11172 Cable length, based on the voltage level, is near the limit.

This message appears when a cables length based on the nominal voltage level is larger than
0.8 times of the limit.
11180 Cable length (ft), compared to average of other cables, is larger than the limit.

This message appears when the cable length is larger than 2 times of the limit. The limit is
calculated based on the average of cable length of all other cables.
11190 Impedance of this branch, based on the voltage level, is larger than the limit.

This message appears when the impedance of cable, impedance or transmission line is larger
than the limit as set below.

Voltage Level Default Value Minimum Maximum


INI Variable
(kV) (p.u.) (p.u.) (p.u.)
<1 LF_OutRange_Impedance_1kV 300 1 1000
1 & < 35 LF_OutRange_Impedance_35kV 300 1 1000
35 & < 110 LF_OutRange_Impedance_110kV 300 1 1000
110 LF_OutRange_Impedance_P110kV 300 1 1000

11192 Impedance of this branch, based on the voltage level, is near limit.

This message appears when the impedance of cable, impedance or transmission line is greater
than 80% of the limit.
11196 Impedance of this transformer is larger than the limit.

This message appears when the impedance of a transformer is larger than the limit as set
below when load flow does not converge or is larger than 2 times of the limit as set below
when load flow converges.

Default Value Minimum Maximum


INI Variable
(%) (%) (%)
LF_OutRange_Impedance_Transformer 7 3 10

11198 Impedance of this transformer is near limit.

This message appears when the impedance of a transformer is less than but greater than 80%
of the limit.
11200 Impedance of this branch (Line, Cable and Impedance) compared to average of other branch impedances is larger than the limit.
This message appears when the impedance of a Cable, Impedance or Transmission Line is
larger than 2 times of the limit. The limit is calculated based on the average impedance of all
other branches.
11210 Susceptance of this branch (Line, Cable and Impedance), based on the voltage level, is larger than the limit.

This message appears when the susceptance of cable, impedance or transmission line is larger
than the limit as set below.