You are on page 1of 1

Heat Loss Charts

Distribution Heat Loss per 30 meters of Uninsulated Steam Line, MJ/yr


Line
Diameter, Steam Pressure, bar
mm
1 bar 10 bar 21 bar 41 bar

25 150 300 400 520

50 250 500 660 900

100 440 900 1200 1600

200 780 1620 2100 2900

300 1000 2400 3200 4200


Based on horizontal steel pipe, 24C ambient air, no wind velocity, and 8760 operating hours per year.

Distribution Heat Loss per 100 Feet of Uninsulated Steam Line, MMBtu/yr
Line
Diameter, Steam Pressure, psig
inches
15 150 300 600

1 140 285 375 495

2 235 480 630 840

4 415 850 1120 1500

8 740 1540 2030 2725

12 1055 2200 2910 3920


Based on horizontal steel pipe, 75F ambient air, no wind velocity, and 8760 operating hours per year.