lit/person/d

area ay
student 45
employee 135
teacher 135

Area area ht Occupancy

Basement
FAHU 1 chemistry lab 86 3.4 22
FAHU 1 preparation 8.4 3.4
FAHU 1 physics lab 84 3.4 21
FAHU 1 preparation 7 3.4
FAHU 1 biology lab 74 3.4 19
FAHU 1 preparation 18.5 3.4
FAHU 1 store 23 3.4
FAHU 1 office 12.3 3.4 3
FAHU 1 office 14.4 3.4 4
FAHU 1 corridor 255 3.4 64
FAHU 1 male toilet 38.6 3.4
FAHU 1 male toilet 11 3.4
FLOOR Ground Floor
FAHU 1 Classroom 1 41.5 3.4 10
FAHU 1 Classroom 2 44.7 3.4 11
FAHU 1 Classroom 3 41.5 3.4 10
FAHU 1 Classroom 4 44.7 3.4 11
FAHU 1 Classroom 5 44.7 3.4 11
FAHU 1 Classroom 6 41.6 3.4 10
FAHU 1 Staff Room 26.4 3.4 7
FAHU 1 male toilet 38.8 3.4
FLOOR First Floor
FAHU 1 Classroom 1 41.5 3.4 10
FAHU 1 Classroom 2 44.7 3.4 11
FAHU 1 Classroom 3 41.5 3.4 10
FAHU 1 Classroom 4 44.7 3.4 11
FAHU 1 Classroom 5 44.7 3.4 11
FAHU 1 Staff Room 26.4 3.4 7
FAHU 1 male toilet 38.8 3.4
FAHU 1 Corridor
FAHU 1 principal 82 3.4 21
FLOOR Second Floor
FAHU 1 Classroom 1 41.5 3.4 10
FAHU 1 Classroom 2 44.7 3.4 11
FAHU 1 Classroom 3 41.5 3.4 10
FAHU 1 Classroom 4 44.7 3.4 11
FAHU 1 Classroom 5 44.7 3.4 11
FAHU 1 Staff Room 26.4 3.4 7
FAHU 1 male toilet 38.8 3.4
FAHU 1 Corridor
FAHU 1 LIBRARY 83 3.4 21
FAHU 1 computer lab 47 3.4 12
FLOOR Third Floor
FAHU 1 Classroom 1 41.5 3.4 10
FAHU 1 Classroom 2 44.7 3.4 11
FAHU 1 Classroom 3 41.5 3.4 10
FAHU 1 Classroom 4 44.7 3.4 11
FAHU 1 Classroom 5 44.7 3.4 11
FAHU 1 Staff Room 26.4 3.4 7
FAHU 1 Corridor
FAHU 1 Music Room 47 3.4 12
FLOOR Fourth Floor
FAHU 1 Multipurpose 294 3.8 74
FAHU 1 Rom 44.7 3.8 11
FAHU 1 Store 15.4 3.8 4
(3.25
area sq.m/student)
78 24

TC SC AIR QTY FRESH AIR EXTRACT PRESSURE NOMINAL


KW KW L/S L/S L/S

20.2 15.15 1084 587 700 - 24.6


2 1.5 107 + 2.8
19.7 14.775 1057 181 + 24.6
1.6 1.2 86 + 2.8
17.4 13.05 933 582 700 - 24.6
4.3 3.225 231 + 2.8
5.4 4.05 290 7 + 6.21
2.9 2.175 156 11 + 3.335
3.4 2.55 182 14 + 3.91
59.8 44.85 3208 237 + 73.8
9.1 6.825 488 105 - 10
2.6 1.95 139 70 - 2.99

9.7 7.275 520 87 + 12.3


10.5 7.875 563 95 + 12.3
9.7 7.275 520 87 + 12.3
10.5 7.875 563 95 + 12.3
10.5 7.875 563 95 + 12.3
9.8 7.35 526 87 + 12.3
6.2 4.65 333 25 + 7.1
9.1 6.825 488 210 - 10.6

9.7 7.275 520 87 + 12.3


10.5 7.875 563 95 + 12.3
9.7 7.275 520 87 + 12.3
10.5 7.875 563 95 + 12.3
10.5 7.875 563 95 + 12.3
6.2 4.65 333 41 + 8
9.1 6.825 488 210 - 10
382
19.2 14.4 1030 179 + 20

9.7 7.275 520 87 + 12.3


10.5 7.875 563 95 + 12.3
9.7 7.275 520 87 + 12.3
10.5 7.875 563 95 + 12.3
10.5 7.875 563 95 + 12.3
6.2 4.65 333 41 + 8
9.1 6.825 488 210 - 10
298
19.5 14.625 1046 127 + 24.6
11 8.25 590 102 + 12.3

9.7 7.275 520 87 + 12.3


10.5 7.875 563 95 + 12.3
9.7 7.275 520 87 + 12.3
10.5 7.875 563 95 + 12.3
10.5 7.875 563 95 + 12.3
6.2 4.65 333 41 + 8
165
11 8.25 590 102 + 12.3

68.9 51.675 3696 369 + 84.6


10.5 7.875 563 95 + 12.3
3.6 2.7 193 24 + 12.3
NOMINAL ACH

OU B 1 13.38358
OU B 1
OU B 1
OU B 1
OU B 3
OU B 3
OU B 1
OU B 1
OU B 1
OU B 2
OU B 4
OU B 3

OU GF 1
OU GF 1
OU GF 1
OU GF 1
OU GF 1
OU GF 1
OU GF 1
OU GF 1

OU 1F 1
OU 1F 1
OU 1F 1
OU 1F 1
OU 1F 1
OU 1F 1
OU 1F 1

OU 1F 3

OU 2F 1
OU 2F 1
OU 2F 1
OU 2F 1
OU 2F 1
OU 2F 1
OU 2F 1

OU 2F 3
OU 2F 3

OU 3F 1
OU 3F 1
OU 3F 1
OU 3F 1
OU 3F 1
OU 3F 1

OU 3F 3

OU 4F 3
OU 4F 1
OU 4F 1
SCHEDULE OF VRF AIR CONDITIONERS - BASEMENT

NOMINAL NOMINAL
SR.NO. LOCATION REF. TOTAL SENSIBLE
CAPACITY CAPACITY
KW KW
BASEMENT
1 chemistry lab FCU 14 12.3 9.2
2 preparation FCU 2 2.8 2.1
3 physics lab FCU 14 12.3 9.2
4 preparation FCU 2 2.8 2.1
6 office FCU 4 3.3 2.5
7 office FCU 5 4.0 3.0
8 male toilet FCU 13 10.0 7.5
9 male toilet FCU 13 10.0 7.5

10 store FCU 1 2.2 1.7


11 corridor FCU 15 14.1 10.6

12 biology lab FCU 14 12.3 9.2


13 preparation FCU 2 2.8 2.1
14 male toilet FCU 3 3.0 2.3
15 male toilet FCU 5 4.0 3.0

16 canteen FCU 14 12.3 9.2


17 canteen FCU 3 3.0 2.3
18 male toilet FCU 13 10.0 7.5

SCHEDULE OF VRF AIR CONDITIONERS - GROUND FLOOR

NOMINAL NOMINAL
SR.NO. LOCATION REF. TOTAL SENSIBLE
CAPACITY CAPACITY
KW KW
GROUND FLOOR
1 Classroom 1 FCU 14 12.3 9.2
2 Classroom 2 FCU 14 12.3 9.2
3 Classroom 3 FCU 14 12.3 9.2
4 Classroom 4 FCU 14 12.3 9.2
5 Classroom 5 FCU 14 12.3 9.2
6 Classroom 6 FCU 14 12.3 9.2
7 Staff Room FCU 9 7.1 5.3
8 male toilet FCU 13 10.0 7.5
9 Corridor FCU 14 12.3 9.2

10 Classroom 9 FCU 14 12.3 9.2


11 Classroom 12 FCU 14 12.3 9.2
12 principal FCU 7 5.6 4.2
13 secretary FCU 6 4.5 3.4
14 Admin FCU 6 4.5 3.4
15 nurses room FCU 7 5.6 4.2
16 security FCU 2 2.8 2.1

13 Classroom 7 FCU 14 12.3 9.2


14 Classroom 8 FCU 14 12.3 9.2
15 Classroom 10 FCU 14 12.3 9.2
16 Classroom 11 FCU 14 12.3 9.2
17 Staff Room FCU 9 7.1 5.3
18 Music Room FCU 14 12.3 9.2
19 male toilet FCU 13 10.0 7.5

SCHEDULE OF VRF AIR CONDITIONERS - FIRST FLOOR

NOMINAL NOMINAL
SR.NO. LOCATION REF. TOTAL SENSIBLE
CAPACITY CAPACITY
KW KW
FIRST FLOOR
1 Classroom 1 FCU 14 12.3 9.2
2 Classroom 2 FCU 14 12.3 9.2
3 Classroom 3 FCU 14 12.3 9.2
4 Classroom 4 FCU 14 12.3 9.2
5 Classroom 5 FCU 14 12.3 9.2
6 Classroom 6 FCU 14 12.3 9.2
7 Staff Room FCU 9 7.1 5.3
8 male toilet FCU 13 10.0 7.5

9 Corridor 12.3 9.2


FCU 14

10 Classroom 9 FCU 14 12.3 9.2


11 Classroom 12 FCU 14 12.3 9.2
12 principal FCU 7 5.6 4.2
13 secretary FCU 6 4.5 3.4
14 PRO FCU 6 4.5 3.4
15 principal FCU 7 5.6 4.2
16 security FCU 2 2.8 2.1
17 Meeting FCU 12 9 6.8

13 Classroom 7 FCU 14 12.3 9.2


14 Classroom 8 FCU 14 12.3 9.2
15 Classroom 10 FCU 14 12.3 9.2
16 Classroom 11 FCU 14 12.3 9.2
17 Classroom 13 FCU 14 12.3 9.2
18 Staff Room FCU 10 8 6.0
19 male toilet FCU 13 10.0 7.5

SCHEDULE OF VRF AIR CONDITIONERS - SECOND FLOOR

NOMINAL NOMINAL
SR.NO. LOCATION REF. TOTAL SENSIBLE
CAPACITY CAPACITY
KW KW
SECOND FLOOR
1 Classroom 1 FCU 14 12.3 9.2
2 Classroom 2 FCU 14 12.3 9.2
3 Classroom 3 FCU 14 12.3 9.2
4 Classroom 4 FCU 14 12.3 9.2
5 Classroom 5 FCU 14 12.3 9.2
6 Classroom 6 FCU 14 12.3 9.2
7 Staff Room FCU 9 7.1 5.3
8 male toilet FCU 13 10.0 7.5

9 Corridor 10.6
FCU 15 14.1

10 Classroom 9 FCU 14 12.3 9.2


11 Classroom 12 FCU 14 12.3 9.2
12 LIBRARY FCU 14 12.3 9.2
13 social spl FCU 12 9 6.8
14 audit FCU 5 4.0 3.0
15 librarian FCU 5 4.0 3.0
16 computer lab FCU 14 12.3 9.2
17 computer lab FCU 14 12.3 9.2

13 Classroom 7 FCU 14 12.3 9.2


14 Classroom 8 FCU 14 12.3 9.2
15 Classroom 10 FCU 14 12.3 9.2
16 Classroom 11 FCU 14 12.3 9.2
17 Classroom 13 FCU 14 12.3 9.2
18 Staff Room FCU 10 8 6.0
19 male toilet FCU 13 10.0 7.5

SCHEDULE OF VRF AIR CONDITIONERS - THIRD FLOOR

NOMINAL NOMINAL
SR.NO. LOCATION REF. TOTAL SENSIBLE
CAPACITY CAPACITY
KW KW
THIRD FLOOR
1 Classroom 1 FCU 14 12.3 9.2
2 Classroom 2 FCU 14 12.3 9.2
3 Classroom 3 FCU 14 12.3 9.2
4 Classroom 4 FCU 14 12.3 9.2
5 Classroom 5 FCU 14 12.3 9.2
6 Classroom 6 FCU 14 12.3 9.2
7 Staff Room FCU 9 7.1 5.3
8 male toilet FCU 13 10.0 7.5

9 Corridor 10.6
FCU 15 14.1

10 Classroom 9 FCU 14 12.3 9.2


11 Classroom 12 FCU 14 12.3 9.2
12 Music Room FCU 14 12.3 9.2
13 Music Room FCU 12 9 6.8
14 DR Studio FCU 14 12.3 9.2

13 Classroom 7 FCU 14 12.3 9.2


14 Classroom 8 FCU 14 12.3 9.2
15 Classroom 10 FCU 14 12.3 9.2
16 Classroom 11 FCU 14 12.3 9.2
17 Classroom 13 FCU 14 12.3 9.2
18 Staff Room FCU 10 8 6.0
19 male toilet FCU 13 10.0 7.5

SCHEDULE OF VRF AIR CONDITIONERS - FOURTH FLOOR


NOMINAL NOMINAL
SR.NO. LOCATION REF. TOTAL SENSIBLE
CAPACITY CAPACITY
KW KW
FOURTH FLOOR
1 Rom FCU 14 12.3 9.2
2 Multipurpose FCU 15 14.1 10.6
3 male toilet FCU 13 10.0 7.5
4 Store FCU 14 12.3 9.2

5 12.3 9.2
Female pra FCU 14
6 Male pra FCU 14 12.3 9.2
7 Corridor FCU 14 12.3 9.2
8 store FCU 11 8.6 6.5

10 Multipurpose FCU 15 14.1 10.6


11 Room FCU 14 12.3 9.2
12 Room FCU 14 12.3 9.2
13 Male toilet FCU 13 10.0 7.5
14 Store FCU 14 12.3 9.2
NOMINAL
AIR QTY ON COIL OFF COIL ESP QTY OUTDOOR
UNIT
L/S DEG C DEG C PA KW

538 22.0/17.0 12.5/12.0 75 2 24.6


108 22.0/17.0 12.5/12.0 30 1 2.8
538 22.0/17.0 12.5/12.0 75 2 24.6
108 22.0/17.0 12.5/12.0 30 1 OU-B-1 = 2.8
135 22.0/17.0 12.5/12.0 30 1 82 3.3
135 22.0/17.0 12.5/12.0 30 1 4
483 22.0/17.0 12.5/12.0 75 1 10
483 22.0/17.0 12.5/12.0 75 1 10

97 22.0/17.0 12.5/12.0 30 1 OU-B-2 = 2.2


677 22.0/17.0 12.5/12.0 75 5 78 70.5

538 22.0/17.0 12.5/12.0 75 2 24.6


108 22.0/17.0 12.5/12.0 30 1 OU-B-3 = 2.8
135 22.0/17.0 12.5/12.0 35 1 40 3
135 22.0/17.0 12.5/12.0 35 1 4

538 22.0/17.0 12.5/12.0 75 8 98.4


OU-B-4 =
135 22.0/17.0 12.5/12.0 35 1 3
117
483 22.0/17.0 12.5/12.0 75 1 10

NOMINAL
AIR QTY ON COIL OFF COIL ESP QTY OUTDOOR
UNIT
L/S DEG C DEG C PA KW

538 22.0/17.0 12.5/12.0 75 1 12.3


538 22.0/17.0 12.5/12.0 75 1 12.3
538 22.0/17.0 12.5/12.0 75 1 12.3
538 22.0/17.0 12.5/12.0 75 1 OU-GF-1 = 12.3
538 22.0/17.0 12.5/12.0 75 1 91 12.3
538 22.0/17.0 12.5/12.0 75 1 12.3
233 22.0/17.0 12.5/12.0 35 1 7.1
483 22.0/17.0 12.5/12.0 75 1 10
OU-GF-2 =
538 22.0/17.0 12.5/12.0 75 3 36 36.9

538 22.0/17.0 12.5/12.0 1 12.3


538 22.0/17.0 12.5/12.0 1 12.3
188 22.0/17.0 12.5/12.0 2 11.2
OU-GF-3 =
160 22.0/17.0 12.5/12.0 1 4.5
53
160 22.0/17.0 12.5/12.0 1 4.5
188 22.0/17.0 12.5/12.0 1 5.6
108 22.0/17.0 12.5/12.0 1 2.8

538 22.0/17.0 12.5/12.0 1 12.3


538 22.0/17.0 12.5/12.0 1 12.3
538 22.0/17.0 12.5/12.0 1 12.3
OU-GF-4 =
538 22.0/17.0 12.5/12.0 1 12.3
79
233 22.0/17.0 12.5/12.0 1 7.1
538 22.0/17.0 12.5/12.0 1 12.3
483 22.0/17.0 12.5/12.0 1 10

NOMINAL
AIR QTY ON COIL OFF COIL ESP QTY OUTDOOR
UNIT
L/S DEG C DEG C PA KW

538 22.0/17.0 12.5/12.0 75 1


538 22.0/17.0 12.5/12.0 75 1
538 22.0/17.0 12.5/12.0 75 1
538 22.0/17.0 12.5/12.0 75 1 OU-FF-1 =
538 22.0/17.0 12.5/12.0 75 1 91
538 22.0/17.0 12.5/12.0 75 1
233 22.0/17.0 12.5/12.0 35 1
483 22.0/17.0 12.5/12.0 75 1

OU-FF-2 =
538 22.0/17.0 12.5/12.0 75 8
98.4

538 22.0/17.0 12.5/12.0 1 12.3


538 22.0/17.0 12.5/12.0 1 12.3
188 22.0/17.0 12.5/12.0 2 11.2
OU-FF-3 =
160 22.0/17.0 12.5/12.0 1 4.5
56
160 22.0/17.0 12.5/12.0 1 4.5
188 22.0/17.0 12.5/12.0 1 5.6
OU-FF-3 =
56

108 22.0/17.0 12.5/12.0 1 2.8


483 22.0/17.0 12.5/12.0 1 9

538 22.0/17.0 12.5/12.0 1 12.3


538 22.0/17.0 12.5/12.0 1 12.3
538 22.0/17.0 12.5/12.0 1 12.3
OU-GF-4 =
538 22.0/17.0 12.5/12.0 1 12.3
79.5
233 22.0/17.0 12.5/12.0 1 12.3
483 22.0/17.0 12.5/12.0 1 8
483 22.0/17.0 12.5/12.0 1 10

NOMINAL
AIR QTY ON COIL OFF COIL ESP QTY OUTDOOR
UNIT
L/S DEG C DEG C PA KW

538 22.0/17.0 12.5/12.0 75 1


538 22.0/17.0 12.5/12.0 75 1
538 22.0/17.0 12.5/12.0 75 1
538 22.0/17.0 12.5/12.0 75 1 OU-SF-1 =
538 22.0/17.0 12.5/12.0 75 1 91
538 22.0/17.0 12.5/12.0 75 1
233 22.0/17.0 12.5/12.0 35 1
483 22.0/17.0 12.5/12.0 75 1

OU-SF-2 =
677 22.0/17.0 12.5/12.0 75 8
112 112.8

538 22.0/17.0 12.5/12.0 1 12.3


538 22.0/17.0 12.5/12.0 1 12.3
538 22.0/17.0 12.5/12.0 2 24.6
483 22.0/17.0 12.5/12.0 1 OU-SF-3 = 9
135 22.0/17.0 12.5/12.0 1 91 4
135 22.0/17.0 12.5/12.0 1 4
538 22.0/17.0 12.5/12.0 1 12.3
538 22.0/17.0 12.5/12.0 1 12.3

538 22.0/17.0 12.5/12.0 1


538 22.0/17.0 12.5/12.0 1
538 22.0/17.0 12.5/12.0 1
OU-SF-4 =
79.5
OU-SF-4 =
538 22.0/17.0 12.5/12.0 1
79.5
233 22.0/17.0 12.5/12.0 1
483 22.0/17.0 12.5/12.0 1
483 22.0/17.0 12.5/12.0 1

NOMINAL
AIR QTY ON COIL OFF COIL ESP QTY OUTDOOR
UNIT
L/S DEG C DEG C PA KW

538 22.0/17.0 12.5/12.0 75 1


538 22.0/17.0 12.5/12.0 75 1
538 22.0/17.0 12.5/12.0 75 1
538 22.0/17.0 12.5/12.0 75 1 OU-3F-1 =
538 22.0/17.0 12.5/12.0 75 1 91
538 22.0/17.0 12.5/12.0 75 1
233 22.0/17.0 12.5/12.0 35 1
483 22.0/17.0 12.5/12.0 75 1

OU-3F-2 =
677 22.0/17.0 12.5/12.0 75 7
98 98.7

538 22.0/17.0 12.5/12.0 1


538 22.0/17.0 12.5/12.0 1
OU-3F-3 =
538 22.0/17.0 12.5/12.0 1
59
483 22.0/17.0 12.5/12.0 1
538 22.0/17.0 12.5/12.0 1

538 22.0/17.0 12.5/12.0 1


538 22.0/17.0 12.5/12.0 1
538 22.0/17.0 12.5/12.0 1
OU-SF-4 =
538 22.0/17.0 12.5/12.0 1
79.5
233 22.0/17.0 12.5/12.0 1
483 22.0/17.0 12.5/12.0 1
483 22.0/17.0 12.5/12.0 1
NOMINAL
AIR QTY ON COIL OFF COIL ESP QTY OUTDOOR
UNIT
L/S DEG C DEG C PA KW

538 22.0/17.0 12.5/12.0 75 1 12.3


677 22.0/17.0 12.5/12.0 75 6 OU-4F-1 = 84.6
483 22.0/17.0 12.5/12.0 75 1 120 10
538 22.0/17.0 12.5/12.0 75 1 12.3

22.0/17.0 12.5/12.0 75 1
538 12.3
OU-4F-2 =
538 22.0/17.0 12.5/12.0 75 1 12.3
95
538 22.0/17.0 12.5/12.0 75 5 61.5
483 22.0/17.0 12.5/12.0 75 1 8.6

677 22.0/17.0 12.5/12.0 6 84.6


538 22.0/17.0 12.5/12.0 1 12.3
OU-4F-3 =
538 22.0/17.0 12.5/12.0 1 12.3
131
483 22.0/17.0 12.5/12.0 1 10
538 22.0/17.0 12.5/12.0 1 12.3
90.9
53.2

78.6
62.2

79.5

90.8
119.2

94.7

131.5
SCHEDULE OF TREATED FRESH AIR HANDLING UNIT

TOTAL SENSIBLE
SR.NO. LOCATION REF. AIR QTY
CAPACITY CAPACITY
KW KW L/S
1 ROOF FAHU 1 320 188.2 5540
2 ROOF FAHU 2 364 214.7 6320

SCHEDULE OF CONDENSING UNIT

TOTAL
SR.NO. LOCATION REF. AMBEINT SST
CAPACITY
KW DEG C DEG C
1 ROOF CU 1 320 46.0/30.0 7.2
2 ROOF CU 2 364 46.0/30.0 7.2
ON COIL OFF COIL ESP QTY

DEG C DEG C PA
46.0/30.0 18.0/17.0 400 1
46.0/30.0 18.0/17.0 400 1

QTY

1
1
SCHEDULE OF TREATED EXHAUST FAN

SR.NO. LOCATIONREF. AIR QTY ESP


L/S PA

1 EXF 1 ROOF 700 400

2 EXF 2 ROOF 700 400

3 EXF 3 ROOF 700 400

4 EXF 4 ROOF 1435 350

5 EXF 5 ROOF 350 350

6 EXF 6 ROOF 280 350

7 EXF 7 ROOF 1225 350


TYPE QTY

CENTRIFUGAL CABINET
CHEMICAL RESISTANT 1
BIFURCATED FAN
CENTRIFUGAL CABINET
CHEMICAL RESISTANT 1
BIFURCATED FAN
CENTRIFUGAL CABINET
CHEMICAL RESISTANT 1
BIFURCATED FAN
CENTRIFUGAL CABINET
1
TWIN FAN
CENTRIFUGAL CABINET
1
TWIN FAN
CENTRIFUGAL CABINET
1
TWIN FAN
CENTRIFUGAL CABINET
1
TWIN FAN
kit Bth
shaft 1 ff 2 4
sf 2 4
3f 2 4
4f 2 4
5f 2 4
ph 1 2

shaft 2 ff 2 4
sf 2 4
3f 2 4
4f 2 4
5f 2 4
ph 1 2

shaft 3 ff 2 4
sf 2 4
3f 2 4
4f 2 4
5f 2 4
ph 2 4

shaft 4 ff 2 4
sf 2 4
3f 2 4
4f 2 4
5f 2 4
ph 2 4

shaft 5 ff 2 4
sf 2 4
3f 2 4
4f 2 4
5f 2 4
ph 2 4

shaft 6 ff 2 4
sf 2 4
3f 2 4
4f 2 4
5f 2 4
ph 2 4
shaft 7 ff 2
sf 2
3f 2
4f 2
5f 2
ph 2
80 140 220
80 140 220
80 140 220
80 140 220
80 140 220
40 70 110
1210

80 140 220
80 140 220
80 140 220
80 140 220
80 140 220
40 70 110
1210
80 140 220
80 140 220
80 140 220
80 140 220
80 140 220
80 140 220
1320
80 140 220
80 140 220
80 140 220
80 140 220
80 140 220
80 140 220
1320
80 140 220
80 140 220
80 140 220
80 140 220
80 140 220
80 140 220
1320
80 140 220
80 140 220
80 140 220
80 140 220
80 140 220
80 140 220
1320

0 70 70
0 70 70
0 70 70
0 70 70
0 70 70
0 70 70
420