System Power Input Airflow Sound Pressure System Pipe Size Dimensions
Capacity (kW) UK (m3/min) Level (dBA) Starting Running Mains Cable Max Max Weight Fuse
mm(in)
Model Reference
Nominal Heating / Cooling Nominal SCOP / (mm)
& UK
Sensible (kW) COP / EER SEER
Sil-Lo-Mi- Sil-Lo-Mi- Current Current (A) Phase
Pipe Pipe (kg)
WxDxH
Rating (A)
Nominal Nominal UK UK Cooling Hi-SupHi Hi-SupHi (A) Heating / Inter- Length Height Indoor / Indoor /
SHF Heating / Outdoor Cooling Indoor Outdoor connecting Gas Liquid (m) Indoor /
Heating Cooling Heating Cooling (kW) Nominal UK
(BSEN14511) (BSEN14825) Heating / (m) Outdoor Outdoor
Cooling Cooling [MAX] Cable Outdoor
Nominal conditions cooling: indoor 27C DB, 19C WB; outdoor 35C DB, 24C WB. All fuse ratings are based on British Standard (BS88 - HRC) Notes: *1 - 10 if outdoor higher than indoor
Nominal conditions heating: indoor 20C DB; outdoor 7C DB, 6C WB. *2 - Outdoor to indoor, 20 if outdoor lower than indoor
UK Conditions: Summer; indoor 21C DB, 15C WB; outdoor 27C DB.
UK Conditions: Winter; indoor 21C DB; outdoor -1C WB.
R410A M Series Quick Reference Guide 2013
MXZ Multi-Split Piping Restrictions
MXZ-3D54VA MXZ-4D72VA MXZ-4D83VA MXZ-5D102VA MXZ-6C122VA
Indoor Units Indoor Units
Indoor Units Indoor Units Indoor Units
a a a a a f
15m 15m
c c
15m
c
15m
c
15m
10m 10m
c d d
10m
d e 10m d e 10m
Max Refrigerant Piping Length Max Refrigerant Piping Length Max Refrigerant Piping Length Max Refrigerant Piping Length Max Refrigerant Piping Length
Piping length per indoor unit (a, b, c) 25m Piping length per indoor unit (a, b, c, d) 25m Piping length per indoor unit (a, b, c, d) 25m Piping length per indoor unit (a, b, c, d, e) 25m Piping length per indoor unit (a, b, c, d, e,f) 25m
Total piping length (a+b+c) 50m Total piping length (a+b+c+d) 60m Total piping length (a+b+c+d) 70m Total piping length (a+b+c+d+e) 80m Total piping length (a+b+c+d+e+f) 80m
Max No. of bends per unit 25 Max No. of bends per unit 25 Max No. of bends per unit 25 Max No. of bends per unit 25 Max No. of bends per unit 25
Total No. of bends 50 Total No. of bends 60 Total No. of bends 70 Total No. of bends 80 Total No. of bends 80
Permissible H 20m (In case of outdoor unit lower than indoor unit)
right to make any variation in technical specification to the equipment described, or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantly developing
height = 16mm
and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are supplied subject to
difference
(one way) Between each branch box (h2) h2 15m
Between each indoor unit (h3) h3 12m
Max number of bends per unit (outdoor to indoor) 15
Effective as of July 2013