AL BAWANI QA/QC, 2, FEBRUARY 2016 - R-00 (Standards Cut-off - Dec.

2014) Rev 0 18-May-16

AL BAWANI INSPECTION CHECKLIST BAIC NUMBER DATE APPROVED QR NUMBER

HID Light Fixtures (Low/High-bay) - Assembly, Installation,


BAIC-P-3621 Electrical
and Pre- Commissioning
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

National Guard Family Compound (Industrial Zone) 6600036333 AL BAWANI GENERAL CONTRACTING

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME

AL BAWANI ITP NUMBER AL BAWANI ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

A. General Requirements

Identification procedures shall be implemented for all materials, parts


and components, including partially fabricated assemblies. Identification
Schedule Q
A1 of an item shall be done by using tags, stamps, color coding, stencils or
Att. lV Sec. 4.2
labels. The location and method of identification shall not affect the
function or quality of the material.

Traceability shall be maintained on the equipment. Documents and


Schedule Q
A2 records shall enable the equipment to be traced throughout delivery,
Att. lV Sec. 4.3
storage, fabrication, erection, installation, repair, modification and use.

QC Before Installation- Equipment shall conform to all applicable


Schedule Q
A3 requirements, standards, and specifications prior to release to be used
Att. lV Sec. 3.3
as part of work.

Verify that equipment assembly parts and components shall be free of Schedule Q
A4
damage. Att. lV Sec. 3.3

Schedule "G"
A5 Electrical materials shall be new and unused.
Para. 2.1

Contractor shall implement procedures for handling, storage, and


Schedule Q
A6 preservation of materials as specified in all applicable specifications,
Att. lV Sec. 6
manufacturer recommendations and company's standards.

Luminaires shall be marked, listed or labeled by an independent third


party laboratory (notified body) the associated certificate shall state SAES-P-123
A7
either that the luminaires meet appropriate designated standards or Para. 5.2.3
have been tested and found suitable for use in a specified manner.

All luminaires (fixtures) shall be marked with the maximum lamp wattage
SAES-P-123
A8 or electrical rating, manufacturers name, trademark, or other suitable
Para. 3.2
means of identification. [NFPA 70, NEC Art. 410.74(A)]

A luminaire requiring supply wire rated higher than 60C (140F) shall be
marked with the minimum supply wire temperature rating on the SAES-P-123
A9
luminaire and shipping carton or equivalent. [NFPA 70, NEC Art. Para. 3.2
410.74(A)]

In a completed installation, each outlet box shall be provided with a


SAES-P-123
A10 cover unless covered by means of a luminaire (fixture) canopy,
Para. 3.2
lampholder, receptacle, or similar device. (NFPA 70, NEC Art. 410.22)

Electric-discharge and LED luminaires supported independently of the


outlet box shall be connected to the branch circuit through metal
SAES-P-123
A11 raceway, nonmetallic raceway, Type MC cable, Type AC cable, Type MI
Para. 3.2
cable, nonmetallic sheathed cable, or by flexible cord as permitted in
410.62(B) or 410.62(C). [NFPA 70, NEC Art. 410.24(A)]

Page 1 of 8
AL BAWANI QA/QC, 2, FEBRUARY 2016 - R-00 (Standards Cut-off - Dec. 2014) Rev 0 18-May-16

AL BAWANI INSPECTION CHECKLIST BAIC NUMBER DATE APPROVED QR NUMBER

HID Light Fixtures (Low/High-bay) - Assembly, Installation,


BAIC-P-3621 Electrical
and Pre- Commissioning
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

National Guard Family Compound (Industrial Zone) 6600036333 AL BAWANI GENERAL CONTRACTING

General. Luminaires (fixtures) and lampholders shall be securely


supported. A luminaire (fixture) that weighs more than 3 kg (6 lb) or SAES-P-123
A12
exceeds 400 mm (16 in.) in any dimension shall not be supported by the Para. 3.2
screw shell of a lampholder. [NFPA 70, NEC Art. 410.30(A)]

Outlet boxes or fittings installed as required by 314.23 and complying


SAES-P-123
A13 with the provisions of 314.27(A)(1) and 314.27(A)(2) shall be permitted
Para. 3.2
to support luminaires. [NFPA 70, NEC Art. 410.36(A)]

Inspection. Luminaires (fixtures) shall be installed so that the


connections between the luminaire (fixture) conductors and the circuit
SAES-P-123
A14 conductors can be inspected without requiring the disconnection of any
Para. 3.2
part of the wiring unless the luminaires (fixtures) are connected by
attachment plugs and receptacles. (NFPA 70, NEC Art. 410.8)

Exposed Conductive Parts. Exposed metal parts shall be grounded or


insulated from ground and other conducting surfaces or be inaccessible
to unqualified personnel. Lamp tie wires, mounting screws, clips, and SAES-P-123
A15
decorative bands on glass spaced at least 38 mm (11/2 in.) from lamp Para. 3.2
terminals shall not be required to be grounded. (NFPA 70, NEC Art.
410.42)

Luminaires (fixtures) directly wired or attached to outlets supplied by a


wiring method that does not provide a ready means for grounding shall SAES-P-123
A16
be made of insulating material and shall have no exposed conductive Para. 3.2
parts. (NFPA 70, NEC Art. 410.44 Exception 1)

Luminaires (fixtures) with exposed metal parts shall be provided with a


SAES-P-123
A17 means for connecting an equipment grounding conductor for such
Para. 3.2
luminaires (fixtures). (NFPA 70, NEC Art. 410.46)

Methods of Grounding-Luminaires (fixtures) and equipment shall be


considered grounded where mechanically connected to an equipment SAES-P-123
A18
grounding conductor as specified in 250.118 and sized in accordance Para. 3.2
with 250.122. (NFPA 70, NEC Art. 410.44)

Wiring on or within fixtures shall be neatly arranged and shall not be


exposed to physical damage. Excess wiring shall be avoided.
SAES-P-123
A19 Conductors shall be arranged so that they are not subjected to
Para. 3.2
temperatures above those for which they are rated. (NFPA 70, NEC Art.
410.48)

Luminaires (fixtures) shall be wired so that the screw shells of


lampholders are connected to the same luminaire (fixture) or circuit
SAES-P-123
A20 conductor or terminal. The grounded conductor, where connected to a
Para. 3.2
screw-shell lampholder, shall be connected to the screw shell. (NFPA 70,
NEC Art. 410.50)

Conductor Insulation. Luminaires (fixtures) shall be wired with


conductors having insulation suitable for the environmental conditions, SAES-P-123
A21
current, voltage, and temperature to which the conductors will be Para. 3.2
subjected. (NFPA 70, NEC Art. 410.52)

Properly Secured. Conductors shall be secured in a manner that does SAES-P-123


A22
not tend to cut or abrade the insulation. [NFPA 70, NEC Art. 410.56(A)] Para. 3.2

Protection Through Metal. Conductor insulation shall be protected from SAES-P-123


A23
abrasion where it passes through metal. [NFPA 70, NEC Art. 410.56(B)] Para. 3.2

Luminaire (Fixture) Stems. Splices and taps shall not be located within SAES-P-123
A24
luminaire (fixture) arms or stems. [NFPA 70, NEC Art. 410.56(C)] Para. 3.2

Page 2 of 8
AL BAWANI QA/QC, 2, FEBRUARY 2016 - R-00 (Standards Cut-off - Dec. 2014) Rev 0 18-May-16

AL BAWANI INSPECTION CHECKLIST BAIC NUMBER DATE APPROVED QR NUMBER

HID Light Fixtures (Low/High-bay) - Assembly, Installation,


BAIC-P-3621 Electrical
and Pre- Commissioning
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

National Guard Family Compound (Industrial Zone) 6600036333 AL BAWANI GENERAL CONTRACTING

Splices and Taps. No unnecessary splices or taps shall be made within SAES-P-123
A25
or on a luminaire (fixture). [NFPA 70, NEC Art. 410.56(D)] Para. 3.2

Stranding. Stranded conductors shall be used for wiring on luminaire


SAES-P-123
A26 (fixture) chains and on other movable or flexible parts. [NFPA 70, NEC
Para. 3.2
Art. 410.56(E)]

Tension. Conductors shall be arranged so that the weight of the


SAES-P-123
A27 luminaire (fixture) or movable parts does not put tension on the
Para. 3.2
conductors. [NFPA 70, NEC Art. 410.56(F)]

Bushing having holes 7 mm (9/32 in.) in diameter shall be permitted for


SAES-P-123
A28 use with plain pendant cord and holes 11 mm (13/32 in.) in diameter with
Para. 3.2
reinforced cord. [NFPA 70, NEC Art. 410.62(A)]

Luminaires (fixtures) that require adjusting or aiming after installation


shall not be required to be equipped with an attachment plug or cord
connector, provided the exposed cord is of the hard-usage or extra-hard- SAES-P-123
A29
usage type and is not longer than that required for maximum adjustment. Para. 3.2
The cord shall not be subject to strain or physical damage. [NFPA 70,
NEC Art. 410.62(B)]

Electric-discharge luminaires (lighting fixtures) provided with mogul-


base, screw-shell lampholders shall be permitted to be connected to
branch circuits of 50 amperes or less by cords complying with 240.5. SAES-P-123
A30
Receptacles and attachment plugs shall be permitted to be of lower Para. 3.2
ampere rating than the branch circuit but not less than 125 percent of the
luminaire (fixture) full-load current. [NFPA 70, NEC Art. 410.62(C)(2)]

Electric-discharge luminaires (lighting fixtures) equipped with a flanged


surface inlet shall be permitted to be supplied by cord pendants
equipped with cord connectors. Inlets and connectors shall be permitted SAES-P-123
A31
to be of lower ampere rating than the branch circuit but not less than 125 Para. 3.2
percent of the luminaire (fixture) load current. [NFPA 70, NEC Art.
410.62(C)(3)]

Luminaires (Fixtures) as Raceways. Luminaires (fixtures) shall not be


SAES-P-123
A32 used as a raceway for circuit conductors unless listed and marked for
Para. 3.2
use as a raceway. (NFPA 70, NEC Art. 410.64)

Branch Circuit Conductors and Ballasts. Branch-circuit conductors within


75 mm (3 in.) of a ballast shall have an insulation temperature rating not
SAES-P-123
A33 lower than 90C (194F) unless supplying a luminaire (fixture) listed and
Para. 3.2
marked as suitable for a different insulation temperature. (NFPA 70, NEC
Art. 410.68)

Marking. All luminaires (fixtures) shall be marked with the maximum


SAES-P-123
A34 lamp wattage or electrical rating, manufacturers name, trademark, or
Para. 3.2
other suitable means of identification. [NFPA 70, NEC Art. 410.74(A)]

A luminaire (fixture) requiring supply wire rated higher than 60C (140F)
shall be marked in letters not smaller than 6 mm ( in.) high, SAES-P-123
A35
prominently displayed on the luminaire (fixture) and shipping carton or Para. 3.2
equivalent. [NFPA 70, NEC Art. 410.74(A)]

Electrical Rating. The electrical rating shall include the voltage and
SAES-P-123
A36 frequency and shall indicate the current rating of the unit, including the
Para. 3.2
ballast, transformer, or autotransformer. [NFPA 70, NEC Art. 410.74(B)]

Page 3 of 8
AL BAWANI QA/QC, 2, FEBRUARY 2016 - R-00 (Standards Cut-off - Dec. 2014) Rev 0 18-May-16

AL BAWANI INSPECTION CHECKLIST BAIC NUMBER DATE APPROVED QR NUMBER

HID Light Fixtures (Low/High-bay) - Assembly, Installation,


BAIC-P-3621 Electrical
and Pre- Commissioning
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

National Guard Family Compound (Industrial Zone) 6600036333 AL BAWANI GENERAL CONTRACTING

Cord Bushings. A bushing or the equivalent shall be provided where


flexible cord enters the base or stem of a portable lamp. The bushing SAES-P-123
A37
shall be of insulating material unless a jacketed type of cord is used. Para. 3.2
(NFPA 70, NEC Art. 410.84)

Raceway Fittings. Raceway fittings used to support a luminaire(s)


SAES-P-123
A38 [lighting fixture(s)] shall be capable of supporting the weight of the
Para. 3.2
complete fixture assembly and lamp(s). [NFPA 70, NEC Art. 410.36(E)]

Wet and Damp Locations. Luminaires (fixtures) installed in wet or damp


locations shall be installed so that water cannot enter or accumulate in SAES-P-123
A39
wiring compartments, lampholders, or other electrical parts. [NFPA 70, Para. 3.2
NEC Art. 410.10(A)]

All luminaires installed in wet locations shall be marked, Suitable for


Wet Locations. All luminaires installed in damp locations shall be SAES-P-123
A40
marked Suitable for Wet Locations or Suitable for Damp Locations. Para. 3.2
[NFPA 70, NEC Art. 410.10(A)]

Corrosive Locations. Luminaires (fixtures) installed in corrosive locations


SAES-P-123
A41 shall be of a type suitable for such locations. [NFPA 70, NEC Art.
Para. 3.2
410.10(B)]

Light fixtures shall be suitable for the environment where they are SAES-P-123
A42
installed Para. 5.2.7

B. Specific Requirements for HID (Low-bay) Light Fixtures - Assembly, Installation, and Pre- Commissioning

Mounting method of lighting fixtures shall be based on the best


SAES-P-123
B1 arrangement for illuminance, as well as easy and safe access during
Para. 5.1.15
installation and maintenance.

Ballasts and capacitors for fluorescent and HID fixtures shall be SAES-P-123
B2
Polychlorinated Biphenyl (PCB) free. Para. 5.2.3

LED or High-pressure sodium luminaires shall be used for outdoor area


SAES-P-123
B3 illumination. LED, high-pressure sodium or Metal Halide luminaires shall
Para. 5.2.4
be used for high-bay or low-bay indoor-industrial applications.

Raceway Fittings. Raceway fittings used to support a luminaire(s)


SAES-P-123
B4 [lighting fixture(s)] shall be capable of supporting the weight of the
Para. 3.2
complete fixture assembly and lamp(s). [NFPA 70, NEC Art. 410.36(E)]

Luminaires (fixtures) and lighting equipment shall be grounded as


SAES-P-123
B5 required in Article 250 and Part V of this article. (NFPA 70, NEC Art.
Para. 3.2
410.40)

Exposed metal parts shall be connected to an equipment grounding


conductor or insulated from the equipment grounding conductor and
other conducting surfaces or be inaccessible to unqualified personnel. SAES-P-123
B6
Lamp tie wires,mounting screws, clips, and decorative bands on glass Para. 3.2
spaced at least 38 mm (1-12 in.) from lamp terminals shall not be
required to be grounded. (NFPA 70, NEC Art. 410.42)

Outlet boxes or fittings installed as required by 314.23 and complying


SAES-P-123
B7 with the provisions of 314.27(A)(1) and 314.27(A)(2) shall be permitted
Para. 3.2
to support luminaires. [NFPA 70, NEC Art. 410.36(A)]

Page 4 of 8
AL BAWANI QA/QC, 2, FEBRUARY 2016 - R-00 (Standards Cut-off - Dec. 2014) Rev 0 18-May-16

AL BAWANI INSPECTION CHECKLIST BAIC NUMBER DATE APPROVED QR NUMBER

HID Light Fixtures (Low/High-bay) - Assembly, Installation,


BAIC-P-3621 Electrical
and Pre- Commissioning
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

National Guard Family Compound (Industrial Zone) 6600036333 AL BAWANI GENERAL CONTRACTING

Inspection. Luminaires (fixtures) shall be installed so that the


connections between the luminaire (fixture) conductors and the circuit
SAES-P-123
B8 conductors can be inspected without requiring the disconnection of any
Para. 3.2
part of the wiring unless the luminaires (fixtures) are connected by
attachment plugs and receptacles. (NFPA 70, NEC Art. 410.8)

Raceway Supported Enclosure, Without Devices, Luminaires (Fixtures),


or Lampholders. An enclosure that does not contain a device(s) other
SAES-P-123
B9 than splicing devices or support a luminaire(s) [fixture(s)], lampholder, or
Para. 3.2
other equipment and is supported by entering raceways shall not exceed
1650 cm3 (100 in.3) in size. [NFPA 70, NEC Art. 314.23(E)]

Raceway Supported Enclosure, Without Devices, Luminaires (Fixtures),


or Lampholders. Also It shall have threaded entries or have hubs
identified for the purpose. It shall be supported by two or more conduits
SAES-P-123
B10 threaded wrench tight into the enclosure or hubs. Each conduit shall be
Para. 3.2
secured within 900 mm (3 ft) of the enclosure, or within 450 mm (18 in.)
of the enclosure if all conduit entries are on the same side. [NFPA 70,
NEC Art. 314.23(E)]

Raceway Supported Enclosures, with Devices, Luminaires (Fixtures), or


Lampholders. An enclosure that contains a device(s) or supports a
SAES-P-123
B11 luminaire(s) [fixture(s)], lampholder, or other equipment and is supported
Para. 3.2
by entering raceways shall not exceed 1650 cm3 (100 in.3) in size.
[NFPA 70, NEC Art. 314.23(F)]

Flexible Cord. A box shall be supported from a multiconductor cord or


cable in an approved manner that protects the conductors against strain, SAES-P-123
B12
such as a strain-relief connector threaded into a box with a hub. [NFPA Para. 3.2
70, NEC Art. 314.23(H)(1)]

At the luminaire (fixture) end, the conduit(s) shall be threaded wrench


SAES-P-123
B13 tight into the box or wiring enclosure, or into hubs identified for the
Para. 3.2
purpose. [NFPA 70, NEC Art. 314.23(H)(2)]

Where supported by only a single conduit, the threaded joints shall be


prevented from loosening by the use of set-screws or other effective
means, or the luminaire (fixture), at any point, shall be at least 2.5 m (8 SAES-P-123
B14
ft) above grade or standing area and at least 900 mm (3 ft) measured Para. 3.2
horizontally to the 2.5 m (8 ft) elevation from windows, doors, porches,
fire escapes, or similar locations. [NFPA 70, NEC Art. 314.23(H)(2)]

A luminaire (fixture) supported by a single conduit shall not exceed 300


SAES-P-123
B15 mm (12 in.) in any horizontal direction from the point of conduit entry.
Para. 3.2
[NFPA 70, NEC Art. 314.23(H)(2)]

Flexible Cord Pendants. Covers of outlet boxes and conduit bodies


having holes through which flexible cord pendants pass shall be
provided with bushings designed for the purpose or shall have smooth, SAES-P-123
B16
well-rounded surfaces on which the cords may bear. So-called hard Para. 3.2
rubber or composition bushings shall not be used. [NFPA 70, NEC Art.
314.25(C)]

Lampholders. Where a metal lampholder is attached to a flexible cord,


the inlet shall be equipped with an insulating bushing that, if threaded, is
not smaller than metric designator 12 (trade size 3/8) pipe size. The cord SAES-P-123
B17
hole shall be of a size appropriate for the cord, and all burrs and fins Para. 3.2
shall be removed in order to provide a smooth bearing surface for the
cord. [NFPA 70, NEC Art. 410.62(A)]

Bushing having holes 7 mm (9/32 in.) in diameter shall be permitted for


SAES-P-123
B18 use with plain pendant cord and holes 11 mm (13/32 in.) in diameter with
Para. 3.2
reinforced cord. [NFPA 70, NEC Art. 410.62(A)]

Page 5 of 8
AL BAWANI QA/QC, 2, FEBRUARY 2016 - R-00 (Standards Cut-off - Dec. 2014) Rev 0 18-May-16

AL BAWANI INSPECTION CHECKLIST BAIC NUMBER DATE APPROVED QR NUMBER

HID Light Fixtures (Low/High-bay) - Assembly, Installation,


BAIC-P-3621 Electrical
and Pre- Commissioning
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

National Guard Family Compound (Industrial Zone) 6600036333 AL BAWANI GENERAL CONTRACTING

SAES-P-123
B19 Illuminance Levels shall comply with SAES-P-123- Section 6.
Sec. 6

Project Specs.
B20 Install lighting fixtures at locations as indicated. Section 16500
Para. 3.02.A

Project Specs.
B21 Furnish all fixtures complete with lamps. Section 16500
Para. 3.02.B

Project Specs.
B22 Set lighting fixtures plumb, square, level and in alignment. Section 16500
Para. 3.02.D

C. Specific Requirements for HID (High-bay) Lighting Fixtures - Assembly, Installation, and Pre- Commissioning

Ballasts and capacitors for fluorescent and HID fixtures shall be SAES-P-123
C1
Polychlorinated Biphenyl (PCB) free. Para. 5.2.3

LED or High-pressure sodium luminaires shall be used for outdoor area


SAES-P-123
C2 illumination. LED, high-pressure sodium or Metal Halide luminaires shall
Para. 5.2.4
be used for high-bay or low-bay indoor-industrial applications.

Screw-Shell Type. Lampholders of the screw-shell type shall be installed


for use as lampholders only. Where supplied by a circuit having a SAES-P-123
C3
grounded conductor, the grounded conductor shall be connected to the Para. 3.2
screw shell. (NFPA 70, NEC Art. 410.90)

Electric-Discharge Lamp Auxiliary Equipment. Enclosures. Auxiliary


equipment for electric-discharge lamps shall be enclosed in SAES-P-123
C4
noncombustible cases and treated as sources of heat. [NFPA 70, NEC Para. 3.2
Art. 410.104(A)]

Switching. Where supplied by the ungrounded conductors of a circuit,


SAES-P-123
C5 the switching device of auxiliary equipment shall simultaneously
Para. 3.2
disconnect all conductors. [NFPA 70, NEC Art. 410.104(B)]

Electric-discharge and LED luminairessurface mounted over concealed


outlet, pull, or junction boxes and designed not to be supported solely by
SAES-P-123
C6 the outlet box shall be provided with suitable openings in the back of the
Para. 3.2
luminaire to provide access to the wiring in the box. [NFPA 70, NEC Art.
410.24(B)]

Mounting method of lighting fixtures shall be based on the best


SAES-P-123
C7 arrangement for illuminance, as well as easy and safe access during
Para. 5.1.15
installation and maintenance.

SAES-P-123
C8 Illuminance Levels shall comply with SAES-P-123- Section 6.
Sec. 6

Project Specs.
C9 Install lighting fixtures at locations as indicated. Section 16500
Para. 3.02.A

Project Specs.
C10 Furnish all fixtures complete with lamps. Section 16500
Para. 3.02.B

Page 6 of 8
AL BAWANI QA/QC, 2, FEBRUARY 2016 - R-00 (Standards Cut-off - Dec. 2014) Rev 0 18-May-16

AL BAWANI INSPECTION CHECKLIST BAIC NUMBER DATE APPROVED QR NUMBER

HID Light Fixtures (Low/High-bay) - Assembly, Installation,


BAIC-P-3621 Electrical
and Pre- Commissioning
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

National Guard Family Compound (Industrial Zone) 6600036333 AL BAWANI GENERAL CONTRACTING

Project Specs.
C11 Set lighting fixtures plumb, square, level and in alignment. Section 16500
Para. 3.02.D

Page 7 of 8
AL BAWANI QA/QC, 2, FEBRUARY 2016 - R-00 (Standards Cut-off - Dec. 2014) Rev 0 18-May-16

AL BAWANI INSPECTION CHECKLIST BAIC NUMBER DATE APPROVED QR NUMBER

HID Light Fixtures (Low/High-bay) - Assembly, Installation,


BAIC-P-3621 Electrical
and Pre- Commissioning
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

National Guard Family Compound (Industrial Zone) 6600036333 AL BAWANI GENERAL CONTRACTING

REMARKS:

REFERENCE DOCUMENTS:
1. VE-000A03-B-Vol. 003 -- Construction Specification
2. NFPA 70 -- National Electrical Code, 2014
3. SAES-P-123 -- Lighting 9/03/2014
4. Schedule G -- Material, Tools and Equipment, Oct. 2014
5. Schedule Q - Quality Requirements, May 2015

NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labelling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing
states
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified
purpose.
4. Labelled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization
concerned
with product evaluation, that maintains periodic inspection of production of labelled equipment or materials, and by whose labelling the
manufacturer
indicates compliance with appropriate standards or performance in a specified manner.

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 8 of 8