# Table 8

* Table C.5 & C.6 Span Guideline

min storage capacity Demand No. Unit/


No Description
perday(litre) Required (litre) floor area

1 #1500/ bed
HOSPITAL 1500 185

The capacity of suction cistern 40% of the total daily storage capacity required. The balance of the 60% storage
volume shall beprovided at the elevated (roof top) cistern.

suction cistern

required =
required by panel =

type A 1.22 x1.22x1.22


type B 1.0 x 1.0 x 1.0

Providing :
7 by 5 with 2 layers type A =
total panel provided =
7/8 =

roof tank

stories

required =
required by panel =

Providing :
9 by 6 with 2 layers type A =
total panel provided =
7/8 =
Total Demand Required
(litre)

277500

277500
61666.6666666667

balance of the 60% storage


.

40%
111000 litre
24666.7 gallon
61.7 panel

400 gallon
1000 litre

28000 gallons
70 panel
24500 gallons

60%

166500 litre
37000.0 gallons
92.5

43200 gallons
108
37800 gallons
#
JADUAL KELAPAN [ Kaedah 12]
ANGGARAN PERMINTAAN AIR

Ruang (1) Jenis Premis / Bangunan


Rumah teres kos rendah / rumah pangsa kos rendah
Rumah teres setingkat / rumah kos rendah (kurang daripada RM25,000
/ rumah pangsa sederhana rendah dan sederhana
Rumah teres dua tingkat / rumah pangsa kos tinggi / rumah pangsa /
rumah bandar
Rumah berkembar / kelompok
Banglo / kondominium
Pasar basah
Pasar kering
Rumah kedai (satu tingkat ) kedai kos rendah
Rumah kedai (dua tingkat)
Rumah kedai (tiga tingkat)
Rumah kedai (empat tingkat)
Bengkel perindustrian ringan
Bengkel tunggal / berkembar
Bangunan untuk industri berat*
Bangunan untuk industri sederhana *
Bangunan untuk industri ringan *
Pejabat / kompleks/ perdagangan (penggunaan domestik)
Pusat atau dewan komuniti
Hotel
Institusi pendidikan (selain sekolah dan tadika)
Sekolah / tadika
Sekolah asrama penuh / institusi pengajian tinggi berasrama
Hospital
Masjid atau tempat ibadat yang lain
Penjara
Kem tentera
Terminal bas
Kios petrol (dengan tempat mencuci kereta)
Kios petrol ( tanpa tempat mencuci kereta )
Stadium
Padang golf
Gudang
Restoran
Lapangan terbang

Lain-lain
Kaedah 12]
NTAAN AIR

Ruang (2) Purata Permintaan Air


Harian (Liter)
1100 / unit
1300 / unit

1500 / unit
2000 / unit
2000 / unit
1500 / unit
450 / unit
2000 / unit
3000 /unit
4100 / unit
4550 / unit
1500 / unit
1500 / unit
65,000 / hektar
50,000 / hektar
33, 000 / hektar
1000 / 100 meter persegi
1000 / 100 meter persegi
1500 / bilik
100 / pelajar
50 / pelajar
250 / pelajar
1500 / katil
50 / orang
250 / orang
250 / orang
900 / ruang perkhidmatan
50,000 / /unit
10,000 / unit
55 / orang
1000 / 100 meter persegi
1500 / unit
25 / meter persegi
25 / penumpang
permintaan air sebagaimana yang
dianggarkan oleh pemaju atau pemilik
*

Table C.4 : Minimum storage capacities for hospital, airport and


Type of Building
Hospital
Airport
Heavy Industry
Medium Industry
Light Industry
Light Industrial Workshop
Wet Market
Dry Market
Semi Detached / Bungalow / Workshops

Table C.5: Minimum storage capacities for residential / sh

Type of Building
Dwelling Houses (Rural)
Dwelling Houses And Flats With Individual Storage
Cistern(Urban)
Flats With Shared Storage Cistern
Low Cost Houses (Rural And Urban)
Shop House (Single Storey) / Low Cost Shop
Shop House (Double Storey)
Shop House (Three Storey)
Shop House (Four Storey)
ities for hospital, airport and particular industry
Minimum storage capacity for one day (liters)
1500 / bed
25 / passenger
65000 / hectare
50000 / hectare
33,000 / hectare
1500 / unit
1500 / stall
450 / stall
1500 / unit

capacities for residential / shop premises

Minimum storage capacity for one day (liters)


800 / unit

1300 / unit
1000 / unit
800 / unit
2000 / unit
3000 / unit
4100 / unit
4550 / unit