Protection Relays MiCOM P34x

Low Frequency Record


Functional Overview
IEC 2nd remote Remote Local
Generator Fault Records Disturbance
Band Pass
61850 Comm. port Comm. port Communication
(Description of ANSI code
Filter
Measurements nos., see Protection Function
64S 25
Low FV Overview)

Low FI
59N 59TN
U NEUTR AL2

27 81R 81 O
24 47
VTS 59 81 U 81 AB

I SENSITIVE

I2
+
67
50 51 V 32R 32L 40 46T 50
87T 64 87G C TS 51 78 49GT 67N 50BF 46OC LoL Thru
21 32O 27
_
I1

IE
UNEUTR AL1

50N 64R
59N 27TN 51 N
P345 only Generator Protection
P391
P344 only
Relays
P343 / 4 / 5 only
Rotor Binary R TDs CLIO P342 / P343 /
Always available
Ground Fault Input / Output Optional
P344 / P345
Coupling Unit

Global functions Figure 1: Simple function selection by mouseclick

The following global functions are generally


available in all devices:
4 setting groups
Metering
Event recording
Disturbance recording
Fault recording
Trip circuit supervision via PSL
Breaker state and condition monitoring
6 languages - English, French, German,
Spanish, Russian, Chinese

Main protection functions


The main protection functions are autonomous
and can be individually enabled or disabled to
suit a particular application. Each protection
function is available in 4 separate setting
groups which can be individually enabled or
disabled.Three phase tripping with faulted phase
indication is provided for all protection functions. Three phase biased generator-transformer differential protection is provided
to detect phase faults. This includes ratio and vector compensation as
Generator/transformer differential well as 2nd and 5th harmonic restraint for transformer inrush currents and
(P343/4/5 only) overfluxing. Two high set differential elements are provided to ensure rapid
Three phase generator differential protection is clearance of high fault currents.
provided to detect stator phase faults. This can
be set as either a percentage bias scheme with a
dual slope characteristic or as a high impedance
scheme. When high impedance is used, MiCOM P342/343/344/345:
additional stabilising resistance and a metrosil
Comprehensive protection for all your
will be required.
generator protection requirements