EA0436R1
Description The Flowrite EA 599 Series SQX electronic valve actuator requires a 24 Vac supply
and receives a 0 to 10 Vdc or a 4 to 20 mA control signal to proportionally control a
valve. This actuator is designed to work with Flowrite VF 599 Series Siemens Building
Technologies standard valves with a 3/4-inch (20 mm) stroke.
Application These electronic actuators are designed to be used with Flowrite VF 599 Series valves
and Siemens Building Technologies standard valves with 3/4-inch (20 mm) stroke in
liquid service and steam service applications. They are particularly recommended for
installations requiring quick response and good rangeability.
EA0853R1
SQX
Details
MANUAL
OVERRIDE
KNOB
STEM
RETAINER STEM
POSITION
INDICATOR
STEM
RETAINER
SCREWS (2)
YOKE
SCREW
ACTUATOR
(2)
YOKE
EA0398R1
LOCK SCREW
NOTE: When power is first applied or restored after a power failure, the actuator stem
automatically moves to establish the selected stroke intercept point.
For a Normally Closed or three-way mixing valve (with stem up to close the control
port), the actuator moves to the factory set "0" position. The actuator runs on a pre-
programmed slope until the first time it reaches a mechanical stop at fully open. At
this point, the microprocessor calibrates a new slope determined by the actual
stroke. The slope and intercept now correspond to the actual valve stroke of 0 to 10
Vdc.
For a factory assembled Normally Open valve, the actuator moves to the 1 position.
See Start-Up to confirm this position. The actuator runs on a pre-programmed slope
until the first time it reaches a mechanical stop at fully open. At this point, the
microprocessor calibrates a new slope determined by the actual stroke. The slope
and intercept now correspond to the actual valve stroke of 0 to 10 Vdc. When power
is turned off or in the event of a power failure, the actuator maintains its position.
0 10 Vdc
4 20 mA
0
STROKE
EA0438R1
EA0439R1
1 A B
Figure 6.
Figure 5.
The control signal moves the actuator stem
outward and inward.
3/4 in.
(20mm)
EA0426R1
Speed Control To avoid overheating the stepper motor, the microprocessor will switch from full speed to
step and rest mode (a small step and approximately one-second rest).
Position Indication The actuator position indicated by the position output signal U is calculated by counting
motor steps. For this reason, the actuator runs to the 0 (for NC) or 1 (for NO) position
when the current is switched on to establish the selected intercept point.
After a manual override operation, the position indication may be inaccurate. Command
the actuator to the 0 (for NC) or 1 (for NO) position to reset the intercept value and
recalibrate the position feedback signal.
Manual Operation
PR
ES
S
EA0424R1
Press and turn the manual override knob for manual operation. Clockwise moves the
stem retainer toward 0; counterclockwise moves the stem retainer towards 1.
If a signal is sent to the actuator, while the manual override knob is pressed down, the
stem retainer will not move and the position feedback signal will not be accurate.
Automatic operation The actuator will return to automatic operation when the manual override knob is
released. The position indication may be inaccurate. Command the actuator to the 0 (for
NC) or 1 (for NO) position to reset the intercept value.
The vertical position is the recommended position for mounting. Figure 9 shows the
acceptable mounting positions.
Allow four inches (100 mm) around the sides and back of the actuator and eight inches
(200 mm) above and to the front of the actuator. This service envelope is the minimum
space required to access and service the actuator. See Figure 20 for actuator
dimensions and the recommended service envelope.
Detailed installation instructions for field mounting are shipped with the actuator.
2
ON
ON
EA0475R1
1
Intercept @1 @0 @1 @0
The factory set position of OFF is appropriate for Normally Closed or three-way mixing
valves with stem up to close the control port.
Select the ON position for a Normally Open valve with stem up to open the control port.
Switch 2: Characteristic
Do not change the characteristic switch. It is factory set at OFF. The proper flow
characteristic is designed into the Flowrite 599 series valve.
NOTE: Set the actuator switches as specified. These switches do not reverse the
action from NO to NC or vice versa. The valve body assembly determines the
complete assembly action.
Normally Closed Valve Increasing the control signal moves the stem retainer outward (0 to 1): Valve opens.
Decreasing the control signal moves the stem retainer inward (1 to 0): Valve closes.
Normally Open Valve Increasing the control signal moves the stem retainer outward (0 to 1): Valve closes.
Decreasing the control signal moves the stem retainer inward (1 to 0): Valve opens.
Three Way Valve Increasing the control signal moves the stem retainer outward (0 to 1): Valve opens
between port NC and C.
Decreasing the control signal moves the stem retainer inward (1 to 0): Valve opens
between ports NO and C.
Wiring Do not use auto transformers. Use earth ground isolating step-down Class 2 power
supplies.
The maximum rating for Class 2 step-down transformer is 100 VA. Since the SQX62U
actuator requires 18 VA, one transformer can power a maximum of five actuators.
Operating more than five SQX62U actuators requires additional transformers or separate
100 VA power supplies.
EA0153R1
Figure 11. Connecting Terminals.
G, G0 Operating voltage 24 Vac
G System Potential (SP)
G0 System Neutral (SN)
Y Control input 0 to 10 Vdc
R Input for 4 to 20 mA
M Measuring neutral
U Output for 0 to 10 Vdc or 4 to 20 mA measuring voltage (matches the
input signal)
Y(1,2,3) I Y G0
I
I
N1 R1 P1 K1
24V~
G Y R M U
EA0444R1
G0 Y1
SN
The diagram shows all possible connections. The application determines which
connections are used.
Wiring Diagrams,
Continued
Figure 13. Wiring to Point Termination Modules PTM6.2Y10S and PTM6.2U10 with 0 to 10 Vdc Signal.
HOT
NEUT
1 2 3 4
G G0
5 6 7 8
2 1 2Y 420
U R M Y
CAUTION:
Modules must be in the
same field panel.
U R M Y
1 2 3 4
5 6 7 8
2 1 2I 420
G G0
NEUT
HOT
Figure 14. Wiring to Point Termination Modules PTM6.2Y420 and PTM6.2I420 with 4 to 20 mA Signal.
+
+ Y R
MAX 10 DEVICES PER AOV
-
- GO M
R
R
R
M
M
M
G U
U
U
U
+ Y Y Y + Y R
-
GO
GO
GO
- GO M
MAX
100 VA
G G G G U
MAX 100 VA
+
+ Y R
- - GO M
G U
24
24
NEUT NEUT
AO V BOARD VAC AO V BOARD VAC
EA0168R1
ISOLATING CLASS 2
POWER
TRANSFORMER FOR
TRANSFORMER FOR
24 VAC POWER 24 VAC POWER
Figure 15. SCU Wiring Diagram for SQX in Series with Figure 16. SCU Wiring Diagram for SQX in
0 to 10 Vdc Signal. Parallel with 0 to 10 Vdc Signal.
Accessories G (SP) 1
G Y
24V~ 20W
EA0184R1
G0 Y9
EA0480R1
GO (SN) 2
Figure 17. Packing Heating Element Figure 18. Manual High Signal Selection
599-00417. Unit FZA61.11.
Troubleshooting Check that the wires are connected correctly and attached securely.
If the actuator moves erratically in very small steps, check that it is receiving adequate
power.
Dimensions 11-1/4
(285)
8-13/16
(224)
4-13/16
4-13/16
(122) (122)
2-9/16
(65)
4-1/2
(114)
1-15/16
9-3/8
(49)
(232)
12-7/8
(327)
3/4
(19)
EA0854R1
5
(126)
KNOCKOUTS (3)
FOR STANDARD
8 - 7/8
1/2" CONDUIT
(226) CONNECTOR
EAO399R1
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners.
2001 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc. Your feedback is important to us. If you have Document No. 155-182P25
Landis & Staefa Division comments about this document, please send Printed in the U.S.A.
1000 Deerfield Parkway them to technical.editor@sbt.siemens.com Page 11
Buffalo Grove, IL 60089-4513
U.S.A.
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. 2000 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc. Your feedback is important to us. If you have Document No. 155-182P25
Landis & Staefa Division comments about this document, please send Printed in the U.S.A.
1000 Deerfield Parkway them to technical.editor@sbt.siemens.com Page 12
Buffalo Grove, IL 60089-4513
U.S.A.