You are on page 1of 11

2012 IBC and 2012 NFPA 101 Significant Means of Egress Changes

2012 IBC & 2012 NFPA 101 Questions


Significant Means of Egress
Submit questions in your Go To Webinar Question box
Changes 

 Answers as time permits at the end


 Answers to all questions will be posted after the Webinar
Clay Aler, P.E. Andrew M. Schneider, P.E.
Principal Senior Fire Protection Engineer
caler@koffel.com aschneider@koffel.com

Koffel Associates, Inc.


www.koffel.com

Expertly Engineering Safety From Fire 2

1004.1.2,Table 1004.1.2 - Design Occupant


1004.1 Design Occupant Load Load- Areas without Fixed Seating

 1004.1.1 Cumulative  Table 1004.1.2 revised to include new terminology Occupant Load
Occupant Loads Factor(previously Floor Area in Sq. Ft. Per Occupant)

 Reformats the  Occupant load factor for Exhibit gallery and museum added (30
net)
requirements previously
located in 1004.1 and  Table 1004.1.2 Maximum Floor Area Allowances per Occupant -
now includes Mall buildings - covered and open with a reference
1004.6
to Section 402.4.1 where the occupant load for malls is addressed
 2009 1004.4 (Exiting
from multiple levels)
removed from 2012
 2009 1004.5 (Egress
convergence) moved to
1005.6
3 4

1005 - Means of Egress Capacity 1005 - Means of Egress Capacity


Determination Determination
 2009 1005.1 has been broken down into multiple  Reduced egress width factors for sprinklered buildings
sections and is now 1005.2 1005.5 from 2000 through 2006 IBC reintroduced
 1005.3.1 Stairways  0.2 inches per occupant for stairways
 1005.3.2 Other egress components  0.15 inches per occupant for other egress components
 1005.4 Capacity of the means of egress from any story  Building must be equipped with automatic sprinkler system and
cannot be reduced along the path of travel until termination at the emergency voice/alarm system
public way  Excludes Group H and I-2 occupancies
 1005.5 Where more than 1 exit is required, loss of any 1 exit
cannot reduce the available egress capacity to less than 50% of
the required egress capacity

5 6

Proprietary Presentation by Koffel Associates, Inc. 1


2012 IBC and 2012 NFPA 101 Significant Means of Egress Changes

1007 - Accessible Means of 1007 - Accessible Means of Egress


Egress
 Interior exit access stairways and exterior areas of
rescue assistance are now recognized as an accessible
means of egress component (1007.2)
 Multiple modifications to 1007.7
 Exterior areas for assisted rescue now permitted on stories
above the level of exit discharge
 Stairways as part of MOE for exterior area for assisted rescue no
longer require clear width of 48 inches between handrails in
sprinkler protected buildings
 Revised separation requirements for exterior areas of assisted
rescue (1007.7.4)

7 8

7.2.12.2.3 - Stairs in Accessible


7.14 - Evacuation Elevators
Means of Egress
 (1) The minimum 48 in. clear width .  2009 Edition was
 (2)* For stairs where egress is in the descending Annex B Elevators
direction, a clear width of not less than 37 in. (940 mm), for Occupant-
measured at and below handrail height, shall be Controlled
permitted where all of the following are met: Evacuation Prior
to Phase I
 (a) An approved stair descent device is provided on
Emergency Recall
each floor served by the stair.
Operations
 (b) Additional approved stair descent devices are
 Now code
provided on floors with an occupant load exceeding 200
requirements in
at the ratio of one device per 200 occupants.
2012 Edition
 (c) The required approved stair descent devices are
provided in an approved location on the floor.
9 10

1001.4 - Fire Safety and 1001.4 - Fire Safety and


Evacuation Plans Evacuation Plans

 Addition: Reference to IFC 401.2 and 404 for


requirements regarding fire safety and evacuation plans
 IFC 404 requires plans in certain Group A, B, E, F, H, I, M, and
R occupancies, high rise buildings, certain covered mall buildings
and buildings with an atrium

EXIT
11 12

Proprietary Presentation by Koffel Associates, Inc. 2


2012 IBC and 2012 NFPA 101 Significant Means of Egress Changes

1008.1.9.8 Access-Controlled 1008.1.9.9 - Mag Locks on


Egress Doors Egress Doors
 Egress doors which require
panic hardware are now
permitted to be equipped with
 Relocated from electromagnetic locks
1008.1.4.4 to clarify it is  Panic hardware must be
a different kind of locking listed for use in the release
of electromagnetic locks
mechanism, not a
 Operation of listed
different kind of door
hardware must directly
interrupt the power to the
electromagnet (ensures
compliance with single
operation requirements of
1008.1.9.5)

13 14

7.2.1.6 - Special Locking 7.2.1.5.10.6 - Two Releasing


Arrangements Operations for Existing Hardware
 7.2.1.6.1.1(5) Delayed-Egress Locking Systems  Two releasing
 The egress side of doors equipped with delayed-egress locks operations shall be
shall be provided with emergency lighting in accordance with permitted for existing
Section 7.9. hardware on a door leaf
 7.2.1.6.2(7) Access-Controlled Egress Door Assemblies serving an area having
 The egress side of access-controlled egress doors, other than an occupant load not
existing access-controlled egress doors, shall be provided with exceeding 3, provided
emergency lighting in accordance with Section 7.9. releasing does not
require simultaneous
operations.

15 16

7.2.1.15 - Inspection of Door


8.5.4.3 - Smoke Barrier Doors
Openings
 Latching hardware shall  Where required by the occupancy chapters, the
be required on doors in following doors must be inspected and tested not less
smoke barriers, unless than annually:
specifically exempted by  Panic hardware or fire exit hardware
Chapters 11 through 43.  Exit enclosures
 Electrically controlled
 Special locking arrangements

17 18

Proprietary Presentation by Koffel Associates, Inc. 3


2012 IBC and 2012 NFPA 101 Significant Means of Egress Changes

7.7.3.4 - Exit Discharge 7.4 - Number of Means of Egress

 Stairs and ramps that  A.7.4 - Section 7.4


continue more than one- requires a minimum
half story beyond the number of means of
level of discharge shall egress Several
be provided with an occupancy chapters
approved means to establish not only the
prevent or dissuade minimum number of
occupants from traveling means of egress but
past the level of also the minimum
discharge during number of actual exits
emergency building that must be provided on
evacuation. each floor.
19 20

1009 Stairways 1012 Handrails

 1009.2 Interior Exit Stairways


 Conventional exit stair enclosures required for travel distance  1012.2 exception
or # of exit requirements
 Allows transition pieces
 1009.3 Exit Access Stairways in continuous handrails
 Groups unenclosed stairs formerly located in 1016.1 exceptions to exceed the maximum
and 708.2 exceptions permitted handrail
 Open parking garage stairs and ramps height
 Outdoor facility stairs  1012.8 now clarifies
 Technical production area stairs that intermediate rails do
 Balcony and mezzanine stairs not reduce egress width
 Group I-3 stairs
 Stairs protected by draft curtains and closely spaced sprinklers
 Atrium stairs 21 22

1013.1, 1013.8 - Guards at


1013.3 - Guard Height
Operable Windows
 Guard requirements for operable  Modified exception for
windows with sill height > 72
inches above finished grade minimum required guard
relocated from Ch. 14 to Ch. 10 height for Group R-3
 Minimum window sill height at occupancies and within
which a guard is not required has
been increased from 24 to 36 individual R-2 dwelling
inches units
 Operable sections of windows shall  Decreased from 42 to
not permit openings that allow
passage of a 4-inch diameter 36 inches (to be
sphere where such openings are consistent with the
located within 36 inches of the IRC)
finished floor
 Occupancy must not
 See 1013.8 for exceptions
be more than three
 Window opening control devices
required to comply with ASTM F stories above grade in
2090 23 height 24

Proprietary Presentation by Koffel Associates, Inc. 4


2012 IBC and 2012 NFPA 101 Significant Means of Egress Changes

1011.2 - Floor Level Exit Signs 7.8.1.2.2 - Automatic Motion


in Group R-1 Sensor Lighting-Type Switches
 Addition: Where exit signs are  Unless prohibited by Chapters 11 through 43, automatic
required in Group R-1
occupancies by 1011.1, motion sensortype lighting switches shall be permitted
additional low level exit signs are
now required in means of egress within the means of egress, provided that the switch
serving guest rooms controllers comply with all of the following:
 Provide additional safety for
occupants and fire fighters not  (1) the switch controllers are listed
familiar with surroundings when
smoke layer develops and  (2) the switch controllers are equipped for fail-safe operation and
obscures normal-use exit signs
 Bottom shall be between 10 evaluated for this purpose
and 12 inches above floor  (3) the illumination timers are set for a minimum 15-minute
 Flush mounted to door or duration
wall
 If mounted on wall, edge of  (4) the motion sensor is activated by any occupant movement in
sign must be within 4 the area served by the lighting units
inches of door frame on
latch side  (5) the switch controller is activated by activation of the building
fire alarm system, if provided
25 26

7.2.2.5.5.4 - Photoluminescent
7.8.1.2.3 - Energy Saving Lighting
Markings
 7.8.1.2.3* - Energy saving sensors, switches, timers or  Addresses photoluminescent markings in stair
controllers shall be approved and shall not compromise enclosures.
the continuity of illumination of the means of egress  Numerous changes for this edition.
required by 7.8.1.2.
 Still how to do it not where to do it.
 A.7.8.1.2.3 - A consideration for the approval of
 Manufacturers are telling people it is mandated.
automatic, motion-sensor type lighting switches,
controls, timers or controllers is whether the equipment  Similar to mandatory provisions set by local law in NYC.
is listed as a fail-safe device for use in the means of
egress.

27 28

1019.4 & 1026.5 Egress Balconies and


1018.6 Corridor Continuity Exterior Exit Stairways and Ramps
 Clarification that where  New requirement that
the path of travel within exterior egress
fire-resistance-rated balconies, exit stairways
corridors to an exit and ramps be located >
includes travel along 10 ft from lot lines and
unenclosed exit access other buildings on the
stairways or ramps, the same lot unless the
fire-resistance rating exposing building
must be continuous for exterior walls and
the length of the stair or openings are protected
ramp until the exit per 705

29 30

Proprietary Presentation by Koffel Associates, Inc. 5


2012 IBC and 2012 NFPA 101 Significant Means of Egress Changes

1021.2.1 - Exits from Mixed


1021.2 - Exits from Stories
Occupancy Buildings
 Exits now permitted to be  Added a ratio equation used
arranged where they serve a to determine if a single exit is
portion of a story instead of all allowed to serve the
occupants on that floor
combined occupant load from
 Must meet the following: multiple occupancies in a
 Number of exits from story mixed occupancy building.
complies with 1021.2.4
 If the sum of the ratios of the
 Access to exits from each calculated number of
individual space in the occupants of the space
story complies with 1015.1
divided by the allowable
 All spaces within each number of occupants for each
portion of a story must
occupancy is 1, a single exit
have access to the min.
number of approved exits
is permitted
based on O.L of that
portion, but not less than
two exits 31 32

1021.2.3, Table 1021.2(1) - Exits 1022.5 & 1023.6 - Enclosure Penetrations of


from Dwelling Units Interior Exit Stairways and Exit Passageways

 Penetrations of fire
barriers enclosing an
interior exit stair or ramp
or exit passageway now
permitted in exterior
membrane
 Penetrations must be
properly protected in
accordance with the
membrane penetration
provisions of 714.3.2

33 34

1028.1.1.1 - Separation of Spaces 1028.10.1 Aisle Accessways


under Grandstands and Bleachers Serving Seating at Tables
 Addition: If space  Relocated provisions of
underneath grandstands 2009 1017.4
or bleachers is used for  Now all aisle and aisle
purposes other than accessway requirements
ticket booths < 100 ft2 for assembly spaces are
and toilet rooms, the located in 1028
space must be
separated by fire
barriers
 Barriers must comply
with 711 and have at
least 1-hour fire-
resistance-rated
construction 35 36

Proprietary Presentation by Koffel Associates, Inc. 6


2012 IBC and 2012 NFPA 101 Significant Means of Egress Changes

505.2.2 - Mezzanine Means of


419, 202 - Live/Work Units
Egress
 Definition of Live/Work  Modification: Specific
unit added to 202 mezzanine means of
 Means of egress egress provisions have
components (419.3) been removed
now designed in  Replaced with a general
accordance with Ch. 10 reference to Ch. 10
based on function of  Mezzanines must now
residential space comply with general
 Plumbing facilities means of egress
(419.9) in accordance provisions
with Ch. 29 based on the
function of the non-
residential space 37 38

3.3.185 & 3.3.21.6 - Normally


509 - Incidental Uses - General
Unoccupied Support Areas
 Replaced incidental accessory occupancies with  3.3.185/3.3.21.6* - Normally Unoccupied Building
concept of incidental uses Service Equipment Support Area. A building service
 Removes relationship with mixed-occupancy provisions equipment support area in which people are not
expected to be present on a regular basis.
 Incidental uses - functional extensions of a primary use
which generally pose a greater level of risk to that
occupancy (509.1)
 All uses listed in Table 509
 Classified the same as the building occupancy in which they
reside (no longer permitted to be classified as unique occupancy
groups) (509.2)
 Shall not occupy > 10% of the building area of the story in which
they are located (based on floor area of individual tenant space
in the case of multiple tenants per floor) (509.3)
39 40

7.13 - Normally Unoccupied 7.13 - Normally Unoccupied


Equipment Areas Support Areas Access/Egress
 7.13 - Normally Unoccupied Building Service Equipment
Support Areas. < 45,000 sq ft 45,000 sq ft 90,000 sq ft

 7.13.1* - Hazard of Contents.


 7.13.1.1 - Unless prohibited by Chapters 11 through 43,
No Sprinkler
the provisions of Section 7.13 shall apply in lieu of the Access Panel Doors Per 7.2.1 Doors Per 7.2.1
Protection
provisions of Section 7.1 through Section 7.12 to
normally unoccupied building service equipment support
areas, where such areas do not contain high hazard
contents or operations. Sprinkler
Access Panel Access Panel Doors Per 7.2.1
Protection

41 42

Proprietary Presentation by Koffel Associates, Inc. 7


2012 IBC and 2012 NFPA 101 Significant Means of Egress Changes

7.13 - Normally Unoccupied 7.13 - Normally Unoccupied


Equipment Areas Equipment Areas
 7.13.2 - Egress Doors.  7.13.2.2 - Egress from normally unoccupied building
 7.13.2.1* - Egress from normally unoccupied building service equipment support areas shall be provided by
service equipment support areas shall be provided by doors complying with 7.2.1 where the normally
doors complying with 7.2.1 where the normally unoccupied building service equipment support area
unoccupied building service equipment support area exceeds 90,000 ft2 in buildings protected throughout by
exceeds 45,000 ft2 in buildings not protected throughout an approved, supervised automatic sprinkler system
by an approved, supervised automatic sprinkler system  7.13.2.3 - The absence of sprinklers in the normally
 A.7.13.2.1 - Egress from normally unoccupied building unoccupied building service equipment support area as
service equipment support areas not exceeding 45,000 permitted by an exemption of NFPA 13, shall not cause
ft2 is permitted to be by access panels or other the building to be classified as nonsprinklered for the
hardware not complying with the door requirements of purposes of applying 7.13.2.2.
7.2.1.
43 44

7.13 - Normally Unoccupied 410.6.3, 202 - Technical


Equipment Areas Production Area Terminology
 Means of Egress Path
 Width  Outdated terminology
 Head Room replaced
 Exit Signage  Replaced fly gallery,
 Illumination gridiron, and pinrail with
the all inclusive
 Number of Means of Egress technical production
area
 Means of Egress for
stages and technical
production areas moved http://www.bupssaggu.com/roadshow/images/TrussSystems.jpg

to 410.6
45 46

1015.6 Day Care Means of 407.4 Group I-2 Means of


Egress Egress
 New section requiring a  Group I-2 Exit Access
second means of egress Requirements
for rooms or spaces (1014.2.2 1014.2.7)
providing care for more moved to 407.4
than 10 children (2  The requirements are
years or younger) essentially unchanged

http://www.bupssaggu.com/roadshow/images/TrussSystems.jpg

47 48

Proprietary Presentation by Koffel Associates, Inc. 8


2012 IBC and 2012 NFPA 101 Significant Means of Egress Changes

18.2.3.4 - Health Care Corridors 18.2.3.4 - Stored or Parked?


 (4)(c)i* Projections into the required width shall be permitted for wheeled equipment in use and
carts in use.
 (4)(c)ii* Projections into the required width shall be permitted for wheeled medical emergency
equipment not in use.
 (5)* Where the corridor width is at least 8 ft, projections into the required width shall be permitted
for fixed furniture provided that all of the following conditions are met:
 (a) The furniture is securely attached to the floor or to the wall.
 (b) The fixed furniture does not reduce the clear unobstructed corridor width to less than 6 ft
except as permitted by 18.2.3.4 (2) and (3).
 (c) The fixed furniture is located only on one side of the corridor
 (d) The fixed furniture is grouped such that each grouping does not exceed an area of 50 sq ft
 (e) The fixed furniture groupings addressed in 18.2.3.4(7)(d) are separated from each other by a
distance of at least 10 ft.
 (f)* The fixed furniture is located so as to not obstruct access to building service and fire
protection equipment.
 (g) Corridors throughout the smoke compartment are protected by an electrically supervised
automatic smoke detection system

49 50

18/19.2.5.7 - Suite Intervening 18/19.2.5.7 - Suite Intervening


Rooms Rooms
 18/19.2.5.7.2.1 - Sleeping Suite Arrangement.  18/19.2.5.7.3.1* - Non-Sleeping Suite Arrangement.
 (A)* Occupants of habitable rooms within sleeping suites Occupants of habitable rooms within non-sleeping suites
shall have exit access to a corridor complying with shall have exit access to a corridor complying with
18.3.6 without having to pass through more than one 18/19.3.6 without having to pass through more than two
intervening room. intervening rooms.
 18/19.2.5.7.3.4 - Non-Sleeping Suite Travel Distance.
 (A) Travel distance within a non-sleeping suite to an exit
access door from the suite shall not exceed 100 ft. the
following:
 (1) 100 ft where the suite is arranged with one intervening room
 (2) 50 ft where the suite is arranged with two intervening rooms

51 52

1104.3.1 - Employee Work 1107.6.1 - Accessible Units in R-


Areas 1 Occupancies
 Maximum size of employee  Modification: Not every
work areas exempt from element within or serving an
requirement that common- Accessible unit has to be
use circulation paths within accessible
work areas meet accessibility  Only one full bathroom
route requirements has been need be accessible where
increased from 300 ft2 to multiple bathrooms are
1000 ft2 provided
 Common use circulation  Where multiple family or
path defined by assisted bathrooms serve a
unit, at least 50% but not
permanently installed
less than one room for each
partitions, counters, use at each cluster shall be
casework, or furnishings accessible
 New requirement  5%, but not less than one
consistent with ADA bed shall be accessible
Guidelines 53 54

Proprietary Presentation by Koffel Associates, Inc. 9


2012 IBC and 2012 NFPA 101 Significant Means of Egress Changes

1109.2, 1109.5 - Accessible 1109.6 - Accessible Saunas and


Childrens Facilities Steam Rooms
 Saunas and steam rooms
now required to be accessible
 Added exceptions to
 Exception: where saunas
allow for toilet facilities or steam rooms are
and drinking fountains to clustered at a single
be designed using size location, at least 5% of the
provisions found in ICC saunas and steam rooms
A 117.1 but not less than one of
each type in the cluster
 Can be installed at a shall be accessible
lower height (30 inches  Added to ensure
for water fountains) and compliance with A117.1
still be considered technical requirements
accessible

55 56

1110.4 - Variable Message 1208.3 - Minimum Kitchen Floor


Signs Area
 Variable message signs  Minimum floor area
used in transportation requirement of 50 ft2 for
facilities and emergency kitchens has been
shelters now required to removed
comply with A117.1-  Size limitation had no
2009 relation to life safety or
 VMS signs not required health concerns
in emergency shelters  1208.1 still requires at
where equivalent least 3 ft of clearance
information is provided between counter fronts
and appliances or walls
in an audible manner
(see exception to
1110.4.2. 57 58

1210 - Toilet and Bathroom


Requirements
Questions and Discussion
 2903.1 addressing
water closet
compartments relocated
to 1210.3.1
 2903.2 addressing
urinal partitions
relocated to 1210.3.2
 Term service sinks
added to 1210.2.2
intended to protect walls
and floors adjacent to 60

plumbing fixtures from


damage and decay 59 Expertly Engineering Safety From Fire

Proprietary Presentation by Koffel Associates, Inc. 10


2012 IBC and 2012 NFPA 101 Significant Means of Egress Changes

Future Questions. Upcoming Webinars

 Join our LinkedIn Discussion Groups


 Life Safety Code Go to webinars.koffel.com for more information
 People can join the group and submit their questions or
 People can email linkedin@koffel.com and submit
anonymously
 Smoke Management
 Proposed Changes to the IBC
 Ask the Expert Following our webinars you will receive a link for a survey.
 FAQ.Koffel.com At the end of the survey is a link for a copy of the presentation.

61 62

Thank You
Clay Aler, P.E. Andrew M. Schneider, P.E.
Principal Senior Fire Protection
caler@koffel.com aschneider@koffel.com

Follow us on LinkedIn www.koffel.com

Expertly Engineering Safety From Fire

Proprietary Presentation by Koffel Associates, Inc. 11

You might also like