Outline Specification
03/31/2017
SECTION 263323.11
1.1 WARRANTY
1. Central Battery Equipment (excluding Batteries): One Two Insert number year(s).
2. Standard VRLA Batteries:
1. Input AC Voltage Tolerance: Plus 10 and minus [15] <Insert number> percent.
2. Input Frequency Tolerance: Plus or minus [3] [5] <Insert number> percent.
3. Synchronizing Slew Rate: [1] <Insert number> Hz per second, maximum.
4. Minimum Off-Line Efficiency: [95] [99] <Insert number> percent at 60 Hz, full
load.
5. Minimum Displacement Primary-Side Power Factor: [96] [98] <Insert number>
percent under any load or operating condition.
6. Ambient Temperature Rating (Other Than Batteries): Not less than 68 deg F and
not exceeding 86 deg F.
7. Ambient Storage Temperature Rating (Other Than Batteries): Not less than
minus 4 deg F and not exceeding 158 deg F
8. Ambient Temperature Rating (Batteries): Not less than 32 deg F and not
exceeding 104 deg F.
9. Ambient Storage Temperature Rating (Batteries): Not less than 0 deg F and not
exceeding 104 deg F
10. Humidity Rating: Less than 95 percent (noncondensing).
11. Altitude Rating: Not exceeding 3300 feet.
12. Off-Line Overload Capability: [1.1] [1.5] times the base load current for 60
seconds; minimum of 1.8 times the base load current for three seconds.
C. Inverter and Controls Logic: Microprocessor based, isolated from all power circuits;
provides complete self-diagnostics, periodic automatic testing and reporting; with
alarms.
1. Maximum Battery Recharge Time from Fully Discharged State: [24] <Insert
number> hours.
1. Input AC Voltage Tolerance: Plus 10 and minus [15] <Insert number> percent.
2. Input Frequency Tolerance: Plus or minus [3] [5] <Insert number> percent.
3. Synchronizing Slew Rate: [1] <Insert number> Hz per second, maximum.
4. Minimum Off-Line Efficiency: [95] [99] <Insert number> percent at 60 Hz, full
load.
5. Minimum Displacement Primary-Side Power Factor: [96] [98] <Insert number>
percent under any load or operating condition.
6. Ambient Temperature Rating (Other Than Batteries): Not less than 68 deg F and
not exceeding 86 deg F.
7. Ambient Storage Temperature Rating (Other Than Batteries): Not less than
minus 4 deg F and not exceeding 158 deg F
8. Ambient Temperature Rating (Batteries): Not less than 32 deg F and not
exceeding 104 deg F.
Cornell University CENTRAL BATTERY EQUIPMENT FOR
Verizon Executive Education Center EMERGENCY LIGHTING
263323.11-2
100% Design Development
Outline Specification
03/31/2017
9. Ambient Storage Temperature Rating (Batteries): Not less than 0 deg F and not
exceeding 104 deg F
10. Humidity Rating: Less than 95 percent (noncondensing).
11. Altitude Rating: Not exceeding 3300 feet.
12. Off-Line Overload Capability: [1.1] [1.5] times the base load current for 60
seconds; minimum of 1.8 times the base load current for three seconds.
C. Inverter and Controls Logic: Microprocessor based, isolated from all power circuits;
provides complete self-diagnostics, periodic automatic testing and reporting; with
alarms.
D. Integral Input Disconnecting Means and OCPD: Thermal-magnetic circuit breaker None
Insert disconnecting means.
1. Maximum Battery Recharge Time from Fully Discharged State: 24 Insert number
hours.
a. Normally Closed: [2] <Insert number>[; with trip alarm][; with time delay].
b. Normally Open: [2] <Insert number>[; with trip alarm].
1. Input AC Voltage Tolerance: Plus 10 and minus [15] <Insert number> percent.
2. Input Frequency Tolerance: Plus or minus [3] [5] <Insert number> percent.
Cornell University CENTRAL BATTERY EQUIPMENT FOR
Verizon Executive Education Center EMERGENCY LIGHTING
263323.11-3
100% Design Development
Outline Specification
03/31/2017
C. Inverter and Controls Logic: Microprocessor based, isolated from all power circuits;
provides complete self-diagnostics, periodic automatic testing and reporting; with
alarms.
D. Integral Input Disconnecting Means and OCPD: Thermal-magnetic circuit breaker None
Insert disconnecting means.
1. Maximum Battery Recharge Time from Fully Discharged State: 24 Insert number
hours.
1. Input Line Conditioning: Limit TDD at input terminals of [all] [indicated] central
battery equipment to less than [5] [10] <Insert number> percent and THD(V) to
[3] [5] <Insert number> percent.
Cornell University CENTRAL BATTERY EQUIPMENT FOR
Verizon Executive Education Center EMERGENCY LIGHTING
263323.11-4
100% Design Development
Outline Specification
03/31/2017
2. Input Line Conditioning: Limit TDD and THD(V) at the defined point of common
coupling.
3. Input Line Conditioning: <Insert requirements>.
4. Output Voltage Waveform: Sine wave with maximum [3] [5] <Insert number>
percent TDD throughout battery operating-voltage range, for 100 percent linear
load.
5. Output Voltage Waveform: <Insert requirements>.
a. Normally Closed: [2] <Insert number>[; with trip alarm][; with time delay].
b. Normally Open: [2] <Insert number>[; with trip alarm].
A. Enclosures: Type 1 Insert type steel cabinets with access to components through
hinged doors with flush tumbler lock and latch.
B. Multiple-output voltages.
C. Split-output configuration.