Alarm Configuration on Potevio PSU

Please find the place of the alarm panel which is found on top of controller unit. It has the ability to
configure 6 dry contact o/p s according to customer configuration

4 1

6
3

The dry contact configuration can be found like above please find the bellow figure for
clarification
Please find the way of connecting alarms as Normal close configuration as follow. Use pin 1 and
3 for this configuration.

According to the 3G Alarm configuration the interface can be matched with following
configuration

Potevio PSU
Configuration Default Adjustable
ALU 3G Configuration Dry contact no configuration
Mains Power failure
Port 1 Dry contact 1
Rectifier fail or MCB tripped
Port 2 Drycontact 2
LVD alarm Port 3 Drycontact 3 or 4 Define LVD or BLVD
DC Low voltage alarm Port 4 Can be set
High temperature alarm Port 5 Can be set
AC low voltage alarm Port 6 Drycontact 1 Can be adjustable
Door open Alarm Port 7 Dry contact 5

The Default configuration is like this but it can be customize.

For the 2G alarm configuration the interface that is provided by NOC is not matching with the existing
sum x configuration. Need to match interfaces from ALU and ETS side.
2G configuration according to the interface given through SUM card

Potevio PSU
Configuration Default Adjustable
ALU 2G Configuration Logical port no Dry contact no configuration
Rectifier Faliure
Port 1 Dry contact 2
Mains power alarm
Port 2 Drycontact 1
Door Window Port 3 Drycontact 5
Door Window over ride Port 4
Fire Alarm Port 5 can be set
water Break in Port 6 can be set
Air condition Port 7 N/A
Temperature alarm port 8 Can be set