ANALISIS SISMICO

INDICE
1. GENERALIDADES ......................................................................................................................... 2
1.1. OBJETIVOS DEL TRABAJO: ................................................................................................. 2
1.2. ANTECEDENTES Y JUSTIFICACION .................................................................................. 2
2. MARCO TEORICO.......................................................................................................................... 2
2.1. LOS PRINCIPIOS DE LA SISMO RESISTENCIA ................................................................ 3
2.2. E-030: DISEO SISMO RESISTENTE 2015 .......................................................................... 4
2.3. ZONIFICACION ....................................................................................................................... 4
2.4. CATEGORA DE LAS EDIFICACIONES .............................................................................. 5
2.5. SISTEMAS ESTRUCTURALES.............................................................................................. 7
2.6. DESPLAZAMIENTOS LATERALES PERMISIBLES .......................................................... 9
3. DESCRIPCION DE LA ZONA EN ESTUDIO ............................................................................... 9
3.1. UBICACIN ............................................................................................................................. 9
3.2. SUELOS .................................................................................................................................... 9
4. ANALISIS ESTATICO .................................................................................................................. 10
4.1. PESO DE LA ESTRUCTURA................................................................................................ 10
4.2. FACTOR DE AMPLIFICACION SISMICA Y PERIODO FUNDAMENTAL .................... 11
4.3. FUERZA CORTANTE EN LA BASE ................................................................................... 12
4.4. DISTRIBUCION DE FUERZA CORTANTE EN ELEVACION.......................................... 13
5. ANALISIS DINAMICO MODAL ESPECTRAL .......................................................................... 22
5.1. DESCRIPCIN ....................................................................................................................... 22
5.2. PROPIEDADES MECNICAS DE LOS MATERIALES .................................................... 22
5.3. NORMATIVIDAD:................................................................................................................. 22
5.4. ANLISIS SSMICO .............................................................................................................. 22
5.5. ESPECTRO DE PSEUDO ACELERACION ......................................................................... 23
6. RESULTADOS............................................................................................................................... 25
6.1. PERIODOS Y MODOS DE VIBRACIN ............................................................................. 26
6.2. DESPLAZAMIENTOS Y DISTORSIONES DE ENTREPISO ............................................. 29
7. CONCLUSIONES Y RECOMENDACIONES ............................................................................. 32

DISEO SISMO RESISTENTE 1


ANALISIS SISMICO

1. GENERALIDADES

La presente Memoria corresponde al anlisis ssmico esttico y dinmico PUESTO


POLICIAL, edificacin conformada por 5 niveles con azotea y dos niveles de stano; con
ubicacin en distrito de Castrovirreyna, provincia de Huancavelica, departamento Huancavelica.

1.1. OBJETIVOS DEL TRABAJO:

Mediante la aplicacin de la PROYECTO DE NORMA DISEO


SISMORRESISTENTE NORMA E-030 2015 y haciendo uso del programa Autodesk
Robot Structural Vs. 2015, se realizar el anlisis esttico y dinmico de una edificacin
de concreto armado con sistema aporticado.

Se comparar los resultados de Desplazamientos, distorsiones y fuerzas de corte para el


anlisis esttico, dinmico modal espectral y dinmico tempo historia.

1.2. ANTECEDENTES Y JUSTIFICACION

Autodesk Robot Structural 2015 posee una poderosa e intuitiva interfaz grfica con
procedimientos de modelaje, anlisis, todos integrados usando una base de datos comn.
Aunque es fcil y sencillo para estructuras simples, Autodesk Robot Structural
2015 tambin puede manejar grandes y complejos modelos de edificios, incluyendo un
amplio rango de comportamientos no lineales, hacindolo la herramienta predilecta para
ingenieros estructurales en la industria de la construccin.

2. MARCO TEORICO

DISEO SISMO RESISTENTE 2


ANALISIS SISMICO

2.1. LOS PRINCIPIOS DE LA SISMO RESISTENCIA

Forma regular
La geometra de la edificacin debe ser sencilla en planta y en elevacin. Las formas
complejas, irregulares o asimtricas causan un mal comportamiento cuando la edificacin es
sacudida por un sismo. Una geometra irregular favorece que la estructura sufra torsin o que
intente girar en forma desordenada. La falta de uniformidad facilita que en algunas esquinas
se presenten intensas concentraciones de fuerza, que pueden ser difciles de resistir.

Bajo Peso
Entre ms liviana sea la edificacin menor ser la fuerza que tendr que soportar cuando
ocurre un terremoto. Grandes masas o pesos se mueven con mayor severidad al ser sacudidas
por un sismo y, por lo tanto, la exigencia de la fuerza actuante ser mayor sobre los
componentes de la edificacin. Cuando la cubierta de una edificacin es muy pesada, por
ejemplo, esta se mover como un pndulo invertido causando esfuerzos tensiones muy
severas en los elementos sobre los cuales esta soportada.

Mayor rigidez
Es deseable que la estructura se deforme poco cuando se mueve ante la accin de un sismo.
Una estructura flexible o poco slida al deformarse exageradamente favorece que se presenten
danos en paredes o divisiones no estructurales, acabados arquitectnicos e instalaciones que
usualmente son elementos frgiles que no soportan mayores distorsiones.

Buena estabilidad

Las edificaciones deben ser firmes y conservar el equilibrio cuando son sometidas a las
vibraciones de un terremoto.

DISEO SISMO RESISTENTE 3


ANALISIS SISMICO

Estructuras poco slidas e inestables se pueden volcar o deslizar en caso de una cimentacin
deficiente. La falta de estabilidad y rigidez favorece que edificaciones vecinas se golpeen en
forma perjudicial si no existe una suficiente separacin entre ellas.

Suelo firme y buena cimentacin


La cimentacin debe ser competente para trasmitir con seguridad el peso de la edificacin al
suelo. Tambin, es deseable que el material del suelo sea duro y resistente. Los suelos
blandos amplifican las ondas ssmicas y facilitan asentamientos nocivos en la cimentacin
que pueden afectar la estructura y facilitar el dao en caso de sismo.

Estructura apropiada
Para que una edificacin soporte un terremoto su estructura debe ser slida, simtrica,
uniforme, continua o bien conectada. Cambios bruscos de sus dimensiones, de su rigidez,
falta de continuidad, una configuracin estructural desordenada o voladizos excesivos
facilitan la concentracin de fuerzas nocivas, torsiones y deformaciones que pueden causar
graves daos o el colapso de la edificacin.

Fijacin de acabados e instalaciones


Los componentes no estructurales como tabiques divisorios, acabados arquitectnicos,
fachadas, ventanas, e instalaciones deben estar bien adheridos o conectados y no deben
interaccionar con la estructura. Si no estn bien conectados se desprendern fcilmente en
caso de un sismo.

2.2. E-030: DISEO SISMO RESISTENTE 2015

La norma E-030 hace referencia a todo lo relacionado a la normativa existe sobre el diseo
de las estructuras con respecto a movimientos ssmicos y el estudio de los suelos a lo
largo de la geografa de nuestro pas.

2.3. ZONIFICACION

DISEO SISMO RESISTENTE 4


ANALISIS SISMICO

El territorio nacional se considera dividido en cuatro zonas, como se muestra en la Figura.


La zonificacin propuesta se basa en la distribucin espacial de la sismicidad observada,
las caractersticas generales de los movimientos ssmicos y la atenuacin de stos con la
distancia epicentral, dando como resultado que Castrovirreyna se encuentra en la Zona
3, a cada zona se asigna un factor Z=0.35 segn se indica en la Tabla.

FACTORES DE ZONA
ZONA Z
4 0.45
3 0.35
2 0.25
1 0.1

2.4. CATEGORA DE LAS EDIFICACIONES

Cada estructura debe ser clasificada de acuerdo con las categoras indicadas en la Tabla
N 3. El coeficiente de uso e importancia (U), definido en la Tabla N 5 se usar segn la
clasificacin que se haga. En este caso local policial pertenece a categora A Edificaciones
esenciales cuyo factor de uso U=1.5.

DISEO SISMO RESISTENTE 5


ANALISIS SISMICO

DISEO SISMO RESISTENTE 6


ANALISIS SISMICO

2.5. SISTEMAS ESTRUCTURALES

Los sistemas estructurales se clasificarn segn los materiales usados y el sistema de


estructuracin sismo resistente predominante en cada direccin tal como se indica en la
Tabla N6.
Segn la clasificacin que se haga de una edificacin se usar un coeficiente de reduccin
de fuerza ssmica (R). Para el diseo por resistencia ltima las fuerzas ssmicas internas
deben combinarse con factores de carga unitarios. En caso contrario podr usarse como
(R) los valores establecidos en Tabla N6 previa multiplicacin por el factor de carga de
sismo correspondiente.

DISEO SISMO RESISTENTE 7


ANALISIS SISMICO

El sistema escogido es aporticado para la estructura.

DISEO SISMO RESISTENTE 8


ANALISIS SISMICO

2.6. DESPLAZAMIENTOS LATERALES PERMISIBLES

El mximo desplazamiento relativo de entrepiso, calculado segn el Artculo 16 (16.4),


no deber exceder la fraccin de la altura de entrepiso que se indica en la Tabla N 8.

3. DESCRIPCION DE LA ZONA EN ESTUDIO

3.1. UBICACIN

La zona de estudio se encuentra ubicada en:

Regin : Huancavelica
Provincia : Castrovirreyna

3.2. SUELOS

El rea de estudio se encuentra asentado en un suelo de tipo II Ccuya capacidad portante


es 1kg/cm y en su entorno se encuentra una variedad de tipos de suelo.

Tipo II Perfil de suelo tipo S2:Suelos intermedios


Determinamos los parmetros de sitio:

DISEO SISMO RESISTENTE 9


ANALISIS SISMICO

Por lo tanto el valor de:


S=1.15
Tp(s)=0.6
TL(s)=2.0

4. ANALISIS ESTATICO

Se calculara el Corte Esttico con los valores de los parmetros definidos anteriormente, adems
de definir el peso de la Estructura y el Factor de Amplificacin Dinmica (c)

4.1. PESO DE LA ESTRUCTURA

La estructura clasifico como categora A, por lo tanto el peso que se ha considerado para
el anlisis ssmico es el debido a la carga permanente ms el 50 %de la carga viva.

Carga muerta: El valor de las cargas Muertas empleadas comprende el peso propio de los
elementos estructurales ( losas, vigas, columnas, placas, muros, etc.) segn caractersticas
descritas; adems del peso de los elementos aligerados en losas, el peso de la tabiquera y el
peso de los acabados, segn:

Peso de los acabados: 120 Kg/m2

DISEO SISMO RESISTENTE 10


ANALISIS SISMICO

Peso especfico de tabiquera: 210 Kg/m3


Carga Viva: El valor de la carga viva empleada es de 250 kg/m2 del 1 al 10 nivel , y 100
kg/m2 en azotea.

CARGAS SOBRE LA ESTRUCTURA


CARCA MUERTA
Ladrillo de techo
Ladrillo de techo 0.3 x 0.3 x 0.15 peso = 70 kg/m2 = 0.07 T/m2
Tabiquera
Espesor 0.15 m
Altura de muro 2.6 m
Peso de muro por metro lineal
0.15 m x 0.14 kg/m x 2.6 m = 516 kg/m
Peso de la tabiquera segn Norma E 020
Peso tabiquera: Carga equivalente Kg/m2 =210 kg/m2 = 0.21 T/m2
Acabados
Peso acabados = 120 kg/m2 = 0.12 T/m2
Para piso tpicos: 0.07+0.21 +0.12 = 0.4 T/m2
Ultimo nivel: 0.07+ 0.09 + 0.12 = 0.28 T/m2
CARGA VIVA
Local policial= 250 kg/m2 =0.25 T/m
Ultimo nivel = 100 kg/m2 = 0.1 T/m

4.2. FACTOR DE AMPLIFICACION SISMICA Y PERIODO FUNDAMENTAL

Para el clculo del Factor de Amplificacin Ssmica en los Anlisis se consider el


periodo fundamental estimado en la Norma NTE. E030, segn: C=2.5(Tp/T)< 2.5

DISEO SISMO RESISTENTE 11


ANALISIS SISMICO

DONDE:
Ct=45

Por lo tanto T<Tp y C=2.5

T=

4.3. FUERZA CORTANTE EN LA BASE

La Fuerza Cortante en la Base de la Edificacion se determina como una fraccin del peso
total de la edificacin mediante la siguiente expresin:

DISEO SISMO RESISTENTE 12


ANALISIS SISMICO

NORMA E 0.30 2015


Z= ZONA 3 Factor Z= 0.35
U= CATEGORIA C U= 1.5
S= S2 = 1.15
Tp= 0.6
Tl= 2
Ct= 45
hn= 24
T= 0.5333333
Por lo tanto T<TP C= 2.5
COEFICIENTE DE REDUCCION SISMICA R
PORTICOS Ro= 8.00
irregularidad vertical Ia= 1.00
irregularidad vertical Ip= 1.00
porlo tanto R=Ro x Ia x Ip
R x-x= 8.00 eje X
R y-y= 8.00 eje y
CORTANTE BASAL PARA LOS EJES X, Y
Vxx= 0.18867 X P
Vyy= 0.18867 X P

4.4. DISTRIBUCION DE FUERZA CORTANTE EN ELEVACION

Cortante en el Eje X

DISEO SISMO RESISTENTE 13


ANALISIS SISMICO

Cortante en el eje Y

COMPROBACION DE CORTANTES

DISEO SISMO RESISTENTE 14


ANALISIS SISMICO

PESO TOTAL DE LA EDIFICACION


AZOTEA 6TA PLANTA
Peso Unitario Base (m) Ancho (m) Altura (m) Largo (m) superficie Cantidad Peso (tn) CM (tot) Tn
CM (Ton)
Peso de superficie
Losa aligerada XX 0.31 94.22 1.00 29.20758
Losa aligerada YY 0.31 65.23 1.00 20.22068
Tabiqueria 0.09 159.45 1.00 14.35014
Acabados 0.10 159.45 1.00 15.9446
Peso vigas
VP 104 35X45 2.40 0.35 0.45 43.49 1.00 16.43733
VS 106 35X35 2.40 0.35 0.35 13.50 1.00 3.969
VS 107 35X45 2.40 0.35 0.45 6.50 1.00 2.457
VS 108 30X50 2.40 0.30 0.50 19.50 1.00 7.02
VS 109 30X35 2.40 0.30 0.35 4.50 1.00 1.134
Peso columnas
col 2 35x60 2.40 0.35 0.60 3.00 8.00 12.096
col3 35x45 2.40 0.35 0.45 3.00 4.00 4.536 127.37233
CV (Ton)
Sobrecarga 0.10 159.45 1.00 15.9446

PESO TOTAL DE LA EDIFICACION


AZOTEA 5TA PLANTA
Peso Unitario Base (m) Ancho (m) Altura (m) Largo (m) superficie Cantidad Peso (tn) CM (tot) Tn
CM (Ton)
Peso de superficie
Losa aligerada XX 0.31 161.69 1.00 50.12328
Losa aligerada YY 0.31 306.59 1.00 95.04321
Tabiqueria 0.09 468.28 1.00 42.14511
Acabados 0.12 468.28 1.00 56.19348
Peso vigas
VP 103 35X35 2.40 0.35 0.35 49.75 1.00 14.6265
VP 104 35X45 2.40 0.35 0.45 74.63 1.00 28.20825
VS 106 35X35 2.40 0.35 0.35 53.10 1.00 15.6114
VS 107 35X45 2.40 0.35 0.45 13.00 1.00 4.914
VS 108 30X50 2.40 0.30 0.50 26.00 1.00 9.36
VS 109 30X35 2.40 0.30 0.35 26.55 1.00 6.6906
Peso columnas
col 2 35x60 2.40 0.35 0.60 3.00 12.00 18.144
col3 35x45 2.40 0.35 0.45 3.00 14.00 15.876
col5 35x35 2.40 0.35 0.35 3.00 4.00 3.528 360.46383
CV (Ton)
Sobrecarga 0.10 468.28 1.00 46.8279

DISEO SISMO RESISTENTE 15


ANALISIS SISMICO

PESO TOTAL DE LA EDIFICACION


AZOTEA 4TA PLANTA
Peso Unitario Base (m) Ancho (m) Altura (m) Largo (m) superficie Cantidad Peso (tn) CM (tot) Tn
CM (Ton)
Peso de superficie
Losa aligerada XX 0.31 161.69 1.00 50.12328
Losa aligerada YY 0.31 306.59 1.00 95.04321
Tabiqueria 0.21 468.28 1.00 98.33859
Acabados 0.12 468.28 1.00 56.19348
Peso vigas
VP 103 35X35 2.40 0.35 0.35 49.75 1.00 14.6265
VP 104 35X45 2.40 0.35 0.45 74.63 1.00 28.20825
VS 106 35X35 2.40 0.35 0.35 53.10 1.00 15.6114
VS 107 35X45 2.40 0.35 0.45 13.00 1.00 4.914
VS 108 30X50 2.40 0.30 0.50 26.00 1.00 9.36
VS 109 30X35 2.40 0.30 0.35 26.55 1.00 6.6906
Peso columnas
col 2 35x60 2.40 0.35 0.60 3.00 12.00 18.144
col3 35x45 2.40 0.35 0.45 3.00 14.00 15.876
col5 35x35 2.40 0.35 0.35 3.00 4.00 3.528 416.65731
CV (Ton)
Sobrecarga 0.25 468.28 1.00 117.06975

PESO TOTAL DE LA EDIFICACION


AZOTEA 3RA PLANTA
Peso Unitario Base (m) Ancho (m) Altura (m) Largo (m) superficie Cantidad Peso (tn) CM (tot) Tn
CM (Ton)
Peso de superficie
Losa aligerada XX 0.31 161.69 1.00 50.12328
Losa aligerada YY 0.31 306.59 1.00 95.04321
Tabiqueria 0.21 468.28 1.00 98.33859
Acabados 0.12 468.28 1.00 56.19348
Peso vigas
VP 103 35X35 2.40 0.35 0.35 49.75 1.00 14.6265
VP 104 35X45 2.40 0.35 0.45 74.63 1.00 28.20825
VS 106 35X35 2.40 0.35 0.35 53.10 1.00 15.6114
VS 107 35X45 2.40 0.35 0.45 13.00 1.00 4.914
VS 108 30X50 2.40 0.30 0.50 26.00 1.00 9.36
VS 109 30X35 2.40 0.30 0.35 26.55 1.00 6.6906
Peso columnas
col 2 35x60 2.40 0.35 0.60 3.00 12.00 18.144
col3 35x45 2.40 0.35 0.45 3.00 14.00 15.876
col5 35x35 2.40 0.35 0.35 3.00 4.00 3.528 416.65731
CV (Ton)
Sobrecarga 0.25 468.28 1.00 117.06975

DISEO SISMO RESISTENTE 16


ANALISIS SISMICO

PESO TOTAL DE LA EDIFICACION


AZOTEA 2DA PLANTA
Peso Unitario Base (m) Ancho (m) Altura (m) Largo (m) superficie Cantidad Peso (tn) CM (tot) Tn
CM (Ton)
Peso de superficie
Losa aligerada XX 0.31 161.69 1.00 50.12328
Losa aligerada YY 0.31 306.59 1.00 95.04321
Tabiqueria 0.21 468.28 1.00 98.33859
Acabados 0.12 468.28 1.00 56.19348
Peso vigas
VP 103 35X35 2.40 0.35 0.35 49.75 1.00 14.6265
VP 104 35X45 2.40 0.35 0.45 74.63 1.00 28.20825
VS 106 35X35 2.40 0.35 0.35 53.10 1.00 15.6114
VS 107 35X45 2.40 0.35 0.45 13.00 1.00 4.914
VS 108 30X50 2.40 0.30 0.50 26.00 1.00 9.36
VS 109 30X35 2.40 0.30 0.35 26.55 1.00 6.6906
Peso columnas
col 2 35x60 2.40 0.35 0.60 3.00 12.00 18.144
col3 35x45 2.40 0.35 0.45 3.00 14.00 15.876
col5 35x35 2.40 0.35 0.35 3.00 4.00 3.528 416.65731
CV (Ton)
Sobrecarga 0.25 468.28 1.00 117.06975

PESO TOTAL DE LA EDIFICACION


AZOTEA 1RA PLANTA
Peso Unitario Base (m) Ancho (m) Altura (m) Largo (m) superficie Cantidad Peso (tn) CM (tot) Tn
CM (Ton)
Peso de superficie
Losa aligerada XX 0.31 161.69 1.00 50.12328
Losa aligerada YY 0.31 306.59 1.00 95.04321
Tabiqueria 0.21 468.28 1.00 98.33859
Acabados 0.12 468.28 1.00 56.19348
Peso vigas
VP 103 35X35 2.40 0.35 0.35 49.75 1.00 14.6265
VP 104 35X45 2.40 0.35 0.45 74.63 1.00 28.20825
VS 106 35X35 2.40 0.35 0.35 53.10 1.00 15.6114
VS 107 35X45 2.40 0.35 0.45 13.00 1.00 4.914
VS 108 30X50 2.40 0.30 0.50 26.00 1.00 9.36
VS 109 30X35 2.40 0.30 0.35 26.55 1.00 6.6906
Peso columnas
col 2 35x60 2.40 0.35 0.60 3.00 12.00 18.144
col3 35x45 2.40 0.35 0.45 3.00 14.00 15.876
col5 35x35 2.40 0.35 0.35 3.00 4.00 3.528 416.65731
CV (Ton)
Sobrecarga 0.25 468.28 1.00 117.06975

NIVEL CM CV PS PS (SISMO)
N1 416.65731 117.06975 533.72706 475.192185
N2 416.65731 117.06975 533.72706 475.192185
N3 416.65731 117.06975 533.72706 475.192185
N4 416.65731 117.06975 533.72706 475.192185
N5 360.46383 46.8279 407.29173 383.87778
N6 127.37233 15.9446 143.31693 135.34463
2685.5169 2419.99115

COMPROBACION CORTANTES SOFTWARE


0.18867 p Vxx 456.57973 457.27.20
0.18867 p Vyy 456.57973 457.27.21

DISEO SISMO RESISTENTE 17


ANALISIS SISMICO

INGRESANDO CARGAS ANLISIS SSMICO

Categora A adicionamos 50% carga viva


El Modelo Rigidizado No Cumple Con Las Derivas Estipuladas Por La Norma E 030

CONTROL DE DERIVAS
R(x,y) Desplazamientos Derivas Di=0.75R*Dr Di/Hi Control Dr XX Control Dr XX
NIVEL Altura Hi(cm) Rx Ry Ux(cm) Uy(cm) Dr Ux (cm) Dr Uy (cm) 0.75Rdr Ux 0.75Rdr Uy "X" "Y" X-X X-X Y-Y Y-Y
1 NIVEL 300 8 8 0.3207 0.1413 0.3207 0.1413 1.9242 0.8478 0.006414 0.002826 0.007 CUMPLE 0.007 CUMPLE
2 NIVEL 300 8 8 0.7857 0.3651 0.465 0.2238 2.79 1.3428 0.0093 0.004476 0.007 NO CUMPLE 0.007 CUMPLE
3 NIVEL 300 8 8 1.2426 0.6102 0.4569 0.2451 2.7414 1.4706 0.009138 0.004902 0.007 NO CUMPLE 0.007 CUMPLE
4 NIVEL 300 8 8 1.6065 0.8397 0.3639 0.2295 2.1834 1.377 0.007278 0.00459 0.007 NO CUMPLE 0.007 CUMPLE
5 NIVEL 300 8 8 1.8692 1.0394 0.2627 0.1997 1.5762 1.1982 0.005254 0.003994 0.007 CUMPLE 0.007 CUMPLE
6 NIVEL 300 8 8 1.8845 1.3237 0.0153 0.2843 0.0918 1.7058 0.000306 0.005686 0.007 CUMPLE 0.007 CUMPLE

Rigidizaremos la estructura aumentando la seccin de las columnas en el eje X.

DISEO SISMO RESISTENTE 18


ANALISIS SISMICO

Aumentaremos la seccin de la columna 5


COL 5 (35*35) a RCOL5 (60*35) con fines de aumentar la rigidez de la estructura.
Luego con la columna 3
COL 3(35*45) a RCOL (50*45) con fines de aumentar la rigidez de la estructura
Y por ltimo aumentamos la seccin de las columnas
COL 2 (35*60) a RCOL2 (45*60) fines de aumentar la rigidez de la estructura

Desplazamientos eje X-X

Desplazamientos eje Y-Y

DISEO SISMO RESISTENTE 19


ANALISIS SISMICO

CONTROL DE DERIVAS
INCREMENTANDO SECCION DE COLUMNAS
R(x,y) Desplazamientos Derivas Di=0.75R*Dr Di/Hi Control Dr XX Control Dr XX
NIVEL Altura Hi(cm) Rx Ry Ux(cm) Uy(cm) Dr Ux (cm) Dr Uy (cm) 0.75Rdr Ux 0.75Rdr Uy "X" "Y" X-X X-X Y-Y Y-Y
1 NIVEL 300 8 8 0.2992 0.1605 0.2992 0.1605 1.7952 0.963 0.005984 0.00321 0.007 CUMPLE 0.007 CUMPLE
2 NIVEL 300 8 8 0.7572 0.4171 0.458 0.2566 2.748 1.5396 0.00916 0.005132 0.007 NO CUMPLE 0.007 CUMPLE
3 NIVEL 300 8 8 1.2115 0.6991 0.4543 0.282 2.7258 1.692 0.009086 0.00564 0.007 NO CUMPLE 0.007 CUMPLE
4 NIVEL 300 8 8 1.5761 0.9656 0.3646 0.2665 2.1876 1.599 0.007292 0.00533 0.007 NO CUMPLE 0.007 CUMPLE
5 NIVEL 300 8 8 1.8418 1.1995 0.2657 0.2339 1.5942 1.4034 0.005314 0.004678 0.007 CUMPLE 0.007 CUMPLE
6 NIVEL 300 8 8 1.8635 1.5272 0.0217 0.3277 0.1302 1.9662 0.000434 0.006554 0.007 CUMPLE 0.007 CUMPLE

Por lo tanto tenemos que optar por placas para rigidizar la estructura y que cumplan con las derivas
estipuladas por la norma E 030
Incrementando con 4 placas de 2 metros de largo y ancho 0.25

DISEO SISMO RESISTENTE 20


ANALISIS SISMICO

Desplazamientos eje X-X

Desplazamientos eje Y-Y

CONTROL DE DERIVAS

DISEO SISMO RESISTENTE 21


ANALISIS SISMICO

AADIENDO PLACAS
R(x,y) Desplazamientos Derivas Di=0.75R*Dr Di/Hi Control Dr XX Control Dr XX
NIVEL Altura Hi(cm) Rx Ry Ux(cm) Uy(cm) Dr Ux (cm) Dr Uy (cm) 0.75Rdr Ux 0.75Rdr Uy "X" "Y" X-X X-X Y-Y Y-Y
1 NIVEL 300 8 8 0.1522 0.1617 0.1522 0.1617 0.9132 0.9702 0.003044 0.003234 0.007 CUMPLE 0.007 CUMPLE
2 NIVEL 300 8 8 0.4184 0.4207 0.2662 0.259 1.5972 1.554 0.005324 0.00518 0.007 CUMPLE 0.007 CUMPLE
3 NIVEL 300 8 8 0.7124 0.7048 0.294 0.2841 1.764 1.7046 0.00588 0.005682 0.007 CUMPLE 0.007 CUMPLE
4 NIVEL 300 8 8 0.982 0.9753 0.2696 0.2705 1.6176 1.623 0.005392 0.00541 0.007 CUMPLE 0.007 CUMPLE
5 NIVEL 300 8 8 1.231 1.2139 0.249 0.2386 1.494 1.4316 0.00498 0.004772 0.007 CUMPLE 0.007 CUMPLE
6 NIVEL 300 8 8 1.3055 1.5058 0.0745 0.2919 0.447 1.7514 0.00149 0.005838 0.007 CUMPLE 0.007 CUMPLE

5. ANALISIS DINAMICO MODAL ESPECTRAL

5.1. DESCRIPCIN

La estructura propuesta, es un edificio de 5 pisos y un nivel de azotea, de configuracin


estructural regular en planta y elevacin. Y est destinado al uso de viviendas
multifamiliares comenzando desde el primer piso hasta el dcimo piso .Est constituido
por un sistema estructural Aporticado de concreto armado en la direccin X-X y de
prticos en la direccin Y-Y.

5.2. PROPIEDADES MECNICAS DE LOS MATERIALES

5.3. NORMATIVIDAD:

En todo el proceso de anlisis y diseo se utilizarn las normas comprendidas en el


Reglamento Nacional de Edificaciones (R.N.E.):

Metrado de cargas: Norma E-020


Diseo sismo resistente: Norma E-030

5.4. ANLISIS SSMICO

El anlisis se realiz segn la norma vigente NTE E-030 del Reglamento Nacional de
Edificaciones. Considerando las condiciones de suelo, las caractersticas de la estructura
y las condiciones de uso, se utilizaron los siguientes parmetros ssmicos:

DISEO SISMO RESISTENTE 22


ANALISIS SISMICO

Factor de Zona: Z = 0.35 (Zona 3)


Factor de Uso: U = 1.50 (Edificacin Esencial)
Factor de suelo: S = 1.15 (Suelo Intermedio)
Periodo de la plataforma Tp = 0.6
Periodo que define el inicio de la zona del espectro con desplazamiento de constante.
TL = 2.0

Coeficiente de reduccin direccin horizontal Rx =8 (Sistema de prticos, estructura


regular)

Coeficiente de reduccin direccin vertical Ry =8 (Sistema de porticos, estructura


regular)

A partir de estos valores se determin el espectro de pseudo aceleraciones, como se ve en


la figura 1 y 2.

5.5. ESPECTRO DE PSEUDO ACELERACION

Para el Anlisis Dinmico de la Estructura se utiliza un Espectro de respuesta segn la


NTE-E.030, para la fuerza cortante mnima en la base y compararlos con los resultados
de un anlisis esttico. Todo esto para cada direccin de la Edificacin en la planta (X e
Y)

DISEO SISMO RESISTENTE 23


ANALISIS SISMICO

ZUCS = 0.18867
R

ESPECTRO NORMA E-030 2015


0.20000

0.18000

0.16000
Acel. Espectral (m/s2)

0.14000

0.12000

0.10000

0.08000

0.06000

0.04000

0.02000

0.00000
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50

Periodo T (s)

DISEO SISMO RESISTENTE 24


ANALISIS SISMICO

6. RESULTADOS

DISEO SISMO RESISTENTE 25


ANALISIS SISMICO

6.1. PERIODOS Y MODOS DE VIBRACIN

DETERMINACION DEL ESPECTRO

Con estas cargas y con las propiedades de las secciones transversales, se puede determinar
los periodos de vibrar.
Se determin 10 periodos de vibracin. En la tabla siguiente se observa el periodo
fundamental en la direccin Y igual a 0.393 segundos, con una participacin de masa
efectiva del 100%; y en la direccin X, se tiene un periodo de 0.23 segundos con 100%
de participacin de masa efectiva.

DISEO SISMO RESISTENTE 26


ANALISIS SISMICO

PRIMERA FORMA MODAL

SEGUNDA FORMA MODAL

TERCERA FORMA MODAL

DISEO SISMO RESISTENTE 27


ANALISIS SISMICO

DECIMA FORMA MODAL

FORMA MODAL CUADRADO DE LOS CUADRADOS

DISEO SISMO RESISTENTE 28


ANALISIS SISMICO

6.2. DESPLAZAMIENTOS Y DISTORSIONES DE ENTREPISO

Segn la norma vigente para cada direccin de anlisis, las distorsiones calculadas por el
programa deben ser multiplicados por 0.75R.

En la tabla 03 se resumen los desplazamientos mximos en cada nivel, calculados por el


programa Autodesk Robot Structural 2015. Y en la Tabla 04 y 05 se muestran las
distorsiones calculadas en concordancia con la NTE E-030.

ANALSIS ESPECTRAL CONTROL DE DERIVAS EJE X

DISEO SISMO RESISTENTE 29


ANALISIS SISMICO

ANALSIS ESPECTRAL CONTROL DE DERIVAS EJE Y

DISEO SISMO RESISTENTE 30


ANALISIS SISMICO

ESPECTRAL
R(x,y) Desplazamientos Derivas Di=0.75R*Dr Di/Hi Control Dr XX Control Dr XX
NIVEL Altura Hi(cm) Rx Ry Ux(cm) Uy(cm) Dr Ux (cm) Dr Uy (cm) 0.75Rdr Ux 0.75Rdr Uy "X" "Y" X-X X-X Y-Y Y-Y
1 NIVEL 300 8 8 0.0143 0.0205 0.0143 0.0205 0.0858 0.123 0.000286 0.00041 0.007 CUMPLE 0.007 CUMPLE
2 NIVEL 300 8 8 0.0417 0.0587 0.0274 0.0382 0.1644 0.2292 0.000548 0.000764 0.007 CUMPLE 0.007 CUMPLE
3 NIVEL 300 8 8 0.074 0.1057 0.0323 0.047 0.1938 0.282 0.000646 0.00094 0.007 CUMPLE 0.007 CUMPLE
4 NIVEL 300 8 8 0.1052 0.155 0.0312 0.0493 0.1872 0.2958 0.000624 0.000986 0.007 CUMPLE 0.007 CUMPLE
5 NIVEL 300 8 8 0.1349 0.202 0.0297 0.047 0.1782 0.282 0.000594 0.00094 0.007 CUMPLE 0.007 CUMPLE
6 NIVEL 300 8 8 0.1295 0.2445 -0.0054 0.0425 -0.0324 0.255 -0.000108 0.00085 0.007 CUMPLE 0.007 CUMPLE

Como se observa en el cuadro 4 y 5, la distorsin de la estructura en estudio es menor a 0.007 cm, que
es lo mximo permitido por la NTE E-030 en el eje X e Y, por lo que se concluye que la estructura tiene
suficiente rigidez en la direccin X e Y como para resistir las cargas ssmicas

DISEO SISMO RESISTENTE 31


ANALISIS SISMICO

7. CONCLUSIONES Y RECOMENDACIONES

El modo de vibracin 2 sali por torsin, lo que indica que posiblemente la edificacin tenga
problemas y fallas en los elementos no estructurales ante un sismo demasiado fuerte.
La edificacin cumpli con los desplazamientos menores a 0.007 cm. para estructuras de
concreto armado y aporticas como se indica en la norma de sismo resistencia.
El Vd no cumpli con la norma, por lo que se tuvo que emplear un factor de correccin.
El edificio multifamiliar es una estructura segura que no colapsar sobre si misma ante un
caso de sismo, ya que cumple con todas las especificaciones fijadas en la norma E-030.

DISEO SISMO RESISTENTE 32