2/10/2016

Good morning,
MV line 1 was disconnected by CEZ at 07:30 AM .
The MV line was connected at 07:50 AM and at 07:55 AM all the inverters were
started to work properly .

Good morning,
MV line 1 it was disconnected again by CEZ at 09:55 AM .
The MV line was reconnected at 10:06 AM and at 10:11 AM all the inverters we
re started to work properly .
Best regards.

Good afternoon,
At 13:31 the inverter 1.3.1 it stopped few times with the alarm High frequency .
Every time when started to work it produced active power (-25 KW ) and reac
tive power (583 KVar).
After one general reset , the inverter starts to working well at 13:55 .

4/10/2016
Good afternoon,
MV line 2 was disconnected by CEZ at 14:31 .
The MV line was connected at 14:57 and at 15:02 all the inverters have start
ed to work properly .

5/10/2016
Good afternoon,
Between hours 10:27 - 12:06 the CEZ it made an intervention at PC1 to check the
measure group .This is the reason that the MV line 1 was disconnected.

Good afternoon,
All the inverters from line 2 were stopped two time with the error Asymmetry
of grid currents and voltage:
- First time the inverters were stopped between the hours 12:16 12 :21 ;
- Second time the inverters were stopped between the hours 12:27 12 :36;
All the inverters have made an automatic reset.

6/10/2016
Good morning,
MV line 1 it was disconnected by CEZ at 08:04 AM .
The MV line was connected at 08:21 AM and all the inverters have started to w
ork properly at 08: 26 AM .

Best regards.
6/10/2016
Good afternoon,
At 15:08 the MV line was disconnected by CEZ . The error displayed on the F650
protection relay was High Voltage and MIN/ MAX Frequency.
At 15: 26 after I connected MV line 1 some equipments doesn't work in the m
onitoring system.
After checks made I found burned at:
- CT 1.1 - timer relay from the reactive box : Schneider elect
ric model RE17RBMU;
- CT 1.2 - arrester cartridge from communication box (Isotrol
box): model : DEHNguard DG MOD 275 ;
- CT 1.3 - arrester cartridge and power supply from communication
box (Isotrol box): model :DEHNguard DG MOD 275 and power supply Phoenix Co
ntact model STEP-PS/1A/24/1,75;
- At string boxes 1.1.07, 1.2.04, 1.2.05, 1.2.06, 1.2.07, 1.3.08,
1.3.10 , 1.3.18 we found burned the power supply : Mean Well , model: RS-25-48
, 48V/0.57 A.
All the inverters started to work properly at 15 :37.

8/10/2016
Good afternoon,
At 12:53 the MV line was disconnected by CEZ . The error displayed on the F65
0 protection relay was High Voltage and MIN/ MAX Frequency.
At 13: 08 after I connected MV line 1 some equipments doesn't work in the m
onitoring system.
After checks made I found burned at:
- CT 1.1 - timer relay from the reactive box : Schneider elect
ric model RE17RMMU;
- CT 1.2 - power supply from communication box (Isotrol box):
Phoenix Contact model STEP-PS/1A/24/1,75 ;
- CT 1.3 - arrester cartridge and power supply from communication
box (Isotrol box): model DEHNguard DG MOD 275 and power supply Mean Well
MDR -60 -24 , 24V/2.5A;
- At string boxes 1.1.06, 1.2.05, 1.2.07 we found burned the pow
er supply : Mean Well , model: RS-25-48 , 48V/0.57 A.
We changed at CT1.2 and CT 1.3 the equipments that was burned.
All the inverters started to work properly at 13 :30.
9/10/2016
Good afternoon,
MV line 1 was two time disconnected by High voltage:
- First time the line it was disconnected between hours : 16:55 - 17: 2
1 .
- Second time the line it was disconnected between hours : 17:35 - 17:55
.

Best regards,
Ionel Constantin
11/10/2016
Good morning,
MV line 1 it was disconnected by CEZ at 09:00 AM .
The line was connected at 09:42 AM and all the inverters have started to wor
k properly at 09:46 AM.
Good afternoon,
The MV line 2 was disconnected by CEZ at 13:20 .
I spoke with the dispatcher from Monsson and said that CEZ has an fault on lin
e OHL 20 KV Caracal Porcine1 ( earthing fault ).
Now the MV line is still without voltage.
Also yesterday I connected two times the MV breaker only to check the medium
voltage detector because I had the tension only at two phases
. The problem was from CEZ not at medium voltage detector .
Good morning,
MV line 2 it was reconnected today at 07:50 AM.
Only yesterday the production it was affected ( between hours : 13 :20 - 18:
00 ).
12.10.2016
Good afternoon,
MV line 2 it was disconnected by CEZ at 13:00 .
The line was connected at 13:23 and all the inverters from line 2 have star
ted to work properly at 13:27 .
Good afternoon,
MV line 1 it was disconnected by CEZ at 17:21 .
The line was connected at 17:37 and all the inverters started to work prope
rly at 17:42 .
Best regards.
13/10/2016
Good afternoon,
MV line 1 it was disconnected by CEZ at 10:46 AM . The alarm displayed on th
e F650 protection relays was High Voltage.
Both MV breakers were connected at 10:54 AM and all the inverters starte
d to work properly at 10:59 AM .
14/10/2016
Good afternoon,
MV line 1 it was disconnected by CEZ at 11:40 AM . The alarm displayed on th
e F650 protection relays was High Voltage.
Both MV breakers were connected at 12:08 PM and all the inverters starte
d to work properly at 12:12 PM.
15/10/2016
Good morning,
MV line 1 it was disconnected by CEZ at 09:32 AM . The alarm displayed on th
e F650 protection relays was High Voltage and df/dt.
The MV breaker from connection point no1 was connected at 09:52 AM and
all the inverters started to work properly at 09:57 AM.
The MV line 1 it was disconnected by CEZ at 10:40 AM . The alarm displayed o
n the F650 protection relay was Max/Min frequency.
The MV breaker from connection point no1 was reconnected at 10:57 AM and a
ll the inverters started to work properly at 11:02 AM.
19/10/2016
Good afternoon,
MV line 1 it was disconnected by CEZ at 11:31 AM .
The line was connected at 11:49 AM and all the inverters started to work pr
operly at 11:53 AM .