4
Shape 1 11/2 2 3 4
W14 x 233 3 21/2
1 1 W14 x 233
x 211 1 /2 2 /2
x 176 2
x 176 31/2
1 x 145 11/2
x 145 1 /2 2 x 132 3
x 109 11/2 3 x 109 11/2 11/2
x 99
x 99 21/2
x 61 4
x 68 2
x 43 2 21/2 31/2 41/2
x 43 3 31/2

W12 x 190 11/2


W12 x 190 21/2
x 152 21/2 21/2 2
x 152
x 120 11/2 2
1
x 136 11/2
x 96 1 /2 3 x 106 3
x 87 4
x 96 11/2 11/2 21/2
x 58
x 87
x 40 2 21/2 31/2 41/2 x 65 2
1
1
x 40 3 31/2
W10 x 112 3 /2
x 88 11/2 2 3 W10 x 112 2
1
x 77 1 /2 4 4 x 100 11/2 3
x 54 2 21/2 31/2 x 88
x 33 41/2 x 77 11/2 11/2 21/2
x 60 2
W8 x 67 11/2 2 3 x 39 3 31/2
x 58 4 x 33 2
x 48 11/2
1 2 21/2 31/2
x 28 W8 x 67 11/2 21/2 3
1 1
x 21 4 /2 x 48 1 /2
x 18 21/2 3 4 x 35 11/2 2 31/2
x 28 3
W6x 25 2 21/2 31/2 x 18 2 21/2 4
x 20 11/2 41/2
x 16 3 W6 x 25 2 3 31/2
1
x 12 2 2 /2 4 4
x 15 1
1 /2 2
x 9 5 x 9 21/2 31/2 4

For SI: 1 in. = 25.4 mm. For SI: 1 in. = 25.4 mm.

Note: Note:
1. The tabulated thicknesses are based on the assumed properties of 1. The tabulated thicknesses are based on the assumed properties of
normal weight concrete given in Table 709.5.1B. structural lightweight concrete given in Table 709.5.1B.

FLORIDA BUILDING CODE BUILDING 7.37


709.5.1.4.6-709.5.2.1.3

709.5.1.4.6 The fire resistance of structural steel


columns protected with concrete masonry units or
clay masonry units, as illustrated in Figure
709.5.1G, shall be permitted to be determined from
the following expression:

where
R = fire resistance rating of column assembly,
hours FIGURE 709.5.1 G
W = average weight of steel column, pounds per CONCRETE OR CLAY MASONRY PROTECTED
ft STRUCTURAL STEEL COLUMNS
D = heated perimeter of steel column, inches Notes:
(see Figure 709.5.1G) d = depth of a wide flange column, outside diameter of pipe
column, or outside dimension of structural tubing column.
Te = equivalent thickness of concrete or clay inches
masonry unit, inches (see Table 709.3.1 t
web = thickness of web of wide flange column, inches
footnote 1 or 709.4.1) w = width of flange of wide flange column, inches
K = thermal conductivity of concrete or clay
masonry unit, Btu/hr ft F 709.5.2 Structural steel beams and girders.
(see Table 709.5.1G) 709.5.2.1 Determination offireresistance
As = cross-sectional area of steel column, square 709.5.2.1.1 These procedures establish a basis for
inches determining the fire resistance of structural steel
dm = density of the concrete or clay masonry unit, beams and girders which differ in size from that
lb per cu ft specified in approved fire resistant assemblies as a
p = inner perimeter of concrete or clay masonry function of the thickness of fire resistant material
protection, inches (see Figure 709.5.1G) and the weight, W, and heated perimeter, D, of the
beam or girder. As used in these sections, W is the
average weight of a structural steel member in lbs
TABLE 709.5.1 G per linear ft. The heated perimeter, D, is the inside
THERMAL CONDUCTIVITY OF CONCRETE OR CLAY perimeter of the fire resistant material in inches as
MASONRY UNITS illustrated in Figure 709.5.2.
DENSITY (d m ) OF UNITS THERMAL CONDUCTIVITY (K) 709.5.2.1.2 The weight to heated perimeter ratios
(lb/ft3) OF UNITS (W/D), for both contour and box fire resistant pro-
(Btu/hr ft F) tection profiles, for the wide flange shapes most
often used as beams or girders are given in Table
Concrete Masonry Units 709.5.2. For different shapes, the weight to heated
80 0.207
perimeter ratios (W/D) shall be determined in
85 0.228
90 0.252
accordance with the definitions given in this sec-
tion.
95 0.278
100 0.308 709.5.2.1.3 Except as provided for in 709.5.2.2,
105 0.340 structural steel beams in approved fire resistant
assemblies shall be considered the minimum per-
no 0.376 missible size. Other beam or girder shapes may be
115 0.416 substituted provided that the weight to heated
120 0.459 perimeter ratio (W/D) of the substitute beam is
equal to or greater than that of the beam specified in
125 0.508 the approved assembly.
130 0.561
135 0.620

140 0.685
145 0.758
150 0.837
Clay Masonry Units
120 1.25
130 2.25 |

For SI: 1 lb/ft3 = 16.0185 kg/m3. Btu/hr ft F = 1.731 W/(m K).

7.38 FLORIDA BUILDING CODE BUILDING


TABLE 709.5.2 FIGURE 709.5.2

TABLE 709.5.2 TABLE 709.5.2 (continued)


WEIGHT TO HEATED PERIMETER RATIOS (W/D) WEIGHT TO HEATED PERIMETER RATIOS (W/D)
FOR TYPICAL WIDE FLANGE BEAM AND GIRDER SHAPES FOR TYPICAL WIDE FLANGE BEAM AND GIRDER SHAPES

Structural Contour Box Structural Contour Box Structural Contour Box Structural Contour Box
Shape Profile Profile Shape Profile Profile Shape Profile Profile Shape Profile Profile

W36 x 300 2.47 3.33 x 93 1.38 1.80 x58 1.08 1.69 x 15 0.48 0.63
x280 2.31 3.12 x 83 1.24 1.62 x53 0.99 1.55 x 12 0.38 0.51
x260 2.16 2.92 x 73 1.10 1.44 x50 1.04 1.54
x245 2.04 2.76 x 68 1.03 1.35
x45 0.95 1.40 W8x67 1.61 2.55
x230 1.92 2.61 x 62 0.94 1.23
x210 1.94 2.45 x 57 x40 0.85 1.25 x58 1.41 2.26
0.93 1.17
x 194 1.80 2.28 x 50 0.83 1.04 x35 0.79 1.11 x48 1.18 1.91
xl82 1.69 2.15 x 44 0.73 0.92 x30 0.69 0.96 x40 1.00 1.63
xl70 1.59 2.01 x26 0.60 0.84 x35 0.88 1.44
x 160 1.50 1.90 W18xll9 1.69 2.42 x22 0.61 0.77 x31 0.79 1.29
x 150 1.41 1.79 x 106 1.52 2.18 x!9 0.53 0.67 x28 0.80 1.24
x 135 1.28 1.63 x 97 1.39 2.01 x 16 0.45 0.57 x24 0.69 1.07
x 86 1.24 1.80 x 14 0.40 0.50 x21 0.66 0.96
W33 x 241 2.11 2.86 x 76 1.11 1.60
x 18 0.57 0.84
x221 1.94 2.64 x 71 1.21 1.59
x201 1.78 2.42 W l 0 x 112 2.14 3.38 xl5 0.54 0.74
x 65 1.11 1.47
x 152 1.51 1.94 x 60 1.03 1.36 x 100 1.93 3.07 xl3 0.47 0.65
x 141 1.41 1.80 x 55 0.95 1.26 x 88 1.7 2.75 x 10 0.37 0.51
x 130 1.31 1.67 x 50 0.87 1.15 x 77 152 2.45
x 118 1.19 1.53 x 46 0.86 1.09 x 68 1.35 2.20 W6x25 0.82 1.33
x 40 0.75 0.96 x 60 1.20 1.97 x20 0.67 1.09
W30x211 2.00 2.74 x 35 0.66 0.85 x 54 1.09 1.79 x 16 0.66 0.96
x 191 1.82 2.50 x 49 0.99 1.64 xl5 0.51 0.83
x 173 1.66 2.28 W16x 100 1.56 2.25
x 45 1.03 1.59 x 12 0.51 0.75
x 132 1.45 1.85 x89 1.40 2.03
x 124 1.37 1.75 x77 1.22 1.78 x 39 0.94 1.40 x 9 0.39 0.57
x 116 1.28 1.65 x67 1.07 1.56 x 33 0.77 1.20
x 108 1.20 1.54 x57 1.07 1.43 x 30 0.79 1.12 W5x 19 0.76 1.24
x 99 1.10 1.42 x50 0.94 1.26 x 26 0.69 0.98 x 16 0.65 1.07
x45 0.85 1.15 x 22 0.59 0.84
W27 x 178 1.85 2.55 x40 0.76 1.03 x 19 0.59 0.78 W4xl3 0.65 1.05
x 161 1.68 2.33 x36 0.69 0.93 x 17 0.54 0.70
x 146 1.53 2.12 x31 0.65 0.83
x 114 1.36 1.76 x26 0.55 0.70
For SI: I plf/in. = 0.059 kg/m/mm.
x 102 1.23 1.59
x 94 1.13 1.47 WI4x 132 1.83 3.00
x 84 1.02 1.33 xl20 1.67 2.75
x 109 1.53 2.52
x 99 1.39 2.31
W24 x 162 1.85 2.57 x 90 1.27 2.11
x 146 1.68 2.34 x 82 1.41 2.12
x 131 1.52 2.12 x 74 1.28 1.93
x 117 1.36 1.91 x 68 1.19 1.78
x 104 1.22 1.71 x 61 1.07 1.61
x 94 1.26 1.63 x 53 1.03 1.48
x 84 1.13 1.47 x 48 0.94 1.35
x 76 1.03 1.34 x 43 0.85 1.22
x 68 0.92 1.21 x 38 0.79 1.09
x 62 0.92 1.14 x 34 0.71 0.98
x 55 0.82 1.02 x 30 0.63 0.87
x 26 0.61 0.79
x 22 0.52 0.68
W21 x 147 1.83 2.60
x 132 1.66 2.35 W12x87 1.44 2.34
xl22 1.54 2.19 x79 1.32 2.14 FIGURE 709.5.2
x 111 1.41 2.01 x72 1.20 1.97 DETERMINATION OF THE HEATED PERIMETER
x 101 1.29 1.84 x65 1.09 1.79 OF STRUCTURAL STEEL BEAMS AND GIRDERS

(continued)

FLORIDA BUILDING CODE BUILDING 7.39


709.5.2.2- 709.6.2.7

709.5.2.2 Spray-applied fire resistant materials 709.6.1.2 Fire resistance ratings calculated using the
709.5.2.2.1 The provisions in this section apply to procedures in this section shall be used only for one (1)
unrestrained structural steel beams and girders pro- hour rated assemblies.
tected with spray-applied cementitious or mineral
fiber materials. Larger or smaller unrestrained beam 709.6.13 When dissimilar membranes are used on a
and girder shapes may be substituted for beams wall assembly, the calculation shall be made from the
specified in approved unrestrained or restrained fire least fire resistant (weaker) side.
resistant assemblies provided that the thickness of
the fire resistant material is adjusted in accordance 709.6.2 Walls, floors and roofs.
with the following expression:
709.6.2.1 These procedures apply to both loadbearing
and nonloadbearing assemblies.

709.6.2.2 The fire resistance rating of a wood framed


assembly is equal to the sum of the time assigned to the
membrane on the fire-exposed side, the time assigned
to the framing members and the time assigned for addi-
where tional contribution by other protective measures such
h = thickness of spray-applied fire resistant as insulation. The membrane on the unexposed side
material in inches, shall not be included in determining the fire resistance
W = weight of the structural steel beam or of the assembly.
girder in lb per linear ft, and
D = heated perimeter of the structural steel 709.6.2.3 Table 709.6.2A gives the time assigned
beam or girder in inches. membranes on the fire-exposed side.
Subscript 1 refers to the beam and fire resistant
material thickness in the approved assembly. 709.6.2.4 For an exterior wall having more than five
Subscript 2 refers to the substitute beam or girder (5) ft (1524 mm) of horizontal separation, the wall is
and the required thickness of fire resistant material. assigned a rating dependent on the interior membrane
and the framing as described in Tables 709.6.2A and
709.5.2.2.2 The equation in 709.5.2.2.1 is limited to 709.6.2B. The membrane on the outside or nonfire-
beams with a weight to heated perimeter ratio (W/D) of exposed side of exterior walls having more than five
0.37 or greater. The minimum thickness offireresistant (5) ft (1524 mm) of horizontal separation may consist
material shall not be less than three eighths (3/8) inch of sheathing, sheathing paper, and siding as described
(9.5 mm). in Table 709.6.2C.

709.5.2.3 Structural steel trusses. The fire resistance 709.6.2.5 In the case of a floor or roof, the standard test
of structural steel trusses protected with cementitious provides only for testing for fire exposure from below.
or mineral fiber materials spray-applied to each of the Except as noted in 701.6.3, floor or roof assemblies of
individual truss elements may be determined in accor- wood framing shall have an upper membrane consist-
dance with this section. The thickness of thefireresis- ing of a subfloor and finish floor conforming to Table
tant material shall be determined in accordance with 709.6.2D or any other membrane that has a contribu-
709.5.1.3. The weight to heated perimeter ratio (W/D) tion to fire resistance of at least fifteen (15) minutes in
of truss elements which can be simultaneously exposed Table 709.6.2A.
to fire on all sides shall be determined on the same
basis as columns, as specified in 709.5.1.1. The weight
to heated perimeter ratio (W/D) of truss elements 709.6.2.6 Table 709.6.2E gives the time increments
which directly support floor or roof construction shall that can be added to thefireresistance when glass fiber,
be determined on the same basis as beams and girders, rockwool or slag mineral wool insulation is incorporat-
as specified in 709.5.2.1. ed in the assembly.

709.5.2.4 Determining conditions of restraint. See 709.6.2.7 Fastening of wood framed assemblies and
Table 701.3 for guidance on restrained and unre- the fastening of membranes to the wood framing mem-
strained assemblies. bers shall be done in accordance with Table 2306.1 and
2504.4.1.
709.6 Wood assemblies
709.6.1 General
709.6.1.1 This section contains procedures for calcu-
lating the fire resistance ratings of walls, floor/ceiling
and roof/ceiling assemblies based in part on the stan-
dard method of testing referenced in 701.

7.40 FLORIDA BUILDING CODE BUILDING


TABLE 709.6.2A - TABLE 709.6.2C

TABLE 709.6.2A TABLE 709.6.2B


TIME ASSIGNED TO WALLBOARD MEMBRANES1,2,3,4 TIME ASSIGNED FOR CONTRIBUTION OF WOOD F R A M E D

DESCRIPTION OF FINISH TIME, (min) TIME ASSIGNED TO


DESCRIPTION FRAME, (mln)
3
/8-in wood structural panel bonded
with exterior glue 5 Wood studs 16 in (406 mm) o.c. 20
l5
/32-in wood structural panel bonded Wood floor and roof joists 16 in
with exterior glue 10 (406 mm) o.c. 10
l9
/32-in wood structural panel bonded
Notes:
with exterior glue 15
3
1. This table does not apply to studs or joists spaced more than 16 inch-
/8 in gypsum wallboard 10 es (406 mm) o.c.
1
/2-in gypsum wallboard 15 2. All studs shall be nominal 2x4 and all joists shall have a nominal
5
/8-in gypsum wallboard 30 thickness of at least 2 inches (51 mm).
1
/2-in Type X gypsum wallboard 25 3. Allowable spans for joists shall be determined in accordance with
5
/8-in Type X gypsum wallboard 40 2307.3.1 and 2309.1.1.
Double3/8-inngypsum wallboard 25
1
/ 2 + 3 / 8 -in gypsum wallboard 35
Double 1/2-in gypsum wallboard 40

For SI: 1 inch = 25.4 mm.


Notes:
1. These values apply only when membranes are installed on framing
members which are spaced 16 inches o.c.
2. Gypsum wallboard installed over framing or furring shall be installed
so that all edges are supported, except 5/8-inch Type X gypsum wall-
board may be installed horizontally with the horizontal joints stag-
gered 24 inches each side and unsupported but finished.
3. On wood framed floor/ceiling or roof/ceiling assemblies, gypsum
board shall be installed with the long dimension perpendicular to
framing members and shall have all joints finished.
4. The membrane on the unexposed side shall not be included in deter-
mining the fire resistance of the assembly. When dissimilar mem-
branes arc used on a wall assembly, the calculation shall be made
from the least fire resistant (weaker) side.

TABLE 709.6.2C
MEMBRANE1 ON EXTERIOR FACE OF WOOD STUD WALLS

SHEATHING PAPER EXTERIOR FINISH


5
/8-in T & G lumber Lumber siding
5
/16-in exterior glue plywood Sheathing paper Wood shingles and shakes
1 1
/2-in gypsum wallboard /4-in wood structural panels exterior type
5 1
/8-in gypsum wallboard /4-in hardboard
1
/2-in fiberboard Metal siding
Stucco on metal lath
Masonry veneer
3
None /8-in exterior grade wood structural panels

For SI: 1 inch = 25.4 mm.

Note:
1. Any combination of sheathing, paper and exterior finish listed may be used.

FLORIDA BUILDING CODE BUILDING 7.41


TABLE 709.6.2.D 709.7

TABLE 709.6.2D
FLOORING OR ROOFING OVER WOOD FRAMING1

STRUCTURAL SUBFLOOR OR
ASSEMBLY MEMBERS ROOF DECK FINISH FLOORING OR ROOFING

Hardwood or softwood flooring on building paper

15
Floor Wood /32-in wood structural panels Resilient flooring, parquet floor felted-synthetic-fiber
or 11/16-in T & G softwood floor coverings, carpeting, or ceramic tile on 3/8-in
thick panel-type underlay

Ceramic tile on 1 1/4-in mortar bed

15
Roof Wood /32-in wood structural panels Finish roofing material
or 11 / 16 in T & G softwood with or without insulation

For SI: l in. = 25.4 mm.


Note:
1. This table applies only to wood joist construction. It is not applicable to wood truss construction.

TABLE 709.6.2E 709.6.3.2 Formula (4) in 709.6.3.1 applies only where


TIME ASSIGNED FOR ADDITIONAL PROTECTION the unexposed face represents the smaller side of the
column. If a column is recessed into a wall, its full
DESCRIPTION OF FIRE RESISTANCE, dimension shall be used for the purpose of these calcu-
ADDITIONAL PROTECTION (min)
lations.
Add to the fire resistance rating of
wood stud walls if the spaces between 709.6.3.3 Allowable loads on beams and columns are
the studs are completely filled 15 determined using design values given in Design Values
with glass fiber mineral wool batts for Wood Construction, a supplement to the
weighing not less than 2 Ib/cu ft ANSI/AF&PA National Design Specification for Wood
(0.6 Ib/sq ft of wall surface) or rockwool Construction.
or slag mineral wool batts weighing not less
than 3.3 Ib/cu ft (1 Ib/sq ft of wall surface). 709.6.3.4 Where minimum 1-hour fire resistance is
3
required, connectors and fasteners shall be protected
For S1: 1 Ib/cu ft = 16.0185 kg/m . from fire exposure by 11/2inches (38 mm) of wood, or
other approved covering or coating for a 1-hour rating.
709.6.3 Design of fire resistant exposed wood members Typical details for commonly used fasteners and con-
709.6.3.1 The fire resistance rating, in minutes, of tim- nectors are shown in AITC Technical Note No. 7.
ber beams and columns with a minimum nominal
dimension of 6 inches is equal to: 709.6.3.5 Wood members are limited to dimensions of
6 inches nominal or greater. Glued laminated timber
Beams: (1) 2.54Zb (4 - 2(b/d)) for beams which beams use standard laminating combinations except
may be exposed to fire on four sides. that a core lamination is removed. The tension zone is
(2) 2.54Zb (4 - (b/d)) for beams which moved inward and the equivalent of an extra nominal
may be exposed tofireon three sides. 2-inch thick outer tension lamination is added.
Columns: (3) 2.54Zd (3 - (d/b)) for columns which
may be exposed to fire on four sides 709.7 Other reference documents. Refer to 701.5.2 and
(4) 2.54Zd (3 - (d/2b)) for columns NBS BMS 71, NBSFire Tests of Building Columns, and
which may be exposed tofireon three NBS TRBM-44 for fire resistance ratings of materials and
sides. assemblies.
Where: b = the breadth (width) of a beam or
larger side of a column before expo-
sure tofire,inches.
d = the depth of a beam or smaller
side of a column before exposure to
fire, inches.
Z = load factor, based on Figure 709.6.3A

7.42 FLORIDA BUILDING CODE BUILDING


FIGURE 709.6.3A - FIGURE 709.6.3B

FIGURE 709.6.3B
EFFECTIVE LENGTH FACTORS

FIGURE 709.6.3A
LOAD FACTOR
Ke = the effective length factor as noted in Figure 709.6.3B.
1 = the unsupported length of columns, inches.

FLORIDA BUILDING CODE BUILDING 7.43


7.44 FLORIDA BUILDING CODE BUILDING

You might also like