Selection Guide

Intrinsic Safety Modules


Table of Contents

Isolated Barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Switch Amplifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Solenoid Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

SMART Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

Temperature Repeater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29

SMART Current Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31

Converter Barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33


Universal Temperature Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35

Frequency Converters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37

Transmitter Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43

HART Loop Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46

Strain Gauge Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49

Zener Barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51


1-channel, 327 Ohm Max . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55

2-channel, 327 Ohm Max . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57

2-channel, 646 Ohm Max . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59

2-channel, 36 Ohm + 0.9 V Max . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61

2-channel, 250 Ohm Max . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Power Feed Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65

Power Rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67

USB Interface Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68

2 Rockwell Automation Publication 937-SG001C-EN-P January 2015


Isolated Barriers

With galvanic optical or transformer isolation, these modules provide an interface within the intrinsic safety circuit that
is electrically separated from the control system. A key advantage of isolated barriers is that they do not require a
ground between the module and the intrinsically safe device. Available in 12.5 mm (0.5 in) and 20mm (0.8 in) widths.

Switch Amplifiers SMART Current Drivers


Switch Amplifiers are used to transfer SMART Current Drivers drive SMART I/P
digital signals (NAMUR converters, electrical valves, and
sensors/mechanical contacts) from a positioners in hazardous areas.
hazardous area to a safe area. Select
modules are available with relay
output or transistor output, in
addition to signal splitters. A unique
collective error messaging feature is
available when used with the Power Solenoid Drivers
Rail system. Due to its compact Solenoid Drivers supply power to
housing design and low heat solenoids, LEDs, and audible alarms
dissipation, this device is useful for located in a hazardous area.
detecting positions, end stops, and
switching states in space-critical
applications.

SMART Transmitter Power Supplies


SMART Transmitter Power Supplies
supply 2-wire SMART transmitters in a
hazardous area, and can also be used
with 2-wire SMART current sources.
They transfer the analog input signal
to the safe area as an isolated current
value. Modules with splitter feature
provide two isolated output signals.

Temperature Repeaters
Temperature Repeaters transfer RTD
resistance values from hazardous
areas to safe areas. A 2-, 3-, or 4-wire
mode is available depending on the
required accuracy. The monitor
registers the same load as if it were
connected directly to the resistance
in a hazardous area.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 3


937 Intrinsic Safety Isolated Barriers

Catalog Number Explanation


Note: Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; some combinations may not produce a valid catalog number.

937T H DI SAR - KD 1
a b c - d e

a c d
Module Prole Functionality Power
Code Description Code Description Code Description
H High-density 12.5mm module SAR Switch Amplier with Relay Output IP Input Loop Powered
S Standard 20 mm module SRS Switch Amplier with Relay Output, Splitter DC 24V DC
SAT Switch Amplier withTransistor Output BC 20...90V DC/48...253V AC
STS Switch Amplier with Transistor Output, Splitter KD 115V AC
Solenoid Driver KF 230V AC
SND
b
TXP SMART Transmitter, Power Supply
I/O Type
TXS SMART Transmitter, Power Supply, Splitter
Code Description e
RRP Repeater, Resistance Measuring
DI Digital In Channels
SCD SMART Current Driver
DO Digital Out Code Description
AI Analog In 1 Single Channel
AO Analog Out 2 Dual Channel

4 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Isolated Barriers

Specifications
Switch Amplifier, Relay Output
Supply
2-ch, 115V AC Connection terminals 14, 15
937TS-DISAR-KD2 Rated voltage 103.5 ... 126V AC , 45 ... 65 Hz
Power loss 1.2 W
Power consumption 1.3 W
Input
Connection terminals 1+, 2+, 3-; 4+, 5+, 6-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 8V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I 0.1 mA, short-circuit I >6 mA
Pulse/Pause ratio 20 ms / 20 ms
Output
output I: terminals 7, 8, 9 ; output II:
Connection
terminals 10, 11, 12
Output I signal ; relay
Output II signal ; relay
Energized/De-energized delay approx. 20 ms/ 20 ms
Mechanical life 107 switching cycles
Transfer characteristics
Switching frequency 10 Hz
Electrical isolation
reinforced insulation according to IEC/EN
Features Input/Output
61010-1, rated insulation voltage 300 Ve
 2-channel isolated barrier reinforced insulation according to IEC/EN
Input/power supply
61010-1, rated insulation voltage 300 Ve
 115V AC supply
reinforced insulation according to IEC/EN
 Dry contact or NAMUR inputs Output/power supply
61010-1, rated insulation voltage 300 Ve
 Relay contact output
 Line fault detection (LFD) reinforced insulation according to IEC/EN
Output/Output
61010-1, rated insulation voltage 300 Ve
 Reversible mode of operation
Directive conformity
 Up to SIL2 acc. to IEC 61508/IEC 61511
Electromagnetic compatibility
This isolated barrier is used for intrinsic safety applications. It Directive 2004/108/EC EN 61326-1:2006
transfers digital signals (NAMUR sensors/mechanical Low voltage
contacts) from a hazardous area to a safe area. The proximity Directive 2006/95/EC EN 61010-1:2010
sensor or switch controls a form C changeover relay contact
Conformity
for the safe area load. The normal output state can be
Electromagnetic compatibility NE 21:2006
reversed using switches S1 and S2. Switch S3 is used to
enable or disable line fault detection of the field circuit. Protection degree IEC 60529:2001
During an error condition, the relays revert to their de- Input EN 60947-5-6:2000
energized state and the LEDs indicate the fault according to
NAMUR NE44.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 5


937 Intrinsic Safety Isolated Barriers

Switch Amplifier, Relay Output Front view

2-ch, 115V AC, continued Removable terminals


blue

937TS-DISAR-KD2 1 2 3
4 5 6

LED yellow: LED green:


Environmental and Mechanical Specifications Relay output Power supply
Operating temperature -20 ... 60 C (-4 ... 140 F) 1
LED red: OUT CHK PWR

Protection degree IP20 LB/SC channel


2

S1
Switch S1
S2 (Mode of operation channel )
Weight approx. 150 g LED yellow: S3

Relay output I II
Switch S2
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , (Mode of operation channel )
Dimensions
housing type B2 LED red: 7 8 9
LB/SC channel 10 11 12
Switch S3
13 14 15
on 35 mm DIN mounting rail (LB/SC-monitoring)
Mounting
acc. to EN 60715:2001
Removable terminals
Data for application in connection with Ex-areas black

Group, category, type of protection <Ex> II (1) G [Ex ia] IIC, II (1) D [Ex ia] IIIC

Input [Ex ia] IIC, [Ex ia] IIIC Product Features


Voltage Uo 10.6V Cat. No. 937TS-DISAR-KD2
Current Io 19.1 mA
Power Po 51 mW (linear characteristic)
Supply
Maximum safe voltage Um 126.5V AC
Output 20 mm 115 mm (4.5'')
(0.78")
253V AC/2 A/cos > 0.7;
Contact loading 126.5V AC/4 A/cos > 0.7;
40V DC/2 A resistive load
Maximum safe voltage Um 253V AC

=
Electrical isolation

107 mm (4.21'')
93 mm (3.66'')
safe electrical isolation acc. to
Input/Output
IEC/EN 60079-11, voltage peak value 375V
safe electrical isolation acc. to

=
Input/power supply
IEC/EN 60079-11, voltage peak value 375V
Directive conformity
EN 60079-0:2009, EN 60079-11:2007,
Directive 94/9/EC
EN 61241-11:2006
Note: Maximum safe voltage is not rated voltage. Approximate Dimensions
Cat. No. 937TS-DISAR-KD2

Configuration

Switch position

S Function Position
Mode of operation with high input current I 1+ 7
1 Output I (relay)
with low input current II 8 I
energized I 10 k 2+ 9
Mode of operation with high input current I 10 k
1
4
2
5
3
6 2 Output II (relay) 3-
with low input current II 400 R 2 k
energized
1 ON I
OUT CHK PWR
3 Line fault detection
2
OFF II 4+ 10
S1
1

S1 11 II
1

S2 S2 II 10 k 5+ 12
2
2

S3
3

S3 10 k
3

Operating status
7
10
8
11
9
12
6-
13 14 15
I II Control circuit Input signal 400 R 2 k
Initiator high impedance /
low input current
contact opened
14
Initiator low impedance /
high input current 15
230 V AC
contact closed
Lead breakage
Line fault
lead short-circuit
Zone 0, 1, 2
Factory settings: switch 1, 2 and 3 in position I Div. 1, 2

Configuration
Wiring Diagram
Cat. No. 937TS-DISAR-KD2
Cat. No. 937TS-DISAR-KD2

6 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Isolated Barriers

Specifications
Switch Amplifier, Relay Output
Description 230V AC, 2-channel
2-ch, 230V AC Signal Type Digital input, relay output
Supply
937TS-DISAR-KF2
Connection terminals 14, 15
Rated voltage 207 ... 253V AC, 45 ... 65 Hz
Power loss 1.2 W
Power consumption 1.3 W
Input
Connection terminals 1+, 2+, 3-; 4+, 5+, 6-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 8V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I 0.1 mA, short-circuit I >6 mA
Pulse/Pause ratio 20 ms / 20 ms
Output
output I: terminals 7, 8, 9 ;
Connection
output II: terminals 10, 11, 12
Output I signal ; relay
Output II signal ; relay
Energized/De-energized delay approx. 20 ms/ 20 ms
Mechanical life 107 switching cycles
Transfer characteristics
Features Switching frequency 10 Hz
Electrical isolation
 2-channel isolated barrier
 230V AC supply reinforced insulation according to IEC/EN
Input/Output
 Dry contact or NAMUR inputs 61010-1, rated insulation voltage 300 Veff
 Relay contact output
reinforced insulation according to IEC/EN
 Line fault detection (LFD) Input/power supply
61010-1, rated insulation voltage 300 Veff
 Reversible mode of operation
 Up to SIL2 acc. to IEC 61508/IEC 61511 reinforced insulation according to IEC/EN
Output/power supply
61010-1, rated insulation voltage 300 Veff
This isolated barrier is used for intrinsic safety applications. It
transfers digital signals (NAMUR sensors/mechanical reinforced insulation according to IEC/EN
Output/Output
contacts) from a hazardous area to a safe area. The proximity 61010-1, rated insulation voltage 300 Veff
sensor or switch controls a form C changeover relay contact
Directive conformity
for the safe area load. The normal output state can be
Electromagnetic compatibility
reversed using switches S1 and S2. Switch S3 is used to
enable or disable line fault detection of the field circuit. Directive 2004/108/EC EN 61326-1:2006
During an error condition, the relays revert to their de- Low voltage
energized state and the LEDs indicate the fault according to Directive 2006/95/EC EN 61010-1:2010
NAMUR NE44. Conformity
Electromagnetic compatibility NE 21:2006
Protection degree IEC 60529:2001
Input EN 60947-5-6:2000

Rockwell Automation Publication 937-SG001C-EN-P January 2015 7


937 Intrinsic Safety Isolated Barriers

Switch Amplifier, Relay Output


2-ch, 230V AC, continued
937TS-DISAR-KF2
1+ 7
8 I
Environmental and Mechanical Specifications I 10 k 2+ 9
10 k
3-
Operating temperature -20 ... 60 C (-4 ... 140 F) 400 R 2 k

Protection degree IP20 4+ 10


11 II
II 10 k 5+ 12
Weight approx. 150 g 10 k
6-
400 R 2 k
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in),
Dimensions
housing type B2 14
230 V AC
15
on 35 mm DIN mounting rail acc. to
Mounting
EN 60715:2001 Zone 0, 1, 2
Div. 1, 2
Data for application in connection with Ex-areas
Group, category, type of protection Ex II (1) G [Ex ia] IIC, II (1) D [Ex ia] IIIC Wiring Diagram
Input [Ex ia] IIC, [Ex ia] IIIC Cat. No. 937TS-DISAR-KF2

Voltage Uo 10.6 V
Configuration
Current Io 19.1 mA
Switch position
Power Po 51 mW (linear characteristic) S Function Position
Mode of operation with high input curren t I
Supply 1 Output I (relay)
with low input curren t II
energized

Maximum safe voltage Um 253V AC 1


4
2
5
3
6 2
Mode of operation
Output II (relay)
with high input curren t I

with low input curren t II


energize
Output 1
OUT CHK PWR
3 Line fault detection
ON I
2
OFF II
S1
1

S1

253V AC/2 A/cos > 0.7;


1

S2 S2
2
2

S3
3

S3
3

Operating status
Contact loading 126.5V AC/4 A/cos > 0.7; 7
10
8
11
9
12
13 14 15
I II Control circuit Input signal
40V DC/2 A resistive load Initiator high impedance /
low input current
contact opened
Initiator low impedance /
Maximum safe voltage Um 253V AC contact closed
high input current

Lead breakage
Line fault
Electrical isolation lead short-circuit

safe electrical isolation acc. to IEC/EN 60079-11, Factory settings: switch 1, 2 and 3 in position I
Input/Output
voltage peak value 375V
safe electrical isolation acc. to IEC/EN 60079-11, Configuration
Input/power supply Cat. No. 937TS-DISAR-KF2
voltage peak value 375V
Directive conformity 20 mm 115 mm (4.5'')
(0.78")
EN 60079-0:2009, EN 60079-11:2007 ,
Directive 94/9/EC
EN 61241-11:2006
=

Front view
107 mm (4.21'')
93 mm (3.66'')

Removable terminals
blue

1 2 3
4 5 6
=

LED yellow: LED green:


Relay output Power supply

1
LED red: OUT CHK PWR
2
LB/SC channel Switch S1
S1
S2 (Mode of operation channel )
LED yellow: S3

Relay output I II
Switch S2 Approximate Dimensions
(Mode of operation channel ) Cat. No. 937TS-DISAR-KF2
LED red: 7 8 9
LB/SC channel 10 11 12
Switch S3
13 14 15
(LB/SC-monitoring)

Removable terminals
black

Product Features
Cat. No. 937TS-DISAR-KF2
8 Rockwell Automation Publication 937-SG001C-EN-P January 2015
937 Intrinsic Safety Isolated Barriers

Specifications
Switch Amplifier, Relay Output
Description 24V, 2-channel
2-ch, 24V DC Signal Type Digital Input
Supply
937TH-DISAR-DC2
Connection Power Rail or terminals 9+, 10-
Rated voltage 19 ... 30V DC
Ripple 10%
Rated current 30 mA
Power loss 600 mW
Power consumption 600 mW
Input
Connection terminals 1+, 2-; 3+, 4-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 10V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I 0.1 mA, short-circuit I >6.5 mA
Pulse/Pause ratio 20 ms / 20 ms
Output
Connection terminals 5, 6; 7, 8
Output I signal ; relay
Output II signal ; relay
Minimum switch current 2 mA / 24V DC
Energized/De-energized delay 20 ms / 20 ms
Mechanical life 107 switching cycles
Transfer characteristics
Switching frequency 10 Hz
Electrical isolation
Features
reinforced insulation acc. to EN 50178, rated
Input/Output
insulation voltage 300Ve
 2-channel isolated barrier
reinforced insulation acc. to EN 50178, rated
 24V DC supply (Power Rail) Input/power supply
insulation voltage 300Ve
 Dry contact or NAMUR inputs
reinforced insulation acc. to EN 50178, rated
 Relay contact output Output/power supply
insulation voltage 300Ve
 Line fault detection (LFD) Basic insulation according to EN 50178, rated
 Housing width 12.5 mm Input/input
insulation voltage 300Ve
 Up to SIL2 acc. to IEC 61508 reinforced insulation acc. to EN 50178, rated
Output/Output
insulation voltage 300Ve
This isolated barrier is used for intrinsic safety applications. It Directive conformity
transfers digital signals (NAMUR sensors/mechanical Electromagnetic compatibility
contacts) from a hazardous area to a safe area. The proximity Directive 2004/108/EC EN 61326-1:2006
sensor or switch controls a form A normally open relay Low voltage
contact for the safe area load. The normal output state can
Directive 2006/95/EC EN 61010-1:2010
be reversed using switches S1 and S2. Switch S3 is used to
enable or disable line fault detection of the field circuit. Conformity
During an error condition, relays revert to their de-energized Electromagnetic compatibility NE 21
state and LEDs indicate the fault according to NAMUR NE44. Protection degree IEC 60529
A unique collective error messaging feature is available when
used with the Power Rail system. Due to its compact housing
design and low heat dissipation, this device is useful for
detecting positions, end stops, and switching states in space-
critical applications.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 9


937 Intrinsic Safety Isolated Barriers

Switch Amplifier, Relay Output Front view


Removable terminals
blue

2-ch, 24V DC, continued


1 2 LED green:
3 4
Power supply
937TH-DISAR-DC2 LED yellow/red:
Status output/
Environmental and Mechanical Specifications 1
PWR
error channel I
OUT/CHK

Operating Temperature -20 ... 60 C (-4 ... 140 F) 2 LED yellow/red:


1 Status output/
Protection degree IP20 S
2
3
error channel II
4
I II
Mass approx. 100 g Switch 1 ... 4

12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in) , 5 6

Dimensions 7 8
Place for labeling
housing type A2 9 10

on 35 mm DIN mounting rail acc. to


Mounting Removable terminals
EN 60715:2001 black
Data for application in connection with Ex-areas
<Ex> II (1)G [Ex ia Ga] IIC , <Ex> II (1)D
Group, category, type of protection
[Ex ia Da] IIIC , <Ex> I (M1) [Ex ia Ma] I
Product Features
Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Cat. No. 937TH-DISAR-DC2
Voltage Uo 10.5V
Current Io 17.1 mA Configuration

Power Po 45 mW (linear characteristic)


Switch position
Supply S Function Position
Mode of operation with high input current I
Maximum safe voltage Um 253V AC 1 2
1 Output I (relay)
energized
with low input current II
3 4

Mode of operation with high input current I


Output 2 Output II (relay) with low input current II
energized
253V AC/2 A/cos > 0.7; 3
Line fault detection
Input I
ON
OFF
I
II
Contact loading 126.5V AC/4 A/cos > 0.7; 1
1
4
Line fault detection ON I
2 Input II OFF II
30V DC/2 A resistive load S
2
3
4
3
I II

4 Operating status
Maximum safe voltage Um 253V AC
5
7
6
8
I II Control circuit Input signal
Group, category, type of protection, 9 10
Initiator high impedance/
low input current
<Ex> II 3G Ex nA nC IIC T4 Gc contact opened
temperature class Initiator low impedance/
contact closed
high input current

Lead breakage,
Output I, II lead short-circuit
Line fault

50V AC/2 A/cos > 0.7; Factory settings: switch 1, 2, 3 and 4 in position I
Contact loading
30V DC/ 2 A resistive load
Configuration
Electrical isolation
Cat. No. 937TH-DISAR-DC2
safe electrical isolation acc. to IEC/EN 60079-11,
Input/Output
voltage peak value 375V
safe electrical isolation acc. to IEC/EN 60079-11,
Input/power supply
voltage peak value 375V
Directive conformity
EN 60079-0:2009, EN 60079-11:2007 ,
Directive 94/9/EC
EN 60079-15:2005 , EN 61241-11:2006
114

1+ 5
I 10 k I
2- 6
400 R 2 k

3+ 7
II 10 k II
4- 8
400 R 2 k

12.5 119

9+
10-
24 V DC

Zone 0, 1, 2 ERR 24 V DC Zone 2


Div. 1, 2 Power Rail Div. 2

Wiring Diagram Approximate Dimensions


Cat. No. 937TH-DISAR-DC2 Cat. No. 937TH-DISAR-DC2

10 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Isolated Barriers

Specifications
Switch Amplifier, Relay Output
937TS-DISRS-KD1
with Splitter
Description 115V AC, 1-channel with Splitter
1-ch, 115V AC Signal Type Digital Input, Relay Output
Supply
937TS-DISRS-KD1 Connection terminals 14, 15
Rated voltage 103.5 ... 126V AC , 45 ... 65 Hz
Power loss 1.2 W
Power consumption 1.3 W
Input
Connection terminals 1+, 2+, 3-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit
approx. 8V DC / approx. 8 mA
current
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I 0.1 mA, short-circuit I >6 mA
Pulse/Pause ratio 20 ms / 20 ms
Output
output I: terminals 7, 8, 9 ;
Connection
output II: terminals 10, 11, 12
Output I signal ; relay
Output II signal or error message ; relay
Energized/De-energized delay approx. 20 ms/ 20 ms
Mechanical life 107 switching cycles
Transfer characteristics
Features
Switching frequency 10 Hz
 1-channel isolated barrier Electrical isolation
 115V AC supply Input/Output
reinforced insulation according to IEC/EN 61010-1,
 Dry contact or NAMUR inputs rated insulation voltage 300 Veff
 Relay contact output Input/power supply
reinforced insulation according to IEC/EN 61010-1,
rated insulation voltage 300 Veff
 Fault relay contact output
reinforced insulation according to IEC/EN 61010-1,
 Line fault detection (LFD) Output/power supply
rated insulation voltage 300 Veff
 Reversible mode of operation
reinforced insulation according to IEC/EN 61010-1,
 Up to SIL2 acc. to IEC 61508/IEC 61511 Output/Output
rated insulation voltage 300 Veff
Directive conformity
This isolated barrier is used for intrinsic safety applications. It
Electromagnetic compatibility
transfers digital signals (NAMUR sensors/mechanical
Directive 2004/108/EC EN 61326-1:2006
contacts) from a hazardous area to a safe area. The proximity
sensor or switch controls a form C changeover relay contact Low voltage
for the safe area load. The normal output state can be Directive 2006/95/EC EN 61010-1:2010
reversed using switch S1. Switch S2 allows output II to be Conformity
switched between a signal output or an error message Electromagnetic compatibility NE 21:2006
output. Switch S3 is used to enable or disable line fault Protection degree IEC 60529:2001
detection of the field circuit. During an error condition, the Input EN 60947-5-6:2000
relays revert to their de-energized state and the LEDs
indicate the fault according to NAMUR NE44.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 11


937 Intrinsic Safety Isolated Barriers

Switch Amplifier, Relay Output


with Splitter 10 k
10 k
1+
2+
7
8
9
I

3-

1-ch, 115V AC, continued 400 R 2 k

10
11 II
12
937TS-DISRS-KD1
14
Environmental and Mechanical Specifications 15
115 V AC

Operating temperature -20 ... 60 C (-4 ... 140 F)


Zone 0, 1, 2
Protection degree IP20 Div. 1, 2

Weight approx. 150 g


Wiring Diagram
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) Cat. No. 937TS-DISRS-KD1
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-areas Configuration

Group, category, type of protection <Ex> II (1) G [Ex ia] IIC, II (1) D [Ex ia] IIIC
Switch position

Input [Ex ia] IIC, [Ex ia] IIIC S


Mode of operation
Function
with high input current
Position
I
1 Output I (relay)
with low input current II
Voltage Uo 10.6 V 1 2 3
energized
switching state like output I I
4 5 6 Assignment
2 fault signal output
Current lo 19.1 mA 1
Output II (relay)
(de-energized if fault)
II
OUT CHK PWR
ON I
3 Line fault detection
S1
Power Po 51 mW (linear characteristic) OFF II

1
S1
1

S2 S2

2
2

S3
3

S3

3
Supply 7
10
8
11
9
12
Operating status
13 14 15
I II
Control circuit Input signal
Maximum safe voltage Um 126.5V AC Initiator high impedance/
low input current
contact opened
Output Initiator low impedance/
contact closed
high input current

Lead breakage,
253V AC/2 A/cos > 0.7; lead short-circuit
Line fault

Contact loading 126.5V AC/4 A/cos > 0.7; Factory settings: switch 1, 2 and 3 in position I
40V DC/2 A
Maximum safe voltage Um 253V AC Configuration
Electrical isolation Cat. No. 937TS-DISRS-KD1
safe electrical isolation acc. to IEC/EN 60079-11,
Input/Output
voltage peak value 375 V
safe electrical isolation acc. to IEC/EN 60079-11, 20 mm 115 mm (4.5'')
Input/power supply
voltage peak value 375 V (0.78")

Front view
=

Removable terminal 107 mm (4.21'')


93 mm (3.66'')

blue

1 2 3
4 5 6

LED yellow: LED green:


=

Relay output Power supply


OUT CHK PWR

LED red: Switch S1


S1
LB/SC S2 (mode of operation)
S3

I II

Switch S2
(output selection II)
Approximate Dimensions
7 8 9
10 11 12
13 14 15
Switch S3 Cat. No. 937TS-DISRS-KD1
(LB/SC-monitoring)

Removable terminals
black

Product Features
Cat. No. 937TS-DISRS-KD1

12 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Isolated Barriers

Specifications
Switch Amplifier, Relay Output
Description 230V AC, 1-channel with Splitter
with Splitter Signal Type Digital Input, Relay Output
1-ch, 230V AC Supply
Connection terminals 14, 15
937TS-DISRS-KF1 Rated voltage 207 ... 253V AC, 45 ... 65 Hz
Power loss 1.2 W
Power consumption 1.3 W
Input
Connection terminals 1+, 2+, 3-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/ approx. 8V DC /
short-circuit current approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I 0.1 mA, short-circuit I >6 mA
Pulse/Pause ratio 20 ms / 20 ms
Output
output I: terminals 7, 8, 9 ;
Connection
output II: terminals 10, 11, 12
Output I signal ; relay
Output II signal or error message ; relay
Energized/De-energized delay approx. 20 ms/ 20 ms
Mechanical life 107 switching cycles
Transfer characteristics
Switching frequency 10 Hz
Electrical isolation

Features Input/Output
reinforced insulation according to IEC/EN 61010-1,
rated insulation voltage 300 Veff
 1-channel isolated barrier
 230V AC supply reinforced insulation according to IEC/EN 61010-1,
Input/power supply
rated insulation voltage 300 Veff
 Digital input, relay output
reinforced insulation according to IEC/EN 61010-1,
This isolated barrier is used for intrinsic safety applications. It Output/power supply
rated insulation voltage 300 Veff
transfers digital signals (NAMUR sensors/mechanical
contacts) from a hazardous area to a safe area. The proximity reinforced insulation according to IEC/EN 61010-1,
Output/Output
sensor or switch controls a form C changeover relay contact rated insulation voltage 300 Ve
for the safe area load. The normal output state can be
Directive conformity
reversed using switch S1. Switch S2 allows output II to be
switched between a signal output or an error message Electromagnetic compatibility
output. Switch S3 is used to enable or disable line fault Directive 2004/108/EC EN 61326-1:2006
detection of the field circuit. During an error condition, the Low voltage
relays revert to their de-energized state and the LEDs Directive 2006/95/EC EN 61010-1:2010
indicate the fault according to NAMUR NE44. Conformity
Electromagnetic compatibility NE 21:2006
Protection degree IEC 60529:2001
Input EN 60947-5-6:2000

Rockwell Automation Publication 937-SG001C-EN-P January 2015 13


937 Intrinsic Safety Isolated Barriers

Switch Amplifier, Relay Output


with Splitter 1+ 7
8 I
10 k 2+ 9
10 k
1-ch, 230V AC, continued 400 R 2 k
3-

937TS-DISRS-KF1 10
11
12
II

Environmental and Mechanical Specifications


14
Operating temperature -20 ... 60 C (-4 ... 140 F) 15
230 V AC

Protection degree IP20


Zone 0, 1, 2
Weight approx. 150 g Div. 1, 2

Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2


Wiring Diagram
on 35 mm DIN mounting rail Cat. No. 937TS-DISRS-KF1
Mounting
acc. to EN 60715:2001
Data for application in connection with Ex-areas Configuration

Group, category, type of protection Ex II (1) G [Ex ia] IIC, II (1) D [Ex ia] IIIC Switch position

Input [Ex ia] IIC, [Ex ia] IIIC S Function Position


Mode of operation with high input current I
Voltage Uo 10.6V 1 Output I (relay)
energized
with low input current II

1 2 3 switching state like output I I


Current Io 19.1 mA 4 5 6
2
Assignment
Output II (relay)
fault signal output
II
1
(de-energized if fault)
OUT CHK PWR

Power Po 51 mW (linear characteristic) S1


3 Line fault detection
ON
OFF II
I

1
S1
1

S2 S2

2
2

S3
Supply
3

S3

3
7 8 9 Operating status
10 11 12
13 14 15
I II
Maximum safe voltage Um 253V A Control circuit Input signal
Initiator high impedance/
low input current
Output contact opened
Initiator low impedance/
high input current
contact closed
253V AC/2 A/cos > 0.7; Lead breakage,
lead short-circuit
Line fault

Contact loading 126.5V AC/4 A/cos > 0.7;


Factory settings: switch 1, 2 and 3 in position I
40V DC/2 A resistive load
Maximum safe voltage Um 253V AC
Electrical isolation Configuration
safe electrical isolation acc. to IEC/EN 60079-11, Cat. No. 937TS-DISRS-KF1
Input/Output
voltage peak value 375V
safe electrical isolation acc. to IEC/EN 60079-11,
Input/power supply 20 mm 115 mm (4.5'')
voltage peak value 375V (0.78")

Directive conformity
EN 60079-0:2009, EN 60079-11:2007,
Directive 94/9/EC
EN 61241-11:2006 =

Front view 107 mm (4.21'')


93 mm (3.66'')

Removable terminal
blue

1 2 3
4 5 6
=

LED yellow: LED green:


Relay output Power supply
OUT CHK PWR

LED red: Switch S1


S1
LB/SC S2 (mode of operation)
S3

I II

Switch S2
(output selection II)
7 8 9
Approximate Dimensions
10 11 12
13 14 15
Switch S3 Cat. No. 937TS-DISRS-KF1
(LB/SC-monitoring)

Removable terminals
black

Product Features
Cat. No. 937TS-DISRS-KF1
14 Rockwell Automation Publication 937-SG001C-EN-P January 2015
937 Intrinsic Safety Isolated Barriers

Specifications

Switch Amplifier, Relay Output Description 24VDC, 1-channel with splitter


Signal Type Digital Input, Relay Output
with Splitter Supply

1-ch, 24V DC Connection Power Rail or terminals 9+, 10-


Rated voltage 19 ... 30V DC
937TH-DISRS-DC1 Ripple 10%
Rated current 30 mA
Power loss 500 mW
Power consumption 500 mW
Input
Connection terminals 1+, 2-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 10V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I 0.1 mA, short-circuit I >6.5 mA
Pulse/Pause ratio 20 ms / 20 ms
Output
output I: terminals 5, 6 ;
Connection
output II: terminals 7, 8
Output I signal ; relay
Output II signal or error message ; relay
Minimum switch current 2 mA / 24V DC
Energized/De-energized delay 20 ms / 20 ms
Features
Mechanical life 107 switching cycles
 1-channel isolated barrier Transfer characteristics
 24V DC supply (Power Rail) Switching frequency 10 Hz
 Dry contact or NAMUR inputs
Electrical isolation
 Relay contact output
reinforced insulation acc. to EN 50178, rated
 Fault relay contact output Input/Output
insulation voltage 300 Veff
 Housing width 12.5 mm reinforced insulation acc. to EN 50178, rated
 Up to SIL2 acc. to IEC 61508 Input/power supply
insulation voltage 300 Veff
reinforced insulation acc. to EN 50178, rated
This isolated barrier is used for intrinsic safety applications. It Output/power supply
insulation voltage 300 Veff
transfers digital signals (NAMUR sensors/mechanical
reinforced insulation acc. to EN 50178, rated
contacts) from a hazardous area to a safe area. The proximity Output/Output
insulation voltage 300 Veff
sensor or switch controls a form A normally open relay
Directive conformity
contact for the safe area load. The normal output state can
Electromagnetic compatibility
be reversed using switch S1. Switch S2 allows output II to be
switched between a signal output and an error message Directive 2004/108/EC EN 61326-1:2006
output. Switch S3 enables or disables line fault detection of Low voltage
the field circuit. Directive 2006/95/EC EN 61010-1:2010
Conformity
During an error condition, relays revert to their de-energized Electromagnetic compatibility NE 21
state and LEDs indicate the fault according to NAMUR NE44.
Protection degree IEC 60529
A unique collective error messaging feature is available when
used with the Power Rail system.

Due to its compact housing design and low heat dissipation,


this device is useful for detecting positions, end stops, and
switching states in space-criticalap plications.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 15


937 Intrinsic Safety Isolated Barriers

Switch Amplifier, Relay Output Front view


Removable terminals
with Splitter blue

1 2

1-ch, 24V DC, continued 3 4


LED green:
Power supply

937TH-DISRS-DC1 PWR
LED yellow/red:
Status output I/
OUT/CHK Fault signal
Environmental and Mechanical Specifications 1
2
S

Operating Temperature -20 ... 60 C (-4 ... 140 F) 3


4
I II

Switch 1 ... 4
Protection degree IP20
5 6
Mass approx. 100 g 7
9
8
10
Place for labeling

12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in) , Removable terminals


Dimensions
housing type A2 black

on 35 mm DIN mounting rail acc. to EN


Mounting
60715:2001
Data for application in connection with Ex-areas
Ex II (1)G [Ex ia Ga] IIC , Ex II (1)D [Ex ia Da] Product Features
Group, category, type of protection Cat. No. 937TH-DISRS-DC1
IIIC < Ex> I (M1) [Ex ia Ma] I
Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage Uo 10.5 V Configuration

Current Io 17.1 mA Switch position

Power Po 45 mW (linear characteristic) S


Mode of operation
Function
with high input current
Position
I
1 Output I (relay ) with low input current II
Supply 1
3
2
4
energize d
switching state like relay I I
Assignment
Maximum safe voltage Um 253V AC 2
Output II (relay )
fault signal output
(de-energized if fault)
II

ON I
Output I, II 1
3 Line fault detection
OFF II
4 no function
1

Maximum safe voltage Um 253V AC S


2
3
2
4
3
I II Operating status
253V AC/2 A/cos > 0.7; 126.5V AC/4 4
Contact loading I II
Control circuit Input signal
A/cos > 0.7; 30V DC/2 A resistive load 5
7
9
6
8
10
Initiator high impedance/
contact opened
low input current

Initiator low impedance/


Group, category, type of protection, contact closed
high input current
Ex II 3G Ex nA nC IIC T4 Gc Lead breakage,
temperature class lead short-circuit
Line fault

Output I, II Factory settings: switch 1, 2, 3 and 4 in position I

50V AC/2 A/cos > 0.7; 30V DC/2 A resistive


Contact loading
load
Configuration
Electrical isolation Cat. No. 937TH-DISRS-DC1
safe electrical isolation acc. to IEC/EN 60079-
Input/Output
11, voltage peak value 375 V
safe electrical isolation acc. to IEC/EN 60079-
Input/power supply
11, voltage peak value 375 V
Directive conformity
EN 60079-0:2009, EN 60079-11:2007 , EN
Directive 94/9/EC
60079-15:2005 , EN 61241-11:2006
114

12.5 119

Approximate Dimensions
Wiring Diagram Cat. No. 937TH-DISRS-DC1
Cat. No. 937TH-DISRS-DC1
16 Rockwell Automation Publication 937-SG001C-EN-P January 2015
937 Intrinsic Safety Isolated Barriers

Switch Amplifier Transistor


Specifications
Output
Description 24V, 2-channel
2-ch, 24V DC Signal Type Digital Input, Transistor Output
937TH-DISAT-DC2 Supply
Connection Power Rail or terminals 9+, 10-
Rated voltage 19 ... 30V DC
Ripple 10%
Rated current 30 ... 20 mA
800 mW including maximum power
Power loss
dissipation in the output
Power consumption
Input

Connection terminals 1+, 2-; 3+, 4-

Rated values acc. to EN 60947-5-6 (NAMUR)


Open circuit voltage/short-circuit current approx. 10V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I 0.1 mA, short-circuit I >6.5 mA
Pulse/Pause ratio 20 ms / 20 ms
Output
Connection terminals 5, 6; 7, 8
Output I signal ; Transistor
Output II signal ; Transistor
Features
Minimum switch current 2 mA / 24V DC
 2-channel isolated barrier Energized/De-energized delay 20 ms / 20 ms
 24V DC supply (Power Rail) Mechanical life 107 switching cycles
 Housing width 12.5 mm Transfer characteristics
 Up to SIL2 acc. to IEC 61508 Switching frequency 5 kHz
Electrical isolation
This isolated barrier is used for intrinsic safety applications. reinforced insulation acc. to EN 50178, rated
The device transfers digital signals (NAMUR sensors or dry Input/Output
insulation voltage 300 Ve
contacts) from a hazardous area to a safe area. Each input reinforced insulation acc. to EN 50178, rated
controls a passive transistor output. Via switches the mode of Input/power supply
insulation voltage 300 Ve
operation can be reversed and the line fault detection can be basic insulation according to EN 50178, rated
switched off. A fault is signalized by LEDs acc. to NAMUR Output/power supply
insulation voltage 50 Ve
NE44 and a separate collective error message output basic insulation according to EN 50178, rated
Output/Output
insulation voltage 50 Ve
Directive conformity
Electromagnetic compatibility Directive 2004/108/EC
Conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Protection against electrical shock IEC 61010-1:2010
Input EN 60947-5-6:2000

Rockwell Automation Publication 937-SG001C-EN-P January 2015 17


937 Intrinsic Safety Isolated Barriers

Switch Amplifier Transistor Front view Removable terminals


blue

Output
1 2 LED green:
2-ch, 24V DC, continued 3 4
Power supply

LED yellow/red:
937TH-DISAT-DC2 Status output/
PWR Fault signal channel I
1

Environmental and Mechanical Specifications 2


OUT/CHK
LED yellow/red:
Status output/
Operating Temperature -20 ... 60 C (-4 ... 140 F) S1
S2
Fault signal channel II
S3
S4

Protection degree IP20 I II

Switch 1 ... 4
Mass approx. 100 g 5 6
7 8
Place for labeling
12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in) , 9 10

Dimensions
housing type A2 Removable terminals
black
on 35 mm DIN mounting rail
Mounting
acc. to EN 60715:2001
Data for application in connection with Ex-areas
Ex II (1)G [Ex ia Ga] IIC
Product Features
Group, category, type of protection Ex II (1)D [Ex ia Da] IIIC Cat. No. 937TH-DISAT-DC2
Ex I (M1) [Ex ia Ma] I
Input Ex ia
Voltage Uo 10.5 V
1+ 5+
Current Io 17.1 mA I 10 k I
2- 6-
400 R 2 k
Power Po 45 mW (linear characteristic)
Supply 3+ 7+
II 10 k II
4- 8-
Maximum safe voltage Um 253V AC 400 R 2 k

Output
9+
10-
24 V DC
Maximum safe voltage Um 253V AC
Group, category, type of protection, ERR 24V DC
Ex II 3G Ex nA IIC T4 Gc Zone 0, 1, 2 Power Rail Zone 2
temperature class
Electrical isolation
safe electrical isolation acc. to Wiring Diagram
Input/Output
IEC/EN 60079-11, voltage peak value 375V Cat. No. 937TH-DISAT-DC2
safe electrical isolation acc. to
Input/power supply
IEC/EN 60079-11, voltage peak value 375V
Directive conformity Directive 94/9/EC
114

I (A)
4

1
12.5 119
0.5
0.4

0.15

20 30 50 100 200 U (V) Approximate Dimensions


40 115 253 Cat. No. 937TH-DISAT-DC2

Configuration
Cat. No. 937TH-DISAT-DC2

18 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Isolated Barriers

Specifications
Switch Amplifier, Transistor
Description 24V, 1-channel with splitter
Output with Splitter Signal Type Digital Input, Transistor Output
1-ch, 24V DC Supply
Connection Power Rail or terminals 9+, 10-
937TH-DISTS-DC1 Rated voltage 19 ... 30V DC
Ripple 10%
Rated current 30 ... 20 mA
800 mW including maximum power
Power loss
dissipation in the output
Input
Connection terminals 1+, 2-; 3+, 4-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 10V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I 0.1 mA, short-circuit I >6.5 mA
Pulse/Pause ratio 20 ms / 20 ms
Output
Connection terminals 5, 6; 7, 8
Output I signal ; Transistor
Output II signal ; Transistor
Minimum switch current 2 mA / 24V DC
Energized/De-energized delay 20 ms / 20 ms
Mechanical life 107 switching cycles
Features Transfer characteristics
Switching frequency 5 kHz
 1-channel isolated barrier
Electrical isolation
 24V DC supply (Power Rail)
reinforced insulation acc. to EN 50178,
 Housing width 12.5 mm Input/Output
rated insulation voltage 300 Veff
 Up to SIL2 acc. to IEC 61508
reinforced insulation acc. to EN 50178,
Input/power supply
rated insulation voltage 300 Veff
This isolated barrier is used for intrinsic safety applications.
basic insulation according to EN 50178,
The device transfers digital signals (NAMUR sensors or dry Output/power supply
rated insulation voltage 50 Veff
contacts) from a hazardous area to a safe area. The input
basic insulation according to EN 50178,
controls two passive transistor outputs. Via switches the Output/Output
rated insulation voltage 50 Veff
mode of operation can be reversed and the line fault
Directive conformity
detection can be switched off. Via switch the function of the
Electromagnetic compatibility Directive 2004/108/EC
second output can be defined as a signal output or an error
output. A fault is signalized by LEDs acc. to NAMUR NE44 and Conformity
a separate collective error message output. Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Protection against electrical shock IEC 61010-1:2010
Input EN 60947-5-6:2000

Rockwell Automation Publication 937-SG001C-EN-P January 2015 19


937 Intrinsic Safety Isolated Barriers

Switch Amplifier, Transistor Front view

Removable terminal
Output with Splitter blue

1 2

1-ch, 24V DC, continued 3 4


LED green:
Power supply

937TH-DISTS-DC1 PWR
LED yellow/red:
Status output/
OUT/CHK
Fault signal
S1

Environmental and Mechanical Specifications S2


S3
S4

Operating Temperature -20 ... 60 C (-4 ... 140 F) I II

Switch 1 ... 4
Protection degree IP20 5 6
7 8
9 10 Place for labeling
Mass approx. 100 g
Removable terminals
12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in) , black
Dimensions
housing type A2
on 35 mm DIN mounting rail acc. to EN
Mounting
60715:2001
Data for application in connection with Ex-areas Product Features
Input Cat. No. 937TH-DISTS-DC1
Voltage 10.5 V
Current 17.1 mA 1+ 5+
10 k I
Power 45 mW (linear characteristic) 400 R 2 k
2- 6-

Supply
Maximum safe voltage 253V AC 7+
II
8-
Output
Maximum safe voltage 253V AC
9+
24 V DC
Group, category, type of protection, 10-
Ex II 3G Ex nA IIC T4 Gc
temperature class
ERR 24V DC

Electrical isolation Zone 0, 1, 2 Power Rail Zone 2

safe electrical isolation acc. to Wiring Diagram


Input/Output Cat. No. 937TH-DISTS-DC1
IEC/EN 60079-11, voltage peak value 375 V
safe electrical isolation acc. to
Input/power supply
IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
EN 60079-0:2012 , EN 60079-11:2012 ,
Directive 94/9/EC
EN 60079-15:2010

S1
S1
S2 S2
S3
S4
I II
S3
S4
I II
114

Configuration
12.5 119 Cat. No. 937TH-DISTS-DC1

Approximate Dimensions
Cat. No. 937TH-DISTS-DC1

20 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Isolated Barriers

Specifications
Solenoid Driver
Decription 24V DC, 1-channel
1-ch, 24V DC Signal Type Digital Output
Supply
937TH-DOSND-IP1 Connection Loop powered
Power loss 1W
Input
Connection terminals 5, 6
Rated voltage Ui 19 ... 30V DC
72 mA at Ui = 19 V, 50 mA at Ui =
30 V with 265 W output load
45 mA at Ui = 19 V, 31 mA at Ui =
Current
30 V with shorted output
14 mA at Ui = 19 V, 11 mA at Ui =
30 V no load at output
Inrush current 200 mA after 100 ms
Output
Connection terminals 1+, 2-
Internal resistor Ri 238
Current Ie 45 mA
Voltage Ue 12 V
Features Open loop voltage Us 22.7 V
Output rated operating current 45 mA
 1-channel isolated barrier
These values are valid for the rated
 24V DC supply (loop powered) Output signal
operating voltage 19 ... 30V DC.
 Current limit 45 mA at 12V DC single operation: typ. 1.7 ms/50 ms;
 Housing width 12.5 mm Energized/De-energized delay
periodical: typ. 5 ms/50 ms
 Up to SIL3 acc. to IEC 61508

This isolated barrier is used for intrinsicsafety applications. It


supplies power to solenoids, LEDs, and audible alarms
located in a hazardous area. It is loop powered, so the
available energy at the output is received from the input
signal. The output signal has a resistive characteristic. As a
result the output voltage and current are dependent on the
load and the input voltage. At full load, 12 V at 45 mA is
available for the hazardous area application.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 21


937 Intrinsic Safety Isolated Barriers

Solenoid Driver
1-ch, 24V DC, continued
937TH-DOSND-IP1

Environmental and Mechanical Specifications


Operating temperature -20 ... 60 C (-4 ... 140 F)
Protection degree IP20
Weight approx. 100 g
12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in) ,
Dimensions Removable terminal
housing type A2 black

Mounting 35 mm DIN Rail per EN 60715:2001


Data for application in connection with Ex-areas
Ex II (1)G [Ex ia Ga] IIC , Ex II (1)D [Ex ia Da] IIIC , Product Features
Group, category, type of protection Ex I (M1) [Ex ia Ma] I Cat. No. 937TH-DOSND-IP1
[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Output
Voltage Uo 25.2 V
Current Io 110 mA
Power Po 693 mW
Input
Maximum safe voltage Um 250V
Group, category, type of protection,
Ex II 3G Ex nA IIC T4 Gc
temperature class
Electrical isolation
safe electrical isolation acc. to IEC/EN 60079-11, Wiring Diagram
Input/Output
voltage peak value 375V Cat. No. 937TH-DOSND-IP1
Directive conformity
EN 60079-0:2009, EN 60079-11:2007 ,
Directive 94/9/EC
EN 60079-15:2005 , EN 61241-11:2006

114

12.5 112

Approximate Dimensions
Cat. No. 937TH-DOSND-IP1

22 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Isolated Barriers

SMART Power Supply Specifications


Desciption 24V DC, 1-channel
1-ch, 24V DC Signal Type Analog input
Supply
937TH-AITXP-DC1 Connection Power Rail or terminals 9+, 10-
Rated voltage 19 ... 30V DC
Ripple 10 %
Rated current 45 mA
Power loss 800 mW
Power consumption 1.1 W
Input
Connection terminals 1+, 2-; 3+, 4-
Input signal 4 ... 20 mA limited to approx. 30 mA
Open circuit
voltage/short-circuit terminals 1+, 2-: 22 V / 30 mA
current
Voltage drop terminals 3+, 4- : approx. 5 V
Available voltage terminals 1+, 2-: 15 V at 20 mA
Output
Connection terminals 5-, 6+
Load 0 ... 300 W (source mode)
4 ... 20 mA or 1 ... 5 V (on 250 W, 0.1 % internal shunt)
Output signal
4 ... 20 mA (sink mode), operating voltage 15.5 ... 26 V
Ripple 20 mV rms
Transfer characteristics
at 20 C (68 F)
Features 0.1 % incl. non-linearity and hysteresis (source mode 4 ... 20 mA)
Deviation
0.2 % incl. non-linearity and hysteresis (sink mode 4 ... 20 mA)
 1-channel isolated barrier
0.2 % incl. non-linearity and hysteresis (source mode 1 ... 5 V)
 24V DC supply (Power Rail)
< 2 mA/K (0 ... 60 C (32 ... 140 F)); < 4 mA/K (-20 ... 0 C (-4 ... 32 F))
 Input for 2-wire SMART transmitters and current sources
Inuence of ambient (source mode and sink mode 4 ... 20 mA)
 Output for 4 mA ... 20 mA or 1 V ... 5 V temperature < 0.5 mV/K (0 ... 60 C (32 ... 140 F)); < 1 mV/K (-20 ... 0 C (-4 ... 32 F))
 Sink or source mode (source mode 1 ... 5 V)
 Housing width 12.5 mm eld side into the control side:
 Up to SIL2 acc. to IEC 61508 bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Frequency range
control side into the eld side:
This isolated barrier is used for intrinsic safety applications. bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
The device supplies 2-wire SMART transmitters in a Settling time 200 ms
hazardous area, and can also be used with 2-wire SMART Rise time/fall time 20 ms
current sources. It transfers the analog input signal to the Electrical isolation
safe area as an isolated current value. Digital signals may be
superimposed on the input signal in the hazardous or safe Input/Output reinforced insulation acc. to EN 50178, rated insulation voltage 300Ve
area and are transferred bi-directionally. Selectable output of
current source, sink mode, or voltage output is available via Input/power supply reinforced insulation acc. to EN 50178, rated insulation voltage 300Ve
DIP switches. If the HART communication resistance in the Output/power
reinforced insulation acc. to EN 50178, rated insulation voltage 300Ve
loop is too low, the internal resistance of 250 between supply
terminals 6 and 8 can be used. Test sockets for the Directive conformity
connection of HART communicators are integrated into the Electromagnetic compatibility
terminals of the device. Directive
EN 61326-1:2006
2004/108/EC
Conformity
Electromagnetic
NE 21:2006
compatibility
Protection degree IEC 60529:2001

Rockwell Automation Publication 937-SG001C-EN-P January 2015 23


937 Intrinsic Safety Isolated Barriers

SMART Power Supply Front view

Removable terminals
1-ch, 24V DC, continued blue

937TH-AITXP-DC1 1
3
2
4

LED green:
Power supply
Environmental and Mechanical Specifications
Ambient temperature -20 ... 60 C (-4 ... 140 F) PWR

Protection degree IP20 S1


S2
S3

Weight approx. 100 g S4


I II

Switch 1 ... 4
12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 in),
Dimensions 5 6
housing type A2 7 8
9 10
Place for labeling

Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001 Removable terminals


black
Data for application in connection with Ex-areas
<Ex>II (1)G [Ex ia Ga]IIC , <Ex> II (1)D[Ex ia Da] IIIC,
Group, category, type of protection
<Ex> I (M1) [Ex ia Ma] I
Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Product Features
Supply Cat. No. 937TH-AITXP-DC1

Maximum safe voltage Um 250V AC


Equipment terminals 1+, 2-
Operating mode
Voltage Uo 25.2 V Output as current source
S1 4 mA ... 20 mA
Current Io 100 mA S2
Power Po 630 mW S3
S4
Equipment terminals 3+, 4-
I II
PWR

Voltage Ui < 30 V Output as voltage source


S1 1 V ... 5 V
Current Ii < 128 mA S1
S2 S2
S3

Voltage Uo 7.2 V S4
S3
I II

S4
Current Io 100 mA
I II
Power Po 25 mW
Output as current sink
S1 4 mA ... 20 mA
Group, category, type of protection, S2
<Ex> II 3G Ex nA IIC T4 Gc
temperature class S3
Electrical isolation S4

safe electrical isolation acc. to IEC/EN 60079-11, I II


Input/Output
voltage peak value 375V
safe electrical isolation acc. to IEC/EN 60079-11, Configuration
Input/power supply Cat. No. 937TH-AITXP-DC1
voltage peak value 375V
Directive conformity
EN 60079-0:2009, EN 60079-11:2007, 12.7 mm 114 mm (4.49'')
Directive 94/9/EC EN 60079-15:2005 , EN 60079-26:2007, (0.5")

EN 61241-11:2006 , EN 50303:2000
46 mm (1.82'')

1+
104 mm (4.1'')

119 mm (4.7'')
HART

7-

2- 5-
HART

3+ V
58 mm (2.28'')

6+
HART

250
mA 8+

4-

9+
10-
24 V DC

Zone 0, 1, 2 24 V DC
Zone 2
Approximate Dimensions
Div. 1, 2 Power Rail
Div. 2 Cat. No. 937TH-AITXP-DC1
Wiring Diagram
Cat. No. 937TH-AITXP-DC1

24 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Isolated Barriers

SMART Power Supply


2-ch, 24V DC Specifications
937TS-AITXP-DC2 Desciption 24V DC, 2-channel
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage 20 ... 35V DC
Ripple within the supply tolerance
Power loss 1.8 W
Power consumption 2.7 W
Input
Connection terminals 1+, 3-; 4+, 6-
Input signal 0/4 ... 20 mA
Available voltage 16 V at 20 mA, terminals 1+, 3
Output
Connection terminals 7-, 8+; 10-, 11+
Load 0 ... 550 Ohm
Output signal 0/4 ... 20 mA (overload > 25 mA)
Ripple 50 mA rms
Transfer characteristics
at 20 C (68 F), 0/4 ... 20 mA
 2-channel isolated barrier Deviation 10 mA incl. calibration, linearity, hysteresis, loads
 24V DC supply (Power Rail) and uctuations of supply voltage
 Input 2-wire SMART transmitters Inuence of ambient temperature 0.25 A/K
 Output for 0/4... 20 mA
eld side into the control side: band width with 1 Vpp
 Terminals with test points signal 0 ... 7.5 kHz (-3 dB)
 Up to SIL2 acc. to IEC 61508
Frequency range
This isolated barrier is used for intrinsic safety applications. safe area to hazardous area: band width with 1 VSS
The device supplies 2-wire SMART transmitters in a signal 0.3 ... 7.5 kHz (-3 dB)
hazardous area. It transfers the analog input signal to the safe
area as an isolated current value. Settling time 200 s

Rise time/fall time 20 s


Digital signals may be superimposed on the input signal in
the hazardous or safe area and are transferred bi- Electrical isolation
directionally. Output/power supply functional insulation, rated insulation voltage 50V AC
Output/Output functional insulation, rated insulation voltage 50V AC
If the HART communication resistance in the loop is too low, Directive conformity
the internal resistance of 250 between terminals 8, 9 and Electromagnetic compatibility
11, 12 can be used. Directive 2004/108/EC EN 61326-1:2006
Conformity
Test sockets for the connection of HART communicators are
integrated into the terminals of the device. Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
The device supports the following SMART protocols: Protection against electrical shock UL 61010-1:2004

 HART
 BRAIN
 Foxboro

Rockwell Automation Publication 937-SG001C-EN-P January 2015 25


937 Intrinsic Safety Isolated Barriers

SMART Power Supply Front view


Removable terminals
blue

2-ch, 24V DC, continued


937TS-AITXP-DC2 1 2
4 5
3
6

Environmental and Mechanical Specifications LED green:


PWR Power supply
Ambient temperature -20 ... 60 C (-4 ... 140 F)
Protection degree IP20
Weight approx. 150 g
7 8 9
20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), 10 11 12
Dimensions 13 14 15

housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001 Removable terminals
black
Data for application in connection with Ex-areas
Ex II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD],
Group, category, type of protection [Ex ia] I (-20 C Tamb 60 C)
[circuit(s) in zone 0/1/2] Product Features
Cat. No. 937TS-AITXP-DC2
Input Ex ia IIC
Voltage 25.2 V
Current 93 mA
1+ 7-
Power 0.586 W

HART

HART
I
3- 8+
Supply
9
250
Maximum safe voltage 250V
4+ 10-

HART
Group, category, type of protection,

HART
II
Ex II 3G Ex nA II T4 [device in zone 2] 6- 11+
temperature class
12
250
Electrical isolation
14+
15-
24 V DC
safe electrical isolation acc. to IEC/EN 60079-11,
Input/Output
voltage peak value 375 V
Zone 0, 1, 2 24 V DC Zone 2
safe electrical isolation acc. to IEC/EN 60079-11, Div. 1, 2 Power Rail Div. 2
Input/power supply
voltage peak value 375 V
Directive conformity Wiring Diagram
EN 60079-0:2012 , EN 60079-11:2007 , Cat. No. 937TS-AITXP-DC2
Directive 94/9/EC
EN 60079-15:2010 , EN 61241-11:2006
20 mm 115 mm (4.5'')
(0.78")
=

107 mm (4.21'')
93 mm (3.66'')
=

Approximate Dimensions
Cat. No. 937TS-AITXP-DC2

26 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Isolated Barriers

Specifications
SMART Power Supply
Desciption 24V DC, 1-channel with Splitter
with Splitter Signal Type Analog input
1-ch, 24V DC Supply
Connection Power Rail or terminals 9+, 10-
937TH-AITXS-DC1 Rated voltage 18 ... 30V DC
Ripple within the supply tolerance
Rated current
approx. 1.4 W at 20 mA transfer
Power loss
current, 250 W in both outputs
Power consumption 2W
Input
Connection terminals 1+, 2- (sink); 3+, 4- (source)
Input signal 0/4 ... 20 mA
Voltage drop 6.1 V at 20 mA (terminals 3, 4)
terminals 3+, 4-: 310
Input Resistance
terminals 1+, 2-: 500 (250 load)
Available voltage 15 vat 20 mA terminals 1+, 2-
Output
source: terminals 5-, 6+; 7-, 8+
Connection
sink: terminals 5+, 6-, 7+, 8-
channel 1: 0 ... 500
Features Load
channel 2: 0 ... 500
 1-channel isolated barrier Output signal 0/4 ... 20 mA or 0/1 ... 5 V
 24V DC supply (Power Rail) Ripple 50 A rms
 Input for 2-wire SMART transmitters and current sources Transfer characteristics
 Signal splitter (1 input and 2 outputs) Iout < 20 mA; Vout < 7.5 mV incl. calibration,
Deviation
 Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V linearity, hysteresis and uctuation of supply voltage,
 Terminal blocks with test sockets at 20 C (68 F), 0/4 ... 20 mA, 0/1 ... 5 V
 Up to SIL2 acc. to IEC 61508 Inuence of ambient temperature 0.25 A/K
eld side into the control side: bandwidth with 0.5 Vpp
This isolated barrier is used for intrinsic safety applications. Frequency range
signal 0 ... 7.5 kHz (-3 dB)
The device supplies 2-wire transmitters in the hazardous area,
control side into the eld side: bandwidth with 0.5 Vpp
and can also be used with current sources. It transfers the signal 0.3 ... 7.5 kHz (-3 dB)
analog input signal to the safe area as two isolated output
Settling time 200 s
signals. Bi-directional communication is supported for SMART
transmitters that use current modulation to transmit data Rise time/fall time 20 s
and voltage modulation to receive data. The output is Electrical isolation
selected as a current source, current sink, or voltage source Output/power supply functional insulation, rated insulation voltage 50V AC
via switches. Test sockets for the connection of HART Output/Output functional insulation, rated insulation voltage 50V AC
communicators are integrated into the terminals of the Directive conformity
device. Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Conformity
Electromagnetic compatibility NE 21:2006
Protection degree IEC 60529:2001
Protection against electrical shock UL 61010-1

Rockwell Automation Publication 937-SG001C-EN-P January 2015 27


937 Intrinsic Safety Isolated Barriers

SMART Power Supply Front view

with Splitter, continued Removable terminals


blue

1-ch, 24V DC, continued 1 2


3 4

937TH-AITXS-DC1 LED green:


Power supply

PWR

Environmental and Mechanical Specifications S1


S2

Ambient temperature -20 ... 60 C (-4 ... 140 F) S3


S4
I II

Protection degree IP20 Switches S1, S2, S3, S4


5 6
Weight approx. 100 g 7 8
9 10
Place for labeling

12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 in), Removable terminals


Dimensions
housing type A2 black

Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001


Data for application in connection with Ex-areas
<Ex> II (1)G [Ex ia Ga] IIC , <Ex> II (1)D [Ex ia Da]
Group, category, type of protection
IIIC , <Ex> I (M1) [Ex ia Ma] I
Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Product Features
Supply Cat. No. 937TH-AITXS-DC1

Maximum safe voltage Um 250V


Equipment terminals 1+, 2-
Voltage Uo 25.2V
- +
Voltage Uq 28.2V 1+ 5 + V

HART
HART
I
+ -

HART
Current Io 93 mA 6
2-
Power Po 656 mW 3+
- +
7
HART

Equipment terminals 3+, 4- mA + V


II
+ -
4- 8
Voltage Ui 30V
Current Ii 115 mA 9+
24 V DC
10-
Power Pi 700 mW
Zone 0, 1, 2 24V DC Zone 2
Voltage Uo 5V Div. 1, 2 Power Rail Div. 2
Current Io 6.8 mA
Power Po 1.6 mW
Output Wiring Diagram
Cat. No. 937TH-AITXS-DC1
Maximum safe voltage Um 250V
Group, category, type of protection,
<Ex> II 3G Ex nA II T4 Gc [device in zone 2]
temperature class 12.7 mm
(0.5")
114 mm (4.49'')

Electrical isolation
safe electrical isolation acc. to IEC/EN 60079-11,
Input/Output
46 mm (1.82'')

voltage peak value 375 V


safe electrical isolation acc. to IEC/EN 60079-11,
Input/power supply
104 mm (4.1'')

119 mm (4.7'')

voltage peak value 375 V


Directive conformity
58 mm (2.28'')

EN 60079-0:2009, EN 60079-11: 2012,


Directive 94/9/EC
EN 60079-15: 2010

Approximate Dimensions
Cat. No. 937TH-AITXS-DC1

28 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Isolated Barriers

Specifications
Temperature Repeater
Description 24V DC, 1-channel
1-ch, 24V DC Signal Type Digital Output
937TH-AIRRP-DC1 Supply
Connection Power Rail or terminals 9+, 10-
Rated voltage 19 ... 30V DC
Ripple within the supply tolerance
Rated current <20 mA
Power consumption 0.35 W (24 V and 1 mA sense current)
Input
Connection terminals 1, 2, 3, 4
Line fault detection yes , at Pt100
Lead resistance <10 % of resistance value
Transmission range 0 ... 10 mA
Available voltage 9V
Line fault detection 50 nA
Output
Connection terminals 5-, 7-, 6+, 8+
Current 0 ... 10 mA
Available voltage 0 ... 7 V
Features <10 or >400 , depending on lead disconnected
Fault signal
(measuring current 1 mA)
Transfer characteristics
 1-channel isolated barrier
 24V DC supply (Power Rail) Im 1 mA: 0.1 % of Rm or 0.1
(the larger value is applicable)
 Resistance and RTD input (Pt100, Pt500, Pt1000)
Deviation Im < 1 mA: accuracy reduces in proportion to Im.
 Resistance output
e. g. Im = 0.1 mA: 1 % of Rm or 1 (the larger value
 Accuracy 0.1 % is applicable).
 Line fault detection (LFD) for Pt100
Im 1 mA, Rm 100 : 0.01 %/K in the range -20 ...
 Housing width 12.5 mm +60 C (253 ... 333 K)
Inuence of ambient temperature
Im < 1 mA or Rm < 100 : temperature stability
This isolated barrier is used for intrinsic safety applications. It reduces in proportion to Im or Rm
transfers resistance values of RTDs or potentiometers from signal response time 2 ms (10 ... 90 %)
hazardous areas to safe areas. A 2-, 3-, or 4-wire technique is response to application of Im: Rm >
available depending on the required accuracy. The input card 50 and Im < 5mA: < 5ms
of the control system measures the same load as if it were Rise time response to application of Im: Rm >
connected directly to the resistance in a hazardous area. 30 and Im < 5mA: < 10ms
response to application of Im: Rm >
18 and Im < 5mA: <20ms
Electrical isolation
reinforced insulation acc. to EN 50178,
Input/Output
rated insulation voltage 300 Ve
reinforced insulation acc. to EN 50178,
Input/power supply
rated insulation voltage 300 Ve
Output/power supply functional insulation, rated insulation voltage 50V AC
Directive conformity
Electromagnetic compatibility Directive
EN 61326-1:2006
2004/108/EC
Directive 2004/108/EC EN 61326-1:2006
Conformity
Electromagnetic compatibility NE 21:2006
Protection degree IEC 60529:2001
Protection against electrical shock UL 61010-1

Rockwell Automation Publication 937-SG001C-EN-P January 2015 29


937 Intrinsic Safety Isolated Barriers

Temperature Repeater Front view


Removable terminals
blue

1-ch, 24V DC, continued


LED green:
937TH-AIRRP-DC1
1 2
3 4
Power supply

PWR

Environmental and Mechanical Specifications


S1

Operating temperature -20 ... 60 C (-4 ... 140 F) I II

Switch S1
Protection degree IP20
Weight approx. 100 g 5 6
7 8
9 10 Place for labeling
12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in),
Dimensions
housing type A2
Removable terminals
Mounting 35 mm DIN Rail per EN 60715:2001 black

Product Features
Cat. No. 937TH-AIRRP-DC1

Measuring curr ent


I (mA)

10

4+ 6+
6
3+ 8+
4
mA

2 1- 7-
0.5
2- 5-
2 4 6 8 8.4 10 12 k
Max. resistance
of sensor

9+
10-
24 V DC

Zone 0, 1, 2 24V DC Zone 2


Div. 1, 2 Power Rail Div. 2

Output Curve Wiring Diagram


Cat. No. 937TH-AIRRP-DC1 Cat. No. 937TH-AIRRP-DC1

12.7 mm 114 mm (4.49'')


(0.5")

46 mm (1.82'')
2-wi re technique 3-wi re technique 3-wi re technique 4-wi re technique
negativ e positiv e
measuring lin e measuring lin e
104 mm (4.1'')

119 mm (4.7'')

8 6 5 7 8 6 5 7 8 6 5 7 8 6 5 7
+ + - - + + - - + + - - + + - -
58 mm (2.28'')

DCS , PL C, DCS , PL C, DCS , PL C, DCS , PL C,


Signal Signal Signal Signal
converter converter converter converter

Approximate Dimensions
Cat. No. 937TH-AIRRP-DC1

Connection Types
Cat. No. 937TH-AIRRP-DC1

30 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Isolated Barriers

Specifications
SMART Current Driver
Description 24V DC, 1-channel
1-ch, 24V DC
Signal Type Analog Output
937TH-AOSCD-DC1 Supply
Connection Power Rail or terminals 9+, 10-
Rated voltage 19 ... 30V DC
Ripple 10 %
Rated current 30 mA
Power loss 600 mW
Power consumption 700 mW
Input
Connection terminals 5-, 6+
Input signal 4 ... 20 mA limited to approx. 30 mA
depending on switch conguration
Input voltage open loop voltage of the control system < 23V
open loop voltage of the control system < 27V
depending on switch conguration
open loop voltage of the control system < 23V:
Voltage drop approx. 6 V at 20 mA
open loop voltage of the control system < 27V:
approx. 10 V at 20 mA
Features Input resistance >100 k, with field wiring open
Output
 1-channel isolated barrier
 24V DC supply (Power Rail) Connection terminals 1+, 2-
 Current output up to 650 Ohm load Current 4 ... 20 mA
 HART I/P and valve positioner Load 0 ... 650
 Lead breakage monitoring Voltage 13V at 20 mA
 Accuracy 0.1 % Ripple 20 mVrms
 Housing width 12.5 mm Transfer characteristics
 Up to SIL2 acc. to IEC 61508 at 20 C (68 F), 0/4 ... 20 mA
Deviation
0.1 % incl. non-linearity and hysteresis
This isolated barrier is used for intrinsic safety applications. It Inuence of ambient < 2 mA/K (0 ... 60 C (32 ... 140 F));
drives SMART I/P converters, electrical valves, and positioners temperature < 4 mA/K (-20 ... 0 C (-4 ... 32 F))
in hazardous areas. Digital signals are superimposed on the eld side into the control side:
analog values at the field or control side and are transferred bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
bi-directionally. Current transferred across the DC/DC Frequency range
control side into the eld side:
converter is repeated at terminals 1 and 2. An open field bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
circuit presents a high input impedance to the control side Rise time 10 to 90 % 100 ms
to allow lead breakage monitoring by control system. If the
Electrical isolation
loop resistance for the digital communication is too low, an
Input/Output
internal resistor of 250 between terminals 6 and 8 is reinforced insulation acc. to EN 50178,
available, which may be used as the HART communication Input/power supply
rated insulation voltage 300Ve
resistor. Sockets for the connection of a HART communicator Output/power supply
are integrated into the terminals of the device. Directive conformity
Directive 2004/108/EC EN 61326-1:2006
Electromagnetic compatibility NE 21
Protection degree IEC 60529

Rockwell Automation Publication 937-SG001C-EN-P January 2015 31


937 Intrinsic Safety Isolated Barriers

SMART Current Driver Front view


Removable terminals
blue
1-ch, 24V DC, continued
LED green:
937TH-AOSCD-DC1 1
3
2
4 Power supply

Environmental and Mechanical Specifications PWR

Operating temperature -20 ... 60 C (-4 ... 140 F) S1


S2
S3
Protection degree IP20 S4
I II
Switch 1 ... 4
Weight approx. 100 g
5 6
12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in) 7 8
9 10 Place for labeling
Dimensions
housing type A2
Mounting 35 mm DIN Rail per EN 60715:2001 Removable terminals
black
Data for application in connection with Ex-areas
<Ex> II (1)G [Ex ia Ga] IIC , <Ex> II (1)D [Ex ia Da]
Group, category, type of protection
IIIC , <Ex> I (M1) [Ex ia Ma] I
Product Features
Output [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Cat. No. 937TH-AOSCD-DC1
Supply
Maximum safe voltage Um 250V AC
1+ 7-
Equipment terminals 1+, 2-

HART
5-

HART
mA
Voltage Uo 25.2V

P
6+
2-
Current Io 100 mA 250
8+

Power Po 630 mW
Group, category, type of protection,
<Ex> II 3G Ex nA IIC T4 Gc
temperature class 9+
10-
24 V DC

Electrical isolation
Zone 0, 1, 2 24 V DC Zone 2
safe electrical isolation acc. to IEC/EN 60079-11, Div. 1, 2 Power Rail Div. 2
Input/Output
voltage peak value 375 V Wiring Diagram
safe electrical isolation acc. to IEC/EN 60079-11, Cat. No. 937TH-AOSCD-DC1
Output/power supply
voltage peak value 375 V
Directive conformity
EN 60079-0:2009, EN 60079-11:2007 ,
Directive 94/9/EC EN 60079-15:2005 , EN 60079-26:2007 ,
EN 61241-11:2006 , EN 50303:2000 1 2
3 4

PWR

S1
S1
S2
S3
S2
S4
I II S3
S4
114

5 6
7 8 I II
9 10

12.5 122

Configuration
Approximate Dimensions Cat. No. 937TH-AOSCD-DC1
Cat. No. 937TH-AOSCD-DC1

32 Rockwell Automation Publication 937-SG001C-EN-P January 2015


Converter Barriers

Converters add functionality to the isolators by receiving signals from a hazardous area instrument e.g.,
temperature sensors, or load cells and then converting them to an industry standardized signal such as
0/420mA or 0/210V. Pulse evaluation units process a frequency signal at the input. A lead fault
monitoring system signals a lead breakage or lead short-circuit on the signal cables.

Universal Temperature Strain Gauge Converters


Converters Strain Gauge Converters are used
Universal Temperature Converters with strain gauges, load cells and
are designed to connect RTDs, resistance measuring bridges.
thermocouples or potentiometers
in the hazardous area, and
provide a proportional 0/4 mA ...
20 mA signal to the safe area.

Universal Frequency Converters


Universal Frequency Converters
Transmitter Supply Converters change a digital input (NAMUR
Transmitter Supply Converters sensor/mechanical contact) into a
supply 2-wire and 3-wire proportional, adjustable
transmitters in a hazardous area, 0/4 mA ... 20 mA analog output
and can also be used with active and functions as a switch amplifier
current sources. and a trip alarm.

HART Loop Converters FDT Interface


HART Loop Converters provide Configuring converter modules is convenient with a PC
power to transmitters or can be using Field Device Tool (FDT) software. Some
connected to existing HART loops specialized functions can only be selected using the
in parallel. They are able to FDT. The FDT interface is the specification describing
evaluate up to four HART variables the standardized data exchange between devices and
(PV, SV, TV, QV). Of those four control system or engineering or asset management
HART variables, the data tools. Examples include: PACTwareTM , FieldCare,
contained in any three of them FactoryTalk AssetCentre, and Process Device
can be converted to three Configuration. FDT frame software can be downloaded
different 4 mA ... 20 mA current at http://www.pactware.com. PACTware is trademark of
signals. PACTware Consortium

Rockwell Automation Publication 937-SG001C-EN-P January 2015 33


937 Intrinsic Safety Converter Barriers

Catalog Number Explanation


Note: Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; some combinations may not produce a valid catalog number.

937C U AI TXF - KD 1
a b c - d e

a c d
Module Prole Functionality Power
Code Description Code Description Code Description
H High-density 12.5mm module TMP Converter, Temperature IP Input Loop Powered
S Standard 20 mm module FRQ Converter, Frequency with trip alarm DC 24V DC
U Universal 40 mm module TXF Converter, Transmitter Power Supply with trip alarm BC 20...90V DC/48...253V AC
HLP Converter, HART Loop Power KD 115V AC
STR Converter, Strain Gauge KF 230V AC

b  FDT Software required to program this module.

I/O Type
Code Description e
DI Digital In Channels
DO Digital Out Code Description
AI Analog In 1 Single Channel
AO Analog Out 2 Dual Channel

34 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Converter Barriers

Universal Temperature Converter


1-ch, 24V DC
937CS-AITMP-DC1
Specifications
Description 24V DC, 1-channel
Signal Type Analog Input
Supply
Connection terminals 14+, 15- or power feed module/Power Rail
Rated voltage 20 ... 30V DC
Ripple within the supply tolerance
Power loss/power consumption 0.98 W / 0.98 W
Input
Connection terminals 1, 2, 3, 4
type Pt10, Pt50, Pt100, Pt500, Pt1000
(EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST,
RTD Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)
Measuring current approx. 200 mA with RTD
Types of measuring 2-, 3-, 4-wire connection
Features
Lead resistance 50 per lead
 1-channel isolated barrier Measuring circuit monitoring sensor breakage, sensor short-circuit
 24V DC supply (Power Rail) type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
 TC, RTD, potentiometer or voltage input Thermocouples type L (DIN 43710: 1985)
 Current output 0/4 mA ... 20 mA type TXK, TXKH, TXA (P8.585-2001)
 Sink or source mode Cold junction compensation external and internal
 Configurable by PACTware Measuring circuit monitoring sensor breakage
 Line fault (LFD) and sensor burnout detection Voltage selectable within the range -100 ... 100 mV
 Up to SIL2 acc. to IEC 61508/IEC 61511
0 ... 20 k (2-wire connection),
Potentiometer
0.8 ... 20 k (3-wire connection)
This isolated barrier is used for intrinsic safety applications. It Input resistance 1 M (-100 ... 100 mV)
is designed to connect RTDs, thermocouples, or
Output
potentiometers in the hazardous area, and provide a
proportional 0/ 4 mA ... 20 mA signal to the safe area.The output I: terminal 7: source (-), sink (+),
Connection
terminal 8: source (+), terminal 9: sink(-)
barrier offers 3-port isolation between input, output, and
Output Analog current output
power supply.
Current range 0 ... 20 mA or 4 ... 20 mA
A removable terminal block is available for thermocouples Fault signal
downscale 0 or 2 mA, upscale 21.5 mA
when internal cold junction compensation is desired (Cat. (acc. NAMUR NE43)
No. 937A-TCJC). load 0...550
Source
open-circuit voltage 18V
A fault is indicated by a red flashing LED per NAMUR NE44 Voltage across terminals 5 ... 30 V. If the current is
and user-configured fault outputs. supplied from a source > 16.5 V,
series resistance of (V - 16.5)/0.0215 is needed,
Sink
The unit is easily programmed with the FDT configuration where V is the source voltage.
software. A collective error messaging feature is available The maximum value of the resistance is
when used with the Power Rail system. (V - 5)/0.0215

Rockwell Automation Publication 937-SG001C-EN-P January 2015 35


937 Intrinsic Safety Converter Barriers

Universal Temperature Converter


1-ch, 24V DC, continued
937CS-AITMP-DC1
Transfer characteristics Front view Removable terminals
blue
Deviation
Pt100: (0.06 % of measurement value in K + 0.1 % of
span + 0.1 K (4-wire connection)) 1 2
4 5
3
6

thermocouple: (0.05 % of measurement value in C +


LED green:
0.1 % of span + 1 K (1.2 K for types R and S)) Power supply
After calibration this includes 0.8 K error of LED red:
Fault signal ERR PWR

the cold junction compensation


PROGRAM

mV: (50 mV + 0.1 % of span) Programming jack

potentiometer: (0.05 % of full scale + 0.1 % of span, 7 8 9


10 11 12
(excludes errors due to lead resistance)) 13 14 15

deviation of CJC included:


Removable terminals
Pt100: (0.0015 % of measurement value in black
K +0.006 % of span)/K Tamb*)
thermocouple: (0.02 K + 0.005 % of measurement
value in C + 0.006 % of span)/K Tamb*)
Inuence of ambient temperature
mV: (0.01 % of measurement value + Product Features
0.006 % of span)/K Tamb*) Cat. No. 937CS-AITMP-DC1
Potentiometer: 0.006 % of span/K Tamb
Tamb = ambient temperature change
referenced to 23 C (296 K) K-CJC-**
+ 1 7
+
Inuence of supply voltage < 0.01 % of span V
- - 2 8+
T T T V
Inuence of load 0.001 % of output value per 100 3
9-

4
worst case value (sensor breakage and/or sensor short
circuit detection enabled)

Reaction time mV: 1 s, thermocouples with CJC: 1.1 s,


thermocouples with xed reference temperature: 1.1 s, 14+
24 V DC
3- or 4-wire RTD: 920 ms, 15-

2-wire RTD: 800 ms, Potentiometer: 2.05 s


Zone 0, 1, 2 ERR 24 V DC Zone 2
Electrical isolation Div. 1, 2 Power Rail Div. 2

functional insulation, rated insulation voltage 50V AC


Wiring Diagram
There is no electrical isolation between
Cat. No.937CS-AITMP-DC1
Output/supply, programming input the programming input and the supply.
The programming cable provides galvanic isolation
so that ground loops are avoided.
20 mm 115 mm (4.5'')
Directive conformity (0.78")

Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
46 mm (1.82'')

Conformity
104 mm (4.1'')

119 mm (4.7'')

Electromagnetic compatibility NE 21:2006


Protection degree IEC 60529:2001
58 mm (2.28'')

Protection against electrical shock UL 61010-1:2004


Environmental and Mechanical Specifications
Operating temperature -20 ... 60 C (-4 ... 140 F)
Protection degree IP20
Weight approx. 130 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 Approximate Dimensions
Cat. No. 937CS-AITMP-DC1
Mounting 35 mm DIN Rail per EN 60715:2001

36 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Converter Barriers

Frequency Converter
1-ch, 24V DC
Specifications
937CU-DIFRQ-DC1
Description 24V DC, 1-channel
Signal Type Digital Input
Supply
Connection terminals 23+, 24- or power feed module/Power Rail
Rated voltage 20 ... 30V DC
Rated Current approx. 100 mA
Power loss/power consumption 2 W / 2.2 W
Input
Input I: intrinsically safe: terminals 1+, 3-
Connection
Input II: non-intrinsically safe: terminals 13+, 14-
sensor acc. to EN 60947-5-6 (NAMUR)
Input I
or mechanical contact
Pulse duration > 50 s
Input frequency 0.001 ... 5000 Hz
Lead monitoring breakage I 0.15 mA; short-circuit I >6.5 mA
Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
Active/Passive I >4 mA (for min. 100 ms) / I< 1.5 mA
Open circuit voltage/ 18V /
short-circuit current 5 mA
Output
output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
Connection
Features outout III: terminasl 19+, 20-
output IV: terminals 8+, 7-
 1-channel isolated barrier
Output I, II signal, relay
 24V DC supply (Power Rail)
Mechanical life 5 x 107 switching cycles
 Input for NAMUR sensors or dry contacts
Energized/De-energized delay approx. 20 ms / approx. 20 ms
 Input frequency 1 mHz ... 5 kHz
 Current output 0/4 mA ... 20 mA Output III electronic output, passive
 Relay and transistor output Contact loading 40V DC
 Start-up override 1-signal: (L+) - 2.5V
Signal level (50 mA, short-circuit/overload proof)
 Line fault detection (LFD)
0-signal: switched off (off-state current 10 A)
 Up to SIL2 acc. to IEC 61508/IEC 61511
Output IV analog
This isolated barrier is used for intrinsic safety applications. Current range 0 ... 20 mA or 4 ... 20 mA
The device is a universal frequency converter that changes a Open loop voltage 24V DC
digital input signal into a proportional free adjustable Load 650 W
0/4 mA ... 20 mA analog output signal and functions as a downscale I 3.6 mA , upscale 21.5 mA
switch amplifier and a trip alarm. Fault signal
(acc. NAMUR NE43)
Collective error message Power Rail
The functions of the switch outputs (2 relay outputs and 1
potential free transistor output) are easily adjustable [trip
value display (min/max alarm), serially switched output, pulse
divider output, error signal output]. The device is easily
configured by the use of keypad or with the PACTware
configuration software. A fault is signalized by LEDs acc. to
NAMUR NE44 and a separate collective error
message output.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 37


937 Intrinsic Safety Converter Barriers

Frequency Converter
1-ch, 24V DC, continued Environmental and Mechanical Specifications
937CU-DIFRQ-DC1 Operating temperature -20 ... 60 C (-4 ... 140 F)
Protection degree IP20
Transfer characteristics Weight approx. 130 g
Input I 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) ,
Dimensions
Measurement range 0.001 ... 5000 Hz housing type B2
Resolution 0.1 % of the measurement value , 0.001 Hz Mounting 35 mm DIN Rail per EN 60715:2001
Accuracy 0.1 % of the measurement value , > 0.001 Hz Data for application in connection with Ex-areas
Measuring time < 100 ms <Ex> II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I
Group, category, type of protection
(-20 C Tamb 60 C)
0.003 %/K (30 ppm)
Inuence of ambient temperature Supply
Output I, II Maximum safe voltage Um 40V DC

Response delay 200 ms Input I terminals 1+, 3- Ex ia IIC, Ex iaD


Voltage Uo 10.1V
Output IV
Current Io 13.5 mA
Resolution < 10 mA
Power Po 34 mW (linear characteristic)
Accuracy < 20 mA Input II terminals 13+, 14- non-intrinsically safe
Inuence of ambient temperature 0.005 %/K (50 ppm) Maximum safe voltage Um 40V
Electrical isolation Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
reinforced insulation according to IEC/EN 61010-1, Maximum safe voltage Um 253V
Input I/other circuits
rated insulation voltage 300Ve
253V AC/2 A/cos > 0.7; 40V DC/2 A resistive load
reinforced insulation according to IEC/EN 61010-1, Contact loading
Output I, II/other circuits (TV 99 ATEX 1471)
rated insulation voltage 300Ve
Output III terminals 19+, 20- non-intrinsically safe
reinforced insulation according to IEC/EN 61010-1,
Mutual output I, II, III Maximum safe voltage Um 40V
rated insulation voltage 300Ve
Output IV terminals 8+, 7- non-intrinsically safe
Output III/ basic insulation according to IEC/EN 61010-1, rated
power supply and collective error insulation voltage 50Ve Maximum safe voltage Um 40V DC
Output III/ basic insulation according to IEC/EN 61010-1, rated Interface RS 232
start-up override insulation voltage 50Ve Maximum safe voltage Um 40V
basic insulation according to IEC/EN 61010-1, rated Group, category, type of protection,
Output III/IV <Ex> II 3G Ex nA nC IIC T4
insulation voltage 50Ve temperature class
Output IV/power functional insulation acc. to IEC 62103, rated insulation Output I, II
supply and collective error voltage 50Ve
Contact loading 50V AC/2 A/cos > 0.7; 40V DC/1 A resistive load
Start-up override/power supply functional insulation acc. to IEC 62103, rated insulation
Electrical isolation
and collective error voltage 50Ve
Interface/power supply functional insulation acc. to IEC 62103, rated insulation safe electrical isolation acc. to IEC/EN 60079-11,
Input I/other circuits
and collective error voltage 50Ve voltage peak value 375V
Directive conformity
basic insulation according to IEC/EN 61010-1, rated
Interface/output III EN 60079-0:2009, EN 60079-11:2007 , EN 60079-
insulation voltage 50Ve Directive 94/9/EC
Directive conformity
15:2005 , EN 60079-26:2007 , EN 61241-11:2006

Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Low voltage
Directive 2006/95/EC EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Protection degree IEC 60529:2001
Input EN 60947-5-6:2000

38 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Converter Barriers

Frequency Converter
1-ch, 24V DC, continued
937CU-DIFRQ-DC1
Front view
Removable terminal
blue

1 2 3 4 5 6
LED green:
Power supply LC display
1 PWR
IN/
CHK

LED yellow/red: OUT


1 2

Input pulses/ 3

fault signal ESC

RS232

OK
Keypad
LED yellow:
Output I ... III

Place for labeling


7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24

Programming jack Removable terminals


black

Product Features
Cat. No. 937CU-DIFRQ-DC1

400 R 2 k 10
1+ 11 I
12
10 k 10 k
16
3- 17 II
18
19+ III
20-
8+ IV
mA
7-
13+
14-

23+
24-
24 V DC

Zone 0, 1, 2 ERR 24 V DC Zone 2


Div. 1, 2 Power Rail Div. 2

Wiring Diagram
Cat. No.937CU-DIFRQ-DC1

40 mm (1.6") 115 mm (4.5'')


46 mm (1.82'')
104 mm (4.1'')

119 mm (4.7'')
58 mm (2.28'')

Approximate Dimensions
Cat. No. 937CU-DIFRQ-DC1

Rockwell Automation Publication 937-SG001C-EN-P January 2015 39


937 Intrinsic Safety Converter Barriers

Frequency Converter
1-ch, AC/DC
Specifications
937CU-DIFRQ-BC1 Description 20..90V DC/48...253V AC, 1-channel
Signal Type Digital Input
Supply
Connection terminals 23+, 24-
Rated voltage 20 ... 90V DC/48...253V AC 50..60Hz
Rated Current approx. 100 mA
Power loss/power consumption 2 W / 2.2 W
Input
Connection Input I: intrinsically safe: terminals 1+, 3-
Input II: non-intrinsically safe: terminals 13+, 14-
sensor acc. to EN 60947-5-6 (NAMUR) or
Input I
mechanical contact
Pulse duration > 50 s
Input frequency 0.001 ... 5000 Hz
Lead monitoring breakage I 0.15 mA; short-circuit I >6.5 mA
Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
Active/Passive I >4 mA (for min. 100 ms) / I< 1.5 mA
Open circuit voltage/ 18V /
short-circuit current 5 mA
Output
output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
Connection
Features outout III: terminasl 19+, 20-
output IV: terminals 8+, 7-
 1-channel isolated barrier
Output I, II signal, relay
 Universal usage at different power supplies
Mechanical life 5 x 107 switching cycles
 Input for NAMUR sensors or dry contacts
Energized/De-energized delay approx. 20 ms / approx. 20 ms
 Input frequency 1 mHz ... 5 kHz
 Current output 0/4 mA ... 20 mA Output III electronic output, passive
 Relay and transistor output Contact loading 40V DC
 Start-up override 1-signal: (L+) - 2.5V
Signal level (50 mA, short-circuit/overload proof)
 Line fault detection (LFD)
 Up to SIL2 acc. to IEC 61508/IEC 61511 0-signal: switched o (o-state current 10 mA)
Output IV analog
This isolated barrier is used for intrinsic safety applications. Current range 0 ... 20 mA or 4 ... 20 mA
The device is a universal frequency converter that changes a Open loop voltage 24V DC
digital input signal into a proportional free adjustable 0/4 mA Load 650
... 20 mA analog output signal and functions as a switch
downscale I 3.6 mA , upscale 21.5 mA
amplifier and a trip alarm. Fault signal
(acc. NAMUR NE43)

The functions of the switch outputs (2 relay outputs and 1


potential free transistor output) are easily adjustable [trip
value display (min/max alarm), serially switched output, pulse
divider output, error signal output]. The device is easily
configured by the use of keypad or with the PACTware
configuration software. A fault is signalized by LEDs acc. to
NAMUR NE44.

40 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Converter Barriers

Frequency Converter Environmental and Mechanical Specifications


Operating temperature -20 ... 60 C (-4 ... 140 F)
1-ch, AC/DC, continued Protection degree IP20

937CU-DIFRQ-BC1 Weight approx. 130 g


20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in),
Dimensions
Transfer characteristics housing type B2
Input I Mounting 35 mm DIN Rail per EN 60715:2001
Measurement range 0.001 ... 5000 Hz Data for application in connection with Ex-areas
Resolution 0.1 % of the measurement value , 0.001 Hz
<Ex> II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I
Group, category, type of protection
Accuracy 0.1 % of the measurement value , >0.001 Hz (-20 C Tamb 60 C)
Measuring time < 100 ms
Supply
Inuence of ambient temperature 0.003 %/K (30 ppm)
Maximum safe voltage Um 253V AC / 125V DC
Output I, II
Input I terminals 1+, 3- Ex ia IIC, Ex iaD
Response delay 200 ms
Voltage Uo 10.1V
Output IV
Current Io 13.5 mA
Resolution < 10 mA
Power Po 34 mW (linear characteristic)
Accuracy < 20 mA
Input II terminals 13+, 14- non-intrinsically safe
Inuence of ambient temperature 0.005 %/K (50 ppm) Maximum safe voltage Um 40V
Electrical isolation Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
reinforced insulation according to IEC/EN 61010-1, Maximum safe voltage Um 253V
Input I/other circuits
rated insulation voltage 300Ve
253V AC/2 A/cos >0.7; 40V DC/2 A resistive load
reinforced insulation according to IEC/EN 61010-1, Contact loading
Output I, II/other circuits (TV 99 ATEX 1471)
rated insulation voltage 300Ve
Output III terminals 19+, 20- non-intrinsically safe
reinforced insulation according to IEC/EN 61010-1,
Mutual output I, II, III Maximum safe voltage Um 40V
rated insulation voltage 300Ve
reinforced insulation according to IEC/EN 61010-1, Output IV terminals 8+, 7- non-intrinsically safe
Output III/power supply
rated insulation voltage 300Ve Maximum safe voltage Um 40V DC
basic insulation according to IEC/EN 61010-1, rated RS 232, Programming adapter for parameterization via
Output III/start-up override Interface
insulation voltage 50Ve the USB interface of a PC/Notebook
basic insulation according to IEC/EN 61010-1, rated Maximum safe voltage Um 40V
Output III/IV
insulation voltage 50Ve Electrical isolation
reinforced insulation according to IEC/EN 61010-1, safe electrical isolation acc. to IEC/EN 60079-11,
Output IV/power supply Input I/other circuits
rated insulation voltage 300Ve voltage peak value 375V
reinforced insulation according to IEC/EN 61010-1, Directive conformity
Start-up override/power supply
rated insulation voltage 300Ve
EN 60079-0:2009, EN 60079-11:2007,
reinforced insulation according to IEC/EN 61010-1, Directive 94/9/EC
Interface/power supply EN 60079-26:2007 , EN 61241-11:2006
rated insulation voltage 300Ve
basic insulation according to IEC/EN 61010-1,
Interface/output III
rated insulation voltage 50Ve
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Low voltage
Directive 2006/95/EC EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Protection degree IEC 60529:2001
Input EN 60947-5-6:2000

Rockwell Automation Publication 937-SG001C-EN-P January 2015 41


937 Intrinsic Safety Converter Barriers

Frequency Converter
1-ch, AC/DC, continued
937CU-DIFRQ-BC1
Front view
Removable terminal
blue

1 2 3 4 5 6
LED green:
Power supply LC display
1 PWR
IN/
CHK

LED yellow/red: OUT


1 2

Input pulses/ 3

fault signal ESC

RS232

OK Keypad
LED yellow:
Output I ... III

Place for labeling


7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24

Programming jack Removable terminals


black

Product Features
Cat. No. 937CU-DIFRQ-BC1

400 R 2 k 10
1+ 11 I
12
10 k 10 k
16
3- 17 II
18
19+ III
20-
7- IV
mA
8+

13+
14-

23
24
AC/DC

Zone 0, 1, 2
Div. 1, 2

Wiring Diagram
Cat. No.937CU-DIFRQ-BC1

40 mm (1.6") 115 mm (4.5'')


46 mm (1.82'')
104 mm (4.1'')

119 mm (4.7'')
58 mm (2.28'')

Approximate Dimensions
Cat. No. 937CU-DIFRQ-BC1

42 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Converter Barriers

Transmitter Power Supply


Specifications
1-ch, 24V DC
Description 24V DC, 1-channel
937CU-AITXF-DC1 Signal Type Analog Input
Supply
Connection Power Rail or terminals 23+, 24-
Rated voltage 20 ... 30V DC
Rated current approx. 130 mA
Power loss 2W
Power consumption 2.5 W
Input
Connection terminals 1, 2, 3,
Input signal 0/4 ... 20 mA
Available voltage 15V at 20 mA
Open circuit voltage/ 24V /
short-circuit current 33 mA

Input resistance 45 (terminals 2, 3)

Lead monitoring breakage I < 0.2 mA; short-circuit I > 22 mA


Output
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 8+, 7-
Features Output signal 0 ... 20 mA or 4 ... 20 mA
Output I, II signal, relay
 1-channel isolated barrier
Contact loading 250V AC / 2 A / cos 0.7 ; 40 DC / 2 A
 24V DC supply (Power Rail)
 Input 2-wire and 3-wire transmitters and 2-wire current Mechanical life 5 x 107 switching cycles
sources Output III Signal, analog
 Output 0/4 mA ... 20 mA Current range 0 ... 20 mA or 4 ... 20 mA
 Two relay contact outputs Open loop voltage 24V DC
 Programmable high/low alarm Load 650 W
 Linearization function (max 20 points) downscale I 3.6 mA, upscale I 21 mA (acc.
Fault signal
 Line fault detection (LFD) NAMUR NE43)
 Up to SIL2 acc. to IEC 61508/IEC 61511

This isolated barrier is used for intrinsic safety applications.


The device supplies 2-wire and 3-wire transmitters, and can
also be used with current sources. Two relays and an active
0/4 mA ... 20 mA current source are available as outputs. The
relay contacts and the current output can be integrated in
security-relevant circuits. The current output is easily scaled.
On the display the measured value can be indicated in
various physical units. The device is easily configured by the
use of keypad or with the PACTware configuration software.
The input has a line fault detection. A fault is signalized by
LEDs acc. to NAMUR NE44 and a separate collective error
message output.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 43


937 Intrinsic Safety Converter Barriers

Transmitter Power Supply Environmental and Mechanical Specifications


Operating temperature -20 ... 60 C (-4 ... 140 F)
1-ch, 24V DC, continued Protection degree IP20
Weight 300 g
937CU-AITXF-DC1 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) , housing type
Dimensions
C3
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Transfer characteristics Data for application in connection with Ex-areas
Input I
EC-Type Examination Certicate TV 01 ATEX 1701
Accuracy < 30 mA
Inuence of ambient temperature 0.003 %/K (30 ppm) <Ex> II (1) G [Ex ia] IIC
Group, category, type of protection
Output I, II <Ex> II (1) D [Ex iaD]
Response delay 200 ms at bounce from 0 ... 20 mA Input Ex ia IIC, Ex iaD
Output III Supply
Resolution 10 mA Maximum safe voltage Um 40V DC
Accuracy < 20 mA Equipment terminals 1+, 3-
Inuence of ambient temperature 0.005 %/K (50 ppm) Voltage Uo 25.8V
Current Io 93 mA
< 650 ms at bounce from 0 ... 20 mA at the input, 90
Reaction time Power Po 0.603 W
% of output full-scale value
Electrical isolation Equipment terminals 2-, 3
reinforced insulation according to IEC/EN 61010-1, Voltage Ui < 30V
Input/Other circuits
rated insulation voltage 300Ve Current Ii 115 mA
reinforced insulation according to IEC/EN 61010-1, Voltage Uo 5V
Output I, II/other circuits
rated insulation voltage 300Ve
Current Io 0.3 mA
reinforced insulation according to IEC/EN 61010-1,
Mutual output I, II, III Power Po 0.3 mW
rated insulation voltage 300Ve
Output III/power supply and collective functional insulation acc. to IEC 62103, Equipment terminals 1+, 2 / 3-
error rated insulation voltage 50Ve Voltage Uo 25.8V
Interface/power supply and collective functional insulation acc. to IEC 62103, Current Io 112 mA
error rated insulation voltage 50Ve
Power Po 720 mW
Directive conformity
Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Electromagnetic compatibility
Maximum safe voltage Um 253V AC / 40V DC
Directive 2004/108/EC EN 61326-1:2006
253V AC/2 A/cos > 0.7; 40V DC/2 A resistive load
Low voltage Contact loading
(TV 01 ATEX 1701)
Directive 2006/95/EC EN 61010-1:2010 Output III terminals 8+, 7- non-intrinsically safe
Conformity Maximum safe voltage Um Um 40V
Electromagnetic compatibility NE 21:2006 Interface RS 232
Protection degree IEC 60529:2001
Maximum safe voltage Um 40V

Statement of conformity TV 02 ATEX 1885 X , observe statement of conformity


Group, category, type of protection,
<Ex> II 3G Ex nA nC IIC T4
temperature class
Output I, II
Contact loading 50V AC/2 A/cos > 0.7; 40V DC/1 A resistive load
Electrical isolation
safe electrical isolation acc. to IEC/EN 60079-11,
Input/Other circuits
voltage peak value 375V
Directive conformity
EN 60079-0:2009, EN 60079-11:2007, EN60079-
Directive 94/9/EC
15:2005 , EN 60079-26:2007 , EN 61241-11:2006

44 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Converter Barriers

Transmitter Power Supply


1-ch, 24V DC, continued
937CU-AITXF-DC1

Front view
Removable terminal
blue

1 2 3 4 5 6
LED green:
Power supply LC display
PWR
FLT

LED red: OUT


1 2

Fault signal
ESC
LED yellow: RS232

Output I OK
Keypad
LED yellow:
Output II
Place for labeling
7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24

Programming jack Removable terminals


black

Product Features
Cat. No. 937CU-AITXF-DC1

10
1+ 11 I
12
HART

2- 16
17 II
18
mA
3
7- III
mA
8+

23+
24-
24 V DC

Zone 0, 1, 2 Fault 24V DC Zone 2


Div. 1, 2 Power Rail Div. 2

Wiring Diagram
Cat. No.937CU-AITXF-DC1

40 mm (1.6") 115 mm (4.5'')


46 mm (1.82'')
104 mm (4.1'')

119 mm (4.7'')
58 mm (2.28'')

Approximate Dimensions
Cat. No. 937CU-AITXF-DC1

Rockwell Automation Publication 937-SG001C-EN-P January 2015 45


937 Intrinsic Safety Converter Barriers

HART Loop Converter


Specifications
1-ch, 24V DC
Description 24V DC, 1-channel
937CU-AIHLP-DC1 Signal Type Analog Input
Supply
Connection Power Rail or terminals 23+, 24-
Rated voltage 19 ... 30V DC
Rated current approx. 130 mA at 24V DC
Power loss 2.5 W
Power consumption 3.1 W
HART signal channels (intrinsically safe)
Conformity HART eld device input (revision 5 to 7)
Input
Connection terminals 1, 2, 3, 4, 5, 6
Input signal HART communication, transmitter supply
Open circuit voltage/ typ. 24V /
short-circuit current 28 mA
Open circuit voltage/short-circuit
250 5 % (terminals 2, 3 and with jumper on 5, 6)
current
Available voltage 15.5V at 20 mA, short-circuit protected
Output
output I: terminals 10, 11, 12,
Features output II: terminals 16, 17, 18
Connection output III: terminals 7, 8, 9,
 1-channel isolated barrier
output IV: terminals 13, 14, 15,
 24V DC supply (Power Rail) output V: terminals 19, 20, 21
 HART field device input (revision 5 to 7) with transmitter
power supply Output I, II
 Usable as signal splitter (1 input and multiple outputs) Output signal relay and LED yellow
 Two relay outputs (changeover contacts) Mechanical life 107 switching cycles
 Three analog outputs 4 mA ... 20 mA Energized/De-energized delay approx. 20 ms / approx. 20 ms
 Sink and source mode output Output III, IV, V
 Configurable by keypad Output signal analog
Current range 4 ... 20 mA , source or sink mode
This isolated barrier is used for intrinsic safety applications. It Load 650 , source mode
is a HART loop converter that provides power to transmitters Voltage range 5 ... 30V , sink mode from external supply
or can be connected to existing HART loops in parallel. It is
downscale I 2 mA, upscale I 21.5 mA
able to evaluate up to four HART variables (PV, SV, TV, QV). Of Fault signal
(acc. NAMUR NE43) or hold measurement value
those four HART variables, the data contained in any three of
Other outputs HART communicator on terminals 22, 24
them can be converted to three different 4 mA ... 20 mA
current signals. These loop signals can be connected to Collective error message Power Rail and LED red
display devices or analog inputs on the process control
system/ control system. In addition to the current outputs,
two form C changeover relay contacts are available and can
be programmed to operate at trip values from the HART
variables. The unit is easily programmed by the use of a
keypad located on the front of the unit or with the
PACTware configuration software.

46 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Converter Barriers

HART Loop Converter Environmental and Mechanical Specifications


Operating temperature -20 ... 60 C (-4 ... 140 F)
1-ch, 24V DC, continued Protection degree IP20
Weight 300 g
937CU-AIHLP-DC1 Dimensions
40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) ,
housing type C3
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Transfer characteristics
Data for application in connection with Ex-areas
Output III, IV, V
Group, category, type of protection <Ex> II (1)GD [Ex ia] IIC, [Ex iaD]
Resolution 2 mA
Input Ex ia, Ex iaD
Accuracy < 20 mA, 10 mA typ.
Supply
Inuence of ambient temperature < 2 mA/K
Maximum safe voltage Um 253V AC
Duration of measurement/Response
HART message acquisition time plus 100 ms Equipment terminals 1, 4/3 (with link between terminals 4 and 5)
delay
programmable either for fault or trip value Voltage Uo 25.2V
Relay
(with direction, hysteresis and delay) Current Io 104.9 mA
Electrical isolation Power Po 0.661 W
functional insulation acc. to IEC 62103, Equipment terminals 2, 5/3
Output I/II
rated insulation voltage 250Ve
Voltage Ui < 28V
reinforced insulation acc. to IEC 62103,
Output I, II/other circuits Power Pi < 1.33 W
rated insulation voltage 300Vrms
functional insulation acc. to IEC 62103, Voltage Uo 1.1V
Output III/IV/V/power supply
rated insulation voltage 50Ve Current Io 11.9 mA
Directive conformity Power Po 4 mW
Electromagnetic compatibility Output I, II terminals 10, 11, 12; 16, 17, 18 , non-intrinsically safe
Directive 2004/108/EC EN 61326-1:2006 Maximum safe voltage Um 253V
Low voltage 253V AC/1 A/cos > 0.7; 30V DC/1 A resistive load
Contact loading
Directive 2006/95/EC EN 50178:1997 (BASEEFA 07 ATEX 0174)
Conformity 50V AC/1 A/cos > 0.7; 30V DC/1 A resistive load
Electromagnetic compatibility NE 21:2006 (self-declared)
Protection degree IEC 60529:2001 terminals 7, 8, 9; 13, 14, 15; 19, 20, 21 ,
Output III, IV, V
non-intrinsically safe
Protection against electrical shock IEC 60664-1
Maximum safe voltage Um 253V
Electrical isolation
safe electrical isolation acc. to IEC/EN 60079-11,
Input/Other circuits
voltage peak value 375V
Directive conformity
EN 60079-0 , EN 60079-11 ,
Directive 94/9/EC
EN 61241-0 , EN 61241-11

Rockwell Automation Publication 937-SG001C-EN-P January 2015 47


937 Intrinsic Safety Converter Barriers

HART Loop Converter


1-ch, 24V DC, continued
937CU-AIHLP-DC1

Front view Removable


terminals
blue

1 2 3 4 5 6
LED green: LC display
Power supply
ERR PWR

1 2

LED red: OUT

Fault indication ESC

RS232

LEDs yellow: OK Keypad


Relay status

Place for labeling


7 8 9 10 11 12
13 14 15 16 17 18
19 20 21
Programming jack 22 23 24
Removable
terminals
black

Product Features
Cat. No. 937CU-AIHLP-DC1

+ 10
1+ 11 I
HART 12
+ +
HART

2+ 16
HART

mA 17 II
- - -
3- 18
7
mA 8+ III
4 + V
9- -
13
5 IV
mA 14+
250 + V
15- -
6 19
mA 20+ V
+ V
21- -
22
HART

23+
24-
24 V DC

Zone 0, 1, 2 ERR 24V DC Zone 2


Div. 1, 2 Power Rail Div. 2

Wiring Diagram
Cat. No. 937CU-AIHLP-DC1

40 mm (1.6") 115 mm (4.5'')


46 mm (1.82'')
104 mm (4.1'')

119 mm (4.7'')
58 mm (2.28'')

Approximate Dimensions
Cat. No. 937CU-AIHLP-DC1

48 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Converter Barriers

Strain Gauge Converter


Specifications
1-ch, 24V DC
Description 24V DC, 1-channel
937CU-AISTR-DC1 Signal Type Analog Input
Supply
Connection Power Rail or terminals 23+, 24-
Rated voltage 20 ... 35V DC
Ripple within the supply tolerance
Power consumption 3W
Interface
Connection Power Rail or terminals 19+, 20 GND, 21-
Type RS 485
RS232, Programming adapter for
Programming interface parameterization via the USB interface of a
PC/Notebook
Field circuit
Connection terminals 1+, 2-, 3+, 4-, 5+, 6-
Lead resistance 25 W per lead
Connection terminals 1+, 2-
Sensor supply 1 ... 5V
Connection terminals 3+, 4- (supply); 5+, 6- (signal)
Short-circuit current 50 mA
Load 116 up to 5V, 85 up to 4V
Features Input
Input I: terminals 1+, 2-;
 1-channel isolated barrier Connection Input II: terminals 13+, 14-;
 24V DC supply (Power Rail) Input III: terminals 15+, 14-
 Strain gauge input (full or half bridge) Programmable Tare 0 ... 500 % of span
 Output 0 mA ... 20 mA or 0V ... 10V Input I Signal, analog
 Relay contact output Input signal -100 ... 100 mV
 Programmable high/low alarm Input resistance 1 M for voltage measurement
 Configurable by PACTware or keypad Input II, III tare adjustment, calibration and zero
 RS 485 interface Open circuit voltage/short-circuit current 18V / 5 mA
 Line fault detection (LFD) Active/Passive I > 4 mA/ I < 1.5 mA
Output
This isolated barrier is used for intrinsic safety applications.
Output I: terminals 10, 11, 12;
The device is used with strain gauges, load cells and Connection Output II: terminals 16, 17, 18;
resistance measuring bridges. Designed to provide 5V Output III: terminals 7-, 8+, 9-
excitation voltage, this barriers high quality A/D converter Output I, II Relay output
allows it to be used with those devices requiring 10V. Up to
253V AC/2 A/500 VA/cos min. 0.7; 40V
four 350 strain gauges connected in parallel may be Contact loading
DC/2 A resistive load
powered and evaluated. The device is easily configured by
Mechanical life 2 x 107 switching cycles
the use of keypad or with the PACTware configuration
software. The current measurement for tare, zero point, and Output III Analog output
final value can be entered in this manner. A fault is signalized Current range -20 ... 20 mA
by LEDs acc. to NAMUR NE44 and a separate collective error Load 550
message output. 0 ... 10V; output resistance 500 W
Analog voltage output
(bridge between terminal 7 and 9)
0 ... 20 mA or 4 ... 20 mA;
Analog current output
load 0 ... 550 W (terminals 7 and 8)
downscale -21.5 mA (-10.75V) or
Line fault detection
2 mA (1V), upscale 21.5 mA (10.75V)
Rockwell Automation Publication 937-SG001C-EN-P January 2015 49
937 Intrinsic Safety Converter Barriers

Strain Gauge Converter


1-ch, 24V DC, continued
937CU-AISTR-DC1

Transfer characteristics Environmental and Mechanical Specifications


Deviation Operating temperature -20 ... 60 C (-4 ... 140 F)
Resolution/accuracy 0.05 % incl. non-linearity and hysteresis Protection degree IP20
Temperature eect 0.01 %/K Weight 250 g
Reaction time 300 ... 850 ms 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) ,
Dimensions
Electrical isolation housing type C3
reinforced insulation according to IEC 61140, on 35 mm DIN mounting rail
Output I, II against each other Mounting
rated insulation voltage 300Ve acc. to EN 60715:2001
reinforced insulation according to IEC 61140, Data for application in connection with Ex-areas
Output I, II/other circuits
rated insulation voltage 300Ve <Ex> II (1)GD [Ex ia] IIC, [Ex iaD],
Group, category, type of protection
functional insulation, [circuit(s) in zone 0/1/2]
Other circuits from each other
rated insulation voltage 50Ve Power Rail or terminals 23+, 24-
Supply
Directive conformity non-intrinsically safe
Electromagnetic compatibility Maximum safe voltage Um 40V DC
Directive 2004/108/EC EN 61326-1:2006 Input I terminals 1+, 2- Ex ia IIC, Ex iaD
Low voltage Voltage Uo 14V
Directive 2006/95/EC EN 50178:1997 Current Io 238 mA
Conformity Power Po 833 mW (linear characteristic)
Electromagnetic compatibility NE 21:2006 terminals 13+, 14-; 15+, 14-
Input II and III
non-intrinsically safe
Protection degree IEC 60529:2001
Maximum safe voltage Um 40V DC
Protection against electrical shock IEC 61140
terminals 10, 11, 12; 16, 17, 18
Output I, II
non-intrinsically safe
Maximum safe voltage Um 253V AC / 40V DC
253V AC/2 A/500VA/cos min. 0.7;
Contact loading
40V DC/2 A resistive load
Output III terminals 7-, 8+, 9- non-intrinsically safe
Maximum safe voltage Um 40V DC
RS232, Programming adapter for
Interface parameterization via the USB interface
of a PC/Notebook
Maximum safe voltage Um 40V DC
Electrical isolation
safe electrical isolation acc. to
Input I/other circuits
IEC/EN 60079-11, voltage peak value 375V
Directive conformity
EN 60079-0:2006, EN 60079-11:2007,
Directive 94/9/EC EN 60079-26:2007
EN 61241-0:2006, EN 61241-11:2006

50 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Converter Barriers

Strain Gauge Converter


1-ch, 24V DC, continued
937CU-AISTR-DC1
Front view
Removable terminals
blue

1 2 3 4 5 6
LED green:
Power supply LC display
PWR
ERR

LED red: OUT


1 2

Fault signal
ESC
LED yellow: RS232

Output I OK
Keypad
LED yellow:
Output II
Place for labeling
7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24

Programming jack Removable terminals


black

Product Features
Cat. No. 937CU-AISTR-DC1

10
3+ 11 I
5+ 12
16
17 II
1+ 18
2- 7-
mA
8+ III
9-
6- 13+
4- 14-
15+
19+
20 GND RS 485
21-
23+
24-
24 V DC

Zone 0, 1, 2 RS 485 ERR 24 V DC


Div. 1, 2 Power Rail

Wiring Diagram
Cat. No. 937CU-AISTR-DC1

40 mm (1.6") 115 mm (4.5'')


46 mm (1.82'')
104 mm (4.1'')

119 mm (4.7'')
58 mm (2.28'')

Approximate Dimensions
Cat. No. 937CU-AISTR-DC1

Rockwell Automation Publication 937-SG001C-EN-P January 2015 51


Zener Barriers

Zener barriers have long been a cost-effective solution for providing an intrinsically safe interface with field devices located in
the hazardous area. Allen-Bradley Zener barriers provide protection for electrical signals within hazardous areas and feature a
narrow profile of just 12.5 mm to maximize control panel space. Zener barrier prevents the transfer of unacceptably high
energy from the safe area into the hazardous area. These Zener barriers have a positive polarity, which means the anodes of
the Zener diodes are grounded. Depending on the application, increased or decreased intrinsic safety parameters apply for
serial or parallel connection. These barriers simply snap onto a standard DIN rail for easy installation and grounding.

Zener barriers are available


in the following types:

 Standard one- or two-channel barriers

 The diode return feature prevents a current into the hazardous


area, therefore the current assumption for intrinsic safety
calculations is zero

 In addition to the diode return feature, the high power version


has a smaller serial resistance and therefore provides higher
voltage to the field device

Rockwell Automation Publication 937-SG001C-EN-P January 2015 53


Intrinsic Safety Zener Barriers

Catalog Number Explanation


Note: Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; some combinations may not produce a valid catalog number.

937Z H DP A N - 1
a b c d - e

a c d
Module Profile Max. Series Resistance Options
Code Description Code Description Code Description
H High-density 12.5mm module A 646 Ohm D Diode Return
B 327 Ohm P Diode Return w/High Power
C 36 Ohm + 0.9V N None
D 250 Ohm

b e
Type Channels
Code Description Code Description
DP DC Positive Polarity 1 Single Channel
2 Dual Channel

54 Rockwell Automation Publication 937-SG001C-EN-P January 2015


Intrinsic Safety Zener Barriers

Zener Barrier
1-Ch, 327 Ohm Max Specifications

937ZH-DPBN-1 Signal Type


Nominal resistance
DC Positive Polarity
300 Ohm
Series resistance max. 327 Ohm
Fuse rating (non-replaceable) 50 mA
Hazardous area Connection terminals 1, 2
Safe area Connection terminals 7, 8
Working voltage max. 26.9 V , 26.5 V at 10 A
Data for application in connection with Ex-areas
Ex II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC,
Group, category, type of protection [Ex ia Ma] I (-20 C Tamb 60 C)
[circuit(s) in zone 0/1/2]
Voltage 28 V
Current 93 mA
Power 650 mW
Supply
Maximum safe voltage 250 V
Series resistance min. 301 Ohm
Group, category, type of protection,
Ex II 3G Ex nA IIC T4 Gc [device in zone 2]
temperature class
Directive conformity
EN 60079-0:2009, EN 60079-11:2007,
Directive 94/9/EC
EN 61241-11:2006 , EN 60079-15:2010
The Zener Barrier prevents the transfer of unacceptably high
Operating temperature -20 ... 60 C (-4 ... 140 F)
energy from the safe area into the hazardous area. The zener
diodes in the Zener Barrier are connected in the reverse Storage temperature -25 ... 70 C (-13 ... 158 F)
direction. The breakdown voltage of the diodes is not Relative humidity max. 75 % , without moisture condensation
exceeded in normal operation. If this voltage is exceeded, Degree of protection IP20
due to a fault in the safe area, the diodes start to conduct, self-opening connection terminals,
Connection
causing the fuse to blow. The Zener Barrier has a positive max. core cross-section 2 x 2.5 mm
polarity, i. e. the anodes of the zener diodes are grounded. Weight approx. 150 g
Dimensions 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 in)
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001

Rockwell Automation Publication 937-SG001C-EN-P January 2015 55


Intrinsic Safety Zener Barriers

Zener Barrier
1-Ch, 327 Ohm Max, continued
937ZH-DPBN-1

Front view

Terminals
hazardous area

1 2
3 4

Tag holder

5 6
7 8
Terminals
safe area
Shield and ground
connection

Product Features
Cat. No. 937ZH-DPBN-1

1 8
+
x3
-
2 7

Zone 0, 1, 2 Zone 2
Div. 1, 2 Div. 2

Wiring Diagram
Cat. No. 937ZH-DPBN-1
12.5 110
115

Approximate Dimensions
Cat. No. 937ZH-DPBN-1

56 Rockwell Automation Publication 937-SG001C-EN-P January 2015


Intrinsic Safety Zener Barriers

Zener Barrier Specifications

2-Ch, 327 Ohm Max Signal Type


Nominal resistance
DC Positive Polarity
300 Ohm
937ZH-DPBN-2 Series resistance max. 327 Ohm
Fuse rating (non-replaceable) 50 mA
Hazardous area Connection terminals 1, 2; 3, 4
Safe area Connection terminals 5, 6; 7, 8
Working voltage max. 27 V , 26.5 V at 10 A
Data for application in connection with Ex-areas
Ex II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia
Group, category, type of protection Ma] I (-20 C Tamb 60 C)
[circuit(s) in zone 0/1/2]
Voltage 28 V
Current 93 mA
Power 650 mW
Supply
Maximum safe voltage 250 V
Series resistance min. 301 Ohm
Group, category, type of protection,
Ex II 3G Ex nA IIC T4 Gc [device in zone 2]
temperature class
Directive conformity
EN 60079-0:2009, EN 60079-11:2007,
Directive 94/9/EC
EN 61241-11:2006 , EN 60079-15:2010
Operating temperature -20 ... 60 C (-4 ... 140 F)
The Zener Barrier prevents the transfer of unacceptably high
energy from the safe area into the hazardous area. The zener Storage temperature -25 ... 70 C (-13 ... 158 F)
diodes in the Zener Barrier are connected in the reverse Relative humidity max. 75 %, without moisture condensation
direction. The breakdown voltage of the diodes is not Degree of protection IP20
exceeded in normal operation. If this voltage is exceeded, self-opening connection terminals,
Connection
due to a fault in the safe area, the diodes start to conduct, max. core cross-section 2 x 2.5 mm
causing the fuse to blow. The Zener Barrier has a positive Weight approx. 150 g
polarity, i. e. the anodes of the zener diodes are grounded. Dimensions 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 in)
Depending on the application, increased or decreased Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
intrinsic safety parameters apply for serial or parallel
connection. For the detailed parameters refer to the Zener
Barrier certificate.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 57


Intrinsic Safety Zener Barriers

Zener Barrier
2-Ch, 327 Ohm Max, continued
937ZH-DPBN-2

Front view

Terminals
hazardous area

1 2
3 4

Tag holder

5 6
7 8
Terminals
safe area
Shield and ground
connection

Product Features
Cat. No. 937ZH-DPBN-2

1 8

2 x3
7
+

- 3 6
x3

4 5

Zone 0, 1, 2 Zone 2
Div. 1, 2 Div. 2

Wiring Diagram
Cat. No. 937ZH-DPBN-2
12.5 110
115

Approximate Dimensions
Cat. No. 937ZH-DPBN-2

58 Rockwell Automation Publication 937-SG001C-EN-P January 2015


Intrinsic Safety Zener Barriers

Zener Barrier Specifications

2-Ch, 646 Ohm Max Signal Type


Nominal resistance
DC Positive Polarity
600 Ohm
937ZH-DPAN-2 Series resistance max. 646 Ohm
Fuse rating (non-replaceable) 50 mA
Hazardous area Connection terminals 1, 2; 3, 4
Safe area Connection terminals 5, 6; 7, 8
Working voltage max. 27 V , 26.5 V at 10 A
Data for application in connection with Ex-areas
Ex II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia
Group, category, type of protection Ma] I (-20 C Tamb 60 C) [circuit(s) in zone
0/1/2]
Voltage 28 V
Current 46 mA
Power 320 mW
Supply
Maximum safe voltage 250 V
Series resistance min. 607 Ohm
Group, category, type of protection,
Ex II 3G Ex nA IIC T4 Gc [device in zone 2]
temperature class
Directive conformity
EN 60079-0:2009, EN 60079-11:2007, EN 61241-
Directive 94/9/EC
11:2006 , EN 60079-15:2010
Operating temperature -20 ... 60 C (-4 ... 140 F)
The Zener Barrier prevents the transfer of unacceptably high Storage temperature -25 ... 70 C (-13 ... 158 F)
energy from the safe area into the hazardous area. The zener Relative humidity max. 75 % , without moisture condensation
diodes in the Zener Barrier are connected in the reverse Degree of protection IP20
direction. The breakdown voltage of the diodes is not self-opening connection terminals,
exceeded in normal operation. If this voltage is exceeded, Connection
max. core cross-section 2 x 2.5 mm
due to a fault in the safe area, the diodes start to conduct, Weight approx. 150 g
causing the fuse to blow. The Zener Barrier has a positive Dimensions 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 in)
polarity, i. e. the anodes of the zener diodes are grounded.
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Depending on the application, increased or decreased
intrinsic safety parameters apply for serial or parallel
connection. For the detailed parameters refer to the Zener
Barrier certificate.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 59


Intrinsic Safety Zener Barriers

Zener Barrier
2-Ch, 646 Ohm Max, continued
937ZH-DPAN-2

Front view

Terminals
hazardous area

1 2
3 4

Tag holder

5 6
7 8
Terminals
safe area
Shield and ground
connection

Product Features
Cat. No. 937ZH-DPAN-2

1 8

2 x3
7
+

- 3 6
x3

4 5

Zone 0, 1, 2 Zone 2
Div. 1, 2 Div. 2

Wiring Diagram
Cat. No. 937ZH-DPAN-2
12.5 110
115

Approximate Dimensions
Cat. No. 937ZH-DPAN-2

60 Rockwell Automation Publication 937-SG001C-EN-P January 2015


Intrinsic Safety Zener Barriers

Zener Barrier Specifications

2-Ch, 36 Ohm + 0.9V Max Signal Type


Nominal resistance
DC Positive Polarity
diode
937ZH-DPCD-2 Series resistance max. 36 Ohm + 0.9 V
Voltage drop 1.2 V + (36 Ohm x signal current)
Fuse rating (non-replaceable) 50 mA
Hazardous area Connection terminals 1, 2; 3, 4
Safe area Connection terminals 5, 6; 7, 8
Working voltage max. 27V , 26.5V at 10 A
Data for application in connection with Ex-areas
Voltage Uo 28V
Supply
Maximum safe voltage Um 250V
Series resistance diode
Group, category, type of protection, temperature class
Directive conformity Directive 94/9/EC
Operating temperature -20 ... 60 C (-4 ... 140 F)
Storage temperature -25 ... 70 C (-13 ... 158 F)
Relative humidity max. 75 % , without moisture condensation
Degree of protection IP20
self-opening connection terminals,
Connection
max. core cross-section 2 x 2.5 mm
Weight approx. 150 g
Dimensions 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 in)
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
The Zener Barrier prevents the transfer of unacceptably high
energy from the safe area into the hazardous area. The zener
diodes in the Zener Barrier are connected in the reverse
direction. The breakdown voltage of the diodes is not

exceeded in normal operation. If this voltage is exceeded,


due to a fault in the safe area, the diodes start to conduct,
causing the fuse to blow. The Zener Barrier has a positive
polarity, i. e. the anodes of the zener diodes are grounded.

The Zener Barrier is for evaluation of signals from the


hazardous area. The diodes of diode return prevent a current
into the hazardous area, therefore the current assumption for
intrinsic safety calculations is zero. Depending on the
application, increased or decreased intrinsic safety
parameters apply for serial or parallel connection. For the
detailed parameters refer to the Zener Barrier certificate.
Application examples can be found in the system description
of the Zener Barriers.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 61


Intrinsic Safety Zener Barriers

Zener Barrier
2-Ch, 36 Ohm + 0.9V Max, continued
937ZH-DPCD-2

Front view

Terminals
hazardous area

1 2
3 4

Tag holder

5 6
7 8
Terminals
safe area
Shield and ground
connection

Product Features
Cat. No. 937ZH-DPCD-2

x3
1 8

x3
2 7
+

- 3 6
x3
x3
4 5

Zone 0, 1, 2 Zone 2
Div. 1, 2 Div. 2

Wiring Diagram
Cat. No.937ZH-DPCD-2
12.5 110
115

Approximate Dimensions
Cat. No.937ZH-DPCD-2

62 Rockwell Automation Publication 937-SG001C-EN-P January 2015


Intrinsic Safety Zener Barriers

Zener Barrier Specifications

2-Channel, 250 Ohm Max Signal Type


Nominal resistance
DC Positive Polarity
240 Ohm
937ZH-DPDP-2 Series resistance max. 250 Ohm
Fuse rating (non-replaceable) 80 mA
Hazardous area Connection terminals 1, 2; 3, 4
Safe area Connection terminals 5, 6; 7, 8
Working voltage max. 27 V , 26.5 V at 10 A
Data for application in connection with Ex-areas
Ex II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia
Group, category, type of protection Ma] I (-20 C Tamb 60 C)
[circuit(s) in zone 0/1/2]
Voltage Uo 28 V
Current Co 120 mA
Power Po 830 mW
Supply
Maximum safe voltage 250 V
Series resistance min. 235 Ohm
TV 99 ATEX 1484 X , observe statement of conformity
Statement of conformity
Group, category, type of protection, temperature class
Directive conformity
EN 60079-0:2009, EN 60079-11:2007,
Directive 94/9/EC
EN 61241-11:2006 , EN 60079-15:2010
Operating temperature -20 ... 60 C (-4 ... 140 F)
The Zener Barrier prevents the transfer of unacceptably high Storage temperature -25 ... 70 C (-13 ... 158 F)
energy from the safe area into the hazardous area. The zener Relative humidity max. 75 % , without moisture condensation
diodes in the Zener Barrier are connected in the reverse Degree of protection IP20
direction. The breakdown voltage of the diodes is not self-opening connection terminals,
exceeded in normal operation. If this voltage is exceeded, Connection
max. core cross-section 2 x 2.5 mm
due to a fault in the safe area, the diodes start to conduct, Weight approx. 150 g
causing the fuse to blow. The Zener Barrier has a positive
Dimensions 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 in)
polarity, i. e. the anodes of the zener diodes are grounded.
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
This high power version has a smaller serial resistance and
therefore provides higher voltage to the field device. The
Zener Barrier is for evaluation of signals from the hazardous
area. The diodes of diode return prevent a current into the

hazardous area, therefore the current assumption for intrinsic


safety calculations is zero. Depending on the application,
increased or decreased intrinsic safety parameters apply for
serial or parallel connection. For the detailed parameters refer
to the Zener Barrier certificate. Application examples can be
found in the system description of the Zener Barriers.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 63


Intrinsic Safety Zener Barriers

Zener Barrier
2-Channel, 250 Ohm Max, continued
937ZH-DPDP-2

Front view

Terminals
hazardous area

1 2
3 4

Tag holder

5 6
7 8
Terminals
safe area
Shield and ground
connection

Product Features
Cat. No.937ZH-DPDP-2

1 8

x3
2 7
+

- 3 6
x3
x3
4 5

Zone 0, 1, 2 Zone 2
Div. 1, 2 Div. 2

Wiring Diagram
Cat. No. 937ZH-DPDP-2

12.5 110
115

Approximate Dimensions
Cat. No. 937ZH-DPDP-2

64 Rockwell Automation Publication 937-SG001C-EN-P January 2015


Accessories

Power Feed Module Specifications


Desciption Redundant Power Feed Module
24V DC Supply

937A-PSFD Connection terminals 11+, 12-


terminals 8+, 9-
20 ... 30 V DC
Rated voltage The maximum rated operating voltage of the devices
plugged onto the Power Rail must not be exceeded.
Power loss 2.4 W
Output
Power Rail feed Output current 4 A
Fault signal relay output: NO contact
Contact loading 30V AC/ 2 A / cos 0.7 ; 40V DC/ 2 A
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Fusing 5 AT
Conformity
Electromagnetic compatibility NE 21:2006
Protection degree IEC 60529:2001
Environmental and Mechanical Specications
Ambient temperature -25 ... 60 C (-13 ... 140 F)
Protection degree IP20
Mass approx. 100 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in),
Features Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-areas
 Interface for Power Rail Statement of conformity TV 00 ATEX 1618 X
 Used for redundant configuration
Group, category, type of protection,
 Supply rating 4 A, external fused temperature class
<Ex> II 3G Ex nA nC IIC T4
 Relay contact output, reversible Directive conformity
 LED status indication Directive 94/9/EC EN 60079-0:2009 , EN 60079-15:2010

The power feed module is used to supply the devices with


24V DC via the Power Rail. The fuse-protected power feed
module can supply up to 150 individual modules depending
on the power consumption of the devices. Collective error
messages received from the Power Rail activate a
galvanically-isolated mechanical contact.

Note: The accessories listed are for use with 937Intrinsic Safety Isolated Barriers, and Converter Barriers.

Rockwell Automation Publication 937-SG001C-EN-P January 2015 65


937 Intrinsic Safety Accessories for Isolators and Converters

Power Feed Module


24V DC, continued
937A-PSFD
Front view

1 2 3
4 5 6

LED red:
Fault signal
Switch S1
ERR PWR mode of operation
LED green: S1 I II
Position I: NO
Power supply 5 AT
Position II: NC

Fuse carrier

7 8 9
10 11 12
13 14 15

Removable terminals
black

Product Features
Cat. No. 937A-PSFD

10

14 ERR
13 BUS
15

5 AT
8+
11+
24 V DC
9-
12-

BUS ERR 24 V DC Zone 2


Power Rail

Wiring Diagram
Cat. No. 937A-PSFD

20 mm 115 mm (4.5'')
(0.78")
46 mm (1.82'')
104 mm (4.1'')

119 mm (4.7'')
58 mm (2.28'')

Approximate Dimensions
Cat. No. 937A-PSFD

66 Rockwell Automation Publication 937-SG001C-EN-P January 2015


937 Intrinsic Safety Accessories for Isolators and Converters

Power Rail
937A-PR08, -PR20 2 conductors for power supply 1 conductor for
collective
error message
Cover
Power Rail has two conductors for 24VDC power and one
conductor for collective error messaging. Power Rail reduces
wiring and maintenance costs because it eliminates the need
to daisy-chain the wires. It also simplifies expansion just
snap in a new Isolated Barrier or Converter Barrier when
youre ready to expand a system. Power Rail is available in 2
Meter or 0.8 meter lengths, it can be cut to size per
application needs. Power Rail comes standard with two Mount using M4
screws with washers
937A-PREC end caps and a cover. Additional 937A-PREC end End cap
per DIN 125

caps can be ordered separately.


m
5m
12
Features
 35 mm DIN mounting rail with 3-conductor insert Slot for holding
insert
 Provides DC supply voltage to all equipped 937 modules
 Simple to customize to application space
Product Features
 Eliminates daisy-chains Cat. No. 937A-PR
 Available in 0.8 and 2 M lengths

Specifications
Cat. No. 937A-PR08 937A-PR20 937A-PREC
Power Rail, Power Rail - Power Rail End Cap
Desciption
Pkg. Qty. 1, .08M length Pkg. Qty. 1, 2 M length Pkg. Qty. 10
Electrical specifications
Rated voltage 24V DC
Rated current 4A
Environmental specifications
Ambient
-20 ... 60 C (-4 ... 140 F)
temperature

35 x 15 x 800 mm (1.4 x 35 x 15 x 2000 mm 17 x 37 x 24 mm (0.67 x


Dimensions
0.6 x 31.5 in) (1.4 x 0.6 x 78.7 in) 1.46 x 0.95 in)

Rockwell Automation Publication 937-SG001C-EN-P January 2015 67


937 Intrinsic Safety Accessories for Isolators and Converters

USB Interface Cable Specifications


Electrical specifications
937A-USBA Current consumption 50 mA (via USB)
functional insulation acc. to IEC 62103,
Electrical isolation
rated insulation voltage 50 Ve
Environmental and Mechanical Specifications
Operating Temperature -20 ... 60 C (-4 ... 140 F)
Connection to the PC: USB type A
Cable Length 3m

32
3.8
L=3m

55

Features

9
 Isolated USB Interface cable for 937C Modules only

12
 For use with FDT configuration software

27
21
This programming cable is used to configure 937C Converter
14

12
Barriers with FDT software via USB port on a computer.
3.5
10.4

FDT Interface Approximate Dimensions


Cat. No. 937A-USBA
Configuring converter modules is convenient with a PC
using Field Device Tool (FDT) software. Some specialized
functions can only be selected using the FDT. The FDT
interface is the specification describing the standardized data
exchange between devices and control system or
engineering or asset management tools. Examples include:
PACTwareTM , FieldCare, FactoryTalk AssetCentre, and Process
Device Configuration. FDT frame software can be
downloaded at http://www.pactware.com PACTwareTM is
trademark of PACTware Consortium

Cold Junction Compensation


Device
937A-TCJC

Description Cat. No.


Cold junction compensation for
Pkg. Qty. 1 937A-TCJC
937CS-AITMP-DC1 (thermocouples)

68 Rockwell Automation Publication 937-SG001C-EN-P January 2015


Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 937-SG001C-EN-P January 2015


Supersedes Publication 937-SG001B-EN-P September 2014 Copyright 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like