You are on page 1of 28

TECHNICAL CATALOGUE

Fire dampers PL-10, PL-19, PL-20


FIRE DAMPERS

FIRE DAMPERS FIRE DAMPERS


PL-10-1 PL-10-2
Fire dampers are installed in rectangular or circular
ventilation ducts at the passages through the fire
compartments. In case of fire, the fire dampers close
automatically, thus preventing fire from spreading
through the ventilation ducts.
Fire resistance: 90 or 120 min.

Types concerning the release mode:


basic: with thermal release
with electric actuator

PL-19 PL-20
FIRE DAMPERS

Fire dampers Page


Fire dampers PL-10 ....................................................................................................................................................................................................................2
Types.......................................................................................................................................................................................................................................3
Installation...............................................................................................................................................................................................................................4
Ordering key.............................................................................................................................................................................................................................8
Certificate.................................................................................................................... ............................................................................................................9
Fire dampers PL-19................................................................................................................................................................................................................. 10
Types.....................................................................................................................................................................................................................................11
Installation.............................................................................................................................................................................................................................12
Ordering key.......................................................................................................................................................................................................................... 15
Certificate..............................................................................................................................................................................................................................16
Fire dampers PL-20 .................................................................................................................................................................................................................. 17
Types.................................................................................................................................................................................................................................... 18
Installation............................................................................................................................................................................................................................19
Ordering key..........................................................................................................................................................................................................................22
Certificate..............................................................................................................................................................................................................................23
FIRE DAMPERS PL-10

Fire Dampers PL-10


PL-10-1 General
Application:
Fire dampers prevent fire and smoke from spreading through air conditioning
and ventilation ducts in buildings. They are installed in openings of
constructions or on passages through partition compartments with limited
fire resistance (fire walls, partition walls).

Description:
The fire dampers PL-10 consist of a blade of calcium silicate, intumescent
sealant and thermal release mechanism with the release temperature 70C
(or higher for special requirements). A silicon profile sealant makes the fire
dampers PL-10 resistant also to cold smoke thus improving the fire safety.
Due to its special construction a blade is 25 mm thick, which improves energy
efficiency of the fire damper.

PL-10-2 Fire resistance and classification:


The fire dampers are tested according to the norm EN 1366-2.
Fire damper's basic fire resistance is EI 120-S (or EI 90-S depending
on the installation).

Types of fire dampers


PL-10-1 circular fire dampers only with manual-spring actuators for spiral ducts
PL-10-2 circular fire dampers with manual-spring or electric actuators for spiral
ducts

Nominal dimensions PL-10


Nominal diameters DN (mm)

DN (mm) 100 125 150 160 180 200

Standard lengths of PL-10


The standard length of PL-10-1... L = 170 mm.
The standard length of PL-10-2... L = 300 mm.

Installation*:
In rigid walls, the minimum thickness 100 mm
In light walls, the minimum thickness 100 mm (EI 90-S)
In light walls, the minimum thickness 125 mm
In rigid ceiling plates, the minimum thickness 150 mm

* Check for installation details in the installation manual

2
FIRE DAMPERS PL-10 TYPES

PL-10-1/A

5 3 2 1 4
Types of actuators
Manual-spring actuator type PL-10-1/A

1. Housing made of galvanised steel sheet


2. Blade made of calcium silicate and intumescent

25
sealant
3. Thermal release link with melting point at 70C
(optional 120C).
4. Silicone gasket for cold smoke
5. Spring

DN 85

170

PL-10-2/A8

Manual-spring actuator type PL-10-2/A8


5 3 4 2 1 6
1. Housing made of galvanised steel sheet
2. Blade made of calcium silicate and intumescent
sealant
3. Thermal release link with melting point at 70C
(optional 120C).
4. Silicone gasket for cold smoke
5. Spring
6. Release handle
cca 35 DN 85 7 7. Revision cover
300

PL-10-2/E..
5 3 2 1
Electric actuators type PL-10-2/E...

4 1. Housing made of galvanised steel sheet


2. Blade made of calcium silicate and intumescent
sealant
3. Thermal fuse
24,99

4. Silicone gasket for cold smoke


5. Electric actuator

84,76

max 85 DN 300

Duct connection PL-10

Without designation insertion type


M (a fire damper is inserted into a duct), standard type

M sleeve type (a duct is inserted into a fire damper)

3
FIRE DAMPERS PL-10 TYPES

Use of wooden supports during the installation Installation


The fire dampers should be installed according to
the designer's project for the fire safety. A fire
damper should not be statically stressed by
a building's structure.

During the installation the wooden supports should


be used (see the picture).

When mounting, a removable duct extension


should be installed to carry out control inside
a fire damper!

Please, follow the detailed instructions for installation


and use - as available by our sales employees.

Installation in a rigid wall PL-10-1 Installation in a rigid wall


A fire damper should be installed in a rigid wall of
the minumum thickness W = 100 mm into a circular
1 or rectangular opening, gap min. s = 50 mm. A wall
2 can be made of concrete, bricks or aerated bricks.
K Filler is either concrete or mortar. When mounting,
3
the installation dimension K = 35 mm should be
taken into account. For a thicker wall an extension
should be added since the fire damper does not get
through the wall!
A position of an actuator is optional in one or the
other fire compartment.

s
Legend:
DN
1. Wall (fire resistant)
DN+2s 2. Filler
W 3. Fire damper PL-10-1

W Wall thickness (mm)


K 35 (mm)
L Length of a fire damper (mm)
DN Nominal diameter of a fire damper (mm)
s Gap (mm)
Installation in a rigid wall PL-10-2

Legend:
1 1. Wall (fire resistant)
2 2. Filler
3 3. Fire damper PL-10-2

W Wall thickness (mm)


K 165 (mm)
L Length of a fire damper (mm)
DN Nominal diameter of a fire damper (mm)
s Gap (mm)

s
DN

DN+2s

W K

4
FIRE DAMPERS PL-10 INSTALLATION

Installation in a rigid ceiling plate PL-10-1 Installation in a rigid ceiling plate


A fire damper should be installed in a rigid ceiling
plate of the minimum thickness W = 150 mm, gap
4 s = 50 mm. A ceiling plate is made of concrete.
1 2 3 Filler can be either concrete or mortar. When
mounting, the installation dimension K = 165 mm
should be taken into account. For thicker wall an
extension should be added since a fire damper does

W
not get through the wall!

A position of an actuator is optional at the bottom


or at the top in one or the other fire compartment.
s
K

Legend:
1. Ceiling plate (fire resistant)
2. Filler
3. Fire damper PL-10-1
4. Extension (if required)

W Ceiling plate thickness (mm)


K 35 (mm)
DN Nominal diameter of a fire damper (mm)
s Gap (mm)
Installation in a rigid ceiling plate PL-10-2

4
1 2 3
Legend:
1. Ceiling plate (fire resistant )
2. Filler
3. Fire damper PL-10-2
W

4. Extension (if required)

W Ceiling plate thickness (mm)


s K 165 (mm)
K

L Length of a fire damper (mm)


DN Nominal diameter of a fire damper (mm)
s Gap (mm)

5
FIRE DAMPERS PL-10 INSTALLATION

Installation fixed in a light wall

Profile sub Legend:


construction 1. Fire damper PL-10
2. Filler 2 x 50 mm rock wool plates of density
> 130 kg/m3, melting point > 1000C
3. Wall (fire resistant), fire resistant plasterboard
7 plates 2 x 12,5 mm on each side (2+2 plates)
6 2
UW Profile 4. Rock wool 50 mm density > 50 kg/m3
5. Sleeve OPL-10
6. Steel bars of diameter 12 mm
1 K 7. Intumescent coating Intumex CSP-L, 2 layers
UW/CW Profile
8. Flexible duct compensator

5 A fire damper should be installed in a light wall


DN+2s

plate of the minimum thickness W = 100 mm,


8
gap min. s = 100 mm. Fixing in a wall and using
s

8 of flexible duct compensators required. When


2 mounting, the installation dimension K = 165 mm
4 3 UW Profile at the standard length of a fire damper L = 400 mm
should be taken into account.
DN+2s

W CW Profile A position of an actuator is optional in one or the


CW Profile
other fire compartment.

a=< 625mm
UW
Profile

Direct installation in a light wall

Legend:
1. Fire damper PL-10
2. Rock wool 50 mm density > 50 kg/m3
3
3. Wall (fire resistant), fire resistant plasterboard
2 1 plates 2 x 12,5 mm on each side (2+2 plates)
UW Profil
4 4. All gaps should be sealed with fire resistant putty

CW/UW A fire damper should be installed in a light wall of


N
qD

Profil the minimum thickness W = 125 mm. When


mounting, the installation dimension K = 150 mm
at the standard length of a fire damper L = 300 mm
should be taken into account.
UW Profil
A position of an actuator is optional, in one or the
CW Profil
CW Profil other fire compartment
W K
a=<625 mm
UW Profil

6
FIRE DAMPERS PL-10 INSTALLATION

Permitted installation positions of the fire dampers

When mounting, a blade axis and the actuator


position are oriented optionally from horizontal
to vertical position.

Installation in a wall without connection ducts

Legend:
4 3 2 1 5 4 3 2 1 4
1. Fire damper PL-10
2. Partition wall (100, 125 mm , rigid or
lightweight see ways of installation for
each type) or a concrete ceiling 150 mm
3. Optional extension (required for DN > 180)
4. Protection grille PG
5. Air duct

A fire damper can be installed in a fire resistant


partition wall without connection ducts or with
2 10 2 a duct on one side and a protection grille on
4 a free wall.
2
10
2

Maintenance and inspection:


The fire dampers should be maintained and inspected twice a year. If two successive inspections show no malfunctions, it is sufficient to perform further
examinations only once a year. Maintenance and inspection should only be carried out by authorized service.

WARNING
A standard type of the fire dampers PL-10 are not allowed to be installed in the explosion hazardous places. Neither are they allowed to be installed in the ventilation
devices which exhaust mixture of air and explosive gases. In such cases, special explosion-proof fire dampers should be installed. Neither are the standard fire
dampers PL-10 suitable for dusty ambients.

7
FIRE DAMPERS PL-10 ORDERING KEY

Ordering key :

Dimensions:
DN Nominal diameter in mm

Installation accessories:
Without designation no accessories
OPL-10 fixing clamp for installation light installation, light wall*

Connection:
Without designation standard insertion type (a fire damper inserted into a duct)
M Sleeve type (a duct inserted into a fire damper)

Accessories:
T1 Limit switch closed (only for PL-10-2)
T2 Limit switch open (only for PL-10-2)
T12 Limit switch (2 pcs) closed, open (only for PL-10-2)
TS Limit switch closed, max. 24 V- safety low voltage (SELV)
DO Junction box (option for electric actuators, designation E)

Actuators:
E15 Electric actuator Belimo BLF-24 T, (only for PL-10-2)
E16 Electric actuator Belimo BLF-230 T, (only for PL-10-2)
E19 Electric actuator Belimo BLF 24-T-ST + BKN 230-24, (only for PL-10-2)
A Manual actuator - basic, with thermal link, 70C; (only for PL-0-1)
A8 Manual actuator - basic, with thermal link, 70C; (only for PL-0-2)

Types of the fire dampers:


PL-10-1 L = 170 mm, classification EI 120-S (EI 90-S**)
PL-10-2 L = 300 mm, classification EI 120-S (EI 90-S**)

Electric actuators variants E. are fitted with limit switches, additional limit switches (T1, T2, T12) are not applicable. Standard release temperature of the
electric actuator is 72C.
For increased temperatures in the ducts the non-standard release temperatures are available, 120C for manual actuators and 95C for electric actuators
respectively.
Additional protection grilles PG and adjusting are available upon request.
*Check the required accessories and material, concerning the type of installation - for details sees the manual for installation and use
**Depending on the way of installation and wall thickness see the general characteristics - installation

Pressure drop diagram for PL-10


00

5
=1

12

100
DN 150
60
DN

80
=

00
=1
DN

=1

=2
DN

Pa
DN

DN

50

25
v = 5 m/s
16

10

v = 3 m/s
6 Pt

1
4 6 8 10 15 20 30 50 75 100 200 l/s 400

20 30 50 70 100 150 200 300 400 700 1200


V m /h
3

8
FIRE DAMPERS PL-10

Text for a project list:


Circular fire dampers for separation of fire compartments in ventilation and air conditioning systems, resistant to fire and cold smoke, fire resistance EI 120S
(EI 90-S light wall 100 mm), according to EN 13501-3, tested according to EN 1366-2.
Construction characteristics: a fire damper PL-10 consists of a housing made of galvanized steel sheet and blade of calcium silicate, intumescent sealant
and thermal release mechanism with the release temperature 70C. A silicon profile gasket between the housing and blade makes the fire damper also
resistant to cold smoke.
Installed in a rigid or light wall of the minimum thickness 100 mm or in a rigid ceiling plate of the minimum thickness 150 mm, according to the manufacturer's
instructions.

Manufacturer:
Type:

Ordering example:
Manufacturer:
Type:
Quantity:____ pcs

9
FIRE DAMPERS PL-19

FIRE DAMPERS PL-19


PL-19 General
Application:
Fire dampers
e prevent fire and smoke from spreading through air conditioning
and ventilation ducts in buildings. They are installed in openings of
constructions or on passages through partition compartments with limited fire
resistance (fire walls, partition walls).

Description:
A fire damper PL-19 consists of a blade of calcium silicate, intumescent sealant
and thermal release mechanism with the release temperature 70C (or higher
for special requirements). A housing of galvanised steel sheet is separated by
a calcium silicate heat insulated frame. A silicon profile gasket makes the fire
damper PL-19 resistant also to cold smoke, thus improving fire safety.
Due to its special construction the blade is 30 mm thick which improves energy
efficiency of a fire damper.

Fire resistance and classification:


The fire dampers are tested according to the norm EN 1366-2.
Fire damper's basic fire resistance is EI 90-S.

Types of the fire dampers concerning the installation into the ducts
PL-19 rectangular fire damper with flange for installation into the rectangular
ducts
PL-19- Dimensions
Nominal dimensions PL-19
Max. dimensions B x H=1500 x 800 mm
32,5 Min. dimensions B x H=150 x 150 mm
Standard length Lmin = 400 mm
Any dimension B x H within given dimension range available upon request.
32,5

Installation*:
Within rigid walls, the minimum thickness 100 mm
H

Within light walls, the minimum thickness 100 mm


Within rigid ceiling plates, the minimum thickness 150 mm

* Check for installation details in the installation manual

B
30

min. 200 min. 200

10
FIRE DAMPERS PL-19 TYPES

PL-19/A2 Types of actuators

8 7 1 2 9 Manual-spring actuator type PL-19/A2

1. Housing made of galvanised steel sheet,


separated by calcium silicate-heat insulation frame
2. Blade made of calcium silicate and intumescent
5 sealant
3. A2 thermal release link with melting point at
70C (optional 120C).
6 3 4. Silicone gasket for cold smoke
A2 5. Spring
6. Inspection release handle
7. Limit switch T1 - closed
4 8. Limit switch T2 - open
9
9. Revision cover

A2

PL-19/E...
5 1 2 9
Electric actuators type PL-19/E...

1. Housing made of galvanised steel sheet,


separated by calcium silicate-heat insulation frame
2. Blade made of calcium silicate and intumescent
sealant
3. Thermal fuse
4. Silicone gasket for cold smoke
5. Electric actuator
6. Revision cover
3

3 4 9

Flange connection dimensions


R6
Detail A Detail B
12.4
Dim. H or B (mm) No. of holes - n
10.5

12.4

up to 399 0
R6 400 - 699 1
700 - 849 2
32.5

850 - 1339 3
10

R4.7
5 1400 4
R4
.75

16

45

32.5

(n-1) x 300
(n-1) x 300
A 300 300 B A B

n = 1,3 n = 2,4

11
FIRE DAMPERS PL-19 INSTALLATION

Use of wooden supports during the installation Installation


The fire dampers should be installed according to
the designer's project of the fire safety. A fire damper
should not be statically stressed by a building's
structure.

During the installation the wooden supports should


be used (see the picture).

Follow the detailed instructions for installation


and use - as available by our sales employees.

Installation in a rigid wall Legend:


1. Fire damper PL-19
3 2. Filler
W
2 3. Wall (fire resistant)
K
1 W Wall plate thickness (mm)
K Distance from a wall on the actuators side (mm)
L Length of a fire damper (mm)
B or H Nominal width or height of a fire damper (mm)
s Gap (mm)

A fire damper should be installed in a wall of the


H/B

minumum thickness W = 100 mm into a rectangular


opening, gap s = 100 mm. A wall can be made of
concrete, bricks or aerated bricks. Filler is either
concrete or mortar. When mounting, the installation
s

dimension K = 145 mm at the standard length of a


L fire damper L = 400 mm should be taken into
account.
A position of an actuator is optional in one or the
other fire compartment.

Installation in a rigid ceiling plate Legend:


1. Fire damper PL-19
2. Filler
H/B
3. Ceiling plate (fire resistant)

W Ceiling plate thickness (mm)


K Distance from the ceiling on the actuators side (mm)
K

L Length of a fire damper (mm)


B or H Nominal width or height of a fire damper (mm)
L

s Gap (mm)

A fire damper should be installed in a wall of the


s 1 2 3 minumum thickness W = 100 mm into a rectangular
opening, gap s = 100 mm. A wall can be made of
concrete, bricks or aerated bricks. Filler is either
concrete or mortar. When mounting, the installation
dimension K = 145 mm at the standard length of a
fire damper L = 400 mm should be taken into
account.
A position of an actuator is optional in one or the
other fire compartment.

12
FIRE DAMPERS PL-19 INSTALLATION

Installation in a light wall and fixed in a ceiling Legend:


1. Fire damper PL-19
2. Filler 2 x 50 mm rock wool plates of density
> 130 kg/m3, melting point > 1000C.
3 Profile sub construction
4 3. Wall (fire resistant, type W112), fire resistant
6 plasterboard plates 2 x 12,5 mm on each side
2 (2+2 plates)
5 UW Profile
4. Rock wool of thickness 50 mm, density > 50 kg/m3
9 8 8 9 5. Sleeve LWB-19
6. Steel bars of diameter 12 mm fixed in a ceiling
UW / CW Profile
7. Intumescent coating Intumex CSP-L, 2 layers
8. Flexible duct compensator
H + 2s

9. Air duct
A
UW Profile
A fire damper should be installed in a lightweight
s

max. 1000mm wall of the minimum thickness W = 100 mm, gap


1 K
max. 1000mm
B + 2s
min. s = 100 mm. Fixed in a ceiling and use of duct
W
7 compensators required. When mounting, the
7 CW Profile CW Profile CW Profile CW Profile installation dimension K = 145 mm at the standard
A
a=<625 a=<625 a=<625
length of a fire damper L = 400 mm should be
taken into account.
2 A position of an actuator is optional in one or the
7
7 other fire compartment.
3 4

Direct installation in a light wall fixed in a wall, with a cover frame Legend:
1. Fire damper PL-19
2. Filler 2 x 50 mm rock wool plates of density
Profile sub construction > 130 kg/m3, melting point > 1000C
3
3. Wall (fire resistant, type W112), fire resistant
4
A plasterboard plates on each side 2 x 12,5 mm
UW Profile
5 2 (2+2 plates)
1 4. Rock wool 50 mm, density > 50 kg/m3
8
5. Clip angles PKL-19
6. Cover frame fire resistant plasterboard plates
UW / CW Profile 2 x 12,5 mm, on each side (2+2 plates)
7. Intumescent coating Intumex CSP-L, 2 layers
H + 2s

(100 mm on a fire damper, 40 mm on a cover


frame)
UW Profile
8. Air duct

7 A fire damper should be installed in a light wall


s

B + 2s
K 6 plate of the minimum thickness W = 100 mm, gap
min. 80 mm

W
CW Profile CW Profile CW Profile CW Profile
min. s = 100 mm. Fixed in a profile construction of
A a wall and use of a cover frame required. When
3
4
a=<625 a=<625 a=<625 mounting, the installation dimension K = 145 mm
6
at the standard length of a fire damper L = 400 mm
5 should be taken into account.
2 7
A position of an actuator is optional in one or the
other fire compartment.

13
FIRE DAMPERS PL-19 INSTALLATION

Permitted installation positions of the fire dampers


When mounting, a blade axis and the actuator
position are oriented optionally from horizontal to
vertical position.
H

B
B
H
H

B
B

Installation in a wall without connection ducts Legend:


1. Fire damper PL-19
2 2. Partition wall (100 mm, rigid or light see
4 3 1 5 4 3 2 1
ways of installation for each type) or a concrete
ceiling 150 mm
3. Optional extension (required for H > L)
4. Protection grille PG
5. Air duct

A fire damper can be installed in a fire resistant


partition wall without connection ducts or with
3 4 a duct on one side and a protection grille on
a free wall.
4
2 10 2
2
10
2

Maintenance and inspection:


The fire dampers should be maintained and inspected twice a year. If two successive inspections show no malfunctions, it is sufficient to perform further
examinations only once a year. Maintenance and inspection must only be carried out by authorized service.

WARNING
Standard fire dampers PL-19 are not allowed to be installed in the explosion hazardous places. Neither are they allowed to be installed in the ventilation
devices which exhaust mixture of air and explosive gases. In such cases special explosion-proof fire dampers should be installed. Neither are the
standard fire dampers PL-19 suitable for dusty ambients.

14
FIRE DAMPERS PL-19 ORDERING KEY

Ordering key:

Dimensions:
BxH Nominal width and height in mm

Installation accessories:
LWB-19 Brackets for installation installation in a light wall*
PKL-19 Brackets for installation direct installation, light wall*

Accessories:
T1 Limit switch closed
T2 Limit switch open
T12 Limit switch (2 pcs) closed,open
DO Junction box (option for electrical actuators, designation E...)

Actuators:
E5 Electrical actuator Belimo BF 24-T
E6 Electrical actuator Belimo BF 230-T
E9 Electrical actuator Belimo BF 24-T-ST + BKN 230-24
E15 Electrical actuator Belimo BLF-24 T **
E16 Electrical actuator Belimo BLF-230 T **
E19 Electrical actuator Belimo BLF 24-T-ST + BKN 230-24 **
A2 Spring/manual actuator advanced thermal release link 70C - thermal release link replaceable from
the outside

Types of the fire dampers:


PL-19 rectangular fire damper with a flange classification EI 90-S

Electric actuators variants E. are fitted with limit switches, additional limit switches (T1, T2, T12) are not applicable. Standard release temperature
of the electric actuator is 72C.
For increased temperatures in the ducts the non-standard release temperatures are available, 120C for manual actuators and 95C for electric
actuators respectively.
Additional protection grilles PG and adjusting are available upon request.
*Check the required accessories and material concerning the type of installation - for details sees the manual for installation and use

** Application range for actuators E15, E16, E19

BxH 150 200 250 300 350 400 450 500 550
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000

15
FIRE DAMPERS PL-19

Text for a project list:


The rectangular fire dampers for separation of fire compartments in ventilation and air conditioning systems, resistant to fire and cold smoke, fire resistance
EI 90-S according to EN 13501-3, tested according to EN 1366-2.
Construction characteristics: a fire damper PL-19 consists of a housing made of galvanized steel sheet and blade of calcium silicate, intumescent sealant
and thermal release mechanism with the release temperature 70C. A housing of galvanised steel sheet is separated by a calcium silicate heat insulated frame.
A silicon profile gasket makes the fire dampers PL-19 also resistant to cold smoke.
Installation in a rigid or light wall of the minimum thickness 100 mm or in a rigid ceiling plate of the minimum thickness 150 mm, according to the manufacturer's
instructions.

Manufacturer:
Type:

Ordering example:
Manufacturer:
Type:
Quantity:___pcs

16
FIRE DAMPERS PL-20

FIRE DAMPERS PL-20


PL-20 General
Application:
Fire dampers prevent fire and smoke from spreading through air conditioning
and ventilation ducts in buildings. They are installed in openings of constructions
or on passages through partition compartments with limited fire resistance
(fire walls, partition walls).

Description:
The fire dampers PL-20 consist of a blade of calcium silicate, intumescent sealant
and thermal release mechanism with the release temperature 70C (or higher for
special requirements). A housing of galvanised steel sheet is separated by calcium
silicate heat insulated frame. A silicon profile gasket makes fire dampers PL-20
resistant also to cold smoke, thus improving fire safety.
Due to its special construction the blade is 30 mm thick, which improves
airflow efficiency.

Fire resistance and classification:


The fire dampers are tested according to the norm EN 1366-2.
Fire damper's basic fire resistance is EI 90-S.

Types of the fire dampers concerning installation into the ducts


PL-20-F - circular fire damper with a flange
PL-20-S - circular fire damper for spiral ducts
PL-20 - Dimensions
Nominal dimensions PL-20
PL-20-S DN= 100*, 125*, 150,160, 180, 200, 224, 250, 280, 300, 315, 350,
PL-20-F... 355, 400, 500 mm
* Reduced from DN = 150 mm

PL-20-F DN=315, 400, 450, 500, 630 mm


Flange according to DIN 24154 range part 1 (edition 06/90) or EN 12220
A
Standard length PL-20; L min = 400 mm
30
DN

Installation*:
Within rigid walls, the minimum thickness 100 mm
Within light walls, the minimum thickness 100 mm
min. 200 min. 200 Within rigid ceiling plates, the minimum thickness 150 mm
L
PL-20-S...
* Check for installation details in the installation manual
40

PL-20 Dimensions of reduced variants DN 100 and DN 125


DN 100 (DN 125)

20
DN 150

400
495 5

17
FIRE DAMPERS PL-20 INSTALLATION

PL-20/../A2 Types of actuators

8 7 1 2 Manual-spring actuators type PL-20/.../ A2

1. Housing made of galvanised steel sheet, separated


by calcium silicate-heat insulation frame
2. Blade made of calcium silicate and intumescent
5 sealant
3. A2 thermal release link, melting point at 70C
(optional 120C).
4 4. Silicone gasket for cold smoke
A 3
6 5. Spring
6. Release handle
9 7. Limit switch T1 - closed
8. Limit switch T2 - open
9. Revision cover
A2

PL-20//E..

5 1 2 Electric actuators type PL-20/.../E...

1. Housing made of galvanised steel sheet separated


by calcium silicate -heat insulation frame
2. Blade made of calcium silicate and intumescent
A sealant
3. Thermal fuse
4 4. Silicone gasket for cold smoke
3 5. Electric actuator
9. Revision cover
9

Use of wooden supports during the installation Installation


The fire dampers should be installed according to
the designer's project for the fire safety. A fire damper
should not be statically stressed by a building's
structure.

During the installation the wooden supports should


be used (see the picture).

Follow the detailed instructions for installation and


use - as available by our sales employees.

18
FIRE DAMPERS PL-20 INSTALLATION

Installation in a rigid wall Legend:


1. Fire damper PL-20
3 2. Filler
W
2 3. Wall (fire resistant)
K
1 W Wall thickness (mm)
K Distance from a wall on the actuators side (mm)
L Length of a fire damper (mm)
DN Nominal diameter of a fire damper (mm)
s Gap (mm)

A fire damper should be installed in a rigid wall of


qDN

the minimun thickness W = 100 mm into a rectangular


opening, gap s = 100 mm. A wall can be made of
concrete, bricks or aerated bricks. Filler is either
s
conrete or mortar. When mounting, the installation
dimension K = 145 mm at the standard length of a
L fire damper L = 400 mm should be taken into
account.
A position of an actuator is optional in one or the
other fire compartment.

Installation in a rigid ceiling plate Legend:


1. Fire damper PL-20
2. Filler
qDN
3. Ceiling plate (fire resistant)

W Ceiling thickness (mm)


K Distance from a ceiling on the actuators side (mm)
K

L Length of a fire damper (mm)


DN Nominal diameter of a fire damper (mm)
L

s Gap (mm)

A fire damper should be installed in a rigid ceiling


1 2 3 plate of the minimum thickness W = 150 mm, gap
s s = 100 mm. A ceiling plate is made of concrete.
Filler can be either concrete or mortar. When
mounting, the installation dimension K = 145 mm
at the standard length of a fire damper L = 400 mm
should be taken into account.
A position of an actuator is optional in one or the
other fire compartment.

19
FIRE DAMPERS PL-20 INSTALLATION

Installation in a light wall and fixed in a ceiling Legend:


1. Fire damper PL-20
Profile sub construction 2. Filler 2 x 50 mm rock wool plates of density
6 > 130 kg/m3, melting point > 1000C
3. Wall (fire resistant, type W112), fire resistant
3 2
2 UW Profile plasterboard plates 2 x 12,5 mm on each side
4 1 (2+2 plates)
8 9 4. Rock wool thickness 50 mm, density > 50 kg/m3
5. Sleeve OPL-20 Hidria 2 sets
5 6. Steel bars with diameter 12 mm- fixed in a ceiling
7. Intumescent coating Intumex CSP-L, 2 layers
UW / CW
8. Flexible duct compensator

qDN + 2s
Profile
9. Air duct

A fire damper should be installed in a light wall of


7 the minimum thickness W = 100 mm, gap min.
K
s = 100 mm. Necessery fixed in a ceiling by using
s

7 CW Profile
UW Profile
W
qDN + 2s
duct compensators. When mounting, the installation
max 1000 mm max 1000 mm
CW Profile
CW
Profile
dimension K = 145 mm at the standard length of a
fire damper L = 400 mm should be taken into account.
a=<625 mm a=<625 mm A position of an actuator is optional, in one or the
other fire compartment.
7 7
2
3
4

Direct installation fixed in a light wall and with a cover frame Legend:
1. Fire damper PL-20
2. Filler 2 x 50 mm rock wool plates of density
Profile sub construction > 130 kg/m3, melting point > 1000C
3. Wall (fire resistant, type W112), fire resistant
3 plasterboard plates 2 x 12,5 mm on each side
(2+2 plates)
min. 80 mm

4 2
UW Profile
4. Rock wool 50 mm density > 50 kg/m3
5 A 2 5. Clip angles PKL-20
8 6. Cover frame fire resistant plasterboard plates
1
2 x 12,5 mm, on each side (2+2 plates)
7. Intumescent coating Intumex CSP-L, 2 layers,
(100 mm on a blade, 40 mm on a cover frame)
UW / CW 8. Air duct
qDN + 2s

Profile

A fire damper should be installed in a light wall of


the minimum thickness W = 100 mm, gap min.
6 7 s = 100 mm. Necessery fixed in a ceiling by using
K UW Profile duct compensators. When mounting, the installation
s

W CW Profile
dimension K = 145 mm at the standard length of a
qDN + 2s
CW Profile
fire damper L = 400 mm should be taken into account.
A 4
CW Profile
A position of an actuator is optional, in one or the
6
other fire compartment.
5 2 a=<625 mm a=<625 mm

7 7

20
FIRE DAMPERS PL-20 INSTALLATION

Permitted installation positions of the fire dampers


When mounting, a blade axis and actuator position
is oriented optionally from horizontal to vertical
position.

Installation in a wall without connection ducts Legend:


1. Fire damper PL-20
2. Partition wall (100 mm, rigid or light see ways
4 3 2 1 5 4 3 2 1
of installation for each type) or a concrete ceiling
of 150 mm
3. Optional extension (required for DN > L)
4. Protection grille PG
5. Air duct

A fire damper can be installed in a fire resistant


partition wall without connection ducts or with a
3 4 duct on one side and a protection grille on a free wall.
2 10 2
4
2
10
2

Maintenance and inspection:


The fire dampers should be maintained and inspected twice a year. If two successive inspections show no errors, it is sufficient to perform further examinations
only once a year. Maintenance and inspection should only be carried out by authorized service.

WARNING
A standard type of the fire dampers PL-20 are not allowed to be installed in the explosion hazardous places. Neither are they allowed to be installed in the ventilation
devices which exhaust mixture of air and explosive gases. In such cases, special explosion-proof fire dampers should be installed. Neither are the standard fire
dampers PL-20 suitable for dusty ambients.

21
FIRE DAMPERS PL-20 ORDERING KEY

Ordering key:

Dimensions:
DN Nominal diameter v mm

Installation accessories:
OPL-20 Installation clamps lightweight installation, light wall*
PKL-20 Brackets direct installation, light wall*

Accessories:
T1 Limit switch closed
T2 Limit switch open
T12 Limit switch (2 pcs) closed,open
DO Junction box (option for electric actuators, designation E)

Actuators:
E5 Electric actuator Belimo BF 24-T
E6 Electric actuator Belimo BF 230-T
E9 Electric actuator Belimo BF 24-T-ST + BKN 230-24
E15 Electric actuator Belimo BLF-24 T **
E16 Electric actuator Belimo BLF-230 T **
E19 Electric actuator Belimo BLF 24-T-ST + BKN 230-24 **
A2 Spring/manual actuator advanced thermal release link 70C, thermal link replaceable from the outside

Types of the fire dampers:


PL-20-F Circular fire damper with flange classification EI 90-S
PL-20-S Circular fire damper for spiral ducts- classification EI 90-S

Electric actuators variants E. are equipped with limit switches, additional limit switches (T1, T2, T12) are not applicable. Standard release temperature of
the electric actuator is 72C.
For increased temperatures in the ducts the non-standard release temperatures are available, 120C for manual actuators and 95C for electric actuators
respectively.
Additional protection grilles PG and adjusting are available upon request.
* Check the required accessories and materials concerning the type of installation for details see the manual for installation and application.
** Electric actuators type E15, E16, E19 can be used only for the dimension range DN=150-500 mm.

22
FIRE DAMPERS PL-20

Text for a project list:


The circular fire dampers for separation of fire compartments in ventilation and air conditioning systems, resistant to fire and cold smoke, fire resistance
EI 90-S according to EN 13501-3, tested according to EN 1366-2.
Construction characteristics: the fire dampers PL-20 consist of a blade of calcium silicate, intumescent sealant and thermal release mechanism with the
release temperature 70C A housing of galvanised steel sheet is separated by a calcium silicate heat insulated frame. A silicon profile gasket makes the fire
dampers PL-20 also resistant to cold smoke.
Installation in a rigid or light wall of the minimum thickness 100 mm or in a rigid ceiling plate of the minimum thickness 150 mm, according to the manufacturer's
instructions.

Manufacturer:
Type:

Ordering example:
Manufacturer:
Type:
Quantity:___pcs

23
The right for technical changes reserved.

24
Production: Hidria IMP Klima d.o.o., Layout: Grafi~ni studio K, d.o.o., Print: Grafika So~a, June 2010