Medium voltage products

HD4 according to IEC and GOST standards


Gas insulated MV circuit-breakers
12...40.5 kV - 630...3600 A - 16...50 kA
Index

4 1. Description

8 2. Selection and ordering

32 3. Specific product characteristics

36 4. Overall dimensions

50 5. Electric circuit diagram

3
1. Description

General information
HD4 medium voltage circuit-breakers use sulphur hexafluoride
gas (SF6) to extinguish the electric arc and as the insulating
medium.
Breaking in SF6 gas takes place without any arc chopping
and without generation of overvoltages. These characteristics
ensure long electrical life of the circuit-breaker and limited
dynamic, dielectric and thermal stresses on the installation.
The circuit-breaker poles, which make up the breaking part,
are systems with lifelong sealed pressure (IEC 62271-100)
and are maintenance-free.
The ESH type mechanical operating mechanism, with stored
energy has free release and allows opening and closing
operations independently of the operators actions.
The operating mechanism and the poles are fixed to the metal
structure which also acts as a support for the kinetics for
operating the moving contacts.

Autopuffer breaking technique


Electric arc extinction without chopped current
No restriking after breaking
Rapid recovery of the dielectric properties of the means of extinction
Withstand insulation voltage even at zero relative pressure (*)
Sealed-for-life poles
Compact dimensions
Fixed and withdrawable version
Stored energy operating mechanism with anti-pumping device as
standard common to the whole circuit-breaker series
Mechanical safety locks against incorrect operations
Simple personalisation thanks to a complete range of accessories
Maintenance-free
SF6 gas pressure control device (on request).

(*) Up to 17.5 kV.

4
Circuit-breakers in the withdrawable version are fitted with a Thanks to the SF6 autopuffer breaking technique, the HD4
truck to allow racking in and racking out of the switchboard or circuit-breakers do not generate operating overvoltages, and
enclosure. are therefore also highly suitable for retrofitting, upgrading
The light and compact structure of the circuit-breaker ensures and enlarging older installations where the motor, cable, etc.
great sturdiness and excellent mechanical reliability. insulating materials may be particularly sensitive to dielectric
stresses.
Available versions
HD4 circuit-breakers are available in the fixed and Breaking technique
withdrawable version with front operating mechanism. The breaking technique of HD4 circuit-breakers is based
The withdrawable version is available for: PowerCube on compression and self-blast techniques to obtain top
modules and UniGear type ZS1, ZS2, ZS3.2 switchboards. performances at all service current values, with minimum
arc times, gradual arc extinction without chopping, and no
Fields of application restriking or operating overvoltages.
HD4 circuit-breakers are used in power distribution to control The HD4 series brings to medium voltage the advantages
and protect lines, transformer and distribution substations, of the autopuffer breaking technique already used in high
motors, transformers, capacitor banks, etc. voltage.

7 3

6
4

1 Circuit-breaker Main contact Arcing contact Circuit-breaker


closed separation separation open

Main contact separation


8 No electric arc strikes as the current flows through the arcing contacts.
During its run downwards, the moving part compresses the gas contained in the lower chamber. The compressed
gas flows out of the lower chamber into the upper chamber, taking them both to the same pressure.

Arcing contact separation


The current flows thanks to the electric arc which has struck between the arcing contacts.
The gas cannot get out through the nozzle because the hole is still closed by the fixed arcing contact and cannot
get out through the inside of the moving arcing contact either because the electric arc closes this (clogging effect).
with low currents, when the current passes through natural zero and the arc is quenched,
the gas flows through the contacts. The low pressure reached cannot chop the current and the modest amount
of compressed gas is sufficient to restore dielectric resistance between the two contacts, preventing restriking
on the rising front of the return voltage.
2
with high short-circuit currents, the pressure wave generated by the electric arc closes the valve between
the two chambers so that the circuit-breaker starts to operate as a pure self-blast. The pressure increases in
9 the upper volume thanks to heating of the gas and molecular disassociation due to the high temperature. The
increase in pressure generated is proportional to the arc current and ensures quenching on first passage through
current zero.
1 Terminal 6 Fixed arcing contact
2 Insulating case 7 Fixed contact Circuit-breaker open
3 Blasting nozzle 8 Insulating tie-rod The arc has been interrupted, the self-generated pressure in the upper volume is reduced because the gas is
4 Moving arcing contact 9 Anti-explosion valve flowing through the contacts. The valve re-opens and so a new flow of fresh gas comes into the breaking chamber.
5 Moving contact The apparatus is therefore immediately ready to close and trip again up to its maximum breaking capacity.

5
1. Description

Standards and approvals


HD4 circuit-breakers comply with IEC 62271-100 Standards
and with those of major industrialised countries.
They have undergone the following tests and guarantee safety
and reliability of the apparatus in service in all installations.
Type tests: heating, withstand insulation at industrial and
impulse frequency, short-time and peak withstand current,
mechanical duration, making and breaking of short-circuit
currents;
Individual tests: insulation with voltage at industrial
frequency in the main circuits and insulation of the auxiliary
and control circuits, measurement of the main circuit
resistance, mechanical and electrical operation.
The HD4 circuit-breakers are tested according to the
requirements of the IEC 62271-100 Standards.
GOST versions have been approved by Scientific and
Technical Centre Standartelectro-S of Moscow (ask ABB for
the Declaration of Conformity).

Service safety Accessories


Thanks to the availability of a complete range of mechanical HD4 circuit-breakers have a complete range of accessories
and electrical locks (on request), safe distribution which fulfil all installation requirements.
switchboards can be constructed using HD4 circuit-breakers. The operating mechanism is the same type for the whole
The locking devices have been designed to prevent incorrect series and has a standardized range of accessories and spare
operations and to carry out inspection of the installation, parts which are easy to identify and order.
ensuring maximum operator safety. Apparatus use, maintenance and service have been simplified
and require less use of resources.

The terminals and isolating The withdrawable circuit- The nameplate, located on All the control and signalling devices are located on the front of
contacts are silver-plated. breakers feature a device the front panel, enables the circuit-breaker.
enabling them to be racked all the circuit-breaker Suitable locks prevent incorrect operations.
in/out with the door closed. characteristics to be The antipumping device is always provided on the actuator.
identified.

6
ESH operating mechanism
Just one device for the whole series.
The same set of accessories for all the types of HD4 circuit-
breaker.
Fixed strikers to facilitate assembly or replacement of
accessories.
Accessory cabling with socket and plug.

Technical documentation
To obtain in-depth knowledge of technical and application
aspects of the HD4 circuit-breakers please ask for the
following publications:
PowerCube modules
UniGear ZS1 type switchboards
ZS3.2/PowerBloc switchboards
REF542plus unit.

Quality System
Complies with ISO 9001 Standards, certified by an
independent organisation.

Test Laboratory
Complies with UNI CEI EN ISO/IEC 17025 Standards,
accredited by an independent organisation.

Environmental Management System


Complies with ISO 14001 Standards, certified by an
independent organisation.

Health and Safety Management System


Complies with OHSAS 18001 Standards, certified by an
independent organisation.

7
2. Selection and ordering

General characteristics of fixed circuit-breakers


(12 - 17.5 - 24 kV)

Circuit-breaker HD4/GT 12
GOST R 52565-2006 (5)
Standards
IEC 62271-100
Rated voltage Ur [kV] 10
Rated insulation voltage Us [kV] 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 42
Impulse withstand voltage Up [kV] 75
Rated frequency fr [Hz] 50-60
Rated normal current (1)
Ir [A] 630 1250 630 1250 630 630 1250 1600 2000 2500 3150
20 20 20 20 20
25 25 25 25 25 25 25 25
Rated breaking capacity Isc [kA] 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40
50 50 50 50 50
20 20 20 20 20
25 25 25 25 25 25 25 25
Rated short-time
Ik [kA] 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
withstand current (3 s)
40 40 40 40 40
50 50 50 50 50
50 50 50 50 50
63 63 63 63 63 63 63 63
Making capacity Ip [kA] 80 80 80 80 80 80 80 80
100 100 100 100 100
125 125 125 125 125
[O-0.3s-CO-15s-CO]
Operation sequence [O-0.3s-CO-20s-CO]
[O-0.3s-CO-180s-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
Dimension standardization table TN 7360 TN 7361 TN 7200 TN 7201 TN 7202
Pole distance [mm] 150 210 210 210 275
Overall H H [mm] 582 622 714 655 655
dimensions
L [mm] 493 618 618 618 730
L D
D [mm] 459 456 477 493 493
Weight [Kg] 114 114 119 145 165
Absolute SF6 gas pressure (2) [kPa] 380
Operating temperature (3) [C] - 5 ... + 40 C
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1

(1) Rated uninterrupted current defined in free air at 40 C ambient temperature for HD4 17 and HD4 24.
(2) Rated service value.
(3) The standard range is -5 C ... +40 C; on request its available also the range -25 C ... 40 C with mandatory a special pressure-switch (with temperature compensation).
The minimum storage temperature is minus 25 C; the minimum transportation temperature is minus 25 C .
(4) Including insulating shields (available on request).
(5) Declaration of Conformity to GOST R 52565-2006 issued by Autonomous organization Scientific research center Standardtelectro-S of Moscow.

8
HD4 17 HD4 24


17.5 24
17.5 24
38 50
95 125
50-60 50-60
630 1250 1600 630 1250 1600 1600 2000 2500 3150 3600 630 1250 1600 630 1250 1600 1600 2000 2500 3150 3600
20 20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40 40 40 40 40 40
50 50 50 50 50
20 20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40 40 40 40 40 40
50 50 50 50 50
50 50 50 50 50 50 50 50 50 50 50 50
63 63 63 63 63 63 63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80 80 80 80 80 80 80
100 100 100 100 100 100 100 100 100 100
125 125 125 125 125



45 45
10-15 10-15
55-60 55-60
80 80
TN 7177 TN 7178 TN 7163 TN 7165 TN 7179 TN 7242 TN 7174 TN 7165
150 210 210 275 210 275 275 275
640 649 655 655 818 (4)
730 655 818 (4)

493 618 618 730 618 748 730 730


496 496 561 603 600 (4)
496 561 620 (4)

114 114 145 165 119 119 145 165


380 380
- 5 ... + 40 C - 5 ... + 40 C

9
2. Selection and ordering

General characteristics of withdrawable circuit-breakers


for UniGear type ZS1 switchboards (12 - 17.5 - 24 kV) (5)

Circuit-breaker HD4/GT/P 12
GOST R 52565-2006 (8)
Standards
IEC 62271-100
Rated voltage Ur [kV] 10 10
Rated insulation voltage Us [kV] 12 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 42 (6)
38 (6)

Impulse withstand voltage Up [kV] 75 75


Rated frequency fr [Hz] 50-60 50-60
Rated normal current (1)
Ir [A] 630 1250 1250 1600 2000 2500 3150 (4)


20 20 20
25 25 25 25 25 25
Rated breaking capacity Isc [kA]
31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40
50 50 50 50

20 20 20
Rated short-time 25 25 25 25 25 25
Ik [kA]
withstand current (3 s) 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40
50 50 50 50

50 50 50
63 63 63 63 63 63
Making capacity Ip [kA]
80 80 80 80 80 80
100 100 100 100 100
125 125 125 125
[O-0.3s-CO-15s-CO]
Operation sequence [O-0.3s-CO-20s-CO]
[O-0.3s-CO-180s-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
Dimension standardization table TN 7286 TN 7350 TN 7351 TN 7352 TN 7371
Pole distance [mm] 150 210 210 275 275
Overall H H [mm] 628 702 702 702 746
dimensions
L [mm] 532 682 682 882 882
L D
D [mm] 659 640 640 643 643
Weight [Kg] 120 177 177 220 230
Absolute SF6 gas pressure (2) [kPa] 380
Operating temperature (3) [C] - 5 ... + 40 C
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1

(1) Rated uninterrupted current guaranteed with withdrawable circuit-breaker installed in UniGear type ZS1 switchboard at 40 C ambient temperature externally the panel.
(2) Rated service value.
(3) The standard range is -5 C ... +40 C; on request its available also the range -25 C ... 40 C with mandatory a special pressure-switch (with temperature compensation).
The minimum storage temperature is minus 25 C; the minimum transportation temperature is minus 25 C .
(4) Up to 4000 A rated uninterrupted current in switchboard with forced ventilation.

10
HD4/P 17 HD4/P 24


17.5 24
17.5 24
38 50
95 125
50-60 50-60
630 1250 1250 1600 2000 2500 3150 (4)
630 1250 1250 1600 2000 2500 (7)

16 16 16 16 16
20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40
50 50 50 50
16 16 16 16 16
20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40
50 50 50 50
40 40 40 40 40
50 50 50 50 50 50 50
63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80 80
100 100 100 100 100
125 125 125 125



45 45
10-15 10-15
55-60 55-60
80 80
TN 7286 TN 7350 TN 7351 TN 7352 TN 7371 TN 7354 1VCD000099 TN 7355 TN7356
150 210 210 275 275 210 210 275 275
628 702 702 702 746 736 792 821 821
532 682 682 882 882 636 653 842 842
659 640 640 643 643 802 799 788 788
120 177 177 220 230 125 177 177 220
380 380
- 5 ... + 40 C - 5 ... + 40 C

(5) The locking electromagnet (-RL2) in the truck to prevent the circuit-breaker being racked-in with the auxiliary circuits disconnected (plug not inserted in the socket) is included in
the standard equipment.
(6) UniGear type ZS1 switchboard with rated insulation voltage 17.5 kV.
(7) Rated uninterrupted current in switchboard with forced ventilation. In a switchboard with natural ventilation, the rated current is 2300 A.
(8) Declaration of Conformity to GOST R 52565-2006 issued by Autonomous organization Scientific research center Standardtelectro-S of Moscow.

11
2. Selection and ordering

General characteristics of withdrawable circuit-breakers


for PowerCube modules (12 - 17.5 - 24 kV)

Circuit-breaker HD4/GT/W 12
PowerCube enclosures PB1 PB1 PB2 PB2 PB2 PB2 PB2 PB3
GOST R 52565-2006 (6)

Standards
IEC 62271-100
Rated voltage Ur [kV] 12 12
Rated insulation voltage Us [kV] 12 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 42 38
Impulse withstand voltage Up [kV] 75 75
Rated frequency fr [Hz] 50-60 50/60
Rated normal current (1)
Ir [A] 630 1250 630 1250 1250 1600 2000 3150 (4)
16 16 16 16 16 16

25 25 25 25 25 25
Rated breaking capacity Isc [kA]
31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40
50 50
16 16 16 16 16 16

Rated short-time 25 25 25 25 25 25
Ik [kA]
withstand current (3 s) 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40
50 50
40 40 40 40 40 40
- -
63 63 63 63 - 63 63
Making capacity Ip [kA]
80 80 80 80 - 80 80 80
100 100
125 125
[O-0.3s-CO-15s-CO]
Operation sequence [O-0.3s-CO-20s-CO]
[O-0.3s-CO-180s-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
Dimension standardization table TN 7229 TN 7182 TN 7421 TN 7239 1VCD000053
Pole distance [mm] 150 210 210 210 275
Overall H H [mm] 636 702 702 702 742
dimensions
L [mm] 532 682 682 682 882
L D
D [mm] 659 640 640 640 643
Weight [Kg] 120 120 177 177 230
Absolute SF6 gas pressure (2) [kPa] 380

Operating temperature (3) [C] - 5 ... + 40 C

Tropicalization IEC: 60068-2-30, 60721-2-1


Electromagnetic compatibility IEC 62271-1

(1) Rated uninterrupted current guaranteed with withdrawable circuit-breaker installed in a switchboard at 40 C ambient temperature externally the panel.
(2) Rated service value.
(3) The standard range is -5 C ... +40 C; on request its available also the range -25 C ... 40 C with mandatory a special pressure-switch (with temperature compensation).
The minimum storage temperature is minus 25 C; the minimum transportation temperature is minus 25 C .

12
HD4/GT/P 12 HD4/W 17 HD4/P 17 HD4/W 24 HD4/P 24
PB2 PB2 PB3 PB1 PB1 PB2 PB2 PB2 PB2 PB2 PB3 PB2 PB2 PB3 PB4 PB4 PB5 PB5


12 17.5 17.5 24 24
12 17.5 17.5 24 24
42 28 28 50 50
75 95 95 125 125
50-60 50-60 50-60 50-60 50-60
1600 2000 2500 630 1250 630 1250 1250 1600 2000 3150 (4) 1600 2000 2500 630 1250 1600 2000 2500 (5)
16 16 16 16 16 16 16 16 16 16 16
20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40 40 40 40
50 50 50 50 50 50 50 50
16 16 16 16 16 16 16 16 16 16 16
20 20 20 20 20
25 25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
40 40 40 40 40 40 40 40
50 50 50 50 50 50 50 50
40 40 40 40 40 40 40 40 40 40 40
50 50 50 50 50
63 63 63 63 63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 80 80 80
100 100 100 100 100 100 100 100
125 125 125 125 125 125 125 125



45 45 45 45 45
10-15 10-15 10-15 10-15 10-15
55-60 55-60 55-60 55-60 55-60
80 80 80 80 80
TN 7350 TN 7351 TN 7352 TN 7229 TN 7182 TN 7421 TN 7239 1VCD000053 TN 7350 TN 7351 TN 7352 TN 7183 TN 7355 TN 7356
210 210 275 150 210 210 210 275 210 210 275 210 275 275
702 702 702 636 702 702 702 742 702 702 702 792 821 821
682 682 882 532 682 682 682 882 682 682 882 682 842 842
640 640 643 659 640 640 640 643 640 640 643 799 788 788
177 177 220 120 120 177 177 230 177 177 220 125 177 220
380 380 380 380 380
- 5 ...
- 5 ... + 40 C - 5 ... + 40 C - 5 ... + 40 C - 5 ... + 40 C
+ 40 C

(4) Rated uninterrupted current in switchboard with natural ventilation; rated current 3600 A with one fan pre-installed in PB3 cassette; rated current 4000 A with one additional fan
installed by customer in the back of switchgear (see PowerCube Instruction Manual).
(5) Rated uninterrupted current in switchboard with forced ventilation.
(6) Declaration of Conformity to GOST R 52565-2006 issued by Autonomous organization Scientific research center Standardtelectro-S of Moscow.

13
2. Selection and ordering

General characteristics of withdrawable circuit-breakers


for UniGear type ZS3.2 switchboards (40.5 kV)

Circuit-breaker HD4/Z 40.5


GOST R 52565-2006
Standards
IEC 62271-100
Rated voltage Ur [kV] 40.5
Rated insulation voltage Us [kV] 40.5
Withstand voltage at 50 Hz Ud (1 min) [kV] 95
Impulse withstand voltage Up [kV] 185
Rated frequency fr [Hz] 50-60
Rated normal current (1)
Ir [A] 1250 1600 2000 2500
25 25 25 25
Rated breaking capacity Isc [kA]
31.5 (4)
31.5 (4)
31.5 (4)
31.5 (4)

Rated short-time 25 25 25 25
Ik [kA]
withstand current (3 s) 31.5 31.5 31.5 31.5
63 63 63 63
Making capacity Ip [kA]
80 80 80 80
Operation sequence (4)
[O-0.3s-CO-15s-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
Dimension standardization table TN 7227
Pole distance [mm] 280
Overall H H [mm] 1575
dimensions
L [mm] 895
L D
D [mm] 686
Weight [Kg] 280
Absolute SF6 gas pressure (2) [kPa] 550
Operating temperature (3) [C] - 5 ... + 40 C
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility IEC 62271-1

(1) Rated uninterrupted current guaranteed with withdrawable circuit-breaker installed in UniGear type ZS3.2. switchboard at 40 C ambient temperature externally the panel;
2500 A rated current is with forced ventilation.
(2) Rated service value.
(3) The standard range is -5 C ... +40 C; on request its available also the range -25 C ... 40 C with mandatory a special pressure-switch (with temperature compensation).
The minimum storage temperature is minus 25 C; the minimum transportation temperature is minus 25 C .
(4) The operating sequence is O-0.3sec-CO-3min-CO for the rated breaking capacity Isc = 31.5 kA.

14
Standard equipment Moreover:
The basic versions of the circuit-breakers are always three- for fixed circuit-breaker
pole and fitted with: connection terminals (on request for HD4/GT 12)
manual operating mechanism terminal board for auxiliary circuits
mechanical signalling device for closing springs charged/
discharged for withdrawable circuit-breaker
mechanical signalling device for circuit-breaker open/closed isolating contacts
closing pushbutton cord with connector (plug only) for auxiliary circuits
opening pushbutton earthing contact on truck (only for CBE, CBF)
operation counter lock to prevent racking-in of circuit-breaker with different
set of ten open/closed circuit-breaker auxiliary contacts rated current
(four opening (NC) and three closing (NO) available, racking-in/out lever (the quantity must be defined
according to the applications requested) according to the number of pieces of apparatus ordered)
lever for manually charging the closing springs (the quantity locking electromagnet in the truck (/P and /W versions).
must be defined according to the number of pieces of
apparatus ordered).

Terminals for fixed circuit-breaker. Tulip isolating contacts for withdrawable Plier isolating contacts for withdrawable
circuit-breaker. circuit-breaker.

Circuit-breaker racking-out/racking-in lever. Manual charging lever of operating mechanism springs.

15
16
(4)
(3)
(2)
(1)
HD4 24
HD4 17

HD4/P 24
HD4/P 17
HD4/GT 12

HD4/Z 40.5
HD4/GT/P 12

HD4/W 24 - HD4/P 24
HD4/W 17 - HD4/P 17
Fixed circuit-breakers

for PowerCube modules


HD4/W 12 - HD4/GT/P 12
Withdrawable circuit-breakers
Withdrawable circuit-breakers
Withdrawable circuit-breakers

is included in the standard equipment.


Standard fitting: no. 6 auxiliary contacts.
for UniGear type ZS1 switchboards

for UniGear type ZS3.2 switchboards

For this version it is only available without LED.












-MO1 shunt opening release.

1A











-MO2 additional shunt opening release.

1B

Application of the pressure switch is only possible in the factory.


Table of availability of accessories











-MO3 shunt opening release with demagnetisation.

1C
-MC shunt closing release.











-MU undervoltage release (power supply on supply side).

3A
-MU undervoltage release with electronic time delay device
2. Selection and ordering











3B
(power supply on supply side).











4
Mechanical override of undervoltage release trip.

-BB5 undervoltage release electric signalling (energised or











5
de-energised).

Set of 14 auxiliary contacts: 5 closing contacts for signalling circuit-











breaker open and 7 opening contacts for signaling circuit-breaker
6A

closed.

Set of 15 auxiliary circuit-breaker contacts: 4 make and 5 break

(alternative to the 10 provided as standard, of which a maximum of 3


6B

make and 4 break are available depending on the accessories requested).

-BB4 transient contact.

The locking electro-magnet in the truck (-RL2) to prevent the circuit-breaker being racked-in with the auxiliary circuits disconnected (plug not inserted in the socket)

-BT3 position contact of the withdrawable circuit-breaker (installed

on the truck). It is compulsory if the RL1 locking magnet is present.


Withdrawable circuit-breaker transmitted contacts (installed in the

(1)
circuit-breaker truck).











10
-MS spring charging geared motor.











11
-FB1 thermomagnetic protection of spring charging geared motor.











Electric signalling of springs charged.

12A











Electric signalling of springs discharged.

12B











Opening pushbutton lock.

13A











Closing pushbutton lock.

13B











14
Open circuit-breaker key lock.











15
-RL1 operating mechanism locking magnet.

(4)
(4)
(4)
(4)
(4)
(4)
16
-RL2 truck locking magnet.











17
Interlock for fixed circuit-breaker.











18
Mechanical isolation interlock with the switchgear door.

(3)
Two-level pressure switch (2).
19A

Two-level pressure switch plus SF6 control device with three LEDs (2).
19B/C











20

Insulating partitions.











21

3-lobed key for manual operation.

17
2. Selection and ordering

Optional accessories
The accessories identified with the same number are alternative to each other; consult the table at the end of the
chapter for the electrical characteristics.

supplementary shunt
opening release -MO2

shunt closing release


-MC
shunt opening release
-MO1

1 Shunt opening release 2 Shunt closing release -MC


1A Shunt opening release -MO1 Allows the closing command of the apparatus to be
Allows the opening command of the apparatus to be enabled transmitted by remote control.
by remote control. To guarantee the closing action, the current impulse must
This release is only suitable for instantaneous service; there last at least 100 ms. This release is suitable for both
is always an auxiliary contact -BB1 to de-energize it after the instantaneous and permanent duty (an auxiliary contact that
circuit-breaker has opened. To guarantee the release action, de-energizes it after the circuit-breaker has closed is not
the current impulse must last at least 100 ms. The coil of this envisaged). Permanently energized, the release provides
release can be controlled by any CCC (Control Coil Continuity) the electrical anti-pumping function when both the opening
device and TCS (Trip Circuit Supervision) circuit opening and closing remote commands (electrical) are maintained. If
supervision device. shunt closing release -MC and undervoltage release -MU are
energized by the same supply voltage and automatic closing
1B Additional shunt opening release -MO2 of the circuit-breaker is required when the auxiliary voltage
returns, there must be a delay of at least 50 ms between
Similarly to shunt opening release -MO1, this allows the
undervoltage release energizing and energizing of the shunt
opening command of the apparatus to be transmitted by
closing release to allow the closing operation to take place.
remote control. It can be energized by the same circuit as
Release functionality cannot be controlled by CCC and TCS
main shunt opening release -MO1 or by a circuit that is
devices.
completely separate from release -MO1. This release is only
This can only be done by the ABB STU device (accessory
suitable for instantaneous service. There is always an auxiliary
supplied on request).
contact -BB1 to de-energize it after the circuit-breaker has
opened. To guarantee the release action, the current impulse
must last at least 100 ms. The coil of this release can be
controlled by any CCC (Control Coil Continuity) device and
TCS (Trip Circuit Supervision) circuit opening supervision
device.

1C Demagnetizing shunt opening release -MO3


The opening solenoid (-MO3) is a special demagnetizing
release for use in conjunction with protection relays against
overcurrents of the self-supplied type (e.g. the old ABB
PR521 series). It is an alternative to the additional shunt
opening release (-MO2).

18
undervoltage release
-MU

electronic time-lag device -KT

3 Under-voltage release -MU 3A Undervoltage release -MU (only for power supply
Undervoltage release -MU opens the circuit-breaker when branched on the supply side of the circuit-breaker)
there is a sensible reduction or lack of the voltage that 3B Undervoltage release -MU with electronic time-lag
energizes it. The circuit-breaker can only close when device -KT (only for power supply branched on the
the release is energized (the closing lock is obtained supply side of the circuit-breaker).
mechanically). It can be used for remote release (by means Circuit-breaker closing is inhibited when the undervoltage
of a pushbutton of the normally closed type), for locking on release (equipped with electronic time-lag device -KT) is not
automatic closing and/or opening in the absence of voltage energized. Electronic time-lag device -KT is only designed
in the auxiliary circuits. Energized by means of the secondary to delay the tripping action of undervoltage release MU at
output of a voltage transformer, it provides locking upon preset, adjustable times (0.5 - 1 - 1.5 - 2 - 3 s).
automatic closing/opening in the absence of voltage in the This device is consigned with the 0.5 s time setting. Consult
Medium Voltage main circuit. If shunt closing release -MC the Chapter on circuit diagrams, note I, page 69). Electronic
and undervoltage release -MU are energized by the same time-lag device -KT must be installed inside the operating
supply voltage and automatic closing of the circuit-breaker enclosure of the circuit-breaker.
is required when the auxiliary voltage returns, there must To avoid tripping, use of the delayed undervoltage release
be a delay of at least 50 ms between undervoltage release is convenient when the supply network of release -MU may
energizing and energizing of the shunt closing release to allow often be liable to brief voltage dips or tiny power outages.
the closing operation to take place. The voltage of the undervoltage release must be within the
operating range of the electronic time-lag device.

19
2. Selection and ordering

Optional accessories

4 Mechanical override of undervoltage release tripping 6 Auxiliary and signalling contacts


with undervoltage excluded electrical signalling. 6A Auxiliary contacts BB1,-BB2 for all 12 kV to 36 kV
The mechanical undervoltage override is a manually switched fixed and withdrawable series
two-position device installed on the front of the circuit- Electrical signalling of circuit-breaker open/closed can be
breaker operating mechanism. Its purpose is to prevent the obtained with a set of 14 auxiliary contacts for the fixed
undervoltage release from tripping so that the circuit-breaker version and 14 auxiliary contacts for the plug-in version.
can be operated as though it were without an undervoltage Note
release. The undervoltage override is always equipped with The following contacts are available for the fixed and plug-
an electrical contact for signalling undervoltage excluded. in circuit-breaker with the standard set of fourteen auxiliary
The mechanical override is essential when the undervoltage contacts and the maximum number of electrical accessories:
release is supplied by the secondary of a transformer on the five closing contacts for signalling circuit-breaker open
load side of the circuit-breaker. In this case, the installation seven opening contacts for signalling circuit-breaker closed.
can only be energized by excluding the undervoltage. The The auxiliary contacts of fixed circuit-breakers are always
mechanical override can be operated after the circuit-breaker wired to the terminal box.
has closed so as to restore undervoltage functionality. The Please refer to the following circuit diagrams:
mechanical override is useful when inspections/maintenance 1VCD400192 for fixed circuit-breakers up to 24 kV and
must be performed with the circuit-breaker withdrawn from 36 kV circuit-breakers with 350 mm pole center-distance
the switchgear and with the auxiliary circuits de-energized. 1VCD400193 for 36 kV fixed circuit-breakers with 275 mm
Specify when ordering the apparatus if the mechanical pole center-distance
override is required since it cannot be installed by the 1VCD400197 for withdrawable circuit-breakers up to 24 kV
customer at a later date. (with auxiliary contacts -BB1,-BB2 independent from
connected/isolated signalling contacts -BT1,-BT2)
1VCD400199 for withdrawable circuit-breakers up to 24 kV
(with auxiliary contacts -BB1,-BB2 interconnected with
connected/isolated signalling contacts -BT1,-BT2)
5 Electrical signalling of the state of undervoltage 1VCD400194 for 36 kV withdrawable circuit-breakers
release -BB5 Note: The main shunt opening release and/or the additional shunt opening release
An undervoltage release energized or undervoltage release use 1 and/or 2 closing contacts a, thereby reducing the number of auxiliary
contacts available. Always check the maximum number of contacts available with
de-energized signalling contact can be supplied on request. non-standard equipment.
It must be specified when ordering the apparatus since it
cannot be installed by the customer at a later date.

20
Auxiliary contacts BB1 and BB2 conform to the following
standards/regulations/directives:
IEC 62271-100
IEEE C37.54
EN 61373 cat.1 class B / impact and vibration test
Germanish Loyd regulation / vibrations envisaged by the
shipping registers
UL 508
EN 60947 (DC-21A DC-22A DC-23A AC-21A)
RoHS Directive

General characteristics
Insulation voltage to standard 660 V AC
VDE 0110, Group C 800 V DC
Rated voltage 24 V ... 660 V 6B Auxiliary contacts -BB1-BB2-BB3 for the 40.5 kV
Test voltage 2 kV for 1 min withdrawable series only
Maximum rated current 10 A - 50/60 Hz Electrical signalling of circuit-breaker open/closed includes,
Breaking capacity Class 1 (IEC 62271-1) as standard equipment, a set of 10 auxiliary contacts for the
Number of contacts 5 40.5 kV withdrawable version.
Groups of contacts 10 / 16 / 20 Set of 10 circuit-breaker open/closed auxiliary contacts.
Contact travel 90 Three closing contacts (circuit-breaker open signalling) and
Actuating force 0.66 Nm four opening contacts (circuit-breaker closed signalling) are
Resistance <6.5 m available if the apparatus is equipped with all the electrical
Storage temperature 30 C ... +120 C applications.
Operating temperature
20 C ... +70 C A set of 15 auxiliary contacts for signalling circuit-breaker
(-30 ref. ANSI 37.09)
open/closed can be supplied on request. Four closing
Contact overtemperature 10 K
contacts (circuit-breaker open signalling) and four opening
Mechanical life 10,000 mechanical operations
contacts (circuit-breaker closed signalling) are available if the
Protection class IP20
apparatus is equipped with all the electrical applications.
Cable section 1 mm2

Electrical specifications of the auxiliary contacts of the 40.5 kV


Electrical characteristics (according to IEC 60947) withdrawable circuit-breaker
Rated current Un Breaking capacity (10000 interruptions) Un = 500 V~ 220 V
220 V AC Cosj = 0.70 20 A Icu = 15 A 1.5 A
220 V DC Cosj = 0.45 10 A Cos = 0.4
1 ms 12 A T = 500 V~ 10 ms
24 V DC
15 ms 9A Un Rated voltage
50 ms 6A Cos Power factor
Icu Breaking capacity
1 ms 10 A Ps Inrush power input (inrush duration is given between brackets)
60 V DC
15 ms 6A Pc Continuous service power consumption
T Time constant
50 ms 4,6 A
1 ms 7A
110 V DC 15 ms 4.5 A
50 ms 3.5 A
1 ms 2A
220 V DC 15 ms 1.7 A
50 ms 1.5 A
1 ms 2A
250 V DC 15 ms 1.4 A
50 ms 1.2 A

21
2. Selection and ordering

Optional accessories

7 Transient contact -BB4 with momentary closing during 8 Position contact of withdrawable circuit-breaker -BT3
circuit-breaker opening. Only supplied for withdrawable circuit-breakers for UniGear
This contact closes momentarily (for about 30 ms) when the ZS1 and ZS2 switchgear and PowerCube modules from 12 to
circuit-breaker opens. The transient contact is activated by 36 kV.
the main operating shaft, thus the indication is only provided This contact is installed in the truck. It is in the closed state
when the main contacts of the circuit-breaker effectively open. when the truck is fully racked-in or fully racked-out and is in
the open state when the truck is being racked-in/racked-out.
It is used in conjunction with the locking magnet in the
operating mechanism (-RL1) to prevent remote closing during
movement in the compartment.
It is supplied as standard equipment when locking magnet
-RL1 is installed in the operating mechanism and truck-
mounted contacts are not required (-BT1, -BT2). It cannot be
supplied when truck-mounted contacts are required (-BT1;
-BT2).

22
General characteristics
Insulation voltage to standard 660 V a.c.
VDE 0110, Group C 800 V d.c.
Rated voltage 24 V ... 660 V a.c.
Test voltage 2 kV 50 Hz (for 1 min)
Rated overcurrent 10 A
Number of contacts 5
Contact run 6 mm ... 7 mm
Activation force 26 N
Resistance 3 m
Storage temperature 20 C ... +120 C
Operating temperature 20 C ... +70 C
Contact overtemperature 20 K
Number of cycles 10.000
Unlimited breaking capacity if used with 10 A fuse in series
9 Electrical signalling contacts for circuit-breaker
connected and isolated (-BT1; -BT2)
Electrical characteristics
These contacts are an alternative to the withdrawable circuit-
Un Rated current Breaking capacity
breaker position contact (-BT3) and are recommended when
220 V a.c. Cosj = 0.7 2.5 A 25 A
there are no position contacts on the roof of the circuit-
380 V a.c. Cosj = 0.7 1.5 A 15 A
breaker compartment (for signalling circuit-breaker racked-out
500 V a.c. Cosj = 0.7 1.5 A 15 A
or racked-in). Contacts -BT1, -BT2 are supplied as standard
660 V a.c. Cosj = 0.7 1.2 A 12 A
equipment when locking magnet -RL1 is installed in the
1 ms 10 A 12 A
operating mechanism and position contact BT3 has not been
24 V d.c. 15 ms 10 A 12 A
requested. Contacts -BT1 and BT2 have the same general
50 ms 8A 10 A
and electrical characteristics as auxiliary contacts 7b. -BB1,
200 ms 6A 7.7 A
-BB2, -BB3.
1 ms 8A 10 A
60 V d.c. 15 ms 6A 8A
50 ms 5A 6A
200 ms 4A 5.4 A
1 ms 6A 8A
15 ms 4A 5A
110 V d.c.
50 ms 2A 4.6 A
200 ms 1A 2.2 A
1 ms 1.5 A 2A
15 ms 1A 1.4 A
220 V d.c.
50 ms 0.75 A 1.2 A
200 ms 0.5 A 1A

23
2. Selection and ordering

Optional accessories

10 S pring-loading geared motor -MS 11 Thermal magnetic protection -FB1 of the closing
The geared motor automatically loads the closing spring of spring loading motor
the circuit-breakers operating mechanism after the circuit- Thermal magnetic protection of the closing spring loading
breaker has closed each time and until the yellow spring motor is supplied as part of the standard equipment for
loaded indicator appears. If a power cut occurs when loading 24 V DC rated voltage while it is available on request for other
is in progress, the geared motor stops and automatically voltage values. It is always supplied with electrical signalling
starts loading the springs again when the power returns. of thermal magnetic protection tripped.
Loading can always be completed in the manual mode (as
it is during maintenance work) by means of the dedicated
lever supplied. Check the power available in the supply circuit
to find out whether several motors for loading the closing
springs can operate at the same time. To prevent excessive
power consumption, especially when the installation is put
into service, it is advisable to load the springs by hand before
energizing the auxiliary circuits.

24
electrical signalling of
spring loaded/discharged

spring loaded/discharged
mechanical indicator

Contact for signalling closing spring loaded/discharged 13 Locks and interlocks


-BS2 13 A O pening pushbutton lock (with or without padlock).
This consists of a microswitch, which allows remote signalling
Locks the opening pushbutton with a 4 mm diameter padlock
of the state of the closing spring of the circuit-breaker
(not part of the standard equipment). The padlock is only
operating mechanism.
supplied on request.
One of the following signals can be selected:

12A contact open: electrical signalling of spring loaded 13 B Closing pushbutton lock (with or without padlock).
12B contact closed: spring discharged signal Locks the closing pushbutton with a 4 mm diameter padlock
(not part of the standard equipment). The padlock is only
supplied on request.

25
2. Selection and ordering

Optional accessories

locking magnet on
operating mechanism

14 Circuit-breaker open key lock (different keys or the 15 Locking magnet -RL1 on operating mechanism.
same keys). Local manual closing and remote electrical closing can only
The locking action is performed by a special circular lock. be obtained when electromagnet RL1 is energized. When
Can be supplied with different keys or the same keys (for -RL1 is requested for a withdrawable circuit-breaker, it comes
several circuit-breakers). To apply the key lock, press the with contact -BT2 unless contacts -BT1, -BT2 have been
opening pushbutton, turn the key and remove it. Local manual requested.
closing and remote electrical closing are inhibited once the
key has been removed.

26
Interlock to prevent circuit-breaker Interlock to prevent racking-in/
closing during racking-in/out. out when circuit-breaker is
closed.

Example of interlock application on a plug-in circuit-breaker with truck for ABB


UniGear switchgear or PowerCube enclosure.

16 Locking magnet -RLE2 on truck. 17 Interlock for fixed circuit-breaker (for fixed apparatus
This accessory is mandatory in withdrawable versions for converted to plug-in by the customer).
UniGear switchgear type ZS1 and for PowerCube modules This device can be useful when fixed circuit-breakers are
so as to prevent the circuit-breaker from being racked into converted into withdrawable ones by the customer.
the switchgear when the plug of the auxiliary circuits is It allows the customer to create a mechanical lock that inhibits
disconnected from the switchgear socket. The plug also racking-out/racking-in when the circuit-breaker is closed and
prevents racking-in if the rated current of the circuit-breaker prevents the circuit-breaker from closing during movement.
differs from that of the compartment (dedicated striker pins Note. The device must be requested when the order is placed
prevent the plug from being plugged into the socket if the since it must be assembled in the factory.
circuit-breakers rated current is lower than the rated current
of the panel).

27
2. Selection and ordering

Optional accessories

18 Mechanical isolation interlock with the door of Unigear 19 Gas monitoring device
ZS1, ZS2 switchgear and the PowerCube enclosure. Notes:
This device prevents the circuit-breaker from being racked- specify when ordering the apparatus if the pressure
in when the switchgear door is open. It is only intended for switch is required since it cannot be installed by the
circuit-breakers used in UniGear ZS1 and ZS2 switchgear customer at a later date;
and in PowerCube modules (which must be equipped with a devices 19B and 19C are supplied without LED for the
dedicated actuator on the door). 40.5 kV HD4/Z series
19A Two-level pressure switch
19B Two-level pressure switch with two-level SF6 monitoring
device, three LEDs and supplementary shunt opening
release MO2: circuit-breaker opening and closing lock
19C Two-level pressure switch with two-level SF6 monitoring
device and three LEDs: circuit-breaker locking in the
position it has reached

28
20 Insulating partitions for fixed circuit-breakers.
Consult chapter 4 for a list of the circuit-breakers for which
the partitions are available (on request. Assembly is at the
customers charge).

21 3-lobed key for manual opening and closing


operations
This accessory is only available for the 40.5 kV HD4/Z series.

29
2. Selection and ordering

Characteristics of electrical accessories

Ps = 125 W/VA (Instantaneous service < 45 ms)


Un = 24, 30, 48, 60, 110, 125, 220, 250 V
Shunt opening release (-MO1; -MO2)
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Ps = 250 W/VA (150 ms)
Pc = 5 W/VA (antipumping function - continuous service)
Shunt closing release (-MC) Un = 24, 30, 48, 60, 110, 125, 220, 250 V
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Ps = 250 W/VA (150 ms)
Pc = 5 W/VA (continuous service)
Undervoltage release (-MU) Un = 24, 30, 48, 60, 110, 125, 220, 250 V
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Ps = 1500 W/VA (100 ms)
Pc = 400 W/VA (spring charging time: 6 s)
Spring charging geared motor (-MS) Un = 24, 30, 48, 60, 110, 125, 220, 250 V
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Ps = 250 W/VA (150 ms)
Pc = 5 W/VA (continuous service)
Locking magnets (-RL1; -RL2) Un = 24, 30, 48, 60, 110, 125, 220, 250 V
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Un = 24, 30, 48, 60, 110, 125, 220, 250 V
Gas control device with 3 LEDs Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Un = 500 V~ 220 V

Circuit-breaker auxiliary contacts Icu = 15 A 1.5 A


(only for 40 kV HD4/Z) cos = 0.4
T = 10 ms
Un Rated voltage.
Cos Power factor.
Icu Breaking capacity
Ps Inrush power consumption (the inrush time is indicated in brackets).
Pc Continuous service power consumption.
T Time constant.

30
Identification of the circuit-breaker type Examples of identification
The identification code of a circuit-breaker is made up with The code HD4/P 17.16.25 identifies a withdrawable circuit-
the elements from the table below. breaker for Unigear ZS1 panel with 17.5 kV rated voltage,
For correct identification of a circuit-breaker, it is necessary to 1600 A rated normal current and 25 kA breaking capacity.
refer to the characteristics tables on pages 8 to 14. The code HD4/W 24.20.25 identifies a withdrawable circuit-
The selected circuit-breaker can then be completed with the breaker for PowerCube modules with 24 kV rated voltage,
optional accessories indicated on the following pages. 2000 A rated normal current and 25 kA breaking capacity.

HD4 ... ... ... ...


Version Fixed
UniGear type ZS1 P
PowerCube W-P
ZS3.2 Z
Rated voltage 12 kV 12
17.5 kV 17
24 kV 24
40.5 kV 40
Rated normal current (1)
630 A 06
1250 A 12
1600 A 16
2000 A 20
2500 A 25
3150 A 32
3600 A 36
Rated breaking capacity 16 kV 16
20 kV 20
25 kV 25
31.5 kV 32
40 kV 40
50 kV 50

(1) Rated uninterrupted current defined in free air for fixed circuit-breaker.
For the withdrawable version, see the previous pages.

31
3. Specific product characteristics

Resistance to vibrations Tropicalization

HD4 circuit-breakers are unaffected by mechanically HD4 circuit-breakers are manufactured in compliance with the
generated vibrations. strictest regulations for use in hot-humid-saline climates.
For the versions approved by the naval registers, please All the most important metal components are treated against
contact us. corrosive factors according to UNI EN 12500 Standards
environmental class C.
Galvanisation is carried out in accordance with UNI ISO 2081
Standards, classification code Fe/Zn 12, with a thickness of
12x10-6 m, protected by a conversion layer mainly consisting
of chromates in compliance with the UNI ISO 4520 Standards.
These construction characteristics mean that the whole HD4
series of circuit-breakers and its accessories comply with
climate graph 8 of the IEC 60721-2-1 and IEC 60068-2-2
(Test B: Dry Heat / IEC 60068-2-30 (Test Db: Damp Heat,
cyclic) Standards.

32
Altitude Graph for determining the Ka correction factor
according to the altitude according to IEC 62271-1
STDs

Example
Installation altitude 2000 m
Operation at the rated voltage of 12 kV
Withstand voltage at industrial frequency 28 kV rms
Impulse withstand voltage 75 kVp
Factor Ka obtained from graph = 1.13.

Considering the above parameters, the apparatus will


have to withstand the following values (under test and at
zero altitude, i.e. at sea level):
withstand voltage at industrial frequency equal to:
28 x 1.13 = 31.6 kVrms
impulse withstand voltage equal to:
75 x 1.13 = 84.7 kVp.

From the above, it can be deduced that for installations


at an altitude of 2000 m above sea level, with 12 kV
service voltage, apparatus must be provided with 17.5
kV rated voltage, characterised by insulation levels at
The insulating property of air decreases as the altitude
industrial frequency of 38 kVrms with 95 kVp impulse
increases, therefore this must always be taken into account
withstand voltage.
for external insulation of the apparatus (the internal insulation
does not undergo any variations as it is guaranteed by the kA
1,50
SF6 gas).
The phenomenon must always be taken into consideration
m = 1
during the design stage of the insulating components of
apparatus to be installed over 1000 m above sea level In this Ka = e m (H 1000)/8150
1,40
case a correction coefficient must be considered, which can
be taken from the graph to the side, built up on the basis of
the indications in the IEC 62271-1 Standards.
The following example is a clear interpretation of the
1,30
indications given above.

1,20

1,10

1,00
1000 1500 2000 2500 3000 3500 4000 H

H = altitude in metres;
m = value referred to industrial frequency and the
atmospheric impulse withstand voltages and those
between phase and phase.

33
3. Specific product characteristics

Environmental protection programme Anti-pumping device

HD4 circuit-breakers are manufactured in accordance with The ESH operating mechanism on HD4 circuit-breakers
the ISO 14000 Standards (Guidelines for environmental (in all versions) is fitted with a mechanical anti-pumping
management). device which prevents re-closing due to either electrical or
The production processes are carried out in compliance mechanical commands.
with the Standards for environmental protection in terms of Should both the closing command and any one of the
reduction in energy consumption as well as in raw materials opening commands be active at the same time, there
and production of waste materials. All this is thanks to would be a continuous succession of opening and closing
the medium voltage apparatus manufacturing facility operations.
environmental management system. The anti-pumping device avoids this situation, ensuring that
Assessment of the environmental impact of the life cycle of each closing operation is only followed by a single opening
the product, obtained by minimising energy consumption operation and that there is no closing operation after this. To
and overall raw materials of the product, became a concrete obtain a further closing operation, the closing command must
matter during the design stage by means of targeted selection be released and then relaunched.
of the materials, processes and packing. Furthermore, the anti-pumping device only allows circuit-
Production techniques which prepare the products for simple breaker closure if the following conditions are present at the
dismantling and separation of the components are used same time:
during manufacture of the circuit-breakers. This is to allow operating mechanism springs fully charged
maximum recycling at the end of the useful life cycle of the opening pushbutton and/or opening release (-MO1/-MO2)
apparatus. not enabled
main circuit-breaker contacts open.

34
Switching special loads
The table indicates the breaking capacities which can be guaranteed for switching special loads.

Circuit-breaker HD4
Rated normal current for fixed circuit-breaker In [A] 630 1250 1600 2000 2500 3150 3600
No-load MV/LV transformer breaking Isc [A] 10 10 10 10 10 10 10
No-load cable breaking Isc [A] 12 kV 25 25 25 25 25 25 25
17.5 - 24 kV 31.5 31.5 31.5 31.5 31.5 31.5 31.5
36 - 40.5 kV 50 50 50 50 50 - -
Capacitive current breaking (C2 class) Isc [A] 400 630 1000 1250 1250 1250 1250
Reactance compensation current breaking Isc [A] 630 630 1250 1250 1250 1250 1250
Breaking of rated motor currents Isc [A] 630 630 1250 1250 1250 1250 1250

Spare parts Ordering


Replacement can only be carried out by trained personnel For availability and ordering of spare parts, please contact our
and/or in our workshops: Service, specifying the circuit-breaker serial number.
opening springs
closing springs
complete pole
basic operating mechanism
bushings, terminals and insulating protections.

Replacement which can be carried out by the customer:


isolating contacts
geared motor limit switch contact
KA1 instantaneous relay
KA2 instantaneous relay.

35
4. Overall dimensions

Fixed circuit-breakers without terminals

600
HD4/GT 355
578 20
TN 7200
210 210 2 x M8
Ur 12 kV
Ir 630 A
Isc 25 kA

67.5

35
28

714

622
639.5
63

468.5
M27 x 2
302.5
16
231
43

472 10.5 13 120


598 270 37

618 335
477

Fixed circuit-breakers without terminals

HD4/GT 600

578
TN 7201
210 210
Ur 12 kV
Ir 630 A
Isc 31.5 kA
M30 x 1.5

HD4/GT
TN 7201
310

28
Ur 12 kV
Ir 1250 A
622
655

Isc 25 kA
31.5 kA
40 kA
16
50 kA
266.5

HD4/GT
43

TN 7201
472 35 2.5
Ur 12 kV 10.5 13
20

598 322
Ir 1600 A
618 385
Isc 20 kA 493
25 kA
31.5 kA
40 kA
50 kA

36
Fixed circuit-breakers without terminals

HD4/GT
TN 7202
Ur 12 kV
Ir 2000 A
2500 A
3150 A
Isc 25 kA
31.5 kA
40 kA
50 kA

Fixed circuit-breakers without terminals

HD4/GT
TN 7360
Ur 12 kV
Ir 630 A
1250 A
Isc 20 kA
25 kA
31.5 kA

37
4. Overall dimensions

Fixed circuit-breakers without terminals

HD4/GT
TN 7361
Ur 12 kV
Ir 630 A
1250 A
Isc 20 kA

Fixed circuit-breakers

161
HD4 493
44 176
TN 7177 150 150 92 378.5 92
10 334.5 44
 22

Ur 17.5 kV
 22

50

Ir 630 A
1250 A
1600 A
317
317

Isc 16 kA
28
10

25 kA  22
10

 22
640

31.5 kA YU
582

549.5

540

YU

8
297.5

297.5
257.5

Q60
21.5
43

347
 10.5  13 120
473 1250A 270
37
493 1600A 335 630A

38
Fixed circuit-breakers

600 161
HD4 578 92 379
176
TN 7178 210 210 44 335
92
50 10 44
Ur 17.5 kV

 22
Ir 630 A
1250 A

 22

317
1600 A

317
Isc 16 kA

10
 22
28  22

648.5

10
25 kA

622
558.5
YU

31.5 kA

468.5
YU

306.5
306.5
266.5
8
43

472  13 120
 10.5
598 270
1250A 37
618
1600A 335 630A

Fixed circuit-breakers

600
HD4
578
TN 7163 210 210

Ur 17.5 kV
Ir 1600 A
Isc 40 kA
50 kA
2x 18
310
310

28
HD4
80

TN 7163 15.5 32
655

622

Ur 17.5 kV YU
8

Ir 2000 A YU

Isc 25 kA
306.5

31.5 kA
266.5

Q60
8

40 kA
 13
50 kA
43

472
 10.5 35
598 2.5
20

618 322
385
561

39
4. Overall dimensions

Fixed circuit-breakers

HD4 137.5 137.5 420 min.


730
TN 7165 708
275 275
Ur 17.5 kV
465
Ir 2500 A

349.5
3150 A
3600 A

670 min.
Isc 25 kA

15
31.5 kA

310
28

62
40 kA
50 kA 20 40

655

20

622
YU

468.5
40
HD4
YU

20
20
TN 7165 8

Ur 24 kV

266.5
4 x  18
 13
Ir 2500 A
3150 A
43

602 10.5 115


3600 A 2

20
728 322
35
Isc 25 kA 748 385
603
31.5 kA
40 kA
Insulating partitions (only for 24 kV) to be provided by
the customer (a special kit is available on request).

Fixed circuit-breakers

600
HD4
578
TN 7179 210 210 400 min. 200
105 105 161
Ur 24 kV
92 44 399 176
Ir 630 A 50 10 355
92 44

1250 A
 22

1600 A
 22

Isc 16 kA
670 min.

362

362

20 kA
 22
 22

25 kA
10
729.5

28
712

639.5

622

YU
468.5

YU
342.5
342.5
302.5

10

Q60
8

 13
43

472 120
598 10.5 270
1250A 37
618 1600A 335 630A

Insulating partitions to be provided by the customer


(a special kit is available on request).

40
Fixed circuit-breakers

730
HD4 161
708
44
TN 7242 275 275 92 399 176
92
50 10 355 44
Ur 24 kV
Ir 630 A

 22
1250 A

 22
1600 A

362

362
Isc 16 kA

 22
 22
20 kA

729.5
25 kA 28

10
639.5

620
YU

468.5
YU

10

342.5

342.5
302.5
8
Q60

 13
43

602 120
728  10.5 270
1250A 37
748 335
1600A 630A

Fixed circuit-breakers

730
HD4
708
TN 7174
275 275
Ur 24 kV
Ir 1600- A
2000
Isc 25 kA
2x 18
31.5 kA
310
310

40 kA
80

28
15.5 32
622
655

YU
8

YU

8
306.5
266.5

Q60

13
43

602 10.5 115 3


20

728 322
35
385
748
561

41
4. Overall dimensions

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards

493
HD4/GT/P
150 150
TN 7286 56 72 5.5
202

10
30
Ur 12 kV
Ir 630 A
1250 A
Isc 20 kA 67.5
25 kA

 35
31.5 kA 51

622 MAX
205
621.5
624.5

543
586
HD4/P (*)

63
TN 7286
28
Ur 12 kV
247.5

260
17.5 kV
Q60

78
Ir 630 A

154
20

1250 A
Isc 16 kA 4
4

21.5
 19
4

458 416
25 kA
503 437
31.5 kA 532 570 53
36
659

(*) HD4/P kV for PowerCube.

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards

HD4/GT/P
TN 7350
Ur 12 kV
Ir 1250 A
Isc 40 kA

HD4/GT/P
TN 7350
Ur 12 kV
Ir 1600 A
Isc 20 kA
25 kA
31.5 kA
40 kA
50 kA

HD4/GT/P
TN 7351
Ur 12 kV
Ir 2000 A
Isc 25 kA
31.5 kA
40 kA
50 kA

42
HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards

HD4/GT/P
TN 7352
Ur 12 kV
Ir 2500 A
Isc 25 kA
31.5 kA
40 kA
50 kA

HD4/P
TN 7352
Ur 12 kV (*)
17.5 kV
Ir 2500 A
Isc 25 kA
31.5 kA
40 kA
50 kA

(*) HD4/GT/P 12 for UniGear ZS1 and for PowerCube 12 kV for PowerCube.

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards

HD4/GT/P
TN 7371
Ur 12 kV
Ir 3150 A (*)
Isc 25 kA
31.5 kA
40 kA
50 kA

HD4/P
TN 7371
Ur 17.5 kV
Ir 3150 A (*)
Isc 25 kA
31.5 kA
40 kA
50 kA

(*) 3600 - 4000 A with forced switchboard ventilation (consult the UniGear type ZS1 switchboard technical catalogue).

43
4. Overall dimensions

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards

HD4/P
TN 7354
Ur 24 kV
Ir 630 A
1250 A
Isc 16 kA
20 kA
25 kA

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards

HD4/P (*)
TN 7355
Ur 24 kV
Ir 1600 A
Isc 16 kA
20 kA
25 kA
31.5 kA (**)

(*) Also valid for PowerCube.


(**) Not for PowerCube.

44
HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards

HD4/P (**)
TN 7356
Ur 24 kV
Ir 2000 A
Isc 16 kA
20 kA
25 kA
31.5 kA (***)

HD4/P (**)
TN 7356
Ur 24 kV
Ir 2500 A (*)
Isc 20 kA
25 kA
31.5 kA (***)

(*) 2500 A with forced ventilation; 2300 A with natural ventilation.


(**) Also valid for PowerCube.
(***) Not for PowerCube.

HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards

HD4/P
TN 1VCD000099
Ur 24 kV
Ir 1250 A
Isc 31.5 kA

45
4. Overall dimensions

HD4/W withdrawable circuit-breakers for PowerCube modules

493
HD4/W
150 150
TN 7229
30 202 56 72 5.5

10
Ur 12 kV
17.5 kV
Ir 630 A
1250 A
Isc 16 kA
25 kA 48

 35
205
31.5 kA
625.5

628.5
590

547
636
28

264
Q60

78
158
340 416 4

21.5
 19.5
458 437
20
503 570 53
36
532
659

HD4/W withdrawable circuit-breakers for PowerCube modules

636
HD4/W
578
TN 7182 210 210
Ur 12 kV

10
44 228 56 63 15

17.5 kV
 35

Ir 630 A
1250 A
Isc 16 kA
25 kA
310

31.5 kA
28
695
692

702
640

8
284

89
169

606 4
359
653 40
551 53
682 36
640

46
HD4/W withdrawable circuit-breakers for PowerCube modules

HD4/W
TN 7421
Ur 12 kV
17.5 kV
Ir 1250 A
Isc 40 kA
50 kA

HD4/W withdrawable circuit-breakers for PowerCube modules

636
HD4/W
578
TN 7239 210 210
Ur 12 kV 272
56 63 15
44

10
17.5 kV
Ir 1600 A
2000 A
Isc 16 kA
25 kA
31.5 kA
310

28
695
673

702
640
 79

8
284

89
169

4
606 359 40
653 36 551 53
682 640

47
4. Overall dimensions

HD4/W withdrawable circuit-breakers for PowerCube modules

HD4/W
TN 1VCD000053
Ur 12 kV
17.5 kV
Ir 3150 A
Isc 31.5 kA
40 kA
50 kA

HD4/W withdrawable circuit-breakers for PowerCube modules

HD4/W 636
578
TN 7183 210 210
23
20

272
Ur 24 kV 44
Ir 630 A
1250 A
Isc 16 kA
20 kA
 35

25 kA
310
776

28
767

740

792
649

8
329

125

12.5
202

25.5

610 4 53
460
653 710
682 36

48
HD4/Z withdrawable circuit-breakers for UniGear type ZS3.2 - 40.5 kV switchboards

HD4/Z/40.5 kV
TN 7227
Ur 40.5 kV
Ir 1250 A
1600 A
2000 A
2500 A (*)
Isc 25 kA
31.5 kA

A
1250-1600 A 35 mm
2000-2500 (*) A 79 mm

(*) With natural ventilation in loose enclosure type Powerbloc; with forced ventilation in switchboard type ZS3.2.

49
5. Electric circuit diagram

Application diagrams
The following diagram (No. 400007) shows the circuits of the withdrawable circuit-breakers up to 24 kV
type HD4/P, HD4/W, delivered to the customer by means of connector X.

Graphical symbols for electrical diagrams (IEC 60617 and CEI 3-14 ... 3-26 Standards)

Thermal effect Mass, frame Capacitor (general Passing make contact


symbol) closing momentarily
during release

Electromagnetic effect Conductors in shielded Motor (general symbol) Closing position contact
cable (two conductors (limit switch)
shown)

Timing Connections Rectifier with two Opening position contact


of conductors half-waves (bridge) (limit switch)

Pushbutton control Terminal or clamp Make contact Power circuit-breaker


with automatic opening

Operated by key Socket and plug Break contact Control coil


(female and male) (general symbol)

Earth (general symbol) Resistor Change-over break Lamp (general symbol)


(general symbol) before make contact

50
Specific diagrams are available for other types of circuit-breakers:
fixed circuit-breakers up to 24 kV - 1VCD 400005
HD4/Z 40.5 kV withdrawable circuit- breakers - 1VCD 400013.
In any case, to take into account the evolution of the product, it is always useful to refer to the circuit diagram provided with each circuit-breaker.

51
5. Electric circuit diagram

52
53
5. Electric circuit diagram

Represented operational state -BB5 = Contacts signalling undervoltage release


The diagram indicates the following conditions: energized/de-energized
circuit-breaker open and connected -FB1 = Miniature breaker with thermomagnetic O/C
circuits de-energized release for protection of the spring-charging
closing springs discharged motor (see note F)
key lock with key inserted and trapped
-BS1...2 = Limit switches of the spring-charging motor
SF6 gas pressure at rated service value (380 kPa absolute).
-BD1 = Position contact of the enclosure door.
Foreseen for HD4/C only.
-BT3 = Circuit-breaker position contact. It is open
Caption
during the isolating travel of the breaker
= Reference number of diagram figure -BT5 = Contacts signalling circuit-breaker in the
* = See note indicated by the letter removed position (they are those signalling
-BM = Device for the supervision of shunt opening circuit-breaker in the isolated position located
release coil continuity (see note E) on the enclosure, in the fixed part: see contacts
-BP = Pressure-switches with two operating levels: -BT2 given on circuit diagram 1VCD 400036
operating for low gas pressure. Contacts 11- figures 5-6)
12-14 change position, as regard the position -BT1 = Contacts signalling circuit-breaker in the
indicated on the diagram, when the pressure connected position (see note G)
from 380 kPa absolute gets to a value lower -BT2 = Contacts signalling circuit-breaker in the
than 310 kPa absolute. In case of rated isolated position (see note G)
pressure reset the same contacts change -SC = Pushbutton or contact for the circuit-breaker
again position when the pressure, from a closing
value lower than 310 kPa absolute, gets up -BK = Contact operated by the key lock preventing
to 340 kPa absolute. electrical opening with earthing truck
operating for insufficient gas pressure. connected (It is mandatory for earthing truck
Contacts 21-22-24 change position when with making capacity)
the pressure from 380 kPa absolute absolute -SL1 = Contact locking for circuit-breaker closing
gets to a value lower than 280 kPa absolute. -SO = Pushbutton or contact for the circuit-breaker
In case of rated pressure reset the same opening
contacts change again position when the -TR1, -TR2 = Rectifiers for shunt opening releases -MO1
pressure, from a value lower than 280 kPa and -MO2
absolute, gets up to 310 kPa absolute. -XB = Connector for the circuit-breaker circuits
-KT = Solid-state time-delaying device for the -XB2-XB62 = Connectors of accessories
undervoltage release (see note I) -XB1 = Switchboard terminal board (mounted externelly
-KI = Integrated gas pressure control circuit, to the circuit-breaker)
including: -MC = Shunt closing release
-PG = Green led indicating normal gas pressure -RL1 = Locking magnet on the operating mechanism.
-PR = Red led indicating insufficient gas pressure If de-energized it prevents the circuit-breaker
-PY = Yellow led indicating low gas pressure closing mechanically
-KA1 = Auxiliary relay to double the -BP pressure- -RL2 = Locking magnet on the truck. If de-energized
switch contacts operating for low gas pressure it prevents the circuit-breaker racking-in and
-KA2 = Auxiliary relay to double the -BP pressure- racking-out mechanically (It is possible to limit
switch contacts operating for insufficient gas its consumption by connecting in series a
pressure delaying pushbutton enabling the operation)
-XB5 = Connector -MO1 = First shunt opening release (see note E)
-BR51 = Microprocessor based overcurrent release type -MO2 = Second shunt opening release (see note E)
PR512 external to the circuit-breaker (see note D) -MO3 = Opening solenoid for the PR512
-MS = Motor for the closing springs charging (see microprocessor based release external the
note C) circuit-breaker (see note D)
-QB = Main circuit-breaker -MU = Instantaneous undervoltage release or
-BB1-BB3 = Circuit-breaker auxiliary contacts (no. 3 packs undervoltage release with electronic time-delaying
of 5 contacts) device (see note B)
-BB4 = Auxiliary passing contact (closing momentarily -VF = Filter (provided with voltage supply 220V d.c. or
when circuit-breaker opens) greater)

54
Diagram figures description Fig. 14 = Integrated gas pressure control circuit,
including:
Fig. 1 = Spring charging-motor circuit (see note C).
lock of circuit-breaker closing and opening
Fig. 2 = Shunt closing release (antipumping is achieved
through -KA2 relay auxiliary contacts in case
mechanically).
of insufficient gas pressure (provide the
Fig. 3 = Locking magnet on the operating mechanism.
locking magnet given in fig. 3)
If de-energized it prevents the circuit-breaker
3 leds for local indication of normal, low and
closing mechanically.
insufficient gas pressure
Fig. 4 = Locking magnet on the truck. If de-energized
contacts for remote indication of normal, low
it prevents the circuit-breaker racking-in and
and insufficient gas pressure.
racking-out mechanically (It is possible to limit
For -BP pressure switches tripping values see
its consumption by connecting in series a
the caption.
delaying pushbutton enabling the operation)
Fig. 20 = Contact operated by the key lock, preventing
(see note H).
electrical opening, with earthing truck with
Fig. 5 = Instantaneous undervoltage release (see note
making capacity connected. (It is obligatory
B)
for earthing truck with making capacity when
Fig. 6 = Undervoltage release with solid-state time-
is requested the first shunt opening release
delaying device (see notes B and I)
-MO1).
Fig. 7 = First shunt opening release circuit with
Fig. 21 = Miniature breaker with thermomagnetic O/C
possibility of permanent supervision of coil
release for protection of the spring-charging
continuity (see note E).
motor (see note F).
Fig. 9 = Second shunt opening release circuit with
Fig. 22 = Contact signalling closing springs charged.
possibility of permanent supervision of coil
Fig. 23 = Contact signalling closing springs discharged.
continuity (see note E).
Fig. 24 = Contact signalling undervoltage release
Fig. 10 = Opening solenoid for PR512 microprocessor
energized (see note B).
based release external to the circuit-breaker
Fig. 25 = Contact signalling undervoltage release de-
(see note D).
energized (see note B).
Fig. 11 = Gas pressure control circuit including:
Fig. 26 = Contact signalling miniature breaker for
contacts for remote indication of normal, low
protection of the spring-charging motor on.
and insufficient gas pressure.
Fig. 27 = Contact signalling miniature breaker for
For -BP pressure-switches tripping values see
protection of the spring-charging motor off.
the caption.
Fig. 30 = Passing auxiliary make contact closing
Fig. 12 = Integrated gas pressure control circuit,
momentarily when circuit-breaker opens (-MO1,
including:
-MO2, -MO3 and -MU).
circuit-breaker opening through the -MO2
Fig. 31 = Circuit-breaker available auxiliary contacts.
release and closing lock through a -KA2 relay
Fig. 32 = Circuit-breaker available auxiliary contacts.
auxiliary contact in case of insufficient gas Fig. 51 = Contacts signalling circuit-breaker in the
pressure (provide the locking magnet given in connected and isolated positions located
fig. 3) on the circuit-breaker, they are provided on
3 leds for local indication of normal, low and request (see note G).
insufficient gas pressure
contacts for remote indication of normal, low
and insufficient gas pressure.
For -BP pressure switches tripping values see
the caption.

55
5. Electric circuit diagram

Notes G) The contacts (-BT1 and -BT2) shown in fig. 51 for


A) The circuit-breaker is only fitted with the accessories signalling the circuit-breaker status are located on the
listed in the order confirmation. To make out the order, circuit-breaker (moving part) and are available on request.
please consult the catalogue of the apparatus. However, application of these contacts on the enclosure
B) The undervoltage release can be provided for power is usually foreseen (fixed part): see diagram 401693 for
supply with voltage branched on the supply side of the CBE 11 - 21 - 31 and diagram 401526 for CBE 41 - 51.
circuit-breaker or from an independent source. H) When fig. 9 is requested, the contact of pack -BB3 to
Either the instantaneous undervoltage release or the one terminals 29-30 in fig. 32 is not available.
with electronic delay device can be used (delay can be When figs. 26-27 are requested, the -BB2 contact to
selected between 0.5 3 s; see note I). Circuit-breaker terminals 29-30 of figs. 31-32 is not available.
closing is only possible with the release energised (the When fig. 30 is requested, the contact of pack -BB3 to
closing lock is made mechanically). terminals 23-24 in fig. 32 is not available.
The contact in fig. 24 or the one in fig. 25 is available on I) Make one of the following bridges to select the delay
request. required:
A delay of 50 ms between the moment of consent of the 0.5 s: terminals 6-7
undervoltage release and energisation of the shunt closing 1 s: terminals 6-8
release must be inserted when there is the same power 1.5 s: terminals 6-9
supply for the shunt closing and undervoltage releases 2 s: terminals 6-10
and automatic circuit-breaker closing on return of the 3 s: no bridge.
auxiliary power supply is required. This can be carried out J) When fig. 4 is requested, the contact of pack -BB1 to
by means of a circuit outside the circuit-breaker, including terminals 7-8 in figs. 31-32 is not available.
a permanent closing contact, the contact indicated in fig.
24 and a time-delay relay.
C) Check the power available on the auxiliary circuit to verify Incompatibility
the possibility of starting several motors for charging the The combination of circuits given in the figures below are not
closing springs at the same time. To avoid excessive possible on the same circuit-breaker:
consumption, it is necessary to charge the springs
manually before supplying the auxiliary circuit with 5 - 6 - 14 9 - 10 - 12 - 20 24 - 25
voltage. 5 - 6 - 20 11 - 12 - 14 26 - 27
D) Please see diagram 401530 for the connections between 9 - 10 - 12 - 14 22 - 23 31 - 32
the circuit-breaker auxiliary circuits and the PR512 type of
microprocessor-based overcurrent release located in the
switchboard.
E) The circuit for controlling continuity of the shunt opening
release winding must only be used for this function.
At a power supply lower than 220V, connect the Control
Coil Continuity device, or a relay or a signalling lamp
which consumes a current not exceeding 20 mA.
At a power supply equal to or higher than 220V, connect
a delay or signalling lamp which consumes a current not
exceeding 10 mA.
Other uses might jeopardise release functionality.
F) The -FB1 circuit-breaker in fig. 21 must always be
provided when there is a 24 kV d.c. spring charging
motor.
In case of opening caused by a fault in the motor, before
carrying out manual resetting, recharge the springs by
means of the special handle.

56
Notes
Notes

58
59
Contact us

1VCP000245 - Rev. D, en - Technical catalogue - 2015.10 (HD4 - IEC & GOST) (gs)
Your Service sales contact: www.abb.com/contacts
More Service information: www.abb.com/productguide

The data and illustrations are not binding. We reserve the right to make changes
without notice in the course of technical development of the product.