Professional Documents
Culture Documents
2, Match/April 1975
r
trode (meters)
: Distance betweenapointin
earth (meters)
the electrode and a pointin the i-
-f;-;--
m : Number of subdivisions of the electrode
e : Depth of burial ofan horizontallinearconductor of the elee
trode (meters)
a : Angle between the ox axis and the o'u axis (degrees)
p~ : Length reductionfactor
pp : Resistivity reductionfactor.
1. Theoretical study
r--r--r---- I\
Theelectrode is injecting acurrent Ii in the soil. If the electrode Equation 4, and gives:
length is du then
I = i.du
j J
oj
1+
F
oj
m
E?(++
n=l nJ-
I
yl
nj-
trode, then 6j depends only on the geometrical shape of the electrode
and can be calculated using the matrixmethod [ 6 J . However, inall
practical cases, the worst phase to ground faults to be considered are
faults occuring at the vicinity of a substation. Under this condition the
currentdistribution will be heavier in theconductors which are the
closest to the fault location. ( T h i s has been verified on the scaled down
model. The conductors which were very close to the return electrode
were corroded substantially more than the far ones) [7]. Therefore 6j
must be estimated by the design engineer so as to satisfy equation 8,
electrode configuration and proximity of fault. The following formulae
is proposed to determine 6j.
d .
6.=a 3
J dfj
where,
a is a constant chosen to satisfy equation 8
d d is thedistance between elementj and center of electrode
(effect of electrode configuration)
rl nj- = [(xJ .- xo) 2 + (Yj' YOl2 + c* - (zj-zo)32 I4 d c is the distance between element j and the fault location (effect
of fault proximity)
Ifwe assume a uniform current distribution in the electrode then
1.1.2 Ractical electrode 6 j = l , j = l , . . . m.
Since the potential is a scalar quantity the potential at a point M
1.2.21 Summationmethod of the top layer is the s u m of the potentials due to each element j in-
jecting a current Ij, therefore:
':
If the electrode is large and has a complex geometrical shape(sub-
stations grounding electrode)thenequation 2 can not be used directly.
In order to avoid this difficulty the electrode is divided into small ele-
- 1'
4rrL 1 [ + - m
1
roj
.. .. .
ments 1,2, . ,j, m (figure 4) which can be considered as infintes-
imal. Each
elements
theseof
earth a current Ij such that:
has the same du
length and injects into
253
+-1
'nj+ + k)
nJ+ I
(10)
1.1.22 Integration method
f U
' 0'
(UpJ vpJ (xpJ YpJ extremity Fig. 7. Integration method - horizontal conductor
z =w+zs
z = z = e
S P The total potential at point M due to theconductor is:
0 - x
(16)
I2 0 (wo + 2%) can be obtained by replacing in equation 16 wo by
wo + 2%.
Thus V can be written in a convenient symbolic formas V W
z
Fig. 8. Integration method - non horizontal conductor
Where up, b,vo, wo are related to the xyz coordinates by the follow- 2.1.223 Case of an electrode made of interconnected linear conductors
ing relations:
The potential at a point hj (k, yo, zo) at the top layer will be the
UD = (XD' x ) cow
S
+ (yD-
*
ys) sinrr
-
sum of the potentials due to each linear conductor as calculated by
.equation 17. If a linear conductor is indicated by letter j then the total
u = (xo- xs) c o w
0
+ (yo- ys) sinr (18)potential can bewritten as:
When p i , K, I, L, xp, xs, yp, ys, 4, zp and u are known (earth and Where
electrode d a h ) equation 17 gives the potential V ateachpoint M L is thetotallength of buriedconductors
o9 (x09 %I. of numbertotalm is the linear conductors
up, b,vo, wo being given by equation 18 for horizontal conduc-
2.1.222 Case of a non horizontal linear conductor tors and by equations 19 and 20 for non horizontal conductors. Thus
the final equation will be a function of the following parameters:
This case is shown in figure 8. The uvw coordinatessystem is
chosen so that the conductor is in the plane UO'V.' The origin of the Pyk,1,L,Xs,Ys,Z ,x ,Y > z ,x ,YO,ZOYQ
S P P P O
uvw coordinates being the point xs,y,, zo (point M in plane uo'v),
thus: which are earth and electrode characteristics.
u = v =o
s s 1.2 Electrode grounding resistance
v =o
P The resistance of ground electrodes can be calculated as follows.
Let a be the radius of the buried electrode conductors and let's calcu-
w
9
=
zs - zo late the potentials Vi at different points in earth located at a distance a
from the centre of a conductor. The resistance of the electrode is then
w Z' - 2
P P O given by:
. N
The potential due to this conductor at the point M (u,,, yo, 0) is
identical to that due to an horizontal conductor on the o'u 'axis at a (22)
point M' (do, v',; 0 ) such that: the new equivalent horizontal con-
ductor characteristics are:
Where:
N is thetotalnumberofpointswherethepotential has been
calculated.
The potential can be calculated either by the summation method
or by the integration method.
ut
P
= d u + (wp - ws) 2 2.3 Ground resistance measvrements (mutual resistance)
Direction I Direction
1 I 3
Direction
2
and Vxy is the potential at point y due to electrode X. The potential Fig. 10. Grounding grid configuration
Vxy Can be also calculated by either the summation method or the
integration method.
Note that the second layer resistivity was chosen such a way that
K = 0.6, which corresponds exactly to the reflexion factor measured on
the scaled down earth model [ 1,71. This condition was essential in
order to satisfy the similarity criteriabetween the real and model
earth [7].
Experimental earth surfacepotentialsmeasurements were also
carried outonthe twolayer earth model scaled downbyafactor
ML = 78.7 (1 inch = 2 meters). The model first layer resistivity (water)
was 20 ohm-meters, thereforetheresistivity scale factor pp = 200/
20 = 10.
Simulation criteria study [71 shows then that the potential meas-
ured values on a model having reduction factor p~ and pp are related
Fig. 9. Fall of potential method in ground resistance measurements to thereal case by the following relation:
'real
-
- 'model x -
Ireal
x
3 pT, (26)
Note that it is assumed that the current return electrode c is small I
Where i is a succession of M points taken on the return current The calculated earth surface potentials and the modified experi-
electrode c. mental values were carried out for the different directions 1, 2 and 3
BySolving equation 23, the value of the required probe position &own in figure 10. The theoretical and experimental results were re-
x,,is determined
together
corded
[ 11. in figures 11, 12 and 13.
200 - ---.-e
-- merimental results
I n t e g r a t i o n method
Summation method
K = B800 - 200
~ ~ 0 .+ 6 ~ ~
256
4. Conclusion
c,
3 200
- Summation method ACKNOWLEDGMENT
0
a Theauthors wouldlike to express their appreciation tothe
National Research Council of Canada and the Department of Energy,
-14
-10 -6 -2 2 6 10
14
Mines & Resources of Government of Canada for providing the neces-
Y (meters) sary fmancial support of the work. The authors would like to thank
Figure 12. the management of the ShawiniganEngineering Company Limited,
Montreal, Quebec, for their cooperation.
REFERENCES
t.......
-14
-10 4 -L
Summation method
2 6 10
14
[6]
171
sique et Radium, Vol. 1, Sene VII, No. 4, 1930, pp. 132-140.
T. N. Giao, M. P. Sarma, Effect of two layer earth on the electric
fieldnear HVDC electrodes, IEEE Transactions, Vol.PAS-91,
No. 6, November 1972, pp. 2356-65.
F.Dawalibi, Etude sur modsle riduit duneprise de terre dans
un sol non homoghe, MS Thesis,Ecole Polytechnique, Mon-
Y (meters) treal 1972.
Figure 13.
.........
2.34 2.n
* + * + + + +I..
(1111
.++++++
1.n
.....1-46
X.....X.....X.....I
++++++++++
1.16 -87 81
.++++++
.+++**
.*+*
.+++
.. +++w
+*
.. ++ +* ++ **
It++++*
.*++*++
.++*++*
.+++*++
Figure 1 .++++++
.+++*++
.+*++++ +**++*+*+++
.++++** *+*++++*+*+++++++
.++++*+
.+++***
ow++*+++
.++*+**
grounding griddesigned to meet the usual safety requirements at a .++++++
.++++** 1 M U V YU
typical 138/23 kV substation switchyard with a crushed stone layer, .++++++
covering soil with resistivity below 75 meter-ohms. .++++*+
Anticipated ground current carried by the grid is 10 kA, the fault .. ++ +* *++++ ++ +
clearing time 0.3 seconds, and the depth of burial is 0.5 meters. The
.*++++*
.++++*+
ground grid itself consists of 6 X 4 conductors covering the rectangular st++++++
area of 70 X 50 meters. For the above conditions, the safe limit for
.. +* ++ *++++* ** +++++++
+++++++**
touch voltage inside the switchyard is approximately 1.66 kV. .++*+++ ++****++*++++u
.+++++* ++++++**++**+*
There are severalinteresting facts to be observed. .++*+++ +*++***+*
First, since ourcomputer programcan besetto optimize the .+**+*+ ++++++++
.+++++* ++++++
grounding design on the basis of standard grounding calculations as .*+++++
established in (1 l), the resulting grounding system will meet all the .+++++*
4 e + * + + + *
safety requirements established by an engineer designing this system by .++*++*
conventional methods. .++++++
.++++++ 16.1 YFTEPS
Second, having also available an advanced integration method .+*+++*
which can be employed to produce the potential profie plotof the .++*++*
.+++**+
givendesign, it is easy to evaluate the effectiveness of the simplified .. +
++++
+++ ** ** + *+*++
+++*+*++
approach previously used. .+++++* **++++*++*
If the engineer follows the procedures of IEEE Guide No. 80, he st+++*** + + + + + + + + + + + + + * + 4 +
will realize that equation No. 68 and No. 69 give the touch voltage .++++++ ++++++++*++*
.+++++* ++++++**
value only for the mesh rectangle nearest to the perimeter. Therefore, .++++** *+*+++
he will often economize the design by assuming that, say, no more than .+++++*
.++++++
85% of this value can be expected for theremaining meshes toward the .++++++
center, readily accepting the necessity to subdivide only the corner .*+++++
.++++++
meshes by additional conductors. .+++++*
6 C + + + + + +
This is, of course, the same as designing a grounding system which .++++++
will meet a touch voltage limit of 1.66 kV/.85 = 1.95 kV for the un- .++++++
.++++++
corrected meshesclose to perimeter, while hoping thatthetouch .++++*+
voltage of inner meshes will nowhere exceed the safe value of 1.66 kV. .++++++ +++++++
.++++++ +++++++++++
As it can be observed, this condition has been successfully met in .++++++ +++++++*+++*+++*+u
Figure 2. .++++++ +*++*++++
.++++*+
However,a different picture emergeswhen the soil resistivity is 7w++++++
increased to the value of 150 meter-ohms, Figure 3. .++++++
.++++++
On one hand, not only the nearest, but several meshes close to the .++++*+
perimeter show the mesh voltage well above the required safe limit, d e .++++++
.++++*
spite the fact thatthe design limit waslowered from 1.95kV t o .++++
1.82 kV, and more dense pattern of grid conductors was used. ++* Zl3 KV UU
:++-
On the other hand, the middle portion of the grid appears to be
overdesigned,resultingin touch voltages much lower thanthe safe
value for these center meshes. .. +. .+ .+.+. *. *
Obviously, a grounding grid with equal spacing of conductors may
not be the best solution in many cases, and utilizing of some kind of
..+..++~~~::~+++
unequal spacing technique seems to be desirable. #
However, based on our experience, a word of caution fmt:
1. Unexpectedly, the unequal spacing technique does not neces- Figure 2
sarily guarantee a significant reduction in the number of conductors,
but often assures only their better utilization.
2. It is veryeasy to achieveareverse effect. Dangerous touch We believe that the Authors will c o n f m this or similar concepts
voltages can appear in the center portion of a grounding grid as a result for the optimum grounding electrode configurations in the second part
of even moderate, but uncoordinated changes in spacing.Figure 4 of their paper being prepared.
demonstrates this point. Also, with regard to IEEE Guide No. 80, the forgoing discussion
As shown, the attempt to lower the number of meshes from 13 to was brought out in the hope that the Working Group presently revising
9 by a gradual increase of spacing toward the center, given as 3, 6, 8, this Guide will extend and generalize the equations of the Appendix,
13, 15, 13, 8, 6, and 3 meters, (asopposed to the equal spacing of 6.16 relating them to the unequal spacing and multi-layer ground techniques,
meters for thirteen conductors), produced unsafedesign, with pro- since to-date the Guide deals exclusively with equal spacing and uni-
gressively worse conditions toward the center. form soil concepts. Increasing availability of computers presently seems
Finally, in order to show that the unequal spacing technique is a to justify such a request.
practical approach which can be successfully applied in most cases, an Last but not least, reference should be made to J. Zaborsky 191
optimal solution for the given example is shown in Figures Sa and 5b and E. T. B. Gross et al. [ 101 for the pioneering application work done
respectively. in the method of images and utilizing of integration methods.
258
STATIOl BROUlD POTEITIALPROFILE CLOT
"+++++++++++++++
I I
1.96 1.58
I.... ..... .........
1.19
I
.81
I-
.++++++++++++++++++ .+++++++++++++++ 3METERS
. + + + + + + + + + + + + + + + + + ,,13Kvy*x .+++++++++++++++~ ~ + + + + + + + + +
t
.++++++++++++++++ .+++++++++++++++ +++++++
.++++++++++++++++ .+++++++++++++++
I * + + + + + + + + + + + + + + + + + + .+++++++++++++++ 6 METERS
. . . . . . . . . . . . . . . . . . . . . .+++++++++++++++ +++++
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . + + + + + + + + + + + + A + +
.'++++++++++++++ + ++
+ t + + + + L + + + * +
. . . . . . . . . . . . . . . . . . . . . . . .+++++++++++++++
.++++++++++++++++++++++
. . . . . . . . . . . . . . . . . . . . . . . .
.+++++++++++++++
.. + + + ' + + + + + + *
I " - + + + + + + + + + + + +
+ + + + + + + + + + +
.+++++++++++++++
.+++++++++++++++
.. ++ ++ ++ ++ ++ ++ ++ ++ ++ +++++++++ +
zc+++++++++++++++
.+++++++++++++++
.. ++ ++ + + + + + + + + + + + +
+ + + + + + + A ' + + +
.+++++++++++++++
.+++++++++++++++
.+ + + + + + + + + + + +
.+++++++++++++++
.+++++++++++++++
. ++ ++ +++ +++ ++++++ ++ + +
.++
.+++++++++++++++
,+++++++++++++++
.. ++ ++ ++ ++ ++
27-
.+++++++++++++++
.+++++++++++++++ .. '+ ++ ++ +++++ + +
a*+++++++++++++++
.+++++++++++++++ .. ++ ++ ++ ++ ++ ++ ++ ++ ++ + + +
.+++++++++++++++
.+++++++++++++++ .. ++ ++ + + + + + + + + + + + +
+ + e + + + + + + +
.+++++++++++++++
.+++++++++++++++
.+++++++++++++++ -... ++ +++ +++ +++ ++++++ + +
x*-
.+++++++++++++++
.+++++++++++++++ . + + +++
. + + + +
.+++++++++++++++
4 b + + + + + + + + + + + + + + +
.+++++++++++++++ .. + + + +
. + + + +
+ +
ro2uvwu
.+++++++++++++++ .+++++
.+++++++++++++++ .+++++
.+++++++++++++++ .++++++
.+++++++++++++++ 4:-++++++++
.+++++++++++++++ .+++++++++++
,+++++++++++++++ .++++++++++++++
.+++++++++++++++ .++++++++++++
.+++++++++++++++ .+++++++++
s c + + + + + + + + + + + + + + + .+++++++
.+++++++++++++++ .++++++
.+++++++++++++++ .+++++
.+++++++++++++++ .+++++
.+++++++++++++++ . + + + + +
.+++++++++++++++ 5 e - + + + + + + U
-I 9mm
.+++++++++++++++ .++++++++
.+++++++++++++++ .+++++++++++
. . . . . . . . . . . . . . . . . . . . . . . . .++++++++++++++
. . . . . . . . . . . . . . . . . . . . . . .
sc++++++++++++ +++ ++++++u .+++++++++++++++
. . . . . . . . . . . . . . . . . . . . . . . . .++++++++++++++ KV 124 SAFE LlYlT
. . . . . . . . . . . . . . . . . . . . . . . . .++++++++++*
. . . . . . . . . . . . . . . . . . . . . .+++++++++++
.++++++++++++++++++ .++++++++++++ I d 6 KV DESIGN LlYlT
.+++++++++++++++++ < * - . L .& &. A . & .A a. A . * .' A. L . + .A . . .
.++++++++++++++++
_I
.++++++++++++++++
.+++++++++++++++++ .+++++++++++++++
.+++++++++++++++++++ . + + + + + + + + + + + + + + + g+ $ + + + +++ ++++'+*
.+++++++++++++
7 6 + + + + + + + + + +
.++++++++
~ 181 KV DESIGN LIMIT .+++++++++++++++
.+++++++++++++++ + + + ++
.+++++++ .++++++++++++++++ + + + + + + + + + + ,
.+++++++ .++++++++++++++++ ++
.++++++++ .+++++++++++++++ + + ++
ttf ftt
Figure 3 Figure 4
259
V U l Y C SPACII1
mwqw 1161 - I.5W
.IH
4.32 3.11 3.11 2.e 1.88 1.21 .66 a .m
1M11.........1......,.,1.........1.........1.........1.........1 I#.yI
c++++++++++.++++ .sm
.+++++++++++++++ n.m
. . . . . . . . . . . . . . . . . . . . 5e.m
. . . . . . . . . . . . . . . . . . . . . . . . . . . 4w.m
. . . . . . . . . . . . . . . . . . . . . . . .m
.++++++++++++++++++++u wn
. . . . . . . . . . . . . . . . . . . . . . . w .m
...............................
.++++++++++++++++++++++++u
I1 1.m
. . . . . . . . . . . . . . . . . . . . . . . . 1s.m
I c + + + + + + + + + + + + + + + + + + + + + + u
.++++++++++++++++++++++++u
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. ~ + + + + + + + + + + + + + + + + + + + + + + u
.+++++++++++++++++++++++
.+++++++++++++++++++++++
. . . . . . . . . . . . . . . . . . . . . . . . .
.++++++++++++++++++++++++++
.++++++++++++++++++++++++++++++
2 c + + + + + + + + + + + + + + + + + + + + + + ~ + + + +
.++++++++++++++++++++++++
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
.++++++++++++++++++++++
.+++++++++++++++++++++++
.+++++++++++++++++++++++++
.++++++++++++++++++++++++++u
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.++++++++++++++++++++++++
se+++++++++++++++++++++++
.++++++++++++++++++++++ 1 I KV SAFE k D
EW LIMIT
.++++++++++++++++++++++-
,++++++++++++++++++++++
. + + + + + + + + + + + + + + + + + + + + + + b
. . . . . . . . . . . . . . . . . . . . . . . .
.+++++++++++++++++++++++++
. . . . . . . . . . . . . . . . . . . . . . . . . . .
,+++++++++++++++++++++++++
.++++++++++++++++++++++++ 9 1
4 e - + + + + + + + + + + + + + + + + + + + + + + b
. + + + + + + + + C + + + + + + + + + + + + + b
. . . . . . . . . . . . . . . . . . . . . . .
. + + * + + + + + + + + + + + + + + + + + + + b
.+++++++++++++++++++++++
. . . . . . . . . . . . . . . . . . . . . . . . .
oI1IyIZED u*Qy* WAaUG
160 m n o y SUIL 7 7
.+++++++++++++++++++++++++++
.++++++++++++++++++++++++++++
.+++++++++++++++++++++++++
. . . . . . . . . . . . . . . . . . . . . . . . .
S C + + + + + + + + + + + + + + + + + + + + + + b
. . . . . . . . . . . . . . . . . . . . . . . . ILuPt P A l l R l OF A I D C A Q P IS I3 X
,+++++++++++++++++++++++ 8:
.+++++++++++++++++++++++++
.+++++++++++++++++++++++++++ a I o c o m m M U In x NI ..................jni, s1.1
x
.+++++++++++++++++++++++++++++u A
.*++++++++++++++++++++++++++
.++++++++++++++++++++++++
a10 a m m SIM RATIO USED...............
I D S P A C I ~ P . m m m SIZE IM x WI
TOTU PRID C WO IC mn LeeIH 1111
........ t
...................
X
1.IS9
1.143
1241.464
.+++++++++++++++++++++++ T O T U LP8211 OF ROO a ECnoDCS IMI................ 1m.m
. . . . . . . . . . . . . . . . . . . . . . . . T O T U LLIBTH or SIRIED C M I W C T ~1111.............
~ C + + + + + + + + + + + + + + + + + + + + + + + U u u e a or RODS .................................1311.484
.P.8 . M
.++++++++++++++++++++++++++++
.+++++++++++++++++++++++++++++++
. . . . . . . . . . . . . . . . . . . . . . . . . .
,++++++++++++++++++++++++
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
.++++++++++++++++++++++
T C + + + + + + + + + + + + + + + + + + + + U
..........................
.+++++++++++++++++++
.* ++ ++ +& +&+&+ *+&+ a+ *+ &+ &+ +* &+ +&
. . .
f.. I
Figure 5a
mean
no. SPACIIB
IMI
REFERENCES I
2
2.Qt
2.m
3 1.55 6
J. Zaborszky, Efficiency of Grounding Grids with Nonuniform 4
5
1.51
I .as
Soil, IEEE Trans. Power Apparatus and Systems, Vol. 74, 6 1.lU
pp. 123G1233, December, 1955. 1 I.1N
8 1.8)
E. T. B. Gross, B. Thapar,Grounding Grids for High-Voltage 9 I.HI
Stations, Part IV - Resistance of Grounding Grids in Nonuni- I1
11
1.556
2.61
form Soil, IEEE Trans. Power Apparatus and Systems, Vol. 81, I2 0.682
pp. 782-788, October, 1963.
IEEENo. 80/March 1961, Guide for safety in Alternatine m
Current Substation Grounding, American Institute of Electrical
Engineers, New York, 1961. Figure 5b
260
A. B. Purdy (Appalachian Power Co., Roanoke, Va.) and W. J. Lyon tion between the substation and the current electrode. In such a case,
(American Electric Power Service Corp., Canton, Ohio): Mr. Mukhed- whats the authorsopinionabout the correctprocedure? Have the
kars potential calculations appear to be very thorough and inclusive. authors made any comparison between the results obtained with the
This allows the calculation of ground resistance for all types of elec two methods? If so, what were the result? Finally, I would like to know
trodes in a two-layer earth structure. His fall of potential method in how the authors choose the distance between the ground grid and the
ground resistance measurementsagrees with our field fidings. current electrode.
We have been tryinga simplified equationforgroundmat re-
sistance in a two-layered earth structure:
R =-(-)+
27r rm p z2n
- (+
rm+h
h = height of first layer (4 ft.) Farid Dawalii and Dinkar MukbedLar: The discussers comments add
rm = radius of equivalent hemispherical electrodes considerably to the meaningfulness of the paper and are sincerely a p
Using Mr. Mukhedkars values: preciated. We would like to inform Mr. Silva that we are aware of Dr. J.
Endrenys work and we did not compare our results with his work.
192 - When carrying out the measurement by the fall of potential meth-
rm plate = - lr
- 7.85meters o d , we assumed a two layer earth and used our computer program to
Using this value: detennine the exact position of the potential probe. For better under-
standing of the procedure used reference is made to paper T-73-361-3
or reference 1 of this paper.
Simplified formula proposed by Messrs. Purdy & Lyon seems very
This agrees verywell with the calculated and measured values attractive for a preliminary and quick estimation of ground grid r e
given. We would normally increase. our values by 50% to correct for the sistance in a two layer earth.However, in ground electrodedesign earth
change from a plateto the equivalent hemisphere. surfacepotentialandgrandient is of prime importance and toour
We hope Mr. Mukhedkar can give us a simplified method useful for knowledge there is no simplified formula which gives reliable results
approximating results. for non uniform soils and/or complex electrodes.
Mr. Mukhedkar, what is your opinion as to the gradients that will Small stations which experience heavy faults should be designed
exist external to the station grid duringfaultconditions. Especially with extreme are. Even,if the potential profiie inside the station is
when station sizes in industrial plant areas are very small (2Om X 2Om) kept flat, the step potential at the perimeter of the station will be tre-
and fault currents are inthe 10s of thousands of amperes. mendously high and therefore, undoubtedly hazardous Special investi-
gations ofnew forms of electrodes may be necessary. This is one
Manuscript received February 13, 1974. special condition where computercalculations could beextremely
valuable. Another problem which may beof importance is the high
potential rise of the substation and its consequence on communication
circuits or other circuits (pipelines, railways) which enter or run close
to the station.
We are particularly pleased with Mr. Sverak encouragements and
A f o m De Oliveira E Silva (Cemig, Be10 Horizonte, Brazil): I would like comments. We agree completely with him for the necessity of revising
to compliment the authors for the presentation of new and more exact IEEE guide no. 80. The actual trend for increased short circuit levels,
methods of calculation in a field where the agreement between meas- UHV transmission systems and the escalation in copper price justify
ured and calculated values is in general very poor. My comments will more exact methods for groundingdesign.
be limited to the ground grid resistance calculation and measurement. Since we do not have details of Mr. Sverak computer program, we
In my company we have been using a method of calculating the will not be able to discuss his comments on a quantitative base. How-
grid resistance proposed by J. Endreny, of Ontario Hydro, some years ever, we agree almost completely with his conclusions. The most im-
ago. Sometimes the discrepancy between the calculated and measured portant step in groundingdesign is calculation of earth surface potential.
value is very large.Have the authors made any comparison between When this quantity is known, step and touch potentials can be com-
the two methods? We are beginning research to detennine the causes pared to the safe values. Optimization of the electrodes will follow, the
of the discrepancies, including both the methods of measurement and final form of the electrode will depend on many parameters such as
calculation and this paper will be of great value for us. faultcurrent, earth resistivities, substation size, etc. Unequal spacing
We measure the grid resistance by placing the current electrode at between conductors may save copper however it should be applied with
acertain distance from the substation and varying the position of the care. Such studies are only practical when computer programs are,
potential probes until we obtain three measured values within 10% of available, otherwise oversizing the electrode is necessary if safety must
their mean value, and adopt this mean value as the ground resistance. be reached. In part I1 and 111, as pointed out by Mr. Sverak, we will
Sometimes its necessary to place the current electrode at a very large compare briefly different formsof electrodes and show the performance
distance from the substation to obtain the desired result. of each under the same conditions.
In making the measurement with the potential probe at a fixed Much more work is still necessary before one can understand per-
distance from the substation, the authors are assuming that the charac- fectly all the influence of the numerous parameters involved. We are
teristics of the soil are uniform to the current electrode. When t h i s dis- still investigating in this field.
tance is large, the characteristics of the soil will certainly suffer avaria- Professor E. T.B. Grosss work is referred in part I1 & 111.
Manuscript received February 7,1974. Manuscript received November 20, 1974.
261