CIRCUIT-BREAKER TYPE
Series Size Rated ultimate short-circuit Size
XT 1 breaking capacity at 415 Vac 160 A
2 B = 18 kA (XT1) 250 A
3 C = 25 kA (XT1) Rated insulation
4 N = 36 kA voltage Ui; i.e. the
5 S = 50 kA maximum r.m.s. value
H = 70 kA of voltage which the
6
L = 120 kA (XT2-XT4) circuit-breaker is
7 V = 150 kA (XT2-XT4) capable of
withstanding at the
supply frequency
under specified test
Rated operational conditions.
voltage Ue Rated impulse
withstand voltage
Uimp; i.e. the peak
value of impulse
Tmax XT1B 160 Ue=690V AC/500V DC Ui=800V Uimp=8kV S/N: voltage which the
Ue (V) 230 415 525 690 250 circuit-breaker can
Icu (kA) 25 18 6 3 18 withstand under
Ics (% Icu) 100 100 100 100 100
specified test
conditions.
Tmax Cat A 50-60Hz 2P in series
Seriel number
Cat A
SACE Tmax
XT1B
I on 160
IEC 60947-2
ABB SACE
Italy
Compliance with the
international
Standard
off IEC 60947-2:
Low-Voltage
TEST switchgear and
In = 160A controlgear-Circuit-
breakers.
CIRCUIT-BREAKER TYPE
Series Size Rated ultimate short-circuit Rated
T 1 breaking capacity at 415 Vac uninterrupted
2 B = 16 kA current
3 C = 25 kA 160 A
4 N = 36 kA 250 A
5 S = 50 kA 320 A
H = 70 kA 400 A
6
L = 85 kA (for T2) 630 A
7 L = 120 kA (for T4-T5-T7) 800 A
L = 100 kA (for T6) 1000 A
V = 150 kA (for T7) 1250 A
V = 200 kA 1600 A
Rated insulation
Rated uninterrupted voltage Ui; i.e. the
current Iu maximum r.m.s. value
of voltage which the
circuit-breaker is
Rated operational capable of
voltage Ue withstanding at the
supply frequency
under specified test
conditions.
Rated impulse
withstand voltage
Uimp; i.e. the peak
Tmax T2L160 Iu=160A Ue=690V Ui=800V Uimp=8kV IEC 60947-2 value of impulse
Ue (V) 230 400/415 440 500 690 250 500
voltage which the
Made in Italy
circuit-breaker can
Icu (kA) 150 85 75 50 10 85 85 by ABB SACE
withstand under
Ics (% Icu) 75 75 75 75 75 75 75 specified test
Cat A 50-60Hz 2P 3P conditions.
in series
Rated ultimate short- According to the CE marking affixed on Compliance with the
circuit breaking capacity international Standard ABB circuit-breakers to international
(Icu) and rated service IEC 60947-2, the circuit indicate compliance Standard
short-circuit breaking breakers can be divided with the following CE IEC 60947-2:
capacity (Ics) at into Category A, i.e. directives: Low-Voltage
different voltage values. without a specified Low Voltage Directive switchgear and
short-time withstand (LVD) no. 2006/95/CE controlgear-Circuit-
ASDC008046F0201
CIRCUIT-BREAKER TYPE
Series Size Rated ultimate short-circuit Rated
E X1 breaking capacity at 415 Vac uninterrupted
1 current
2 B = 42 kA 630 A
3 N = 65 kA (50 kA E1) 800 A
S = 75 kA (85 kA E2) 1000 A
4 1250 A
6 H = 100 kA 1600 A
L = 130 kA (150 kA X1) 2000 A
V = 150 kA (130 kA E3) 2500 A
3200 A
4000 A
5000 A
6300 A
Rated uninterrupted
current Iu
Rated operational
voltage Ue Rated short-time
withstand current Icw;
i.e. the maximum
current that
the circuit-breaker can
Iu=3200A Ue=690V carry during a
SACE E3V 32 Icw=85kA x 1s specified time.
Cat B ~ 50-60 Hz IEC 60947-2
made in Italy by
Ue (V) 230 415 440 525 690 ABB-SACE
Icu (kA) 130 130 130 100 100
Ics (kA) 100 100 100 85 85
Gemeinsame Daten
Tensin asignada de servicio Ue [V] 690
Tensin asignada de aislamiento Ui [V] 1000
Tensin asignada soportada a impulso, Uimp [kV] 12
Frecuencia [Hz] 50 - 60
Nmero polos 3-4
Ejecucin Fija - Extrable
SACE Emax 2
Niveles de prestaciones
[A]
[A]
[A]
Corriente permanente nominal Iu @ 40C [A]
[A]
[A]
[A]
Capacidad del polo neutro para interruptores tetrapolares [%Iu]
400-415 V [kA]
Poder asignado de corte ltimo en cortocircuito Icu
690 V [kA]
Poder de corte asignado de servicio en cortocircuito Ics [%Icu]
Corriente asignada admisible de corta duracin lcw (1s) [kA]
Categora de utilizacin (segn IEC 60947-2)
H - Fijo / Extrable [mm]
Dimensiones generales D - Fijo / Extrable [mm]
W - Fijo 3p / 4p /4pFs | Extrable 3p / 4p /4pFs [mm]
Interruptores automticos @ 690-1150 V AC
Interruptores-seccionadores @ 690-1150V AC, 1000 V DC
Versiones disponibles Carro de seccionamiento
Seccionador de tierra con poder de cierre
Carro de puesta a tierra
Control de la Potencia
Generadores