Technical Data Bulletin

TS 30198

Main to Reserve Transfer Station

The Main to Reserve Transfer Station is supplied


with the following standard features:

C Installs quickly
C Helps prevent accidental discharge
of reserve cylinder bank
C Fits standard single gang electrical boxes
C UL listed

Description

The Chemetron Fire Systems Abort Station is a ARCHITECT/ENGINEER SPECIFICATIONS


manually-activated, electric device designed to let the A Chemetron Fire Systems Main to Reserve
user switch the fire suppression system to its reserve Transfer Station, stock number 20100145, shall be pro-
cylinders until the primary cylinders are back in place vided. It shall be used to switch the suppression sys-
and operating normally. Its distinctive appearance and tem from the main agent supply to the reserve, back-
operation make it easy to differentiate from other types up supply.
of system controls. Operating instructions shall be in raised letters,
Normally mounted near the suppression agent stor- stamped into the faceplate. The raised letters shall be
age location, the transfer station is operated by pulling silkscreened in a contrasting color.
the protective pin, which breaks the seal and allows The unit shall consist of a two-pole switch that shall
the toggle switch to be pushed into the Reserve accommodate two independently supervised releasing
position. The toggle switch has a double-pole, double- solenoids. The switch shall be fitted with a protective
throw contact arrangement for two independently guard and pin with a seal to prevent misuse or
supervised releasing solenoids. tampering. To guard against locking out all actuators,
The faceplate is constructed of formed steel and the switch shall have no middle position.
painted red. For permanence, all operating instructions
are in raised letters, stamped into the faceplate. For
added clarity, the letters are silkscreened in a contrast-
ing color. Instructions are arranged in an easy-to-read
format. A back box is available for surface-mounted
installations.

Ordering Information

Shipping Weight
Stock Number Description lbs (kg)
20100145 Main to Reserve Transfer Station .5 (.23)
30100207 Back Box for Surface Mounting .5 (.23)
Technical Data Bulletin
TS 30198

Distributed by
The seller makes no warranties, express or implied,
including, but not limited to, the implied warranties of
merchantability and fitness for a particular purpose, except
as expressly stated in seller's sales contract or sales
acknowledgment form.

4801 Southwick Drive, 3rd Floor


Matteson, IL 60443
708/748-1503
Fax 708/748-2847

1998 Chemetron Fire Systems. All rights reserved (3/98). Chemetron Fire Systems is a registered trademark.