You are on page 1of 35

Tri-pack Films Ltd

Port Qasim Karachi


SUMMARY OF COST

S.No Description Amount

A 1653 PTB Plant Building & Machine Foundation


a. Civil Work Rs. 453,182,142
b. Plumbing Works (Internal) Rs. 966,854

B Utilities Civil Works Rs. 44,284,404

C External Sewerage,Water Supply and Fire Fighting System Rs. 20,456,819

D Roads and Storm Water Drainage Rs. 42,680,801

E Demolition and Relocation of Existing Facilities Rs. 7,046,913

GRAND TOTAL Rs. 568,617,933.00


TRI -PACK FI LM S LI M I TED
1 6 53 PTB PLA N T BUI LDI N G A N D M A CHI N E FO UN DA TI O N S
PO RT Q A SI M KA RA CHI
BI LL O F Q UA N TI TI ES
CI VI L WO RKS

Item Unit Rate Amount


Description of Items Unit Quantity
No. (Rs) (Rs)

SECTION-1 PRELIMINARIES & EARTHWORKS

1.4 Earthwork for structures.


1.4.1 Structural excavation in soil above sub-soil water level for levelling
and grading of building, for foundations and other structures, and
unsuitable excavated material dispose off outside the project premises
any lead as per Specifications and as per approval of the Engineer. M3 7,600 577 4,385,200.0
1.4.2 Compacted backfill in foundations with approved suitable
excavated soil, including breaking clods, dressing, watering,
compacting mechanically in layers not exceeding 230mm thick
depth to 95% Modified Proctor Dry Density, from any lead and 3
any lift as per Specification. M 2,700 484 1,306,800.0
1.4.3 Supply suitable approved earth, from approved outside
sources, including digging, loading and un-loading and filling
under floors and plinth protection etc. including, dressing,
watering, compacting mechanically in layers not exceeding
230mm thick depth to 95% Modified Proctor Dry Density as per
Specifications, any lead and any lift. M3 18,600 1,094 20,348,400.0
1.4.4 Supply, stack and fill sand of approved quality from outside
sources under floors and plinth etc., including dressing,
watering, compacting mechanically in layers not exceeding
230mm thick depth to 95% Modified Proctor Dry Density, from
any lead and any lift as per Specification. M3 330 1,953 644,490.0
SECTION-2 CONCRETE WORKS
2.2 Reinforcement for Concrete
2.2.1 Provide and fix steel reinforcement Grade 60 deformed steel bars
conforming to ASTM A-615, including cleaning, cutting, bending,
placing, binding etc., including provision and cost of spacers and
binder wire, cost of chairs, over-laps not shown on drawings etc., in
any kind of R.C.C works as specified.
a) Reinforcing steel bars of Grade 60 (min. 60,000 psi yield Tone 1,100 120,301 132,331,100.0
strength)
2.3 Non-structural Concrete
2.3.1 Provide and lay lean concrete in foundations, under floors, plinth
protection etc., using approved sand and stone crush as coarse
aggregate including formwork and its removal, leveling, compacting
and curing etc., complete in all respects as per drawings and
Specifications.
a) PCC (1:4:8) M3 1,900 7,578 14,398,200.0
2.3.2 Provide and lay P.C.C. 1:2:4, 50mm (2") thick under floor for tile
work. M2 7,950 457 3,633,150.0
2.4 Structural (Design Mix) Concrete
2.4.1 Provide and lay structural cement concrete of 3000 psi cylinder
crushing strength at 28 days, using O.P. Cement, Bolari/Malir sand,
and Makli/Mangopir - Hub stone crush including formwork and its
removal, placing, compacting, finishing and curing complete in all
respects (including screening and washing of stone aggregate) but
excluding the cost of reinforcement, as per Specifications.
a) R.C.C.Footings / Rafts M3 905 9,899 8,958,595.0
b) R.C.C. Plinth Beam M3 205 16,999 3,484,795.0

1 of 10
TRI -PACK FI LM S LI M I TED
1 6 53 PTB PLA N T BUI LDI N G A N D M A CHI N E FO UN DA TI O N S
PO RT Q A SI M KA RA CHI
BI LL O F Q UA N TI TI ES
CI VI L WO RKS

Item Unit Rate Amount


Description of Items Unit Quantity
No. (Rs) (Rs)
3
c) R.C.C. Retaining Walls M 260 17,822 4,633,720.0
3
d) R.C.C. Suspended Beams / Lintles M 415 13,570 5,631,550.0
e) R.C.C. Bracing Beams M
3
540 15,385 8,307,900.0
3
f) R.C.C. Suspended Slabs / Cantilever Slab M 720 15,448 11,122,560.0
3
g) R.C.C. Slab on Grade M 2,025 11,174 22,627,350.0
3
h) R.C.C. Ramps M 10 11,174 111,740.0
i) R.C.C. Wall for Loading / Unloading and Machine
3
Foundations M 370 10,343 3,826,910.0
j) R.C.C. Parapet M3 60 25,066 1,503,960.0
K) R.C.C. Stair M3 5 45,251 226,255.0
2.4.2 Ditto item 2.4.1 above but structural cement concrete of 3750
psi cylinder crushing strength at 28 days for:-
3
a) R.C.C. Columns / Pads M 1,585 17,718 28,083,030.0
2.4.3 Reinforced, non-structural cement concrete 1:6:12 including
painting steel reinforcement bars with 2 coats of approved rust
proof paint (for future extension).
a) R.C.C. Columns M3 15 17,030 255,450.0
SECTION-3 MASONRY
3.2 Concrete Block Work
3.2.1 Provide and lay cement concrete (min 15N / mm2 or 1500 psi
compressive cube strength at 28 days) 200mm thick solid
concrete block masonary using 1:3 cement: sand block (sand
of Bolari / Malir mix with 15% crushed stone aggregate of 1/4"-
3/8" size) approved by the Engineer, walls laid in 1:5 cement
mortar in foundations upto plinth level, lay with steel dowels
from RCC structure, and including vertical & horizontal steel as
per Typical Details Drawing, curing etc. complete in all
respects, as directed by the Engineer.
M3 835 11,862 9,904,770.0
3.2.2 Provide and lay cement concrete (min 15N / mm2 or 1500 psi
compressive cube strength at 28 days) 200mm thick solid concrete
block masonary using 1:3 cement: sand block (sand of Bolari / Malir
mix with 15% crushed stone aggregate of 1/4"-3/8" size) approved by
the Engineer, walls laid in 1:5 cement mortar in superstructure
including scaffolding and its removal, lay with steel dowels from RCC
structure and including vertical & horizontal steel as per Typical
Drawing, curing etc. complete in all respects, as directed by the M3 2,960 10,450 30,932,000.0
Engineer.
SECTION-4 TERMITE PROOFING
4.1 Termite Control
4.1.1 Provide and apply antitermite treatment to foundation bed & vertical
surfaces and under floors, using the indicated insecticide emulsion
below, applied as specified by the manufacturer.

a) Biflex by FMC or Mirage by Ali Akbar (Pvt) Ltd. or


Termicure by Jaffer Brothers or approved equivalent M2 6,280 186 1,168,080.0
4.1.2 Provide and apply antitermite treatment to inside building along walls,
using the indicated insecticide emulsion below, applied as specified
by the manufacturer.
a) Biflex by FMC or Mirage by Ali Akbar (Pvt) Ltd. or
Termicure by Jaffer Brothers or approved equivalent M2 1,500 186 279,000.0

2 of 10
TRI -PACK FI LM S LI M I TED
1 6 53 PTB PLA N T BUI LDI N G A N D M A CHI N E FO UN DA TI O N S
PO RT Q A SI M KA RA CHI
BI LL O F Q UA N TI TI ES
CI VI L WO RKS

Item Unit Rate Amount


Description of Items Unit Quantity
No. (Rs) (Rs)
4.1.3 Provide and apply antitermite treatment to exterior vertical surfaces of
external walls, using the indicated insecticide emulsion below, applied
as specified by the manufacturer.
a) Biflex by FMC or Mirage by Ali Akbar (Pvt) Ltd. or
2
Termicure by Jaffer Brothers or approved equivalent M 1,050 186 195,300.0
SECTION-5 FLOORINGS / WALL FINISHES
5.2 CERAMIC TILES WORKS
5.2.1 Provide and lay Granitto tiles flooring comprising best quality,
high finish, imported full body, procelain, Masafi series of
"Grannitto Tiles (U.A.E.) Al. Khaleej Ceramics" or approved
equivalent, 600mm x 600mm x 10mm thick heavey duty of
approved colours & patterns laid in 1:4 cement sand mortar
bed and matching joints filling complete in all respect as per
drawing and Specification, sample as approved by the Egineer. M2 8,120 3,621 29,402,520.0
5.2.2 Provide and lay Granitto teiles skirtings total 20mm thick,
comprising 1:3 cement sand undercoat, and 600mm x200mm
best quality, high finish, imported heavey duty granitto of
approved colours tiles complete in all respect as per drawings
and Specifications, sample as approved by the Engineer. M2 280 3,729 1,044,120.0
5.8 Plain Concrete Flooring
5.8.1 Provide and lay PCC 1:2:4 flooring in alternate panels without
permanent division strips, and finishes smooth dust free.
2
a) 50mm thick (in plinth protection) M 480 457 219,360.0
5.9 HEAVY DUTY CONCRETE FLOORING
5.9.1 Provide and lay granolithic floor topping 1:2, 25mm thick, top
surface finished smooth without grinding and polishing
excluding RCC works without dividing into panels; as per
2
Specifications excluding steel reinforcement. M 5,975 1,331 7,952,725.0
5.9.2 Provide and lay heavy duty (granolithic) skirting total 20
mm thick, comprising 10 mm thick 1:3 cement sand under
coat and 10 mm thick1:2 grano topping, hard and smooth with
steel trowel finish complete in all respect as per drawings and
Specifications. M2 35 1,331 46,585.0
SECTION-6 PLASTERING & POINTING
6.1 Cement Plaster
6.1.1 Supply, make, apply and cure 20mm thick smooth finished
plaster in 1:4 cement sand mortar, smooth finished with steel
trowel on internal walls as shown in the drawings including
metal lath strips (whereas required), curing etc; as per
Specifications and as per sample approved by the Engineer. M2 16,150 526 8,494,900.0
6.1.2 Supply, make apply and cure 15mm thick smooth finished 1:3
cement sand plaster (on ceilings), as per Specifications and
as per sample approved by the Engineer. M2 Rate only 550 -
6.1.3 Supply, make, apply and cure 20mm thick smooth finished
plaster with 25mm grooves in 1:4 cement sand mortar, smooth
finished with steel trowel on external wall as shown in drawings
including metal lath strips (whereas required), curing etc; as per
Specifications and as per sample approved by the Engineer. M2 4,500 560 2,520,000.0

3 of 10
TRI -PACK FI LM S LI M I TED
1 6 53 PTB PLA N T BUI LDI N G A N D M A CHI N E FO UN DA TI O N S
PO RT Q A SI M KA RA CHI
BI LL O F Q UA N TI TI ES
CI VI L WO RKS

Item Unit Rate Amount


Description of Items Unit Quantity
No. (Rs) (Rs)
6.1.4 Supply make, apply and cure (2 coats of plaster) final coat of
15mm thick plaster with 25mm grooves in comb plaster in 1:4
cement sand mortar over 15mm thick plaster on external walls
including metal lath strips (where as required) curing etc; as per
Specifications and as per sample approval of the Engineer. M
2
980 942 923,160.0
SECTION-7 DAMP PROOFING AND WATER PROOFING,
INSULATION
7.1 Bitumen Damp-proof Courses (Over Masonry)
7.1.1 Provide and lay 38mm thick horizontal DPC topped with two
coats of specified quality hot bitumen (hot applied system)
fully covering the surface, on dry surface; consisting of 1:1.5:3
cast in situ cement concrete including mixing, compacting,
finishing smooth, curing, formwork and is removal etc.,
including 1 layer of 500 gauge polythene sheet (weighing 2.5
lbs per 100 Sft) with 75mm overlaps over dried bitumen, as per
Specifications and to the approval of the Engineer. M2 245 1,442 353,290.0
7.8 Roof Treatment
7.8.1 Provide and lay PCC 1:2:4 screed with reinforcing #2 steel bars
@300 c/c at both way over R.C.C flat roof slab laid in slope with
a minimum thickness of 40mm as per Specifications and
Instructions of the Engineer. M2 2,850 1,056 3,009,600.0
7.8.2 Providing and applying top protective coating for flat roof slab
comprising as under.
a) Prepare surface for roof treatment; making free from
laitance, grease, oil or loose and flaky particles.
b) Provide and apply two coat of "Master Seal 550" each coat
of 1 Kg / M2as per instructions of the chemical
2
manufacturer ("BASF"). M 2,850 640 1,824,000.0
SECTION-8 ROOF DRAINAGE
8.1 Roof Drainage
8.1.1 Supply, provide and fix in position uPVC rain water down pipe
lines conforming to ISO 3633:1991 and BS 3505 1968 (wall
thickness 3.2mm) including proper joints complete in all
respects, and system leak-free:
a) 150mm dia RM 170 2,399 407,830.0
8.1.2 Provide and fix uPVC Plain Bends with grating (as rain water
inlets at roof), water tight connection leak-free:
a) 150mm dia No. 30 11,380 341,400.0
8.1.3 Provide and fix uPVC Shoe Bends (as rain water outlets), water
tight connection leak-free:
a) 150mm dia No. 30 4,400 132,000.0
8.1.4 Provide and fix C.I. Rain Water down pipe line using pipes of
30 psi pressure; including painting:
b) 150mm dia RM 135 8,649 1,167,615.0
8.1.5 Provide and fix C.I Plain Bend water C.I. grating (as rain water
inlets at Roof), water tight connection leak-free including
painting:-
a) 150mm dia No. 10 10,621 106,210.0
8.1.6 Provide and fix C.I Shoe Bend with (as rain water oulets), water
tight connection leak-including painting:
b) 150mm dia No. 10 4,400 44,000.0

4 of 10
TRI -PACK FI LM S LI M I TED
1 6 53 PTB PLA N T BUI LDI N G A N D M A CHI N E FO UN DA TI O N S
PO RT Q A SI M KA RA CHI
BI LL O F Q UA N TI TI ES
CI VI L WO RKS

Item Unit Rate Amount


Description of Items Unit Quantity
No. (Rs) (Rs)
8.1.7 Provide and lay rain water troughs using non structural
cement concreter 1:2:4 and finish with 10mm (3/8") thick 1:3
grey cement sand plaster complete in all respect and as per No. 30 2,253 67,590.0
Specifications.
SECTION-10 METAL WORKS
10.1 Architectural steel and Iron Works
10.1.1 Provide and fix in position steel sliding door with 50mm x 50mm
x 6mm thick angle frame with 16 gauge M.S. sheet on both side
50mm x 50mm M.S. angle iron bracing, wheel with bearing
roller alongwith accessories & top beam for sliding track welded
to M.S. channel and all arrangement accessories etc., painting
2 coats of red oxide wiht min 2-3 coats of enamel paint (ICI
make or approve equal), and all fixing arrangement complete
in all respects as shown on drawings and as per Specifications,
as per sample approved by the Engineer.
a) Type SSD3 (7000mm x 4000mm)
2
[with openable door] M 56 16,973 950,488.0
b) Type SSD4 (6000mm x 4000mm)
2
[with openable door] M 24 16,973 407,352.0
c) Type SSD5 (4000mm x 4000mm)
[with openable door] M2 64 15,761 1,008,704.0
d) Type SSD6 (2000mm x 4000mm) M2 8 15,761 126,088.0
e) Type SSD7 (800mm x 4000mm) M2 3 15,761 47,283.0
f) Type SSD8 (4500mm x 4000mm) M2 18 15,761 283,698.0
g) Type SSD9 (5500mm x 4000mm) M2 22 15,761 346,742.0
10.1.2 Provide and fix in position single / double leaf double sheeted
steel hinged door in 16 S.W.G. M.S. sheet with "Z" section
50mmx50mmx6mm M.S. angle frame and 6mm M.S. flat plate
welded together to form "Z" section frame, including bracing
38mmx38mmx6mm M.S. angle, 3 Nos. approved heavy duty
hinges per shutter, 3 Nos. M.S.hold-fast for door frame on ether
side, embedded in P.C.C.(1:2:4), painting 2 coats of red oxide
with min 2-3 coats of enamel paint (ICI make or approve equal),
and all hardware complete in all respects as per drawings and
Specifications and as per sample approved by the Engineer.
2
a) Type SD2 (900mm x 2400mm) M 3 15,761 47,283.0
b) Type SD3 (1800mm x 2400mm) M2 26 15,761 409,786.0
c) Type SD4 (1050mm x 2400mm) M2 5 15,761 78,805.0
d) Type SD5 (1050mm x 2100mm) M2 5 15,761 78,805.0
e) Type SD6 (2400mm x 2800mm) M2 65 15,761 1,024,465.0
f) Type SD7 (2000mm x 2800mm) M2 23 15,761 362,503.0
10.1.3 Provide and fix M.S. pipe sleeves caps length 700mm and
20mm dia in flooring joints. No. 11,600 376 4,361,600.0
10.2 Architectural Aluminium Work
10.2.1 Provide and fix glazed Aluminium doors, using sections of
Pakistan Cables (Pvt) Ltd., or Chawla Aluminium or approved
equivalent, min 100mm wide and 2mm thick in natural colour
including imported 10mm thick approved clear glass, all glass
shall be tempered, and all hardware as shown on drawings,
excluding door locks and door closers, as per sample
approved by the Engineer.
a) Type AD1 (1050mm x 2100mm) M2 16 16,973 271,568.0

5 of 10
TRI -PACK FI LM S LI M I TED
1 6 53 PTB PLA N T BUI LDI N G A N D M A CHI N E FO UN DA TI O N S
PO RT Q A SI M KA RA CHI
BI LL O F Q UA N TI TI ES
CI VI L WO RKS

Item Unit Rate Amount


Description of Items Unit Quantity
No. (Rs) (Rs)
2
b) Type AD2 (1800mm x 2100mm) M 27 16,973 458,271.0
2
c) Type AD3 (1000mm x 2100mm) M 3 16,973 50,919.0
10.2.2 Provide and fix glazed Aluminium fixed ventilator using sections
of Pakistan Cables (Pvt) Ltd, Chawla Aluminium or approved
equivalent, 100 mm wide and 2 mm thick in natural colour
frames including 6mm thick imported clear glass, all glass shall
be tempered, and all hardware etc; as shown on drawings, and
as per sample approved by the Engineer.
a) Type AV3 (9500mm x 1000mm) M2 513 15,761 8,085,393.0
b) Type AV4 (8350mm x 1000mm) M2 35 15,761 551,635.0
c) Type AV5 (5500mm x 1000mm) M2 33 15,761 520,113.0
d) Type AV6 (5500mm x 1000mm) M2 22 15,761 346,742.0
e) Type AV7 (5350mm x 1000mm) M2 27 15,761 425,547.0
f) Type AV8 (4900mm x 1000mm) M2 30 15,761 472,830.0
g) Type AV9 (4750mm x 1000mm) M2 20 15,761 315,220.0
10.2.3 Provide and fix aluminium fixed louvers in natural colour frame,
using extruded sections of Pakistan Cables (Pvt) Ltd, or
Chawla Aluminium or approved equivalent, min 25mmx75mm
and 2mm thick with hold-fasts and seal all around outer frame,
including all hardware etc; as shown on drawings, and as per
sample approved by the Engineer.
2
a) Type SLV1 (4600mm x 2350mm) M 100 12,124 1,212,400.0
10.2.4 Provide and fix aluminium frame glazed partitions with
openable doors as shown in drawing, using sections of
Pakistan Cables (Pvt) Ltd., or Chawla Aluminium or approved
equivalent, 100mm wide and 2mm thick of natural colour frame,
with double glazed fixed parts (6+12+6 mm thick) clear glass,
insulated, argon filled and sealed clear, including imported
10mm thick clear glass for openable shutters, all glass shall be
tempered in approved colour and all hardware as shown on
2
drawings, and as per sample approved by the Engineer. M 185 20,206 3,738,110.0
10.2.5 Provide and install Door Locks and best quality handle to
aluminium doors as per sample approved by the Engineer. No. 15 2,253 33,795.0
10.2.6 Provide and install Door Closer, to aluminium doors as per
sample approved by the Engineer. No. 15 6,760 101,400.0
10.4 Structural Steel Works

6 of 10
TRI -PACK FI LM S LI M I TED
1 6 53 PTB PLA N T BUI LDI N G A N D M A CHI N E FO UN DA TI O N S
PO RT Q A SI M KA RA CHI
BI LL O F Q UA N TI TI ES
CI VI L WO RKS

Item Unit Rate Amount


Description of Items Unit Quantity
No. (Rs) (Rs)
10.4.1 Provide, fabricate and fix 1200mm wide M.S. stair comprising
channel section 8" x 3" x 12 lbs/ft side supports for stair welded
on M.S. base plate 300mm x 110mm x 20mm thick fixed on
R.C.C. pedestals with 16 dia anchor bolts and 25mm thick non-
shrinkable grout for levelling base plates, and risers 275mm
wide M.S. chequered plate 6mm thick, including railing 32mm
dia schedule 40 M.S. pipe hand rail and one row of bracing,
L:50mm x 50mm x 6mm balusters 1060mm high on every six
steps, 4 Nos W10 x 22 section M.S. columns girder for
supporting and strengthing of stair welded on M.S. base plate
450mm x 300mm x 20mm with 20 dia anchor bolts fixed on
pedestals, at landing levels W10 x 22 and channel section [4" x
2" x 5 lbs/ft welded to M.S. column and chanels respectively
and chequered plate 6mm thick for landing including all
welding, jointing plates and bolts etc; and 2 coats of anti rust
red oxide paint with min 2-3 coats of ICI enamel paints or
approved equal, including welding and connection with
concrete etc; complete in all respect; as per drawings,
specifications and as per instructions of the Engineer.
a) -0.80m to +5.35m Job 2 626,459 1,252,918.0
10.4.2 Provide and fix heavy duty railing on ramp comprising 50mm
dia mild steel pipe hand rail and 50mm dia mild steel pipe post
etc. with two rows of 25mm dia mild steel pipe bracing including
mild steel flange screwed to ramp slab with rawl plug, as per
Hand rail and Baluster Fixing Detail (Typical), 2 coats of red
oxide paint and 2 coats of enamel paint (ICI make or approved
equivalent) complete in all respect as per drawing and
Specifications. RM 12 2,704 32,448.0
10.4.3 Provide and fix M.S. channel size (200mm x 75mm) corner
quards cast with RCC loading / unloading deck edge including
painting complete in all respect as per instructions of the
Engineer. Kg 450 263 118,350.0
10.4.4 Provide and fix M.S. plate on top of floor pads complete in all respects
as per drawings and Specificaiton including painting.
Kg 11,205 225 2,521,125.0
10.4.5 Provide and fix anchor bolts 20mm dia. Length 150mm welded with
flat steel plate size 30mm x 30mm x 10mm at bottom complete in all
respects as per drawings and Specifications.
No. 1,375 225 309,375.0
10.4.6 Provide, fabricate and installation of Structural steel work
including 100% testing of welds in shop by dye pantration test
(DPT) method etc. complete in all respects as specified and as
shown on drawings excluding plainting.

a) 1 Ls: 50mmx50mmx6mm Kg 150 300 45,000.0


SECTION-11 PAINTING
11.4 Painting Cement Works
11.4.1 Provide and apply one coat of primer Dulux Primeon of ICI
make (or approved equal) and 3 to 4 coats (as may be
approved to have the required finish) of Dulux Plastic Emulsion
Paint of ICI make (or approved equal) as per Specifications and
approved shade, and as per sample by the Engineer. M2 18,650 356 6,639,400.0

7 of 10
TRI -PACK FI LM S LI M I TED
1 6 53 PTB PLA N T BUI LDI N G A N D M A CHI N E FO UN DA TI O N S
PO RT Q A SI M KA RA CHI
BI LL O F Q UA N TI TI ES
CI VI L WO RKS

Item Unit Rate Amount


Description of Items Unit Quantity
No. (Rs) (Rs)
11.4.2 Provide and apply one coat of primer Dulux Primeon of ICI
make (or approved equal) and 3 to 4 coats (as may be
approved to have the required finish) of Dulux Weathersheild
Paint of ICI make (or approved equal) as per Specifications and
approved shade, and as per sample by the Engineer. M2 4,500 404 1,818,000.0
SECTION-12 EXPANSION JOINT FINISHES
12.1.1 Provide and fix 1" thick "Flexcell" filler of minimum 40 kg/M3 dry
density, in expansion joints of approved quality, complete in all
respects as per drawings and as per sample approved by the
2
Engineer. M 120 826 99,120.0
12.1.2 Provide and apply in expansion joints 25mm x 25mm single
component, polyurethane based "Masterflex 472" Elastomeric
polyurethane (PU) joint sealant by "BASF" or approved
equivalent complete in all respects as shown on drawings.
RM 230 826 189,980.0
12.1.3 Provide and fix back up rod 30mm dia or equivalent in
expansion joints. RM 210 150 31,500.0
12.1.4 Provide and install metal covers in expansion joints.
a) Aluminium clip strip on external vertical expansion joint
including bitumastic fillet complete. RM 70 1,127 78,890.0
b) 75mm x 2mm thick aluminium strip on internal vertical
expansion joint; fixed to R.C.C. columns with rawl plug and
screw @ 450mm c/c including bitumastic fillet complete in
all respect. RM 110 1,127 123,970.0
c) 75mm x 1.5mm thick aluminium strip non slip on floor, fixed to
floor with screw @ 150mm c/c and 31mm x 3mm thick M.S flat
embedded in P.C.C. (1:2:4), with 200mm x 25mm x 3mm thick
anchor complete in all respect.
RM 130 676 87,880.0
d) 75mm x 2mm thick alumimium strip on ceiling expansion
joint, fixed to R.C.C. slab / beam with rawl plug and screw
@ 450mm c/c including bitumastic fillet complete in all
respect. RM 12 2,253 27,036.0
12.3 Water Stops
12.3.1 Provide and install min. 200mm wide approved bulb type A-
Class PVC Water Stopper all around basement wall at
construction joint, complete in all respect with full continuity as
per drawings and Specificaitons and as per sample approved
by the Engineer, ensuring complete water-tightness.
RM 145 1,271 184,295.0
SECTION-13 CEILING WORKS
13.1 False Ceiling
13.1.1 Provide and fix suspended false-ceiling system with mineral
fiber acoustic 1200mmx1200mm and 10mm thick tiles of
Marley / Daiken make or equivalent imported tile including
approved support and hanging system and all accessories by
Thermec or equivalent approved as per Specifications and as
shown in drawing complete in all respect as per Manufacturer's
instructions, including all strengthening and edge trimming for
supports for light fittings, diffusers etc., and for making
openings, complete including cleaning and finishing, as per
sample approved by the Engineer. M2 10,600 2,779 29,457,400.0

8 of 10
TRI -PACK FI LM S LI M I TED
1 6 53 PTB PLA N T BUI LDI N G A N D M A CHI N E FO UN DA TI O N S
PO RT Q A SI M KA RA CHI
BI LL O F Q UA N TI TI ES
CI VI L WO RKS

Item Unit Rate Amount


Description of Items Unit Quantity
No. (Rs) (Rs)
13.1.1 Provide and fix suspended false-ceiling system with mineral
fiber acoustic 600mmx600mm and 10mm thick tiles of Marley /
Daiken make or equivalent imported tile including approved
support and hanging system and all accessories by Thermec
or equivalent approved as per Specifications and as shown in
drawing complete in all respect as per Manufacturer's
instructions, including all strengthening and edge trimming for
supports for light fittings, diffusers etc., and for making
openings, complete including cleaning and finishing, as per
sample approved by the Engineer. 2
M 415 2,779 1,153,285.0
SECTION-17 SPECIAL ITEMS (SP)
17.1 Special Items
17.1.1 Provide and fix in position encased C.I. pipes "Teepu" or
"Alpine" make or approved equal including all C.I. fittings &
specials embedded in floors and ecasement of concrete
(1:2:4), with 16-#3 dia steel bares grade-60 and strirrups # 3
dia @ 20 c/c/ including P.C.C. 1:4:8 in lean concrete formwork
and its removal, excavation, backfill etc., including cutting of
pipes, lead caulked joints, painting pipes and fittings as
specified with approved paint and testing the pipelines,
complete.
a) 100mm dia [For Floor drain] RM 300 3,756 1,126,800.0
b) 200mm dia [For Storm drain] RM 60 9,690 581,400.0
c) 300mm dia [For Storm drain] RM 140 23,436 3,281,040.0
17.1.2 Provide and fix stainless steel Syphones, consisting of S.S.
pipe schedule 40, material 304, including fittings, jointing etc.
complete in all respect as per drawings and Specfications.
a) 100 mm dia No. 10 15,023 150,230.0
17.1.3 Provide and fix stainless steel Floor trap with S.S.grating
including testing complete in all respect as per drawings and
Specfications.
a) 275 mm dia No. 10 39,060 390,600.0
17.1.4 Provide and construct R.C.C. Chambers as per Drawing
including all inlet and outlet pipes connections and all work
items like P.C.C. 1:4:8 sub-floor, R.C.C. walls, base slab,
R.C.C. pre-cast cover slab with lifting hook, including steel
rebar of Grade 60, formwork and its removal, 2 coats of hot
bitumen on outside, excavation, backfil etc; as detailed shown
in drawings and as per Specifications of relevant civil works.
a) 600mm x 600mm x 500mm high (avg). No. 16 22,535 360,560.0
17.1.5 Provide and apply two coats of "Master seel 550" by M/s
"BASF" or approved equivalent, each coat of 1 Kg/m2 after
preparation surface R.C.C. wall, making free from laitance,
greese, oil or loose and flaky particals, as per Technical
Specifications and manufacturer's instructions, complete in all
respect and as directed by the Engineer.
Sqm 570 640 364,800.0
17.1.6 Drilling in existing concrete footings to insert bars Grade 60 in
footing and epoxy grouting "Master flow-935" by "BASF" or
appoved eqyuivalent as shown in drawing complete in all
respect and as directed by the Engineer.

a) 225mm deep in footing to insert # 8 bars No. 240 376 90,240.0

9 of 10
TRI -PACK FI LM S LI M I TED
1 6 53 PTB PLA N T BUI LDI N G A N D M A CHI N E FO UN DA TI O N S
PO RT Q A SI M KA RA CHI
BI LL O F Q UA N TI TI ES
CI VI L WO RKS

Item Unit Rate Amount


Description of Items Unit Quantity
No. (Rs) (Rs)
b) 75mm deep in footing to insert # 3 bars No. 176 225 39,600.0
17.1.7 Chizzling existing footing to expose the steel bars of existing
footing for straighting and over laping of new extended footing
steel bars, and apply bonding agent "Concresive-1414" by
BASF" or approved equivalent to expose surface before
concreting as shown in drawing complete in all respect and as
directed by the Engineer. 2
M 135 1,127 152,145.0

Total C/o to Summary of Cost: 453,182,142

10 of 10
TRI -PACK FI LM S LI M I TED
1 6 5 3 PTB PLA N T BUI LDI N G
PO RT Q A SI M KA RA CHI
PLUM BI N G WO RKS ( I N TERN A L)
BI LL O F Q UA N TI TI ES
Sr. Unit Rate
Description of Items Unit Quantity Amount (Rs)
No. (Rs)

(INTERNAL)

SECTION-W2 WATER SUPPLY PIPE LINES


W2.1 Provide, lay and fix Polypropylene Random Co-
polymer (PPRC) pipes of Grade PN-20 conforming to
DIN standard of 8077 / 8078 made by "Dadex" or
Beta" or "LIANSU" or "ROBIN" or approved
equivalent for hot and cold water supply lines with
specials and fittings according to DIN standard of
16962 / PN-25 including cutting, jointing, and testing
as per Manufacturer's Specifications, supported on
walls or run in chases or under floors including pipe
hangers, supports, making requisite number of holes
where required and making good the holes and
chases, complete.
a) 20 mm dia RM 25 443 11,075
b) 25 mm dia RM 60 590 35,400
c) 32 mm dia RM 20 960 19,200
d) 40 mm dia RM 12 1,379 16,548
W2.2 Provide, fix, join and test BSS 1387 medium
quality G.I. pipes for cold water supply "IIL" or
"Jamal" make or approved equivalent and China
make specials (sockets, tees, elbows, bends,
crosses, reducers, plugs and union etc.)
supported on walls or run in chases or uner floor
including pipe hangers, supports, cutting and
making good the chases and holes,
anticorrosive paints, bitumen tape on concealed
pipeline and additional coats of enamel paint of
approved shade on surface pipe lines.
a) 40mm dia RM 100 1,134 113,400
W2.3 Provide, fix, join and test BSS 1387 medium
quality G.I. pipes for Hot water supply "IIL" or
"Jamal" make or approved equivalent and China
make specials (sockets, tees, elbows, bends,
crosses, reducers, plugs and union etc.)
supported on walls or run in chases or uner floor
including pipe hangers, supports, cutting and
making good the chases and holes,
anticorrosive paints, bitumen tape on concealed
pipeline and additional coats of enamel paint of
approved shade on surface pipe lines.
a) 25mm dia RM 10 713 7,130
TRI -PACK FI LM S LI M I TED
1 6 5 3 PTB PLA N T BUI LDI N G
PO RT Q A SI M KA RA CHI
PLUM BI N G WO RKS ( I N TERN A L)
BI LL O F Q UA N TI TI ES
Sr. Unit Rate
Description of Items Unit Quantity Amount (Rs)
No. (Rs)
W2.4 Provide, fix, join and test G.I. pipes for sui gas pipe
line to BS 1387, medium quality "IIL" or "Jamal"
make or approved equivalent and China make
specials of the following diameters pipes and fittings,
giving anticorrosion treatment, applying protective
anti-corrosive painting, and bitumen tape on
concealed pipes, pipe supports hangers, testing and
commissioning etc.
a) 20 mm dia RM 25 586 14,650
b) 25 mm dia RM 60 713 42,780
W2.5 Provide and install Gate Valve of following
nominal dia, "Dadex" or "Beta" make, or
approved equivalent including jointing, fitting,
testing complete.
a) 20 mm dia (ball valve) No. 1 2,253 2,253
b) 25 mm dia No. 4 2,704 10,816
c) 32 mm dia No. 2 3,755 7,510
d) 40 mm dia No. 1 6,008 6,008
SECTION-4 SANITARY, PLUMBING
AND FIXTURES
W2.6 Providing and installing European type W.C. ICL
fregate / 4006 or approved equal, coupled with
low down flushing cistern 4006, uPVC seat and
cover export quality 15mm dia C.P. brass T. stop
cock Master made No. 010 with metal head or
approved equal, making water inlet connections,
cutting of holes in walls, plinth and floor for pipe
connections and making good in cement
concrete 1:2:4 complete including testing. No 3 8,261 24,783
W2.7 Provide and install Water Closet as specified in sub-
items below, with low down flushing cistern Model
No. 2001 of Master make or approved equivalent,
1/2" dia. powder coated brass T.stop-cock Master
make No.081 or approved equal, as per sample
approved, 38mm dia. uPVC flush pipe with extra
bend and length in matching colour with fitting and
clamps, 100mm dia. uPVC P or S trap as required,
supply and waste water connections, complete
including testing.
a) ICL make Orisa/Asian/900 White Standard
quality or approved equal. No. 3 6,308 18,924
TRI -PACK FI LM S LI M I TED
1 6 5 3 PTB PLA N T BUI LDI N G
PO RT Q A SI M KA RA CHI
PLUM BI N G WO RKS ( I N TERN A L)
BI LL O F Q UA N TI TI ES
Sr. Unit Rate
Description of Items Unit Quantity Amount (Rs)
No. (Rs)
W2.8 Provide and fix Wash Hand Basin (W.H.B) as
specified in sub-items below, including approved
C.P. chain & plug, bottle trap, C.P. inlet
connections, 12mm dia. C.P. brass T. stop cock
Master Make No.010 or approved equal, as per
sample approved, 32mm dia. heavy duty
approved, powder coated waste coupling 32mm
dia 16 gauge aluminium waste pipe, all of
approved make, complete including testing.
a) W.H.B. make ICL, Fregate/2006/56 cm white
export quality with pedestal, or approved equal. No. 3 6,759 20,277
b) W.H.B. make ICL, Vanity Type. No. 3 5,257 15,771
W2.9 Provide and fix 12mm dia. C.P. brass bib cock
including muslim shower of Master make or
approved equal as per sample approved,
complete including testing etc. No. 7 3,755 26,285
W2.10 Provid and fix C.P. brass underground stop cock
12mm dia. of Master make or approved equal as
per sample approved, including testing etc. No. 20 1,802 36,040
W2.11 Provide and fix 12mm dia C.P. Mixers with built
in C.P. pipe 12mm dia, of Master make or
approved equal complete including pipe
connections, all fitting as per sample approved,
including testing etc.
a) Wash basin mixer No.024. No. 6 5,257 31,542
b) Sink mixer No.18 No. 2 4,506 9,012
W2.12 Provide and fix mirror, to wall using rawl plugs and
C.P. brass screws with frame as approved, complete.
1) Master make No.2003 or approved equal. No. 6 1,802 10,812
W2.13 Provide and fix Shelf Rack/2004 Model Master make
or approved equal fixed with rawl plugs and C.P.
brass screws, as per sample approved, complete. No. 6 1,202 7,212
W2.14 Provide and fix Towel Rail NO.2005 Model of M/s
Master make or approved equal fixed with rawl plugs
and C.P. brass screws as per sample approved,
complete. No. 3 1,127 3,381
W2.15 Provide and fix Soap Dish No. 2007 of Master make
or approved equal as per sample approved. No. 6 751 4,506
W2.16 Provide and fix Toilet Paper Holder No.2008 of
Master make or approved equal as per sample No. 4 826 3,304
approved.
TRI -PACK FI LM S LI M I TED
1 6 5 3 PTB PLA N T BUI LDI N G
PO RT Q A SI M KA RA CHI
PLUM BI N G WO RKS ( I N TERN A L)
BI LL O F Q UA N TI TI ES
Sr. Unit Rate
Description of Items Unit Quantity Amount (Rs)
No. (Rs)
W2.17 Providing and fixing stainless steel "Rashed
Steel Industries: or "Super Asia" make or
approved equivalent kitchen sink supreme
quality of 20 gauge, brackets, screws, 38mm
dia. Heavy duty waste coupling and aluminium
waste pipe of 16 guage, bottle trap CP inlet
connections all of approved make and quality
complete including testing of the following types
and sizes: bowl (500mm X 1000mm)
a) Double No. 1 7,510 7,510
W2.18 Provide, fixing, testing and commissioning
cooking range of "CANON" or "Ambassador" or
approved equivalent including gas connections
complete in all accessories. No. 1 40,554 40,554
W2.19 Provide and fix Electric Geyser including all
safety valves, controls & fittings of the following
capacities, "Dynamar" or "Ambassador" make or
equivalent, as approved.
a) 10 Gallon Capacity No. 2 18,024 36,048
SECTION-7 APPURTENANCE FOR SEWERS
W2.20 Provide and construct Gully Traps as shown on
drawings, consisting of all work items like
excavation, backfill, cast iron gully traps embedded in
P.C.C.; R.C.C. wall of 4000 psi cylinder strength, 2
coats of hot bitumen outside, 15mm thick puddlo
plaster inside, 6mm thick steel cover with angle iron
frame including making required number of pipes
connection, reinforcement grade 60, complete in all
respect. Execution of work item shall conform to
relevant sections of the Specifications. No. 2 22,530 45,060
SECTION-8 uPVC PIPE LINE
W2.21 Provide, cut, fix, join and test uPVC pipe for soil and
waste conforming to ISO 3633:1991 (wall
thickness=3.2mm) including uPVC fittings with
solvent cement jointing "Dadex" or "Beta" make or
approved equal, including clamping to walls or under
floor, cutting through walls and providing sleeves
through concrete for pipelines and pipe fittings
including testing of the following diameter.
a) 50 mm dia RM 10 1,051 10,510
b) 75 mm dia RM 50 1,871 93,550
c) 100mm dia RM 60 2,779 166,740
W2.22 Provide and fix uPVC floor trap excluding grating,
and cover, as approved.
a) 75 mm No. 11 4,055 44,605
TRI -PACK FI LM S LI M I TED
1 6 5 3 PTB PLA N T BUI LDI N G
PO RT Q A SI M KA RA CHI
PLUM BI N G WO RKS ( I N TERN A L)
BI LL O F Q UA N TI TI ES
Sr. Unit Rate
Description of Items Unit Quantity Amount (Rs)
No. (Rs)
W2.23 Provide and fix uPVC Floor Clean-Out "Dadex" or
"Beta" make or approved equal including testing
complete in all respect as per drawings.
a) 75 mm No. 2 3,455 6,910
b) 100 mm No. 4 3,905 15,620
W2.24 Provide and fix uPVC 75mm dia Vent Cowel on
vent pipes of approved quality by "Dadex" or
"Beta" make or approved equal as per drawings. No. 3 376 1,128

TOTAL C/O TO SUMMARY OF COST: 966,854


TRI -PACK FI LM S LI M I TED
UTI LI TI ES
BI LL O F Q UA N TI TI ES
CI VI L WO RKS
Item Unit Rate Amount
Description of Items Unit Quantity
No. (Rs) (Rs)

SECTION-1 PRELIMINARIES & EARTHWORKS


1.4 Earthwork for structures.
1.4.1 Structural excavation in soil above sub-soil water level for
levelling and grading of building, for foundations and
other structures, and unsuitable excavated material dispose
off outside the project premises any lead as per
Specifications and as per approval of the Engineer. M3 2,400 577 1,384,800
1.4.2 Compacted backfill in foundations with approved
suitable excavated soil, including breaking clods,
dressing, watering, compacting mechanically in layers
not exceeding 230mm thick depth to 95% Modified
Proctor Dry Density, from any lead and any lift as per
Specification. M3 655 484 317,020
1.4.3 Supply suitable approved earth, from approved
outside sources, including digging, loading and un-
loading and filling in plinth protection etc. including,
dressing, watering, compacting mechanically in
layers not exceeding 230mm thick depth to 95%
Modified Proctor Dry Density as per Specifications, M3 125 1,093 136,625
1.4.4 Supply, stack and fill sand of approved quality from
outside sources under plinth protection floors etc.,
including dressing, watering, compacting
mechanically in layers not exceeding 230mm thick
depth to 95% Modified Proctor Dry Density, from any
lead and any lift as per Specification. M3 16 1,953 31,248
SECTION-2 CONCRETE WORKS
2.2 Reinforcement for Concrete
2.2.1 Provide and fix steel reinforcement Grade 60 deformed
steel bars conforming to ASTM A-615, including cleaning,
cutting, bending, placing, binding etc., including provision
and cost of spacers and binder wire, cost of chairs, over-
laps not shown on drawings etc., in any kind of R.C.C
works as specified.
a) Reinforcing steel bars of Grade 60 (min. 60,000 psi
yield strength) Tone 140 120,301 16,842,140
2.3 Non-structural Concrete
2.3.1 Provide and lay lean concrete in foundations, under floors,
plinth protection etc., using approved sand and stone crush
as coarse aggregate including formwork and its removal,
leveling, compacting and curing etc., complete in all
respects as per drawings and Specifications.
a) PCC (1:4:8) M3 185 7,576 1,401,560
2.4 Structural (Design Mix) Concrete
TRI -PACK FI LM S LI M I TED
UTI LI TI ES
BI LL O F Q UA N TI TI ES
CI VI L WO RKS
Item Unit Rate Amount
Description of Items Unit Quantity
No. (Rs) (Rs)
2.4.1 Provide and lay structural cement concrete of 3000 psi
cylinder crushing strength at 28 days, using O.P. Cement,
Bolari/Malir sand, and Makli/Mangopir - Hub stone crush
including formwork and its removal, placing, compacting,
finishing and curing complete in all respects (including
screening and washing of stone aggregate) but excluding
the cost of reinforcement, as per Specifications.

a) R.C.C. Footing / Rafts M3 11 9,897 108,867


3
b) R.C.C. Plinth Beams M 10 16,995 169,950
c) R.C.C. Suspended Beams M3 72 13,568 976,896
3
d) R.C.C. Suspended Slabs M 175 15,445 2,702,875
e) R.C.C. Slab on Grade M3 23 11,172 256,956
f) R.C.C. Parapet M3 17 25,061 426,037
2.4.2 Ditto item 2.4.1 above but structural cement concrete
of 3750 psi cylinder crushing strength at 28 days for:-
a) R.C.C. Raft / Footings M3 345 11,695 4,034,775
b) R.C.C. Columns / Padestals M3 62 17,715 1,098,330
3
c) R.C.C. Walls M 245 17,715 4,340,175
SECTION-3 MASONRY
3.2 Concrete Block Work
3.2.1 Provide and lay cement concrete (min 15N / mm2 or
1500 psi compressive cube strength at 28 days)
200mm thick solid concrete block masonary using 1:3
cement: sand block (sand of Bolari / Malir mix with
15% crushed stone aggregate of 1/4"-3/8" size)
approved by the Engineer, walls laid in 1:5 cement
mortar in plinth protection, lay with steel dowels from
RCC structure, and including vertical & horizontal
steel as per Typical Details Drawing, curing etc.
complete in all respects, as directed by the Engineer. M3 90 11,860 1,067,400
3.2.2 Provide and lay cement concrete (min 15N / mm2 or
1500 psi compressive cube strength at 28 days) 200mm
thick solid concrete block masonary using 1:3 cement: sand
block (sand of Bolari / Malir mix with 15% crushed stone
aggregate of 1/4"-3/8" size) approved by the Engineer,
walls laid in 1:5 cement mortar in superstructure including
scaffolding and its removal, lay with steel dowels from
RCC structure and including vertical & horizontal steel as
per Typical Drawing, curing etc. complete in all respects, as
directed by the Engineer.
M3 51 10,448 532,848
SECTION-4 TERMITE PROOFING
TRI -PACK FI LM S LI M I TED
UTI LI TI ES
BI LL O F Q UA N TI TI ES
CI VI L WO RKS
Item Unit Rate Amount
Description of Items Unit Quantity
No. (Rs) (Rs)
4.1 Termite Control
4.1.1 Provide and apply antitermite treatment to foundation bed
& vertical surfaces and under floors, using the indicated
insecticide emulsion below, applied as specified by the
manufacturer.
a) Biflex by FMC or Mirage by Ali Akbar (Pvt) Ltd. or
Termicure by Jaffer Brothers or approved M2 1,690 186 314,340
equivalent
4.1.2 Provide and apply antitermite treatment to inside building
along walls, using the indicated insecticide emulsion
below, applied as specified by the manufacturer.
a) Biflex by FMC or Mirage by Ali Akbar (Pvt) Ltd. or
Termicure by Jaffer Brothers or approved M2 55 186 10,230
equivalent
4.1.3 Provide and apply antitermite treatment to exterior vertical
surfaces of external walls, using the indicated insecticide
emulsion below, applied as specified by the manufacturer.
a) Biflex by FMC or Mirage by Ali Akbar (Pvt) Ltd. or
Termicure by Jaffer Brothers or approved M2 435 186 80,910
equivalentFLOORINGS / WALL FINISHES
SECTION-5
5.8 Plain Concrete Flooring
5.8.1 Provide and lay PCC 1:2:4 flooring in alternate panels
without permanent division strips, and finishes smooth dust
free.
a) 50mm thick (in plinth protection) M2 185 457 84,545
5.9 HEAVY DUTY CONCRETE FLOORING
5.9.1 Provide and lay granolithic floor topping 1:2, 25mm
thick, top surface finished smooth without grinding
and polishing excluding RCC works without dividing
into panels; as per Specifications excluding steel
reinforcement. M2 1,065 1,331 1,417,515
SECTION-6 PLASTERING & POINTING
6.1 Cement Plaster
6.1.1 Supply, make, apply and cure 20mm thick smooth
finished plaster in 1:4 cement sand mortar, smooth
finished with steel trowel on internal walls as shown in
the drawings including metal lath strips (whereas
required), curing etc; as per Specifications and as per
sample approved by the Engineer. M2 1,050 526 552,300
6.1.2 Supply, make apply and cure 15mm thick smooth
finished 1:3 cement sand plaster (on ceilings), as
per Specifications and as per sample approved by the
Engineer. M2 Rate only 503
TRI -PACK FI LM S LI M I TED
UTI LI TI ES
BI LL O F Q UA N TI TI ES
CI VI L WO RKS
Item Unit Rate Amount
Description of Items Unit Quantity
No. (Rs) (Rs)
6.1.3 Supply, make, apply and cure 20mm thick smooth
finished plaster with 25mm grooves in 1:4 cement
sand mortar, smooth finished with steel trowel on
external wall as shown in drawings including metal
lath strips (whereas required), curing etc; as per
Specifications and as per sample approved by the M2 535 560 299,600
6.1.4 Supply make, apply and cure (2 coats of plaster) final
coat of 15mm thick plaster with 25mm grooves in
comb plaster in 1:4 cement sand mortar over 15mm
thick plaster on external walls including metal lath
strips (where as required) curing etc; as per
Specifications and as per sample approval of the M2 270 942 254,340
Engineer.
SECTION-7 DAMP PROOFING AND WATER
PROOFING, INSULATION
7.1 Bitumen Damp-proof Courses (Over Masonry)
7.1.1 Provide and lay 38mm thick horizontal DPC topped
with two coats of specified quality hot bitumen (hot
applied system) fully covering the surface, on dry
surface; consisting of 1:1.5:3 cast in situ cement
concrete including mixing, compacting, finishing
smooth, curing, formwork and is removal etc.,
including 1 layer of 500 gauge polythene sheet
(weighing 2.5 lbs per 100 Sft) with 75mm overlaps
over dried bitumen, as per Specifications and to the M2 6 1,442 8,652
7.8 Roof Treatment
7.8.1 Provide and lay PCC 1:2:4 screed with reinforcing #2
steel bars @300 c/c at both way over R.C.C flat roof
slab laid in slope with a minimum thickness of 40mm
as per Specifications and Instructions of the Engineer. M2 1,118 1,056 1,180,608
7.8.2 Providing and applying top protective coating for flat
roof slab comprising as under.
a) Prepare surface for roof treatment; making free
from laitance, grease, oil or loose and flaky
particles.
b) Provide and apply two coat of "Master Seal 550"
each coat of 1 Kg / M2as per instructions of the
chemical manufacturer ("BASF"). M2 1,118 640 715,520
SECTION-8 ROOF DRAINAGE
8.1 Roof Drainage
8.1.1 Supply, provide and fix in position uPVC rain water
down pipe lines conforming to ISO 3633:1991 and BS
3505 1968 (wall thickness 3.2mm) including proper
joints complete in all respects, and system leak-free:
a) 100mm dia RM 14 1,577 22,078
b) 150mm dia RM 15 2,373 35,595
8.1.2 Provide and fix uPVC Plain Bends with grating (as
rain water inlets at roof), water tight connection leak-
a) 100mm dia No. 5 6,759 33,795
TRI -PACK FI LM S LI M I TED
UTI LI TI ES
BI LL O F Q UA N TI TI ES
CI VI L WO RKS
Item Unit Rate Amount
Description of Items Unit Quantity
No. (Rs) (Rs)
b) 150mm dia No. 4 11,265 45,060
8.1.3 Provide and fix uPVC Shoe Bends (as rain water
outlets), water tight connection leak-free:
a) 100mm dia No. 5 1,878 9,390
b) 150mm dia No. 4 4,506 18,024
8.1.7 Provide and lay rain water troughs using non
structural cement concreter 1:2:4 and finish with
10mm (3/8") thick 1:3 grey cement sand plaster
complete in all respect and as per Specifications. No. 7 2,253 15,771
SECTION-10 METAL WORKS
10.1 Architectural steel and Iron Works
10.1.1 Provide and fix in position single / double leaf double
sheeted steel hinged sami louvered door in 16
S.W.G. M.S. sheet with "Z" section
50mmx50mmx6mm M.S. angle frame and 6mm M.S.
flat plate welded together to form "Z" section frame,
including bracing 38mmx38mmx6mm M.S. angle, 3
Nos. approved heavy duty hinges per shutter, 3 Nos.
M.S.hold-fast for door frame on ether side, embedded
in P.C.C.(1:2:4), painting 2 coats of red oxide with
min 2-3 coats of enamel paint (ICI make or approve
equal), and all hardware complete in all respects as
per drawings and Specifications and as per sample
approved by the Engineer.
a) Type SD1 (2500mm x 2500mm) M2 25 15,757 393,925
b) Type SD2 (3000mm x 3000mm) M2 18 15,757 283,626
10.1.2 Provide and fix steel rungs 25mm dia @ 300mm c/c
embedded in concrete wall and grouting with epoxy
"Master flow-935" by "BASF" or approved equivalent
including 2 coats of red oxide with 2-3 coats of anti
rust synthetic enamel paint (ICI make or approve
equal), complete in all respect as per drawings and as
per sample approved by the Engineer. No. 34 1,277 43,418
10.1.3 Providing and fixing M.S. sheet cover over tank
consisting of 31mmx31mmx3mm M.S. angle iron
frame embedded in RCC slab and
31mmx31mmx3mm M.S. angle weldded to M.S. sheet
9mm thick, including lifting handle, hinges and 2 coats
of red oxide with 2-3 coats of anti rust synthitic
enamel paint (ICI make or approve equal), complete
in all respect as per drawings and as per sample No. 2 8,261 16,522
10.2 Architectural Aluminium Work
TRI -PACK FI LM S LI M I TED
UTI LI TI ES
BI LL O F Q UA N TI TI ES
CI VI L WO RKS
Item Unit Rate Amount
Description of Items Unit Quantity
No. (Rs) (Rs)
10.2.1 Provide and fix glazed Aluminium fixed ventilator
using sections of Pakistan Cables (Pvt) Ltd, Chawla
Aluminium or approved equivalent, 100 mm wide and
2 mm thick in natural colour frames including 6mm
thick imported clear glass, all glass shall be
tempered, and all hardware etc; as shown on
drawings, and as per sample approved by the
a) Type AV1 (4000mm x 600mm) M2 10 15,757 157,570
b) Type AV2 (3000mm x 600mm) M2 6 15,757 94,542
10.2.2 Provide and fix aluminium fixed louvers in natural
colour frame, using extruded sections of Pakistan
Cables (Pvt) Ltd, or Chawla Aluminium or approved
equivalent, min 25mmx75mm and 2mm thick with
hold-fasts and seal all around outer frame, including
all hardware etc; as shown on drawings, and as per
sample approved by the Engineer.
a) Type SLV1 (6000mm x 500mm) M2 6 12,121 72,726
SECTION-11 PAINTING
11.4 Painting Cement Works
11.4.2 Provide and apply one coat of primer Dulux Primeon
of ICI make (or approved equal) and 3 to 4 coats (as
may be approved to have the required finish) of Dulux
Matt Finish Enamel Paint of ICI make (or approved
equal) as per Specifications and approved shade, and
as per sample by the Engineer. M2 2,120 356 754,720
11.4.2 Provide and apply one coat of primer Dulux Primeon
of ICI make (or approved equal) and 3 to 4 coats (as
may be approved to have the required finish) of Dulux
Weather sheild Paint of ICI make (or approved equal)
as per Specifications and approved shade, and as per
sample by the Engineer. M2 535 404 216,140
SECTION-12 EXPANSION JOINT FINISHES
12.3 Water Stops
12.3.1 Provide and install min. 200mm wide approved bulb
type A-Class PVC Water Stopper all around
basement wall at construction joint, complete in all
respect with full continuity as per drawings and
Specificaitons and as per sample approved by the
Engineer, ensuring complete water-tightness. RM 200 1,271 254,200
SECTION-17 SPECIAL ITEMS (SP)
17.1 Special Items
17.1.1 Provide and apply two coats of "Master seal-180"
chemical coating (0.40kg / M2 / coat) by "BASF" or
approved equivalent to inside of R.C.C. wall and bed
complete as per Technical Specifications and
manufacturer's instruction. M2 890 976 868,640
TRI -PACK FI LM S LI M I TED
UTI LI TI ES
BI LL O F Q UA N TI TI ES
CI VI L WO RKS
Item Unit Rate Amount
Description of Items Unit Quantity
No. (Rs) (Rs)
17.1.2 Provide and apply two coats of "Master seal-550"
chemical coating (1 Kg/M2 /coat) by M/s "BASF" or
approved equivalent to outside of R.C.C. wall,
complete as per Technical Specification and
manufacturer's instructions. M2 315 640 201,600

Total C/o to Summary of Cost: 44,284,404


TRI -PACK FI LM S LI M I TED
1 6 5 3 PTB, PO RT Q A SI M KA RA CHI
PLUM BI N G WO RKS
EXTERN A L SEWERA GE, WA TER SUPPLY A N D
FI RE FI GHTI N G SYSTEM
BI LL O F Q UA N TI TI ES
Sr. Unit Rate
Description of Items Unit Quantity Amount (Rs)
No. (Rs)
(EXTERNAL)
SECTION W-1 EARTHWORK FOR PRESSURE
PIPELINES AND APPURTENANCES
W-1.1 Excavation for pipeline trenches, and appurtenances
including dressing and compacting bottoms,
backfilling trenches in layers including compacting as
specified, and disposal of surplus material, as directed
by the Engineer. M3 290 577 167,330
SECTION W-2 WATER SUPPLY PIPE LINES
W-1.2 Provide, fix, join, test and disinfect BSS 1387
medium quality G.I. pipes for water supply "IIL" or
"Jamal" make of nominal dia. stated in sub-items
below, including China make specials (sockets, tees,
elbows, bends, crosses, reducers, plugs and unions
etc.) buried in trenches or under floors, also including
one coat of approved bitumen, hessian cloth
wrapping and finishing with 2 coats of approved
bitumen paint, complete as per Specifications.
a) 50mm dia RM 170 1,652 280,840
W-1.3 Provide, fix, join, test and disinfect BSS 1387
medium quality G.I. pipes for Sui Gas supply "IIL" or
"Jamal" make of nominal dia. stated in sub-items
below, including China make specials (sockets, tees,
elbows, bends, crosses, reducers, plugs and unions
etc.) buried in trenches or under floors, also including
one coat of approved bitumen, hessian cloth
wrapping and finishing with 2 coats of approved
bitumen paint, complete as per Specifications.

a) 40mm dia RM 145 1,164 168,780


W-1.4 Provide and install Gate Valves of following nominal
dia., grey cast iron body, epoxy coated, stainless steel
wedge, stemp and seat in accordance with BS-5163
from "Teepu" or approved equal make, including
jointing, fitting, testing, complete.

a) 50mm dia No. 1 7,510 7,510


b) 40mm dia (ball valve) No. 1 6,008 6,008
SECTION W-3 EARTHWORK FOR SEWER
LINES AND APPURTENANCES
TRI -PACK FI LM S LI M I TED
1 6 5 3 PTB, PO RT Q A SI M KA RA CHI
PLUM BI N G WO RKS
EXTERN A L SEWERA GE, WA TER SUPPLY A N D
FI RE FI GHTI N G SYSTEM
BI LL O F Q UA N TI TI ES
Sr. Unit Rate
Description of Items Unit Quantity Amount (Rs)
No. (Rs)
W-1.5 Excavation for pipeline trenches, and appurtenances
including dressing and compacting bottoms,
backfilling trenches in layers including compacting as
specified, and disposal of un-suitable and surplus
excavated materials, as directed by the Engineer. M3 125 577 72,125
SECTION W-5 CONCRETE SEWERS PIPE
LINES
W-1.6 Provide and lay R.C.C. pipes, in trenches
including jointing and testing as specified.
a) 230mm dia RM 155 1,352 209,560
SECTION W-6 BEDDING UNDER SEWERS

W-1.7 Provide and lay stone ballast bedding including


levelling, compacting etc., complete as per
drawings and Specifications. M3 25 6,759 168,975
W-1.8 Provide and lay compacted fill with local sand in
trenches brought from outside the project limits,
any lead, complete as per drawings and as per
Specifications. M3 200 1,093 218,600
W-1.9 Provide and lay plain cement concrete (1:2:4)
including placing, compacting, finishing and
curing complete in all respect (including
screening and washing of stone aggregate); for
thrust blocks as per drawings and
Specifications. M3 3 12,767 38,301
SECTION W-7 APPURTENANCE FOR
SEWERS
TRI -PACK FI LM S LI M I TED
1 6 5 3 PTB, PO RT Q A SI M KA RA CHI
PLUM BI N G WO RKS
EXTERN A L SEWERA GE, WA TER SUPPLY A N D
FI RE FI GHTI N G SYSTEM
BI LL O F Q UA N TI TI ES
Sr. Unit Rate
Description of Items Unit Quantity Amount (Rs)
No. (Rs)
W-1.10 Provide and construct R.C.C. Manholes as
shown on drawings, consisting of all work items
like P.C.C. 1:4:8 sub-floor, R.C.C. walls, base
slab, top slab having 3750 psi cylinder strength
including reinforcement Grade 60, formwork and
its removal, M.S. steps, 200mm wide PVC water
stopper bulb type at construction joint all around
the manhole wall, P.C.C 1:2:4 in channels &
benching, 2 coats of hot bitumen outside,
including making required number of main and
branch connections; 560mm insdie dia-meter
C.I. manhole cover with C.I. frame, 150mm thick
R.C.C. slab including reinforcement Grade 60
complete in all respects. Execution of work item
shall conform to relevant drawings and relevant
sections of Specifications. The depth of
manhole shall be measurement from the top of
R.C.C. cover and to the lowest invert level of
sewer.

a) Square Manholes of 900mm x 900mm


internal size, depth up to 2200mm No. 11 52,570 578,270
W-1.11 Provide and construct Septic Tank 4.90M x
1.85M size and 3.73M deep including
excavation, backfilling, all pipe connections and
all work items like P.C.C. 1:4:8 sub floor, R.C.C.
walls, base slab and top slab having 3750 psi
cylinder strength, using O.P. Cement and
approved sand and crush including
reinforcement Grade 60, formwork and its
removal, 200mm wide PVC water stopper bulb
type at construciton joint, 3 Nos.550mm inside
dia-meter heavy duty C.I. manhole cover with
frame, M.S. steps, complete in all respects.
Execution of work item shall conform to relevant
drawings and relevant section of Specifications.
No. 1 675,900 675,900
TRI -PACK FI LM S LI M I TED
1 6 5 3 PTB, PO RT Q A SI M KA RA CHI
PLUM BI N G WO RKS
EXTERN A L SEWERA GE, WA TER SUPPLY A N D
FI RE FI GHTI N G SYSTEM
BI LL O F Q UA N TI TI ES
Sr. Unit Rate
Description of Items Unit Quantity Amount (Rs)
No. (Rs)
W1.12 Provide and construct Soakage pit including all
pipe connectinos and all works items like block
masonry walls in 1:4 cement sand mortar, with
reinforcement and R.C.C. crub at bottom, R.C.C.
perforated slab including 20mm dia P.V.C.
sleeves for holes at the rate of 150mm c/c both
way, and solid R.C.C. top slab having 3750 Psi
cylinder crushing strength using O.P. Cement
and approved sand and stone crush including
reinforcement grade 60, including 50 dia PVC
pipes in wall @ 600mm C/C horizontally and
vertically, silt filling and stone ballast 50mm to
25mm size over perforated slab as per
drawings, 900mm inside dia-meter R.C.C.
manhole cover with C.I. frame, M.S. steps,
75mm dia C.I. vent pipe with cowl, excavation
(well sinking) etc; detailed as shown in drawings
and as per Specifications of relevant civil works.

a) Soakage pit of 4.2M inside dia and 10.5M


depth No 1 1,426,900 1,426,900
SECTION W-8 uPVC PIPE SEWERS
W1.13 Provide, fix cut, join and test uPVC pipe
conforming to ISO 3633:1991 (wall
thickness=3.2mm) including uPVC fittings with
solvent cement joints or rubbing ring joints by
"Dadex" or "Beta" make or approved equivalent,
buried in trenches in correct alignment, making
proof joints complete in all respects as per
drawings and Specifications.
a) 200mm dia RM 30 4,957 148,710
SECTION W-13 FIRE FIGHTING SYSTEM
W-1.14 Provide, fix, join, test and disinfect BSS 1387
M.S. seemless pipes of "Haffaz Engineering
Work, Karachi" or approved equal shedule 40
and test pressure to 12 bars, for Fire Fighting
pipe line, and specials buried in trenches or
under floors, also including one coat of
approved bitumen, wrapped in polyethylene
(P.E.) sheet comply to B.S. 743: 1970 wt. not
less than 130 g/m2 and finishing with 2 coats of
approved bitumen paint, complete as per
Specifications.

a) 150 mm dia RM 900 13,668 12,301,200


TRI -PACK FI LM S LI M I TED
1 6 5 3 PTB, PO RT Q A SI M KA RA CHI
PLUM BI N G WO RKS
EXTERN A L SEWERA GE, WA TER SUPPLY A N D
FI RE FI GHTI N G SYSTEM
BI LL O F Q UA N TI TI ES
Sr. Unit Rate
Description of Items Unit Quantity Amount (Rs)
No. (Rs)
W-1.15 Provide and fix Fire Hose Cabinets for outside
use made of 18 swg. sheet glass front size
(1200mm x 760mm x 250mm) including two
lengths fire hose rubberlined Nylon top, 65mm x
30m length, SYNTEX OSW 500, fitted with male
and female brass coupling and tow jet/spray/fog
nozzles, cabinet with red oxide primer and red
enamel finish, FIRECHIEF" make or approved No. 15 187,750 2,816,250
W-1.16 equivalent.
Provide and fix Pillar Type Fire Hydrants with
100mm flanged inlet, 50mm x 65mm
connections, instantaneous Female, 65mm ball
valve, blank caps with chain, hydrant coted with
epoxy polyster powder, FIRECHIEF maker or
approved equal. No. 15 78,104 1,171,560

Total C/o to Summary of Cost:


20,456,819
TRI -PACK FI LM S LI M I TED
EXTEN SI O N 1 6 5 3 PTB, PO RT Q ASI M KARACHI
RO A D A N D STO RM WA TER DRA I N A GE WO RKS
BI LL O F Q UA N TI TI ES

Rate Amount
Sr. No. Description of Items Unit Quantity
(Rs) (Rs)

A: ROADS
R-1 Stripping of top soil in road area upto 150mm depth
including disposal of excavated material within site
etc. complete as per Specifications and as directed
by the Engineer. M2 6,260 255 1,596,300
R-2 Compaction of natural ground or after stripping with
road roller as per Specifications including
preparation of subgrade; compaction 90 to 95% of
maximum modified AASHTO dry density. M2 6,260 77 482,020
R-3 Structural excavation in common soil for
edge/curb stones etc. including disposal of
surplus material, upto any lead within the site
complete as per Specifications and as directed M3 25 577 14,425
R-4 by the Engineer.
Provide and fill approved suitable soil in open
areas, brought from outside the project limits, any
lead including dressing and ramming as per
Specifications and as directed by the Engineer.
a) With borrow excavation from outside upto any
lead and lift. M3 5,820 1,093 6,361,260
R-5 Make embankment as per lines, grades and levels
shown in drawings and as per Specifications
including cost of excavation, haulage, filling,
placing, moistening, compaction 95% of maximum
modified AASHTO dry density, preparation of
subgrade complete in all respects.
a) With borrow excavation from outside upto any
lead and lift. M3 4,695 1,093 5,131,635
R-6 Providing and laying bituminous prime coat
complete as per Specifications. M2 6260 120 751,200
R-7 Providing and laying 60mm thick plant mix asphalt
concrete wearing course including transportation,
compaction etc. complete as per Specifications. M2 6260 1,041 6,516,660
R-8 Provide and lay granular subbase course of
crushed stone of approved quality and grade ,
including cost of materials, transportation, placing,
mixing, spreading, watering, and compaction to
required depth, and grade to achieve 100%
maximum modified AASHTO dry density (Min. CBR
= 50%) complete as per Specifications. M3 940 2,016 1,895,040
R-9 Provide and lay water bound macadam base course
of crushed stone of approved quality and grade ,
including cost of materials, transportation, placing,
mixing, spreading, watering and compaction to
required depth, and grade to achieve 100%
maximum modified AASHTO dry density (Min. CBR
= 80%) as per Specifications. M3 1,260 2,265 2,853,900

1 of 4
TRI -PACK FI LM S LI M I TED
EXTEN SI O N 1 6 5 3 PTB, PO RT Q ASI M KARACHI
RO A D A N D STO RM WA TER DRA I N A GE WO RKS
BI LL O F Q UA N TI TI ES

Rate Amount
Sr. No. Description of Items Unit Quantity
(Rs) (Rs)
R-10 Provide and lay plain cement concrete under
pavement and edge stones etc. using stone
aggregate including mixing, placing, compacting,
formowrk and curing etc. complete as per drawings
and Specifications.
a) P.C.C. (1:4:8) M3 85 7,576 643,960
R-11 Provide and lay crush stone 20mm down blended
with sand to fill voids using approved crush, and
compaction uner footpath complete as per
Specifications. M3 10 2,265 22,650
R-12 Provide and lay 60mm thick "Tuff Pavers" blocks of
concrete of 5000 psi cube strength at 28 days made
by "Tuff Tiles (Pvt) Ltd", for footpath etc. or
approved equivalent, laid over 19mm thick 1:5
cement sand mortar bed including grouting with
cement sand mortar 1:4 and with matching colour
pigment complete in all respects as shown in
drawings and Specifications, and as approved by
the Engineer. M2 55 1,352 74,360
R-13 Provide and lay precast concrete edge/curb stone
(3000 psi cube strength) in cement sand mortar 1:3
including fabrication, formowrk, curing etc. complete
in accordance with sizes, lines and levels shown in
the drawings and as per Specifications.
a) Edge stone 125mmx300mm RM 30 1,051 31,530
b) Curb stone 150mmx400mm RM 1690 1,051 1,776,190
R-14 Provide and fix traffic signs as per Highway
Department Standards for urban area including
post, plate, paints, foundation etc., complete in all
respects as per drawings and Specifications. No. 10 7,510 75,100
R-15 Provide and lay pavement marking for arrows 4
meter long as per Highway Standards complete as
per drawing and Specifications. No. 3 112,650 337,950
R-16 Provide and Paint using reflective road quality paint
of ICI or other appproved make to manufacturer's
Specifications and as directed by the Engineer, on:
a) 125mm wide M2 210 601 126,210
R-17 Provide and fix Road Studs (Cat-eyes) as per
drawings and Specifications. No. 1,840 676 1,243,840

Total A :
29,934,230
B: STORM WATER DRAINS
D-1 Structural excavation for drains including back fill
and stockpiling of surplus excavated soil for filling in
site areas etc. complete as per Specifications. M3 1,300 1,036 1,346,800

2 of 4
TRI -PACK FI LM S LI M I TED
EXTEN SI O N 1 6 5 3 PTB, PO RT Q ASI M KARACHI
RO A D A N D STO RM WA TER DRA I N A GE WO RKS
BI LL O F Q UA N TI TI ES

Rate Amount
Sr. No. Description of Items Unit Quantity
(Rs) (Rs)
D-2 Provide and lay lean concrete 1:4:8 in foundations
using stone aggregate including formwork, mixing,
pouring, placing, compacting, and curing etc.
complete as per drawings and Specifications. M3 165 7,576 1,250,040

3 of 4
TRI -PACK FI LM S LI M I TED
EXTEN SI O N 1 6 5 3 PTB, PO RT Q ASI M KARACHI
RO A D A N D STO RM WA TER DRA I N A GE WO RKS
BI LL O F Q UA N TI TI ES

Rate Amount
Sr. No. Description of Items Unit Quantity
(Rs) (Rs)
D-3 Provide and lay reinforced cement concrete of min.
3000 psi cylinder strength at 28 days in drains and
culverts etc. including mixing, placing, compacting,
formwork, curing, expansion and construction joints
etc. complete as per drawings and Specifications
but excluding the cost of reinforcement. M3 280 17,818 4,989,040
D-4 Provide and fix reinformcement of steel bars
including cutting, bending and binding as per
drawings and Specifications.
Reinforcing bars of Grade 60 (60,000 psi) tone 36 120,301 4,330,836
D-5 Provide and fix removable steel grating of 12mm
Sq. bars, 30mm c/c welded with angle iron 18mm x
18mm x6mm frame at both ends, 24mm x 24mm
x6m angle iron frame with M.S anchor embedded in
R.C.C. drain wall to support the grating including
welding and painting two coats of red oxide with
three coats of enamel paint (ICI make or approved
2
equal), complete as per drawing and Specifications. M 45 17,273 777,285
D-6 Provide and lay pre-cast concrete cover slab over
drain 750mm x 750mm x150mm thick including cost
of reinforcement steel grade 60, complete in all
respects as per drawings and Speceifications. No. 10 5,257 52,570

Total B :
12,746,571

Total C/o to Summary of Cost (A+B): 42,680,801

4 of 4
TRI -PACK FI LM S LI M I TED
N O RTH WESTERN I N DUSTRI A L ZO N E
PO RT Q A SI M A UTHO RI TY, KA RA CHI
DEM O LI TI O N & RELO CA TI O N O F EXI STI N G FA CI LI TI ES
BI LL O F Q UA N TI TI ES
Item Unit Rate Amount
Description of Items Unit Quantity
No. (Rs) (Rs)

SPECIAL INSTRUCTIONS TO THE BIDDER

Contractor is required to visit the Site and check the


Conditions, Stacking and disposal site of debris etc;
before submission of quote / bid and familiarize
himself with the site conditions and "Safety" policy of
the Company.

Contractor to ensure that the demolition / relocation of


the facilities are to be done after placing a partition
fence / wall around the facilities and the facilities to be
isolated from the Plant Building. The partition fence /
wall should be strong enough to remain in place for
the Project period.

Contractor must use latest automatic equipments


(Excavator, Dozer, Loader, Dump Truck, Jack
Hammer, Cutter, Diamond Cutters Grinders etc.) and
shuold take care of safety conditions and ensure that
there is no damage caused to the adjacent structures.

After the demolition works, site should be cleaned,


levelled and free from underground structures, so that
the new construction can be done properly, to the
satisfaction of the Engineer In-charge.

1 Removal / Dismantling of the existing Construction(s)


and relocation of utilities affecting the Extension works
on the site, is to be carried out as a Lump Sum Item.
For this purpose the Tenderer must visit the Site and
understand and estimate the exact nature, extent and
cost.

The item inter-alia include the following:-

(a) Dismantling of existing Tandoors alongwith gas


pipe-line and safe storing / handing over to the
Employer. The Tandoor is approx 3.7m x 3.9m
x 3m high (02 Nos) and 7m x 7.4m x 3m high
(01 No in 150mm thick block masonry wall
construciton and carefully remove and hand-
over gas pipe-line with valves etc. as per
instructions and satisfaction of the Engineer In-
(b) charge.
Road Paved area near Tandoor to be
demolished and removed: Approx 265 M2.
TRI -PACK FI LM S LI M I TED
N O RTH WESTERN I N DUSTRI A L ZO N E
PO RT Q A SI M A UTHO RI TY, KA RA CHI
DEM O LI TI O N & RELO CA TI O N O F EXI STI N G FA CI LI TI ES
BI LL O F Q UA N TI TI ES
Item Unit Rate Amount
Description of Items Unit Quantity
No. (Rs) (Rs)
(c) Removal of Poles, flood lights, mercury lights
and carefully storing / handing over to the
Employer along with cables.

04 No. of flood light poles

10 Nos. of Mercurry lights at the top edge of


PTP3 Wall.
(d) Remove and hand over trees 20 Nos. medium
size to the Employer.
(e) Removal of M.S. Ladders; one approx 5 M high
from AGL; beside store area and other approx 5
M high for ventiliation area.
(f) Disconnect carefully, remove and hand over to
the Employer:-
01 No. of Electric Panel small on the PTP-3
Wall.

05 RM of Cable coming to the above pannel.

90 RM; 3 Nos H.T Cable (11 Kv, 3x120mm).


(g) Remove / Dismantle / Disconnect and relocate
following:-

10 RM long and 8" dia of Water Pipes for


matalizer; 2 Nos.

10 RM long and 3" dia of Waste RO main line on


PTP-3 Wall

10 RM long and 3" dia of TDO Waste Line

05 RM long and 6" dia of PVC pipe on the PTP-


3 Wall

10 RM long and 8" dia of Water pipes in Utility


Area; 2 Nos.

120 RM long and 6" dia of Water pipes along the


boundary wall; 2 Nos.

120 RM long and 10" dia of Water pipes along


the boundary wall; 2 Nos.
TRI -PACK FI LM S LI M I TED
N O RTH WESTERN I N DUSTRI A L ZO N E
PO RT Q A SI M A UTHO RI TY, KA RA CHI
DEM O LI TI O N & RELO CA TI O N O F EXI STI N G FA CI LI TI ES
BI LL O F Q UA N TI TI ES
Item Unit Rate Amount
Description of Items Unit Quantity
No. (Rs) (Rs)
(h) Demolition / Dismantle 1 No. Waste Shed
Container + Dust Bins of approx 10m x 24m
consisting of 10 Nos. M.S. Columns; 5 Nos. M.S.
Truss of angles, alongwith G.I. Roofing and Wall
System besides PTP-3 Wall towards the road
side.
(i) Removal of existing 8 ft high and approx 90m
long precast boundary wall.
(j) Dismantle and carefully Relocate the Foundation
Stone of PTP-3. L.S. 1 7,046,913 7,046,913

Total Cost: 7,046,913