Professional Documents
Culture Documents
1004.1.1 Cumulative Table 1004.1.2 revised to include new terminology Occupant Load
Occupant Loads Factor(previously Floor Area in Sq. Ft. Per Occupant)
Reformats the Occupant load factor for Exhibit gallery and museum added (30
net)
requirements previously
located in 1004.1 and Table 1004.1.2 Maximum Floor Area Allowances per Occupant -
now includes Mall buildings - covered and open with a reference
1004.6
to Section 402.4.1 where the occupant load for malls is addressed
2009 1004.4 (Exiting
from multiple levels)
removed from 2012
2009 1004.5 (Egress
convergence) moved to
1005.6
3 4
5 6
7 8
EXIT
11 12
13 14
15 16
17 18
7.2.2.5.5.4 - Photoluminescent
7.8.1.2.3 - Energy Saving Lighting
Markings
7.8.1.2.3* - Energy saving sensors, switches, timers or Addresses photoluminescent markings in stair
controllers shall be approved and shall not compromise enclosures.
the continuity of illumination of the means of egress Numerous changes for this edition.
required by 7.8.1.2.
Still how to do it not where to do it.
A.7.8.1.2.3 - A consideration for the approval of
Manufacturers are telling people it is mandated.
automatic, motion-sensor type lighting switches,
controls, timers or controllers is whether the equipment Similar to mandatory provisions set by local law in NYC.
is listed as a fail-safe device for use in the means of
egress.
27 28
29 30
Penetrations of fire
barriers enclosing an
interior exit stair or ramp
or exit passageway now
permitted in exterior
membrane
Penetrations must be
properly protected in
accordance with the
membrane penetration
provisions of 714.3.2
33 34
41 42
to 410.6
45 46
http://www.bupssaggu.com/roadshow/images/TrussSystems.jpg
47 48
49 50
51 52
55 56
61 62
Thank You
Clay Aler, P.E. Andrew M. Schneider, P.E.
Principal Senior Fire Protection
caler@koffel.com aschneider@koffel.com