Fire Dampers are required by all building codes to maintain the required fire resistance ratings
of walls, partitions, and floor when they are penetrated by air ducts or other ventilation
openings. One of the basic requirements of building fire protection as required by all building
codes is the compartmentation or division of buildings using fire rating walls, floors, or other
partitioning methods. This compartmentation is intended to contain any fire to the
compartment of the fire origin and thereby minimise damage to property and protect the lives
of people living and/or working in the building. Smoke dampers on the other hand can be
effectively employed to control the spread of smoke or by simply shutting off the circulation
of air and smoke through ducts or ventilation openings or more actively to be applied as part
of an Engineered Smoke Control System'
Supply Fan
Typical Typical
Non-Smoke Fire-Smoke
Zone Zone
+ + - + +
Damper Positioned Damper Positioned
to Create Positive to Create Negative
Pressurisation Pressurisation
Return/Exhaust Fan
Engineered Smoke Control System
Combination Fire Smoke Damper performs the function of both a Fire Damper and
C. a Smoke Damper at a same location. Combination Fire Smoke Dampers must be
SMOKE DAMPERS qualified under UL Standard 555 as a Fire Damper and under UL Standard 555S
as a Smoke Dampers.
2
n Conaire Knowledge Series Papers 14
TM
DAMPER
Selection Process
3
n Conaire Knowledge Series Papers 14
TM
INSTALLATION
When a Fire & Smoke Damper is being installed, it must fit in
the space available with room for wiring or piping. After the
4
n Conaire Knowledge Series Papers 14
TM
SLEEVE THICKNESS
Dampers are supplied with sleeves and actuators from the factory
and can be installed without the need for additional field installed
sleeves.
do not penetrate the No Screw area Rigid 36 in. Maximum width or 16 (1.5 mm)
24 in. maximum height
designated on the damper sleeve.
Rigid over 36 in. width or 14 (2.0 mm)
Damper size and RIGID or BREAKAWAY duct over 24 in. height
to sleeve connections determine the thickness Breakaway 12 in. wide and under 26 (0.46 mm)
(or no duct) 13-30 in. wide 24 (0.6 mm)
of sleeve required. Sleeve gauge or thickness 31-54 in. wide 22 (0.8 mm)
55-84 in. wide 20 (1.0 mm)
also depends on the damper size. Please refer 85 in. wide and over 18 (1.2mm)
next page for UL qualified breakaway sleeve Important Note :
connections. Sleeve thickness must not be less than the gauge of the connecting duct.
5
n Conaire Knowledge Series Papers 14
TM
J. Breakaway joints of the types shown in fig. nos. 1-8 shall have no
more than two no. 10 (4.8 mm dia.) Sheet metal screws on each
DUCT TO SLEEVE side and on the bottom located in the centre of the slip pocket and
CONNECTION shall penetrate both sides of the slip pocket.
Breakaway joints of the types shown in fig. nos. 1-8 are permitted
on the top and on the bottom of horizontal ducts(vertical dampers)
with flat drive slips not exceeding 500 mm in length as shown in
fig. no. 9 on the sides.
1. PLAIN 'S' SLIP 2. HEMMED 'S' SLIP 3. STANDING 'S' SLIP 4. STANDING 'S' SLIP 5. STANDING 'S' SLIP 6. STANDING 'S' SLIP
(LATERNATE BAR) (ANGLE REINFORCED) (BAR REINFORCED)
Clearances of in. per 2 foot of damper width or height are normally required for galvanized steel
dampers, with a minimum of in. and maximum of 1 in. The damper can rest at the bottom of wall.
6
n Conaire Knowledge Series Papers 14
TM
BEFORE 1. Lift damper using sleeve or frame. Do not lift damper using blades or actuators.
INSTALATION 2. Store the dampers in a covered place only.
3. Clean the damper to remove any foreign material especially on critical components.
4. Insulate the damper and actuator from building material such as mortar dust, drywall
dust, firesafing material, paint over spray, etc prior to and after installation.
5. Check the damper and control operation before actual installation.
CAUTION 1. Do not install screws into No Screw Area mentioned on damper sleeves as they may
interfere with unexposed blade linkage and prevent proper movement of damper blades.
2. Always disconnect the power supply before attending to the motorised dampers.
3. Keep clothes, fingers safely outside the damper frame while removing links from spring
return dampers.
4. Suitable access (such that closure device and actuators can be maintained, etc.) must be
provided for damper inspection and servicing. Where it is not possible to achieve
sufficient size access, it will be necessary to install a removable section of duct. (Refer to
NFPA 90A).
5. Refer to the Electrical Connections diagram, while making the connections.
6. All wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70
latest edition, or any other codes that may apply.