You are on page 1of 1

Vivant Flats Condominium

1 - Source
2 - Primary Settling
7 - Mixing Box 3 - Activated Sludge (Mod. 1) 9 - Effluent
4 6
5 15
2
1
5 - Sludge Digestion

7
8
9 4 - Gravity Thickener
14
11
13
8 - Mixing Box 10 - Effluent
10
6 - Sludge Dewatering
16

Stream Flow TBOD SBOD TSS VSS TKN NH3-N


ID Description m3/d kg/d kg/d kg/d kg/d kg/d kg/d
1 Sludge Recycle 61.6 231.6 0.8 615.6 461.7 43.8 1.7
2 Effluent from Aeration Tank 210.0 238.8 2.6 629.9 472.4 48.8 5.7
4 Raw Wastewater 147.4 32.4 9.7 32.4 25.9 5.9 3.7
5 Mixed Flow 7 148.8 35.5 11.7 34.6 27.5 6.5 4.1
6 Primary Overflow 148.4 24.9 11.7 13.8 11.0 5.0 4.0
7 Thickener Supernatant 0.9 0.4 0.0 1.1 0.8 0.1 0.0
8 Waste Secondary Sludge 1.1 4.2 0.0 11.3 8.5 0.8 0.0
9 Primary Sludges 0.4 10.7 0.0 20.7 16.5 1.5 0.0
10 Thickened Sludge 0.3 3.8 0.0 10.2 7.6 0.7 0.0
11 Mixed Flow 8 0.7 14.5 0.0 30.9 24.1 2.2 0.0
13 Digested Sludge 0.7 8.7 2.3 20.6 14.5 2.2 0.4
14 Dewatering Filtrate 0.6 2.7 2.0 1.0 0.7 0.5 0.3
15 Secondary Clarifier Overflow 147.3 2.9 1.8 2.9 2.2 4.2 4.0
16 Dewatered Cake 0.1 6.0 0.3 19.6 13.8 1.7 0.1

neering\2016-2017 2nd Semester\CE 132\CE132 Project Wastewater Treatment Design\Design References & Sample\CE132 Group 2 Pr