You are on page 1of 9

Battery Healthtype

BB Cabinet Check Form & Chec


Site ID 3100 BB Cabinet Available YN (TEC/Aircon)
Site Technology 2G 2G+3G 2G+3G+4G Sharing Status Guest H
AC Power Staus CP Only CP+DG CP+DG+Solar Non CP+DG Non C
Battery Bank # 1 Make/Mo
Battery Banks Details No. of Battery Banks to be dismantled
ICC500/Powercube 1 Battery Bank # 1 V/Ah
Rectifier Make Huawei Rectifier Model 1000 Rectifier Rating (Rated) - A 200
Rectifier Modules Model R4850G Rectifier Modules Rating (A) 30
Battery Charge Current (A) - Battery Float Voltage (V) - Total Faulty Cells (V)
Post Discharge Test Post Discharge Test 52.5 Total Working Cells (V)
LVD First Shut Down (V) 46 Charging Current (.xC) 0.15 Date of Installation/Test
LVD Second Shut Down (V) 44 Low Batt Voltage Alarm (V) 48

Bank Load Current (A) Discharge Voltage (V)Cell 1 Cell 2 Cell 3 Cell 4 Cell 5
Before Test 32A 52.8 2.2 2.2 2.2 2.2 2.2
30 Mins 32A 50.4 2.1 2.1 2.1 2.1 2.1
60 Mins 32A 49.5 2.1 2 2 2 2
90 MIns 1 32A 49 2 2 2 2 2
120 Mins 32A 48.5 2 2 2 2 2
150 Mins 32A 48 2 2 2 2 2
180 Mins
Before Test
30 Mins
60 Mins
90 MIns 2
120 Mins
150 Mins
180 Mins
Before Test
30 Mins
60 Mins
3
90 MIns 3
120 Mins
150 Mins
180 Mins
Before Test
30 Mins
60 Mins
90 MIns 4
120 Mins
150 Mins
180 Mins
Before Discharge Test batteries should be fully charged.
Check Form & Check List
TEC DC Air Con BB Cabinet Cooling System Operational Y N
Guest Host Non Shared DC Shared Y N IDU ODU
Non CP+DG Non CP+Solar DG+Solar Solar Only Solar+CP DC Shared DG Shared

ery Bank # 1 Make/Mode Agission/FCB600 Battery Bank # 2 Make/Model


attery Bank # 1 V/Ah 2 650 Battery Bank # 2 V/Ah
200 Total Modules Capacity 4 Total Operational Modules 4

Faulty Cells (V) 4


Working Cells (V) 20 Battery Cabinet High Temprature Alarm Installed Y N
Installation/Test 22/11/2016 Battery Cabinet High Temprature Alarm Operational Y N

Cell 6 Cell 7 Cell 8 Cell 9 Cell 10 Cell 11 Cell 12 Cell 13 Cell 14 Cell 15 Cell 16
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
2 2 2.1 2.1 2 2.1 2.1 2 2.1 2.1 2
2 2 2.1 2 2 2.1 2 2 2.1 2 2
2 2 2 2 2 2 2 2 2 2 2
2 2 2 2 2 2 2 2 2 2 2
Cell 17 Cell 18 Cell 19 Cell 20 Cell 21 Cell 22 Cell 23 Cell 24
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
2.1 2.1 2.1 2.1 2.1 2.1 2.1 2
2 2.1 2 2.1 2.1 2.1 2.1 2
2 2 2 2 2 2 2 2
Check List
Same serialized batteries are installed on sites against which they are issued
New batteries are installed as a complete bank, no series or parallel connection with old
Battery discharge test of old batteries as per "backup test procedure" is
All dismantled cells are marked as Working/Faulty, Date of Test, Site ID & Clu
Dismantled batteries are returned to warehouse against same site for which issu
Dismantled batteries are returned to warehouse along with ATN & battery disch
New battery cells are physically inspected and voltage measurement is done befo
Batteries are properly installed in cabinets/racks and terminals are tightened with torque wre
Cooling system (TEC/Air Con) of battery cabinets is in working conditio
Battery cabinets are secured with safety cages immediately after installa
Rectifier Parameters are set as per guidelines
Rectifier operational rating is as per Rectifier operational ratings & charging curre
Battery cabinet high temperature alarm is patched and operational
All installed battery cells are marked with Site ID and Date of Installati
After installation, batteries are transferred on load without any abnormal voltage dr
Status Comments
which they are issued from IMS. OK NOK
el connection with old batteries are done OK NOK
up test procedure" is done OK NOK
of Test, Site ID & Cluster Owner. OK NOK
me site for which issuance is done OK NOK
h ATN & battery discharge report OK NOK
urement is done before installation. OK NOK
tened with torque wrench as per torque value OK NOK
s is in working condition OK NOK
mediately after installation OK NOK
guidelines OK NOK
tings & charging current guidelines OK NOK
ched and operational OK NOK
and Date of Installation OK NOK
y abnormal voltage drop on each cell OK NOK
Comments