INSTALACIONES SANITARIAS

DISTRIBUCION DE AGUA - RAMALES DE SERVICIO


HOJA: DE
OBRA: CALCULO:
NIVEL: FECHA: Mar-11

RAMAL SANITARIO UNIDADES GASTOS DIAMETROLONGITUD DEL TRAMO (mts.) PERDIDA DE CARGA VELOCIDAD
TRAMO PIEZA de gasto Lts./seg. Pulg. NETA EQUIV. TOTAL m/m m.c.a m/seg.

A.CALIE planta alta

1, 2 1 lam 0.75 0.30 1.4 0.42 1.82

2 ,3 1lm ,1du 2.25 0.30 0.5 0.15 0.65

3 , 4 1lm ,1du 2.25 0.30 3 0.9 3.9

planta baja

5,6 1 lam 0.75 0.30 1.4 0.42 1.82

6, 4 1lm ,1du 2.25 0.30 0.5 0.15 0.65

4, 7 2lm ,2du, 4.5 0.30 2 0.6 2.6

7 , 8 2lm,2du,1lv 7.5 0.49 0.5 0.15 0.65

8 , 9 2lm,2du,1lv,1bat 9.5 0.57 1.5 0.45 1.95

10 , 9 1freg 2 0.30 1 0.3 1.3

9 , 11 2lm,2du,1lv,1bat,1fre 11.5 0.66 2 0.6 2.6

12 , 13 2lm,2du,1lv,1bat,1fre 11.5 0.66 2 0.6 2.6

A. FRIA

14 , 13 1freg 2 0.3 1 0.3 1.3

13 , 15 2lm,2du,1lv,1bat,2fre 13.5 0.7 0.7 0.21 0.91

16 , 17 1 lv 3 0.30 0.5 0.15 0.65

17 , 15 1lv, 1bat 5 0.36 0.6 0.18 0.78

15 , 18 2lm,2du,2lv,2bat,2fre 18.5 0.89 0.5 0.15 0.65

A.FRIA planta alta

21 , 22 1 lam 0.75 0.30 1.4 0.42 1.82

22 , 23 1lm, 1wc 3.75 0.30 0.5 0.15 0.65

23 , 24 1lm, 1wc, 1du 5.25 0.5 0.15 0.65

24 , 20 1lm, 1wc, 1du 5.25 0.42 3 0.9 3.9

planta baja

25 , 26 1 lam 0.75 0.30 1.4 0.42 1.82

26 , 27 1lm, 1wc 3.75 0.30 0.5 0.15 0.65

27 , 20 1lm, 1wc, 1du 5.25 0.42 0.5 0.15 0.65

20 , 19 2lm, 2wc, 2du 10.5 0.63 0.5 0.15 0.65

19 , 18 2lm, 2wc, 2du 10.5 0.63 3 0.9 3.9


18 , A 4lm,4du,4lv,2bat,2fre 29 1.26 2 2 0.6 2.6