You are on page 1of 3

Structural D

uring their service life, high-rise build- mix, environment, construction sequence, etc.
ings and the associated nonstructural Although accurately evaluating column shorten-
components endure various move- ing is a very challenging task due to uncertainties

Design
ments and deformations. Although of material parameters, environment, and gravity
the deformations and movements are not life load redistribution, the method presented in the
threatening, inappropriate design of buildings America Concrete Institutes Guide for Modeling
and associated nonstructural components could and Calculating Shrinkage and Creep in Hardened
induce expensive economic consequences in the Concrete (ACI 209) can reasonably estimate
design issues for
long-run and, in order to ensure proper building column shortening if reliable material parameters
structural engineers behavior of the superstructures and the attached are given. According to ASCE 7-2010, the load
nonstructural elements, should not be ignored. In combination for long-term column shortening
this article the possible deformations and move- estimation can be used as D+0.5L, in which D
ments of reinforced concrete high-rise buildings is service dead load and L is service live load.
and the accommodation of the affected compo-
Slab and Beam Deflections Due
nents are discussed.
to Gravity Loads

E
Common Deformations Well-established procedure, including maximum
permissible criteria for reinforced concrete slab and
and Movements

R
beam deflection computation, is specified in ACI 318
Common, inevitable building movements and (Building Code Requirements for Structural Concrete,

U
deformations include: differential
igh
t column short- 2011). The load combination for short-term effect

T
pyr
Coening, lateral story drift, deflection check is D+L, and for long-term effect is
building racking, slab and D+0.5L (Minimum Design Loads for Buildings and
Accommodation to
C
beam deflection, thermal Other Structures, ASCE-7, 2010). It is also a general

e
U
deformation and building practice to use Finite-Element Analysis software to
Reinforced Concrete High- dynamic vibration, etc.
n check floor deflections (especially for two-way flat
i
R
slabs) based on actual reinforcing layout and reason-
Rise Building Deformations z
Differential Column

T
ably assumed material parameters.

and Movements g a
Shortening under
When one checks floor system deflections, it is

S
Gravity Loads
necessary to estimate floor slab edge deflections for
a When subjected to gravity cladding system installation, especially for large
By Songtao Liao, Ph.D., P.E.,
M. ASCE, Benjamin Pimentel, P.E.,
m loads, vertical reinforced
concrete structural members, such as columns
prefabricated concrete/stone panel facade system.
For interior partitions, allowance is needed for
and shear walls, experience short-term and differential deflection between two adjacent floors
Danny Jadeja, M.S., P.E. and
long-term shortening that is zero at the base after the installation of interior partitions. There
Sunghwa Han, M.S., P.E., S.E.,
and accumulates to be the maximum at the have been numerous examples where these joints
LEED AP
roof level. Magnitudes are dependent on con- have not been appropriately installed, particularly
crete mix, gravity stress levels, construction on tall slender buildings, which results in creak-
sequences, loading histories, volume-to-surface ing complained by tenants because of rubbing
ratios and ambient relative humidity, etc. joints as the buildings move under wind loading.
Short-term column shortening is primarily a The long-term deflections of girders, which pick
result of elastic deformation, while long-term up floors above, are particularly important and
shortening is the resultant of concrete creep and the deflection acceptance criteria should be more
shrinkage. For reinforced concrete high-rise build- stringent than code-allowed values. Absolute
ings, the long-term column shortening can be long-term deflection limit values for the girders
as high as 1/8 inch per floor (for a 10-foot story are recommended to control associated deflection
height building), and the cumulative differential of floors above, instead of satisfying the code-
column shortening causes floors to tilt. In order to allowable deflection-over-span ratio alone.
reduce differential column shortening, it is a good In many cases, cambers are specified in con-
practice during the design stage to ensure that the struction documents to ensure level slabs and
layout of vertical members is balanced so that the minimum slab infill. Since there are many uncer-
vertical members experience gravity-induced axial tainties in long-term deflection estimation, a
stresses as equal as possible. For example, in order to camber may be set as one-half of the computed
minimize the differential shortening between shear total long-term deflections including the immedi-
walls and columns, it is desirable to locate columns ate deflections, as building owners and contractors
away from shear walls so that more gravity loads prefer that the cambers are sized to accommodate
will be distributed to shear walls thus resulting only immediate deflection and a portion of the
in smaller gravity-induced axial stress differences long-term deflection. It is also worth noting that
between columns and shear walls. cambers less than inch tend to be ignored by
Differential column shortening should be esti- concrete contractors because the value is within
mated by considering the effects of actual concrete construction tolerance and error range.

16 April 2014
Building Drift and Associated Racking In large scale cast-in-place reinforced concrete Floor Elevation Correction
Due to Lateral Loads podium areas or mat foundation slabs, where
Building floor elevation loss and floor tilting
the concrete floor expansion and contraction
Transient lateral loads acting on buildings are expected due to the differential column
are restrained by structural elements such as
induce not only horizontal story drifts but shortening and should be addressed. During
foundation walls, control strips should be pro-
also temporary shortening and elongation the construction process, the concrete sub-
vided for cracking control.
of vertical members. As a result, transient contractor should adjust formworks to the
dynamic racking of the building is to be Building Dynamic Vibrations prescribed slab elevations in construction docu-
expected during the service life of buildings. ments to level out the to-be-constructed floor,
There are two main types of dynamic vibration
Allowances for building cladding systems and compensate for the immediate shortening
issues in building service life: wind-induced
and interior partitions should be provided and a portion of long-term shortening of ver-
building acceleration and floor vibration. Both
to accommodate the transient story drift and tical members. The concrete sub-contractor
may cause resident discomfort depending on
dynamic racking motions under both wind should monitor floor elevations from a fixed
tenants sensitivity to the motions, and can be
loads and seismic loads. base to make sure that reinforced concrete
reduced to a reasonable limit through well-
Allowable seismic story drift criteria are given vertical structural members are shortening in
planned structural design by adjusting building
in ASCE 7 and vary with seismic risk cate- an orderly fashion.
In the long run, the magni-
stiffness, mass and damping (for instance,
gory and the seismic force resisting structural tude of column shortening for a 10-foot story

E
introducing supplementary damping systems).
system types (ASCE 7-2010). The building height residential building can be as high as 1/8
Although floor vibration usually needs

R
seismic design story drift is computed first inch per floor, which accumulate to be largest
to be checked for light structures such as
by using the prescribed seismic design load at buildings roof level. Usually, the long-term
steel framed floor systems, long span cast-

U
through elastic analysis, and then adjusted absolute floor elevation loss is ignored as long
in-place reinforced igh concrete floor systems
t
with deflection multiplication factor Cd and as appropriate soft joints or connections are

T
pyr
could vibrateCouncomfortably as well when
seismic importance factor Ie. This nonlinear provided for other nonstructural components.
subjected to gymnastic exercise or mechani-

C
seismic story drift is compared with the rela- When the long-term absolute floor elevations
cal equipments vibration. A simple guideline
tive seismic glass fallout limit (fallout), which must be maintained, it is suggested to specify
e
U
was suggested to identify potential vibration
is determined with the dynamic test method lumped elevation corrections every several
recommended by the American Architectural
problem by checking natural frequency of
i n floors. In this case, faade fabrication and

R
floor systems. However, controlling the floor
Manufacturers Association (AAMA).
z installation should also be adjusted accordingly.

T
fundamental frequency alone may result in
Different from the seismic story drift require-
a
uneconomic design of long-span reinforced
g
Faade System

S
ments, the building story drift ratio limit for
concrete floor systems. To limit the long span
wind design is not explicitly specified in build-
a
reinforced concrete floor vibrations, struc-
Faade systems are inherently sensitive to
ing codes and is usually taken as 1/600 ~ 1/400
based on decades of design practice. Depending
on the sensitivity of nonstructural elements to
m
tural stiffness, mass and damping should
all be considered, and floor Finite Element
building movements; therefore, great care and
good communication between the structural
engineer and the faade designer is needed
dynamic analysis is recommended with real-
building lateral story drift, the lateral design to avoid unexpected faade damage in the
istic boundary conditions and reasonably
loads for wind story drift check can be chosen buildings service life (e.g. connection failure,
assumed damping ratio at the design stage.
as 10-year, 50-year and 100-year return periods non-uniformities and irregularities of joints,
Peak accelerations and peak torsional
respectively. The choice of return period should misalignment of faces and panel fallout), espe-
velocities at the topmost occupied floor of
be governed by local code requirements and cially when the faade system is composed of
a high-rise building under wind loading
design engineers judgment. If 10-year return large prefabricated concrete/stone panels, or
should be checked to avoid excessive resi-
period design loads are used, the story drift includes panels of dissimilar materials. Prior
dent discomfort. Approximate estimation
ratio limit should be more stringent than the to cladding installation, a new survey should
formula was given in National Building
conventional drift criteria when the cladding be taken from a fixed base at the ground floor
Code of Canada (NBCC); however, in many
systems are same. It is a typical design practice to establish new benchmarks to divide the
cases wind tunnel testing companies are
that 50-year return period wind design loads available soft joints equally between the exist-
hired to estimate the peak accelerations
are used for story drift check, along with the ing typical floor levels.
based on wind tunnel test results from
commonly used inter-story drift ratio limit Additional long-term building deformations
scaled building models. In addition to
1/400 for high-rise buildings. and transient movements will continue to
building stiffness, mass distribution, damp-
occur after the faade installation. Because
Temperature-induced Deformation ing and building geometry can be adjusted
long-term deformation and deflection are
to reduce the peak accelerations and peak
Expansion/contraction of building members time-dependent, it is important for the
torsional velocities.
and facade systems due to temperature varia- designer to be informed as to when and how
tion can induce large internal forces if they the faade system will be installed, in order to
are constrained. Brittle faade systems, which
Affected Components and prescribe recommended joint sizes. To reduce
are sensitive to thermal movements, tend Measures to Accommodate the faade joint size, the installation of the
to experience larger temperature oscillation faade system may need to be arranged to a
and expansion joints (soft joints) should be
Building Movements later construction stage so that a larger portion
provided. For roof parapets, relief joints are Because of inevitable building deformations of the long-term deflection and deformation
recommended to control the location of cracks and movements, the structure itself and the can occur before installation.
because the parapets are usually exposed to associated nonstructural components must After installation of the faade system, the
weather and experience extreme temperature be appropriately designed in order to ensure soft joint or adjusting device for prefabricated
variation during the buildings service life cycle. proper serviceability performance. cladding system should accommodate the

STRUCTURE magazine 17 April 2014


following items for both vertical and hori- movements, special attention is required to differential deflection between two adjacent
zontal joints: ensure proper behavior of the vertical trans- floors after the installation of interior parti-
Vertical joint: portation system and associated electrical tions. If allowance is not large enough to
Story drift due to wind design loads vertical pipes. For example, elevator guide compensate the floor deflection occurring
(50-year return period) rails are tied back to the reinforced concrete after installation, creaking resulting from
Thermal expansion/contraction of the superstructure and tend to move down- rubbing partitions will be heard. To make
faade system between expansion joints ward as the long-term shortening builds up it worse, non-load bearing partitions could
Horizontal joint: over time. Allowance should be provided inadvertently become load bearing walls caus-
Future additional long-term column between elevator guide rails to accommodate ing the partition walls to fail or develop a
shortening of exterior columns the long-term movements (as mentioned change of load path. As mentioned earlier,
Immediate deflection due to live load before, about 1/8 inch each floor on average). floor deflection is time-dependent so allow-
and long-term deflections due to The elevator stop locations may need to be ance can be relaxed if the installation of
sustained loads at the exterior edges of adjusted as the building undergoes long-term partitions is arranged to a later construction
floor slabs creep and shrinkage. stage. Usually, the permissible allowance is
Thermal expansion/contraction of the generally not less than the clear span between
Vertical Piping
faade system between expansion joints supports divided by 360.

E
Elastic column elongation and Vertical piping should be supported vertically
shortening due to wind design loads in between their expansion joints at one level
Summary

R
(50-year return period) only, and guided laterally at other levels as
Nominal joint size for a faade system necessary. Expansion details and clearance During their service life, reinforced con-

U
should be equal to (or greater than) the above and below rthe ht piping to accommodate crete buildings constantly experience
y ig

T
sum of the calculated relative movements Cop
long-term shortening must be provided: the deformations and movements. The common
and the maximum tolerance permitted for expansion joint should allow for long-term deformations and movements in reinforced

C
abutting faade elements: shortening of 1/8 inch per floor on average. concrete high-rise buildings include differ-

e
U
Additional clearance will be required if the ential column shortening, lateral story drift,
Width of joint = total movement + total tolerance

i n
piping is located adjacent to the periphery building racking, slab and beam deflection,

R
When wind loading acts on faades, the of buildings, where building racking and thermal deformation and building dynamic
z
T
panels may tend to bow in (or out) and could temperature variation will induce extra move- vibration, etc. As long as the inevitable
touch supporting backup members. Large size ments for the piping.
g a movements and deformation and the effects

S
glass panels could collide with the adjacent Horizontal pipe branches which are off ver- on associated structural and nonstructural
supporting structures; therefore, enough sepa- a
tical piping support, and distant from that elements are not ignored by engineers,
ration distance should be provided between
the faade and the adjacent supporting mem- m
support, such as sprinkler piping and gas
lines, must be allowed to move freely up and
impaired serviceability performance can be
avoided by applying precautionary accom-
bers as well. down with respect to the adjacent floors. The modation measures during both design and
Besides interstory drift due to wind design allowance should be increased accordingly if construction stages.
loads, the structural engineer should provide long-term relative floor deflection will affect
seismic inter-story drifts (with nonlinear the horizontal pipes. Extra sloping of hori-
Songtao Liao, Ph.D., P.E., M. ASCE,
effect) for the cladding design engineer to zontal drain pipelines is required in order to
is an associate at Rosenwasser/Grossman
check the glass fallout limit (fallout ) which accommodate the future reduction in slope
Consulting Engineers, P.C. Steven can be
is dependent on glass types and glazing due to differential shortening among building
reached at stevenl@rgce.com.
details (AAMA). vertical members.
Benjamin Pimentel, P.E., is President
Vertical Transportation Interior Partitions
and CEO of Rosenwasser/Grossman
Due to the long-term shortening of vertical For interior partitions or nonstructural Consulting Engineers, P.C. He currently
structural members and possible thermal walls, allowance should also be provided for serves on the Board of Directors for the
Structural Engineering Association of
New York and the Concrete Industry
References Board of New York. Benjamin can be
reached at bpimentel@rgce.com.
American Society of Civil Engineers (ASCE), 2010, Minimum Design Loads for Buildings
and Other Structures, ASCE Standard ASCE/SEI 7-10, Reston, VA. Danny Jadeja, M.S., P.E., is a senior
associate at Rosenwasser/Grossman
ACI 318 (2011), Building Code Requirements for Structural Concrete (ACI 318-11), ACI
Consulting Engineers, P.C. Danny can be
Committee 318, Farmington Hills, MI, 2011.
reached at danny@rgce.com.
Bast, W., McDonnell, T., Parker, L., and Shanks, S, Measured Shortening and Its Effect in a
Sunghwa Han, M.S., P.E., S.E., LEED AP, is
Chicago High-Rise Building, Forensic Engineering (2003): pp. 564-576.
a director of design at Rosenwasser/Grossman
Kazmierczak K., Movements and Tolerances: Considerations for Curtain Wall and Cladding Consulting Engineers, P.C. Sunghwa can be
Design, The Construction Specifier, October, 2008. reached at Sunghwa@rgce.com.
Liao S., Klein G., Mikhlin Y., Grossman J., Vertical Structural Deformation: Estimation and
Control for a Deformation-Sensitive Building, STRUCTURE magazine, September,
2010, pp 34-36.

STRUCTURE magazine 18 April 2014

You might also like