The SF1EL is a 26 mm wide, surface mounted earth leakage circuit breaker with a switched neutral and an additional 50 cm neutral
cable attached. It is applied in commercial and industrial applications.
SF1EL
Surface Mount
Features Applications
Hydraulic-magnetic technology Mining, heavy industrial and commercial applications
100% rating capability, independent of ambient temperature requiring high sensitivity earth leakage protection from
AS/NZS 3111 and AS/NZS 3190 compliant electrical shock and fire hazards
Compact width 26 mm Telecom / datacom equipment
Operating voltage 240 V AC single pole Lighting control
Immune to pulsating DC load current UPS equipment
Ratings 6 to 40 A Alternative energy equipment
Earth leakage sensitivity 10 mA or 30 mA Mobile power generation equipment
Single pole plus switched neutral earth leakage protection Railway signalling and infrastructure
Additional neutral wire
Precision tripping characteristics
Trip indication with mid-trip position
Reset immediately after overload
Suitable to use for electrical isolation
Shell design permits easier installation onto busbar
Medium
S Current Sensitivity Voltage No special
Requirement Type F 1 pole + N Overload No auxiliary delay
Frame rating 40 A 30 mA 240 V AC termination
curve 2
1500
OPERATING
CHARACTERISTICS
10000
CURVE 1
1000
100
Tripping Time (Seconds)
10
0.1
Maximum
0.01
Minimum
0.001
1000
100
105
130
150
200
300
400
500
1500
2000
2500
3000
4000
5000
% Rated Current
100000
1500
OPERATING
CHARACTERISTICS
10000
CURVE 2
1000
100
Tripping Time (Seconds)
10
0.1
Maximum
0.01
Minimum
0.001
100
1000
105
130
150
200
300
400
500
1500
2000
2500
3000
4000
5000
% Rated Current
100000
1500
OPERATING
CHARACTERISTICS
10000
CURVE 3
1000
100
Tripping Time (Seconds)
10
0.1
Maximum
0.01
Minimum
0.001
100
1000
105
130
150
200
300
400
500
1500
2000
2500
3000
4000
5000
% Rated Current
* The published time delay curves are generated at 30oC ambient temperature with the Circuit Breaker mounted in the up-right position. The must hold, must trip and instantaneous
trip current values are not affected by temperature, although delay time for the other operating current values may have to be adjusted using the temperature compensation curve which
is available on request.