401B_21_1_prn

Trip Log - 000016 / 1/18/2016


SIMATIC 7:45:29.190 AM - New Dipalpur / FINAL / 18.01.16 09:19:37

New Dipalpur / FINAL / 400KV / DIA-1 / 401B_21.1

MLFB: 7SA61115AB924PK4----0S----------
Parameter set version: V04.70.07
Device path: C:\Siemens\Digsi4\D4proj\FINAL DIGSI DIPALPUR
21112012\New_Dipa\P7DI\GV\SD\00000022
Author:
Creation date: 16.12.11 15:21:00
Last modified: 18.01.16 09:18:49
Operating mode: Online
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS

1 Indications .................................................................................................................................................................................2
1.1 Trip Log - 000016 / 1/18/2016 7:45:29.190 AM - New Dipalpur / FINAL / 400KV / DIA-1 / ....................................................... 2
401B_21.1/7SA611 V04.70.07

Page 1 of 2
401B_21_1_prn
Indications
Trip Log - 000016 / 1/18/2016
SIMATIC 7:45:29.190 AM - New Dipalpur / FINAL / 18.01.16 09:19:37

1 Indications

Trip Log - 000016 / 1/18/2016 7:45:29.190 AM - New Dipalpur / FINAL / 400KV / DIA-1 /
1.1
401B_21.1/7SA611 V04.70.07
Trip Log - 000016 / 1/18/2016 7:45:29.190 AM - New Dipalpur / FINAL / 400KV / DIA-1 / 401B_21.1/7SA611
V04.70.07
Number Indication Value Date and time Cause State

00301 Power System fault 16 - ON 18.01.2016 07:45:29.190


00302 Fault Event 16 - ON 18.01.2016 07:45:29.190
03682 Distance Pickup L1E ON 0 ms
03701 Distance Loop L1E selected forward ON 0 ms
03802 Distance TRIP command - Only Phase L1 ON 0 ms
02844 AR 1st cycle running ON 1 ms
02801 AR: Auto-reclose in progress ON 1 ms
00533 Primary fault current IL1 6.73 kA 3 ms
01335 Earth fault protection Trip is blocked ON 8 ms
01358 E/F picked up FORWARD ON 9 ms
01336 E/F phase selector L1 selected ON 9 ms
01357 E/F 3I0p PICKED UP ON 9 ms
04006 >Dis.Tele. Carrier RECEPTION Channel 1 ON 29 ms
00591 Single pole open detected in L1 ON 33 ms
14083 E/F 3I0p is blocked ON 38 ms
01332 Earth fault protection is BLOCKED ON 38 ms
01336 E/F phase selector L1 selected OFF 39 ms
01345 Earth fault protection PICKED UP OFF 39 ms
03671 Distance PICKED UP OFF 44 ms
03701 Distance Loop L1E selected forward OFF 44 ms
01123 Fault Locator Loop L1E ON 33 ms
01117 Flt Locator: secondary RESISTANCE 0.51 Ohm 33 ms
01118 Flt Locator: secondary REACTANCE 7.34 Ohm 33 ms
01114 Flt Locator: primary RESISTANCE 0.61 Ohm 33 ms
01115 Flt Locator: primary REACTANCE 8.89 Ohm 33 ms
01119 Flt Locator: Distance to fault 35.1 km 33 ms
01120 Flt Locator: Distance [%] to fault 52.4 % 33 ms
01335 Earth fault protection Trip is blocked OFF 97 ms
00511 Relay GENERAL TRIP command OFF 103 ms
02839 AR dead time after 1pole trip running ON 103 ms
02851 AR: Close command ON 1299 ms
02784 AR: Auto-reclose is not ready ON 1299 ms
00591 Single pole open detected in L1 OFF 1431 ms
14083 E/F 3I0p is blocked OFF 1474 ms
01332 Earth fault protection is BLOCKED OFF 1474 ms