You are on page 1of 1

Job No : GSP-350

Job Name : CEL Noida


Dated : 29.12.14

Heat Dessipiation
Temp. Degree C

Temp. Degree F
Floor Area(sqft)

Light (W/sqft)

CFM / Person

By Pass factor
from Eq Load

Fresh air cfm


CFM /SQFT

Fan Capacity

Working Qty
Type of Unit
Floor Above
Floor Below
Description

Dehu.CFM

Equipment
Occupancy

CFM /Sqft
considered

considered
Sheet No.

Total TR

Total Kw
Selection
Sqft/TR

Unit TR
Phase
RH%

(kw)
S.no

TR
+1

Non Insulated 8 x 3TR /1000CFM


1 1 Seating 2292 24 75 55 1 40 6 5.0 0.06 0.314 338 174 3.3 7584 7922 13.2 CST 1 8 3.0 24
A/C Roof Cassette Units 32.4
Non Insulated
2 2 Cabin-01 91 24 75 55 1 3 0 5.0 0.06 0.314 20 163 3.2 293 314 0.6 1TR Split Unit Split 1 1 1.0 1
A/C Roof 1.35
Non Insulated
3 3 Cabin-02 91 24 75 55 1 3 0 5.0 0.06 0.314 20 163 3.2 293 314 0.6 1TR Split Unit Split 1 1 1.0 1
A/C Roof 1.35
Non Insulated
4 4 Cabin-03 91 24 75 55 1 3 0 5 0.06 0.314 20 163 3.2 293 314 0.6 1TR Split Unit Split 1 1 1.0 1
A/C Roof 1.35
Non Insulated
5 5 Cabin-04 91 24 75 55 1 3 0 5 0.06 0.314 20 163 3.2 293 314 0.6 1TR Split Unit Split 1 1 1.0 1
A/C Roof 1.35
Non Insulated
6 6 Cabin-05 91 24 75 55 1 3 0 5 0.06 0.314 20 163 3.2 293 314 0.6 1TR Split Unit Split 1 1 1.0 1
A/C Roof 1.35
Non Insulated
8 7 Cabin-06 91 24 75 55 1 3 0 5 0.06 0.314 20 163 3.2 293 314 0.6 1TR Split Unit Split 1 1 1.0 1
A/C Roof 1.35
Non Insulated
9 8 GM Cabin 226 24 75 55 1 5 1 5 0.06 0.314 39 180 3.1 710 748 1.3 2TR Split Unit Split 1 1 2.0 2
A/C Roof 2.7
Non Insulated
10 9 Caf 355 24 75 50 1 28 1 5 0.06 0.314 161 117 3.9 1380 1542 3.0 2x2.0TR Split Unit Split 1 2 2.0 4
A/C Roof 5.4
Non Insulated
11 10 Confrence 215 24 75 50 1 12 1 5 0.06 0.314 73 122 4.2 896 968 1.8 2TR Split Unit Split 1 1 2.0 2
A/C Roof 2.7
Meeting Non Insulated
12 11 97 24 75 50 1 6 0 5 0.06 0.314 36 138 3.4 328 363 0.7 1.5TR Split Unit Split 1 1 1.5 2
Room A/C Roof 2.025
Non Insulated
12 12 GM 258 24 75 50 1 7 1 5 0.06 0.314 50 177 3.1 799 849 1.5 2TR Split Unit Split 1 1 2.0 2
A/C Roof 2.7
Non Insulated
12 13 Cabin 70 24 75 50 1 3 0 5 0.06 0.314 19 124 4.4 305 324 0.6 1TR Split Unit Split 1 1 1.0 1
A/C Roof 1.35
Non Insulated
12 14 Cabin 70 24 75 50 1 3 0 5 0.06 0.314 19 124 4.4 305 324 0.6 1TR Split Unit Split 1 1 1.0 1
A/C Roof 1.35
Non Insulated
12 15 Cabin 70 24 75 50 1 3 0 5 0.06 0.314 19 124 4.4 305 324 0.6 1TR Split Unit Split 1 1 1.0 1
A/C Roof 1.35
Non Insulated
12 16 Cabin 70 24 75 50 1 3 0 5 0.06 0.314 19 124 4.4 305 324 0.6 1TR Split Unit Split 1 1 1.0 1
A/C Roof 1.35
Qc Staff & Non Insulated
12 17 247 24 75 50 1 9 1 5 0.06 0.314 60 117 4.8 1190 1250 2.1 2x1.5TR Split Unit Split 1 2 1.5 3
Lab A/C Roof 4.05

Non Insulated 3 x 3TR /1000CFM


12 18 Seating 775 24 75 50 1 18 3 5 0.06 0.314 136 176 3.2 2469 2605 4.4 CST 1 3 3.0 9
A/C Roof Cassette Units
12.15
Total 5294 155 15 1093 18335 19427 34 29 58 78