You are on page 1of 12

SWT 3000 Equipment Manual

Chapter 6: CLE Module

Description of operation 3

Jumper settings 7

Connector pin assignment 8


CLE Module SWT 3000 Equipment Manual

Table of Contents:

Description of operation----------------------------------------------------------------------------------------------------------- 3
The receive section---------------------------------------------------------------------------------------------------------------- 4
The transmit section -------------------------------------------------------------------------------------------------------------- 4
Alarm displays--------------------------------------------------------------------------------------------------------------------- 5
S6 control wires ------------------------------------------------------------------------------------------------------------------- 6
Test sockets ------------------------------------------------------------------------------------------------------------------------ 6
Inhibit line-------------------------------------------------------------------------------------------------------------------------- 6
Jumper settings --------------------------------------------------------------------------------------------------------------------- 7
Connector pin assignment of the CLE------------------------------------------------------------------------------------------ 8
Connecting cable to the PLC unit ESB 2000i --------------------------------------------------------------------------------- 9
Connection of an external SWT 3000 to the PowerLink 50/100------------------------------------------------------------ 9
VFx port 3----------------------------------------------------------------------------------------------------------------------- 9
VFx port 4----------------------------------------------------------------------------------------------------------------------10
Index: --------------------------------------------------------------------------------------------------------------------------------11
Appendix: ---------------------------------------------------------------------------------------------------------------------------12
List of figures ---------------------------------------------------------------------------------------------------------------------12
List of tables ----------------------------------------------------------------------------------------------------------------------12

Page - 2 Edition p3_3_x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual CLE Module

Description of operation
The CLE module (copper line equipment) provides the interface between an SWT 3000 unit op-
erated as a stand-alone unit and a copper transmission line. The teleprotection signal is transmitted
in the VF range from 300-4000 Hz. The following equipment configurations are possible:
z Connection of two SWT 3000 stand-alone units each containing one CLE module.
z Connection of an SWT 3000 stand-alone unit to an ESB 2000i unit. The SWT 3000
unit contains a CLE module as interface and the ESB 2000i unit an NFD module.
The S6 control wire for modules CLE and NFD makes alternate multi-purpose opera-
tion possible (AMP).
The CLE module contains two independent circuit sections:
z A transmit amplifier
z A receive filter
The CLE is connected to the PU3 module in the SWT 3000 unit. This module generates the VF
signal to be transmitted which is fed onto the transmission line by the transmit amplifier of the CLE.
In the opposite direction the VF signal is forwarded from the transmission route to the PU3 via the
receive filter.
The CLE does not have any control elements but three alarm displays and two test sockets on the
front panel. The CLE module does not generate any alarms but displays alarms generated by the
PU3.

MW

NF

Prot.

PU3

PON_PU

SAL S6

Inhibit

PU3 NF

Prot.

4000 Hz 300 Hz

EAL

S/N

SAL Transmit alarm S/N S/N alarm MW Measuring transformer


EAL Receive alarm Prot. Protection circuit S6 Control wire for alternate multi-
purpose op.

Figure 1: Block diagram of the CLE module

SIEMENS AG 2008 Edition p3_3_x 08/09 Page - 3


CLE Module SWT 3000 Equipment Manual

The receive section

The incoming VF signal from the copper line or from a PLC system is fed in at the receive section.
The input is protected against overvoltages up to 2kV that may be transferred to the transmission
route by coupling. The input impedance can be switched over from 600 to approx. 5 k.
Protective circuit HP filter passive Isolating amplifier HP filter active LP filter active

Z=600
5k Z=600

Isolating amplifier

Figure 2: The input circuit of the CLE module Test socket

The wanted signal is then filtered out from any interference signals. The attenuation tolerance dia-
gram of a band pass filter is preset for the input filter. The pass band is from 500-4000 Hz. The
band pass filter is implemented by cascading an active low-pass and high-pass filter.
The forward amplifier can be set to 0dB/+6dB/+12dB by means of links. Greater immunity to 50
Hz interference is obtained by means of the series-connected high-pass filter.
The signal is then transferred to the PU3. The receive signal can be tapped at a test socket. The
test socket is decoupled via an isolating amplifier so that there is no interference of the wanted sig-
nal through short-circuits or insertion of signals. The same voltage level prevails at the test socket
as at the input. The settable thresholds for the level alarm relate to the input of the PU3 and not to
the input of the CLE.

The transmit section

The wanted signal supplied by the PU3 is amplified in the transmit section. There is no filtering as
there is in the receive section since the signal supplied does not have interference of this type. The
PU3 supplies a level up to +4dB. The input signal is amplified by 11 dB to the range up to +15 dB.
The signal is extracted without voltage via a transformer with winding ratios that can be set to 1:2
or 1:16 and matched to the output impedance. This can be set to 600 or 5 k by means of links
with the corresponding output circuit.
Amplifier +11 dB Protection circuit
c11

to the trans-
from the PU3
Z=600 Z=600
mission line
5k

c13

Isolating ampl.

to the measuring input RMS


of the PU3
Z=5k Test socket
DC

Figure 3: Block diagram of the transmit amplifier

The output of the transmit section is again protected against any interference voltages from the
transmission path. The wanted signal can be measured via an isolating amplifier. A measuring
transformer supplies a DC voltage level that is proportional to the amplitude of the output signal to
the PU3 module for test purposes. The PU3 monitors this measured value and generates the
transmitter alarm from it. The output voltage for the 100% value is 4.5 V. A protective circuit re-
stricts this voltage to max. +5V.

Page - 4 Edition p3_3_x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual CLE Module

If any faults should occur in the SWT 3000 unit errored signals must not under any circumstances
be transmitted to the distant station. For this reason the transmitter output can be short-circuited via
a relay. This relay is driven by the PU3 module (PON_PU signal) and only enabled if the unit is op-
erating properly.

Alarm displays

The alarm signals generated by the PU3 module are displayed via red LED on the front panel of
the SWT 3000. LED are provided for the following alarms:

SIEMENS >

SWT 3000 >

LID2 LID1 SAL

OK LIA EAL

S/N

CLE Module

Figure 4: Displays on the CLE module

1. Transmitter alarm SAL


2. Receiver alarm EAL
3. Signal/noise level alarm S/N
The signals are low active and are fed to the LED drive via an integrated inverter module with a
+5V supply voltage.

SIEMENS AG 2008 Edition p3_3_x 08/09 Page - 5


CLE Module SWT 3000 Equipment Manual

S6 control wires

The CLE module contains an opt coupler for the S6 control wire. The S6 control wire is used for
disconnecting voice and data signals in a PLC system in alternate multi-purpose mode.
+5 V +12 V

S6

b23 S6

Figure 5: Block diagram of the S6 control

The circuit is driven on a low-active basis. The opt coupler is activated during transmission of pro-
tection data (S6 control wire =low).

Test sockets

The following test sockets are provided on the front panel of the CLE module:
z 1 ISEP socket for measuring the level of the receive signal
z 1 ISEP socket for measuring the level of the transmit signal
The level at the sockets is measured on a high impedance basis and corresponds to the value at
the measuring point. Incorrect operations such as short circuiting or inserting a signal (U < 5V) at
the measuring sockets does not result in interruption of teleprotection signaling.

Inhibit line

An inhibit line is routed via the CLE module which acts on the inhibit input of the power supply. If
there is no CLE module (in the case of a device with digital interfaces only) link X41 must therefore
be inserted in position 1-2 in the sub rack.

Page - 6 Edition p3_3_x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual CLE Module

Jumper settings

W4
X10 1 2 X12 X11
6 R9
N2
X9 1 2

V5
W3 T1
N4 W2 R7
W1
R8
H3 X2
1

V103

V102
W8
X15 X16
H2
N3
6

R136

R125

R124
H1
T2
D1

1
W6 W5
X5 X4 X3
N5

C100
K1
W7
X13 X14

Figure 6: Position of the jumpers on the CLE module

Table 1: Jumper settings for the input and output impedance


Setting 600 Ohm >5kOhm
Input impedance W4 without W4
Output impedance W5 W6, W7, W8

Table 2: Jumper settings for the receive signal gain


Receive signal gain [dB] Jumper X2 in pos.
0 W1
+6 W2
+12 W3

SIEMENS AG 2008 Edition p3_3_x 08/09 Page - 7


CLE Module SWT 3000 Equipment Manual

Connector pin assignment of the CLE


Table 3: Connector pin assignment of the CLE module
Pin Pin a Pin b Pin c
1 Shield GNDS GNDS
2
3 Ground GND Control wire S6 (S6AB)
4
5 Control wire S6 (S6AB_GND)
6
7 Protection receive signal A
8
9 Protection receive signal B
10
11 Protection transmit signal A
12
13 Protection transmit signal B
14
15 DC value transmit signal
16 S/N Alarm DC value transmit signal GND P5V (+5V)
17 EAL Alarm P5V (+5V)
18 P12V (+12V) M12V (-12V)
19 SAL Alarm
20 GND12 P12V (+12V)
21 INHIBIT INHIBIT
22 M12V (-12V) GND12
23 Enable transmitter output S6 control line from PU3
24 VF signal from PU3
25 VF signal from PU3 GND
26 VF signal to PU3
27 VF signal to PU3 GND Ground GND
28 S6 control wire from PU3
29
30
31 Shield GNDS Shield GNDS
32

Page - 8 Edition p3_3_x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual CLE Module

Connecting cable to the PLC unit ESB 2000i

The cable connection illustrated below is needed for connecting a remote SWT 3000 to the
ESB 2000i PLC system (CLE - NFD):

CLE c11
NFD
a10
F6
c13 c10
c7 a11
F6
c9 c11

c3 a13
S6
c5 a20

a1,c1,a31,c31 a1,c1,a31,c31

F6 Protection signals
S6 Control wire to the PLC unit in alternate multi-purpose mode
NFD Interface module of the PLC unit

Figure 7: Cable connection from the CLE to the PLC unit ESB 2000i

Connection of an external SWT 3000 to the PowerLink 50/100

The connection of the CLE module from an external SWT 3000 to the SUB-D female connector of
the VFx modules is shown in the figures below. In this case the VFx ports 3 resp. 4 must be used.

VFx port 3

SWT 3000 PowerLink


CLE X1 CFS-2 VFx
P12V a18 Connector panel Port 3
SUB-D connector
S6OUT c3

S6OUT_GND c5 12 S6IN_A

GND12 a20 31 S6IN_B

F6OUT_A c11 10 4-wire input A


F6OUT_B c13 29 4-wire input B

F6IN_A c7 11 4-wire output A


F6IN_B c9 30 4-wire output B

Figure 8: Connecting an external SWT 3000 to the port 3 of the VFx modules

SIEMENS AG 2008 Edition p3_3_x 08/09 Page - 9


CLE Module SWT 3000 Equipment Manual

VFx port 4

SWT 3000 PowerLink


CLE X1 CFS-2 VFx
P12V a18 Connector panel Port 4
SUB-D connector
S6OUT c3

S6OUT_GND c5 19 S6IN_A

GND12 a20 37 S6IN_B

F6OUT_A c11 14 4-wire input A


F6OUT_B c13 33 4-wire input B

F6IN_A c7 15 4-wire output A


F6IN_B c9 34 4-wire output B

Figure 9: Connecting an external SWT 3000 to the port 4 of the VFx modules

Page - 10 Edition p3_3_x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual CLE Module

Index:

A M

Alarm displays 3, 5 Measuring socket 4


Multi-purpose 3
B
O
Block diagram 3
Output impedance 4
C
P
Copper line equipment 3
Pass band 4
E
R
EAL 5
Equipment configurations 3 Receive section 4
Receiver alarm 5
F
S
Forward amplifier 4
S/NAL 5
S6 3
I S6 control wires 6
SAL 5
Inhibit line 6 Signal/noise level alarm 5
Input circuit 4
Input impedance 4
Input signal 4 T

Test sockets 6
L Transmit section 4
Transmitter alarm 5
Link assignment 7

SIEMENS AG 2008 Edition p3_3_x 08/09 Page - 11


CLE Module SWT 3000 Equipment Manual

Appendix:

List of figures
Figure 1: Block diagram of the CLE module ---------------------------------------------------------------------------------- 3
Figure 2: The input circuit of the CLE module-------------------------------------------------------------------------------- 4
Figure 3: Block diagram of the transmit amplifier --------------------------------------------------------------------------- 4
Figure 4: Displays on the CLE module----------------------------------------------------------------------------------------- 5
Figure 5: Block diagram of the S6 control------------------------------------------------------------------------------------- 6
Figure 6: Position of the jumpers on the CLE module----------------------------------------------------------------------- 7
Figure 7: Cable connection from the CLE to the PLC unit ESB 2000i----------------------------------------------------- 9
Figure 8: Connecting an external SWT 3000 to the port 3 of the VFx modules------------------------------------------- 9
Figure 9: Connecting an external SWT 3000 to the port 4 of the VFx modules------------------------------------------10

List of tables
Table 1: Jumper settings for the input and output impedance ---------------------------------------------------------------- 7
Table 2: Jumper settings for the receive signal gain --------------------------------------------------------------------------- 7
Table 3: Connector pin assignment of the CLE module ----------------------------------------------------------------------- 8

Page - 12 Edition p3_3_x 08/09 SIEMENS AG 2008

You might also like