Line protection REL 100

1MDB06308-YN
Page 1
Issued Oct 1999
Changed since June 1998
Data subject to change without notice

(SE970130)
Features Simultaneous phase-phase and phase- Positive sequence voltage used for direc-
earth loop impedance measurement, with tional discrimination ensures correct direc-
individual numerical measuring elements tionality even for evolving multiphase faults
for each type of fault and each distance close to the relay point.
zone, ensures fast and reliable fault detec-
Extensive self supervision with fault diag-
tion.
nostic presented on the HMC unit.
Minimum operating time: 13 ms
Detailed reporting for last three distur-
Typical operating time of impedance mea- bances allowing up to 150 time tagged
suring function: 28 ms. events for each disturbance when com-
bined with SMS.
Multiprocessor design guarantees high
availability together with excellent possibili- Basic version of REL 100 includes:
ties for combining optional functions.
- three forward and one reverse distance
Numerical filtering and measuring tech- zones with individual setting of reach in
nique ensure correct performance during reactive and resistive direction as well
CT saturation and CVT transients. as setting of earth return compensating
factor
Versatile local human machine communi-
cation (HMC) from the relay front panel - high set instantaneous overcurrent pro-
together with two optional serial ports tection
brings REL 100 close to the any user wher-
- switch onto fault protection
ever they may be located (in the substa-
tion, in the control centre or in the office). - eight different communication schemes
with built in unblocking function and cur-
rent reversal logic
- three-phase tripping
ABB Line protection REL 100
1MDB06308-YN
Page 2

Features (contd) The following functions are available as - fuse failure supervision function
options:
- synchro-check and dead line check
- 16 programmable signalling output function
relays
- supervision of protected power line
- two additional distance measuring
zones with programmable directionality - stub protection

- phase selective single phase tripping - weak end infeed trip and echo logic

- extensive phase preference logic for - directional or nondirectional earth fault


applications in isolated or resonantly overcurrent protection
earthed networks - accurate fault locator based on well
- power swing detecting element with pro- proven measuring algorithm
grammable effect on different zones

Application REL 100 line protection terminal represents Basic functions


the basic part of REL 1xx HV and EHV line The basic protection function in the REL 100
protection terminals that form a part of the line protection terminal is a full scheme dis-
PYRAMID system. The PYRAMID system tance protection with individual measuring
includes a complete range of complex object elements for different types of faults in differ-
terminals, functional substation monitoring ent impedance zones. The basic relay
and substation control systems. The blocks in includes three forward and one reverse imped-
PYRAMID can be used as stand alone protec- ance zone.
tion units or as building blocks in a complete
Substation Monitoring System (SMS), Sub- The quadrilateral characteristics of each
station Control System (SCS) and/or Relay impedance zone with individual and indepen-
Testing System (RTS). dent setting of reach in reactive and resistive
direction as well as for zero sequence com-
The REL 1xx series includes line protection pensating factor, ensures an optimized appli-
terminals for high and extra high voltage cation for all line length on single lines as
applications. The following terminals, based well as on lines within complex network con-
on numerical distance line protection, are figurations. A quadrilateral characteristic
available: ensures the maximum resistive coverage for
all faults and maximum limitation of load
REL 100 distance protection with or without influence. The load compensated part of the
options reactance characteristic makes REL 100
REL 111 distance protection with or without
applicable for protection of heavily loaded,
options, numerical auto-reclosing long transmission lines.
relay REXA 101
The full scheme distance relay's ability
REL 113 distance protection with or without
options, numerical auto-reclosing to cover evolving faults, faults between dif-
relay REXA 103 ferent circuits on multi-circuit lines and
simultaneous faults makes selective clearing of
REL 120 distance protection with or without
these faults feasible even for sub transmission
options, numerical disturbance
recorder RCRA 100
lines.
REL 131 distance protection with or without
An instantaneous overcurrent protection
options, numerical auto-reclosing
function is added to the basic under imped-
relay REXA 101, numerical distur-
bance recorder RCRA 100
ance function in order to reduce the tripping
time for faults characterized by very high
REL 133 distance protection with or without
fault currents, which can critically influence
options, numerical auto-reclosing
system stability.
relay REXA 103, numerical distur-
bance recorder RCRA 100
ABB Line protection REL 100
1MDB06308-YN
Page 3

Three-phase tripping is provided in the basic Additional functions : Option1


version of REL 100 and single phase tripping Many additional functions in the line protec-
can be obtained for single phase to earth tion terminal REL 100 may be achieved by
faults when the optional microprocessor with optional microprocessors, which can be
additional functions is installed. installed on request without any changes to
the standard REL 100 hardware. The phase
Eight communication schemes have been selection function with separate measuring
incorporated into REL 100 and are con- elements is one of such additional functions.
nected, by logic to different impedance It makes possible single pole tripping of the
zones.Thus most needs on existing communi- circuit breaker for single phase to earth faults
cation schemes, based on zone extension, per- as well as selection of any kind of phase pref-
missive overreach and underreach transfer erence logic if REL 100 is used in isolated or
tripping as well as on blocking principle, can resonantly earthed networks.
be covered. In addition, an unblocking princi-
ple, in two different modes, can be used with Separate and independent setting of reach in
the permissive schemes. both the reactive and resistive directions
makes phase selection in REL 100 independent
In order to prevent the unnecessary tripping of heavy load currents, even when used on long
of healthy systems in multi-circuit lines, a transmission lines.
local current reversal logic can be activated in
REL 100. Communication schemes and cor- The power swing detection function has inde-
responding logic functions can be changed at pendent setting of reach in the resistive and
any time simply by entering the new setting reactive directions. Its measuring principle is
within the setting menu. based on measurement of the transient imped-
ance transition time between two concentric
A built-in switch onto fault function provides impedance polygons. The resulting function
instantaneous three-phase tripping for the can be programmed for each distance zone
whole line section if the circuit breaker is separately.
accidentally closed into a fault. This function
can be activated by an external signal from The fuse failure supervision function is based
the CB control switch or by special logic built on detection of zero sequence voltage without
into a separate optional signal processor. a presence of zero sequence current. Its effect
on operation of distance protection function
Using the HMC unit, RTIA mounted on the can be programmed either to block imped-
front of REL 100, four groups of setting ance measurement or to give information on
parameters may be entered. This same unit fuse failure only.
offers information about the last three distur-
bances, presenting values and phase angles of The synchro-check and voltage check func-
currents and voltages before and during the tions make application of REL 100 line pro-
fault, logic signals during each disturbance as tection terminal possible in cases when the
well as the location of the fault (only if the auto-reclosing function is conditioned by
optional fault location function is included). check of synchronism or zero line voltage.
No additional hardware is necessary for this
Further more, it takes over the functionality purpose.
of measuring instruments installed on the
line, like A-meter, V-meter, var-meter and W- Weak end infeed logic is available, which can
meter. Directionality testing during commis- be programmed to issue echo of communica-
sioning becomes routine using REL 100 and tion signal or also trip a circuit breaker. When
its human machine communication possibili- single phase tripping and/or autoreclosing
ties. isused for single phase faults, the tripping of
the circuit breaker, resulting from weak end
The well-structured design with free standing infeed, can also be phase selective.
functional units enables the addition of a ded-
icated disturbance recorder, an autorecloser
relay and breaker failure units at low cost.
ABB Line protection REL 100
1MDB06308-YN
Page 4

Application (contd) So called power system supervision functions Overcurrent earth fault protection:Option 2
are included in optional functions too. Their A quadrilateral characteristic improves the
functionality is based on measurement of the sensitivity of the distance protection for faults
line current during its normal operation (over- with higher fault resistance compared to a cir-
load protection) and the difference in phase cular characteristic. In either case, distance
currents (broken conductor protection). The protection can not be used for the detection
loss of voltage function, with its tripping and clearance of high resistive earth faults.
logic, can be effectively used in systems hav- Therefore REL 100 can be provided with a
ing built -in automatic restoration function. complementary overcurrent earth fault pro-
tection function. This function can be used as
Overload protection can be transferred to stub a non-directional or directional overcurrent
protection by energization of the correspond- earth fault protection. The type of protection
ing digital input. REL 100 can thus be used to be used is selected by using the HMC unit.
effectively in switchyards having a 11/2
circuit breaker configuration when VTs are Both protection types have selectable time
installed on the line side of the line isolators. characteristics, four of them current depen-
dent and one independent. Current dependent
Additional impedance measuring zones : time characteristics also include the possibil-
Option 4 ity of setting the minimum operating current
and time in order to make the protection
When two additional impedance measuring applicable in networks with existing older
zones are necessary, an additional two micro- types of overcurrent earth fault protection
processors can be added to REL 100, without (e.g. electromechanical).
changing the basic hardware configuration.
This offers a full scheme distance protection, The directional overcurrent earth fault protec-
having a total of six impedance measuring tion uses two directional measuring elements,
zones, as shown in Fig. 1. one directed in forward and one in reverse
direction. This makes it possible to be used
The settings for the resistive and reactive either in a permissive overreach or blocking
reach for these additional zones, as well as communication scheme with the protection
the zero sequence compensating factor are on the remote line end. Communication cir-
done completely independently of one cuits for the directional earth fault protection
another, and independently of the settings for in REL 100 are completely independent of
the basic zones. Further more, these two the communication circuits for distance pro-
zones can be programmed either in forward tection. Further more, similar logic circuits as
or reverse direction, independently of one for the distance protection are also built for
another. Each of the additional zones can be the overcurrent directional earth fault protec-
used also as non-directional impedance pro- tion (switch onto fault, current reversal, weak
tection. end infeed echo and tripping). Their use is
selectable on the HMC unit and they are com-
jX
pletely independent of the logic used for the
Zone 4
distance protection.
Zone 3

Zone 2
Fault locator: Option 3
Zone 1
The optional distance to fault locator,
installed in REL 100 as a separate micropro-
cessor, is an essential complement to the dis-
tance protection function since it measures
R
the distance to the fault with great accuracy.

The complete option provides a fault location


function, measurement of service values for
(96000017)

Zone 5
current, voltage, active and reactive power as
Zone 3R well as frequency and thus eliminates any
need for separate measuring transducers and
instruments on the protected line. Pre-fault
and fault values of currents and voltages at
Fig. 1 Distance protection built into a REL 100
has a quadrilateral characteristic the relay point are recorded together with
their phase relations for the last three
ABB Line protection REL 100
1MDB06308-YN
Page 5

disturbances. These can be read locally from in order to eliminate the influence of electro-
HMC unit as well as remotely through the magnetic interference. In this way REL 100 is
SCS and/or SMS. included into SMS and/or SCS at the same
time. This means that the operator, in the con-
The calculation algorithm takes into consider- trol room, as well as the relay engineer, in his
ation the effect of load currents and additional office, have the possibility to read informa-
apparent fault resistance as seen by the relay tion from the relay or even change the active
due to double end infeed of fault. group of settings or values of the setting
parameters within the setting group.
All secondary and primary values of voltages
and currents together with their phase rela- The software program SM/REL 100, installed
tions are available for testing purposes. in a personal computer makes it possible for
the relay engineer to establish communication
Additional signalling relays with the relay (it can be a direct communica-
The basic version of REL 100 is equipped tion or communication via a telephone net-
with an input-output unit consisting of 19 work), read information from the relay on a
binary inputs and 9 independent output con- PC and store it to PC files. Complete infor-
tacts. REL 100 can optionally be equipped mation on the last three disturbances is avail-
with a RLKG 100 unit that has 16 indepen- able as well as up to 150 time tagged events
dent signalling relays. Each of these can be for each disturbance. Similar possibilities are
programmed to be activated by any of the given to the operator in control room and /or
internal digital signals available for customer control centre,when one communication port
use. This allows adaptability to different sys- is connected to the SPA bus with SCS.Com-
tem requirements. munication with SCS makes it possible for
the REL100 to be time synchronised with
Serial communication other equipment in the substation.Similar
REL 100 can be provided with two optional functionality is possible when connected to
serial communication ports. Communication SMS.
with REL 100 is performed via optical fibres

Design
Input unit A/D Converter unit Measuring unit
RLKD 100 RLLB 100 RLZC 101

Separate disturbance
Testing unit recorder
RCRA 100

(SE970131)

Transformer unit HMC unit Input/output unit Relay unit (option)


RLHB 100 RTIA RLKE 100 RLKG 100

Fig. 2 REL 100 configuration

REL 100 line protection terminal is provided equipment frame. All other units are of plug-
in a 19" equipment frame with a height of 6U. in type and can easily be removed. External
A mother board is mounted at the back of the electrical connections are made with standard
ABB Line protection REL 100
1MDB06308-YN
Page 6

Design (contd) COMBIFLEX terminal sockets to the con- - Relay unit type RLKG 100 has 16 buil-
nectors mounted on the back plane of line tin signalling relays, each of them freely
protection terminal. Optional optical connec- programmable to be controlled by any
tions which are used for remote communica- of the REL 100 internal signals.
tion purposes within SCS and SMS or for
- Remote communication interface unit
transfer of digital information to disturbance
type RTDC 100 is provided with two
recorder type RCRA 100 are made through serial optical ports which makes possi-
the corresponding optical connectors
ble for REL 100 line protection terminal
mounted on the REL 100 back plane.
to be included to SCS and SMS at the
same time. The unit can be installed on
The basic configuration of the line protection
the rear plane of REL 100.
terminal REL 100 consisting of seven ele-
mentary units as presented in Fig 2. - A separate optical interface unit can be
installed on the back side of the A/D
- Testing unit with test switch, type converter unit in REL 100 when distur-
RTXP 18, and dc auxiliary voltage bance recorder unit RCRA 100 is pro-
switch (ON/OFF). vided together with REL 100.
- Transformer unit type RLHB 100 with
five voltage and five current input trans- Basic version
formers. The measuring technique used in REL 100 is
based on pure numerical methods. The mea-
- Input unit, type RLKD 100 consist of suring signal processors operate with numeri-
regulated dc/dc converter which pro- cal signals derived from the analogue to
vides stabilized auxiliary voltage to all digital converter (see Fig. 3).
static circuits and sixteen signalling
input circuits with optocouplers used The basic REL 100 line protection terminal
for galvanic separation of internal and provides a full scheme distance protection
external circuits. with three forward and one reverse directed
- A/D converter for 10 analogue signals impedance zones.
and 16 digital signals operates with
sampling frequency 2000 Hz and is Eight scheme communication logic is
installed together with antialiasing low included in the basic version together with
pass filter in unit type RLLB 100. current reversal logic. These are selectable
independently one of another during setting
- All REL 100 measuring functions are
procedure.
performed in multiprocessor based
measuring unit type RLZC 101.
Four groups of setting parameters are avail-
- Relay input - output unit type RLKE able in REL 100. They are completely inde-
100 comprises basic tripping and sig- pendent of one another.
nalling output relays as well as some
binary input circuits with optocou- The self supervision function is performed
plers used for galvanic separation. continuously and includes:
- Human machine communication unit - normal microprocessor watch-dog func-
type RTIA is installed on front of the tion
REL 100 and serves as the local communi-
- checking of digitized measuring signals
cation facility between the user and equip-
ment. - checksum verification of PROM con-
tents
Following hardware units can be included
with the basic version of the REL 100 line - checksum verification on all signal
protection terminal as options: communications
- Read-Write-Read-Write cycling of
memory cells and internal registers
ABB Line protection REL 100
1MDB06308-YN
Page 7

digital

SP 1

SP 2
Trip
SP 3
Signal

32 bit microcontroller
I SP 4
A/D Led

Communication
U SP 5 RTIA

SP 6 SMS

SP 7 SCS

(96000018)
SP 8

optical
RCRA 130

Fig. 3 REL 100 Block diagram

Transformer unit RLHB 100 A/D converter unit RLLB 100


A total of ten analogue input quantities are All of the analogue signals are filtered in ana-
processed in transformer unit RLHB 100: logue initializing low pass filters before
entering the multiplexer and analogue to digi-
- three currents as phase currents in the
tal converter. A separate signal processor in
protected line. the A/D converter unit performs digital low
- residual current (3I0) of the protected pass filtering. The total bandwidth of the fil-
line. tered signals is then suitable for protection
purposes. The information is then converted
- residual current (3I0) of parallel operat- from parallel to serial mode and transmitted
ing line when used (for purposes of to the measuring unit. The serial signals are
optional fault location function only). also available for remote optical communica-
- three phase to earth voltages of the pro- tion with the optional disturbance recording
tected line. unit, RCRA.
- open delta voltage of the protected line The RLLB 100 has a green LED which indi-
(for purposes of optional directional cates normal operation when lit.
earth fault protection function, when
used). Measuring unit RLZC 101
- one phase to earth voltage from busbar In the basic REL 100 version, the RLZC 101
side of the CB (for purposes of optional unit comprises 32 bit microcontroller and
synchro-check function when used). three signal processors. Encoded serial infor-
mation from the A/D converter unit are
All measuring currents enter the transformer decoded and changed back to parallel infor-
unit via plugs and sockets. If the transformer mation in the measuring unit. Band pass
unit is with drawn the CT input circuits on the numerical filtering of the corresponding cur-
input side of the line protection terminal are rent and voltage signals is performed as well.
automatically short circuited.
ABB Line protection REL 100
1MDB06308-YN
Page 8

Design (contd) The impedance measuring function is per- logical functions, built into REL 100 line pro-
formed by three basic signal processors tection terminals. It controls the output unit as
which calculate the impedance as seen for well as three communication ports:
different fault loops, on the basis of complex
values of measured voltages, currents and - to the human machine communication
changes in currents. The resulting impedance unit RTIA
is compared with the reactance and resistance - to the substation monitoring system
limits determined by the relay settings for
SMS (option)
each fault loop and each distance zone sepa-
rately within each millisecond. - to the substation control system SCS
(option)
The following functions are performed by the
basic three signal processors Human machine Communication unit RTIA
The human machine communication (HMC)
- signal processor no 1: unit type RTIA is plugged into the front of the
measuring unit. It is used for local communi-
calculation of impedances for all three phase
cation. RTIA is used for the following func-
to earth loops for the four basic distance
zones
tions:
- signal processor no 2:
- settings:
calculation of impedances for all three phase
four groups of setting parameters can be set
to phase loops for the four basic distance
or read by the use of menu structured self
zones
explanatory software. Parameters can be
- signal processor no 3: changed separately within different setting
calculation of directional boundaries for all six groups. Selection of the active setting group
fault loops. Directional evaluation is made in can also be performed.
both, forward and reverse direction. - information handling:
the most important information about the last
In order to measure the same operational three disturbances, including time of distur-
impedance for all fault loops, the zero bance, its duration together with starting and
sequence compensation factor KN has been tripping signals are stored in REL 100 and
applied for measurement in phase to earth are available to the user via the HMC unit. If
fault loops. This is used for measurement in the optional fault location function is included in
the reactive direction only and different val- REL 100, information on the distance to the
fault, together with the phasors of pre-fault
ues can be selected for different distance
and fault currents and voltages are available
zones. for the last three disturbances, as well. Infor-
mation about the actual line current, voltage,
The resistive reach is adjustable separately active and reactive power together with fre-
for earth fault measuring and phase fault mea- quency are also available to the user, as are
suring loops and can be set independently of internal logical signals as well as input and
one another for different distance zones. output signals.
- fault tracing:
In order to maintain definite directional mea-
should the self supervision function detect a
surement for faults close to the relaying point, faulty part within REL 100, this will be indi-
the loop voltage signal is used in conjunction cated, using a corresponding code, on the
with a phase locked positive sequence mem- HMC unit.
ory voltage which lasts for approximately 100
- simplified testing:
ms. After this time the directional informa-
tion which has been determined is sealed in of different functions and wiring during com-
until the fault has been cleared (fault current missioning or other testing activities. Testing
of external circuits is also possible by setting
decreased to zero). The circuit is then reset
the REL 100 internal signals as well as input
when normal line voltages are restored. and output signals into logical values 1,0 or to
the actual logical value of particular signal.
The 32 bit microcontroller collects all the Complete signalling, tripping and logical cir-
information from the different signal proces- cuits within the line bay can be tested in this
sors, the A/D converter and the input signal- way.
ling circuits as well as performing different
ABB Line protection REL 100
1MDB06308-YN
Page 9

Output unit RLKE 100 - Directional phase selection and single


The output unit type RLKE 100 has a self phase tripping facilities for solidly
contained regulated dc power supply unit as earthed networks
well as 9 miniature output relays which pro-
- Non directional phase selection with the
vide the following output signals:
following phase preferences for isolated
- TRIPR, TRIPS and TRIPT (tripping of and compensated networks:
all three phases separately)
RTSR cyclic TSR acyclic
- CS (carrier send - reed contact) TRST cyclic RST acyclic
- GT (general trip criteria) RTS acyclic STR acyclic
- GS (general start criteria) TRS acyclic SRT acyclic
- Start/Block AR (control of external - The power swing detection function is
auto-reclosing device) based on well proven measurement of
- Z< Failure (fault detected within REL transient impedance transition time
100 by self supervision function) between two concentric impedance
polygons. The final effect of function
- dc failure (loss of dc auxiliary voltage) on the distance protection function can
Logic inputs for CR (carrier receive), CRG be programmed for each distance zone
(carrier guard) and BLCK (external block) separately.
are also included in this unit. - Weak end infeed echo and trip logic can
be added to the scheme communication
Options: logic to ensure echo and tripping func-
The REL 100 line protection terminal can tion in cases of open circuit breaker or
easily be adapted to the requirements for the weak infeed to the fault on the protected
protection of any power line thanks to its line.
modular design and multiprocessor based
configuration. Adaption is done using addi- - Stub protection can be activated by an
tional hardware modules and/or additional auxiliary contact of the open line dis-
software functions, built into separate signal connecter in 11/2 breaker arrangement
processors and added to the basic version. or in mesh corner.
There is no need to increase the dimensions
of REL 100 when optional functions are - Switch onto fault logic can be selected
added due to the fact that all the space neces- to automatically detect switch onto fault
sary for the additional signal processors has conditions and on this way avoid the
already been provided for in measuring unit problems involved at breaker closing
RLZC 101. commands in 11/2 breaker configura-
tions.
Output relay unit RLKG 100
When optional unit type RLKG 100 is - Fuse failure supervision can be used to
included with the REL 100 basic version (see avoid operation of impedance measur-
Fig. 2), an additional 16 signalling relay con- ing elements for blown fuses in voltage
tacts are available for remote indication of measuring circuits.
operation. More than 80 internal signals are - System supervision will detect abnor-
available for signalling purposes and any of mal line conditions by means of an
them can be programmed to operate any of overload function, broken conductor
these 16 additional signalling relays. function and loss of voltage supervision
function.
Additional functions
The following functions are included in sig- - Synchro check and dead line check
nal processor no.4, which can be included in function can be used when one of the
line protection terminal REL 100: phase to earth voltages on busbars con-
nected to the fifth analogue voltage
- Independent phase selection measuring input transformer.
elements with independently settable
reach in the reactive and resistive direc-
tion for phase to earth measuring loops
as well as for phase to phase measuring
loops.
ABB Line protection REL 100
1MDB06308-YN
Page 10

Design (contd) Earth fault overcurrent protection The distance to the fault will automatically be
The earth fault overcurrent protection func- presented on the HMC unit, RTIA and also
tion is included in signal processor no. 5, available for remote communication purposes
which can be included in line protection ter- when tripping command issued by impedance
minal REL 100 as an option. This represent measuring function in REL 100. Manual
complementary protection to distance protec- starting of calculation is necessary when
tion function for high resistive earth faults. option Additional functions not included in
the line protection terminal.
Earth fault O/C protection can be selected to
be directional or non-directional. Time delay The distance to fault location function is
can be selected between independent and four based on a well proven algorithm which elim-
dependent time delay functions (inverse, very inates the influence of fault resistance and
inverse, extremely inverse and logarithmic). supply to a fault from two sides as well as
Two measuring elements are provided for the influence of load current, on the accuracy of
directional earth fault O/C protection func- measurement. This makes the fault location
tion, one forward and one reverse. function applicable in most complex network
configurations.
The directional function may be used to oper-
ate in scheme communication logic with the When using this optional function, display
same protection on the remote line end. Per- and remote reading of the measured values
missive overreach or blocking communica- such as current, line voltage, active power,
tion schemes can be selected with reactive power and frequency is possible at
communication channels and logic as well as any moment. Further more, phasors of pre-
with auxiliary logic (current reversal, switch fault and fault currents as recorded by the
onto fault and weak end infeed) independent fault locator function are stored for the last
of communication scheme logic for the dis- three disturbances and available for recalcula-
tance protection function. tion of the distance to the fault with changed
line or system parameters if necessary as well
Fault locator as for further analysis purposes.
The fault locator function is included in sig-
nal processor no 6, which can be included in
line protection terminal REL 100.
ABB Line protection REL 100
1MDB06308-YN
Page 11

Bay 1
Line

REL 100 Protection or Bay


automation computer
function

HMC
SCS optical loop
HV Busbar

Bay 2
Line

Stations optical bus within SCS 200


REL 100 Protection or Bay
automation computer
function

SCS optical loop


SMS optical loop

Other line, Generator or


Transformer Bays with
Numerical Protection

Bay 3
Line

REL 100 Protection or Bay


automation computer
function

SCS optical loop

(96000019)
+ SMS-BASE
SM/REL 100
Direct connection Other Software
Telephone network

Fig. 4 REL 100 as a building block within the i SMS and SCS

Additional zones In some cases, two SMS optical loops may be


Two additional distance zones are included in desired one independent of the other, each
signal processors no 7 and 8, which can be one with different competencies regarding
included in line protection terminal REL 100. monitoring and setting functions in REL 100.
These zones, four and five are completely Plastic optical fibres can be used up to the
independent of basic impedance zones and single lengths of 30 meters. Glass fibres can
have the same main characteristics. In addition be used up to the single lengths of 500
to this they can be directed in the forward or meters.
reverse direction as well as be programmed to
operate as non directional impedance zones. One optical loop can be used for remote com-
munication within the substation control sys-
Remote communication tem SCS, and is normally closed within one
When REL 100 equipped with additional bay and/or connected to one bay computer.
hardware unit type RTDC 100, which is This makes communication with REL 100
mounted on the back plane, remote commu- possible via the station bus from operators
nication from one or two locations is pos- work place or even from the control centre,
sible. This makes it possible for REL 100 by using all possibilities of SCS. Other pro-
to be included at the same time into SMS and tection or control units, using SPA communi-
SCS as presented schematically in Fig. 4. cation protocol, can be included into the same
SCS optical communication loop.
ABB Line protection REL 100
1MDB06308-YN
Page 12

Design (contd) Communication programs for remote com- as when operating it locally by means of the
munication with REL 100 within SCS are RTIA, human machine communication unit.
delivered within the control system itself. The following additional functions or limita-
tions are present when remote communica-
A second optical communication loop can be tion with SCS or SMS is used:
built up on the station level and include vari-
- up to 150 time tagged events for each of
ous numerical relays of the PYRAMID range.
The optical loop is closed by an opto/electri- the last three disturbances as stored in
the REL 100 memory, can be presented
cal converter with the RS 232-C connector on
to the user locally or remotely within
its output. Connection to the personal com-
SMS
puter can be done directly (if the PC is
located in the substation) or by use of tele- - the REL 100 internal clock can be syn-
phone modems, via the telephone network chronized with the station clock and
with CCITT characteristics (if the PC is other equipment in substation when
located remotely from the optical loop). REL 100 is connected into a SCS opti-
Instead of an optical loop for purposes of cal communication loop.
SMS connection a star connection can be
Selection of the access level to monitoring
selected. In this case a port expander must be
and setting possibilities within REL 100 via
used as the gateway from the different protec- communication facilities is settable only
tion terminals to the PC (telephone modem).
locally by means of HMC unit RTIA.
For communication with REL 100 within Complementary functions
SMS the SM/REL 100 software package The disturbance recording module type
must be installed on a personal computer RCRA 100 provides the best cost-benefit
(SM/REL 100 also supports communication combination when disturbance recording is
with RELZ 100 Ver. 2.3 and can replace older used as a complementary function to the line
version RDIAL 1). The SM/REL 100 pro- protection terminal REL 100. The already
gram is intended for installation on IBM PC converted numerical signals developed in the
model AT or 100% compatible and is running A/D converter of REL 100 are used for dis-
on MS-DOS or IBM-DOS version 3.3 or turbance recording. This means that the data
higher. acquisition and A/D conversion are common
to the numerical line protection terminal and
Additional requirements are as follows: the disturbance recorder.
- hard disk 3.5 Mbyte + 0.3 Mbyte/
REL 100 RCRA 100 provides a complete disturbance
recording function for line bay with the possi-
- one serial port for the modem or for bility to store 10 analog and 16 binary sig-
connection to optical loop nals.
- one parallel port for a printer
The REL 100 can also be supplied with a sep-
- one floppy disk drive 3 1/2 arate auto-reclosing relay, type REXA.
SM/REL 100 has local facilities for control-
Supporting software
ling the telephone modems. Communication
RCALC, a distance relay calculating program
parameters are selectable in a wide range and
for the simple and accurate calculation of the
make remote communication possible with
parameters for the distance protection func-
REL 100 in practically every communication
tion. This program is available on 3.5" floppy
network with baud rate selectable in the range
disks.Ordering No.RK601 006-DA
between 300 and 9600 baud.
Test plan for preparation of tests for REL 100
Remote communication with REL 100
with FREJA, test equipment, on 3.5" floppy
enables the user to have remote contact with
disk. Ordering No.: RK 912 013-CA
the line protection terminal in the same way
ABB Line protection REL 100
1MDB06308-YN
Page 13

Technical data
Table 1: Energizing quantities, rated values and limits
Quantity Rated value Nominal range Operative range
Current Ir = 1/5 A (0,2-30) x Ir (0,2-4) x Ir cont.
Burden < 0,5 VA for Ir = 1 A (0,2-100) x Ir for 1 s
max. 350 A for 1 s
ac voltage Ph-Ph Ur = 100/110 V (90-132 V) 1,5 x Ur cont.
Burden < 0,5 VA at U r 2,5 Ur for 1 s
Frequency fr = 50/60 Hz 5% 10%
Auxiliary dc voltage EL = (48/60) V 20% 20%
EL = (110/125) V 20% 20%
EL = (220/250) V 20% 20%
power consumption:
before operation 20 W
during operation 30 W
Binary input circuits
dc voltage RL = (48/60) V 20% 20%
RL = (110/125) V 20% 20%
RL = (220/250) V 20% 20%
power consumption:
EL = (48-60) V max. 0,5 W/input
EL = (110-125) V max. 0,7 W/input
EL = (220-250) V max. 1,2 W/input
Ambient temperature 20C -5C to +55C -20C to +70C
Ripple in dc auxiliary voltage max. 2% max. 12% Full wave rectified
Relative humidity (10-90)% (10-90)% (10-90)%

Table 2: Influencing factors, Permissible influence quantities


Dependence on: Within nominal range Within operating range
Ambient temperature 0,05% / 1C Correct function
Frequency 0,5% / 1 Hz Correct function
Ripple in auxiliary dc voltage Negligible Correct function
Interruption in auxiliary dc voltage
without resetting < 50 ms < 50 ms
no unwanted function < 200 ms < 200 ms
restart time < 15 s < 15 s

Table 3: Electromagnetic compatibility tests


Test Type test values Reference standards
1 MHz burst disturbance Class III, 2,5 kV IEC 255-22-1
Electrostatic discharge Class III, 8 kV IEC 255-22-2
Fast transient disturbance IEC 255-22-4
optocoupler inputs Class III, 2 kV
other Class IV, 4 kV

Table 4: Insulation tests


Test Type test values
Dielectric test
- current circuits to earth and other circuits 2,5 kV ac, 1 min
- circuit to circuit and circuit to earth 2,0 kV ac, 1 min
Impulse voltage test 5 kV, 1,2/50 s, 0,5 J
Insulation resistance > 100 Mohm at 500 V dc
ABB Line protection REL 100
1MDB06308-YN
Page 14

Technical data (contd)


Table 5: Mechanical tests
Test Type test values Reference standards
Vibration Class I IEC 255-21-1
Shock and bump Class I IEC 255-21-2

Table 6: Contact data (Reference: IEC255)


Trip relays Signal relays
Max. system voltage 250 V ac, dc 250 V ac, dc
Test voltage across open contact, 1 min 1 kV dc 0,8 kV dc
Current carrying capacity
continuous 5A 0,5 A
1s 15 A 0,5 A
Making capacity at inductive load with L/R > 10 ms
0,2 s 30 A 0,5 A
1,0 s 10 A 0,5 A
Breaking capacity for ac, cos > 0,4 250 V / 8,0 A 250 V / 10 VA
Breaking capacity for dc with L/R < 40 ms 48 V / 1 A 48 V / 0,2 A
110 V / 0,4 A 110 V / 0,09 A
220 V / 0,2 A 220 V / 0,04 A
250 V / 0,15 A 250 V / 0,04 A

Table 7: Additional general data


Weight Approx. 10 kg
Dimensions
width 60C = 483 mm (19)
height 6U = 266 mm
depth 230 mm
Storage temperature -40C to +70C

Table 8: Distance protection - General data for all zones


Operate time
typical 28 ms
Min. operate current 0,2 x Ir
Resetting ratio 105%
Resetting time
for operation forward 40 ms
for operation backward 60 ms
Tripping mode three phase or single and three phase
Setting inaccuracy included in the measuring inaccuracy
Number of zones
basic version 3 forward, 1 reverse
optional 2 direction selectable
Impedance setting range at Ir = 1 A
reactive reach (0,1-150) ohm/phase
resistive reach
phase-phase (0,1-150) ohm/phase
phase-earth (0,1-150) ohm/loop
Setting range of timers
for impedance zones (0,000-10,000) s
for T0 coord. timer (20-100) ms
ABB Line protection REL 100
1MDB06308-YN
Page 15

Table 9: Distance protection: Accuracy at reference conditions


Voltage range Current range SIR Accuracy
Static accuracy at 0 and 85 0,1 x Ur - 1,1 x Ur 0,2 x Ir - 30 x Ir 5%
Static accuracy at 0 and 85 0,03 x Ur - 0,1 x Ur 0,2 x Ir - 30 x Ir 7,5%
Static angular accuracy at
0 and 85 I r - 30 x Ir 3
Static angular accuracy at
0 and 85 0,2 x Ir - Ir 5
Maximal dynamic overreach
at 85 measured with CVTs 0,5 < SIR < 30 +5%

Table 10: Instantaneous high set overcurrent protection - accuracy data table for
reference conditions
Setting range Operate time Accuracy
Static accuracy (1 - 10) Ir 5%
Dynamic overreach at < 100 ms < 25%
Operate time at I > 10 . Iset < 15 ms

Table 11: Option Additional functions


Function Setting range Accuracy
Power swing detection element the same as for impedance
reactive reach at Ir =1A (0,1-150) ohm measuring elements
resistive reach at Ir =1A (0,1-150) ohm
impedance transition time 40 ms fixed
Automatic switch onto fault function
voltage check (25-80)% Ur 5%
current check <15% Ir for 0,2 s 5%
Weak end infeed trip and echo function
voltage check U < (25-80)% Ur 5%
Stub protection I > (20-300)% Ir 5%
Power system supervision overload
I> (20-300)% Ir 5%
time delay 10 s fixed 50 ms
broken conductor
min. phase current Ibc 20% Ir 10%
min. unsymmetry 20% of max. phase current 10%
time delay 10 s fixed 50 ms
loss of voltage function (25-80)% Ur 5%
Synchrocheck and dead line check function
frequency difference <200 mHz 20 mHz
voltage difference <15% Ur 5% Ur
phase deviation <45 5
voltage at
paralleling Uline >80% Ur fixed 10%
Ubus >80% Ur fixed 10%
energizing Ubus >80% Ur fixed 10%
operating time at
paralleling typical 200 ms
at energizing typical 80 ms
ABB Line protection REL 100
1MDB06308-YN
Page 16

Technical data (contd)


Table 12: Options Earth Fault Protection
Non Directional Overcurrent Earth Fault Protection
Setting range Accuracy
Basic current 3I0 (5-300)% Ir 5% Iset
Independent time delay (0-6,0) s 10 ms
Normal inverse characteristic k = (0,05-1,1) IEC 255-3 class 5 60 ms
Very inverse characteristic k = (0,05-1,1) IEC 255-3 class 7,5 60 ms
Extremely inverse characteristic k = (0,05-1,1) IEC 255-3 class 7,5 60 ms
Logarithmic characteristic t = 5,8-1,35 x In I/3I0set (s) 0,04 x [1-I/Iset] at I = (1,3-29) Iset
tmin for dependent characteristic (0,05 6,0) s < 1% + 10 ms
Min. operate current (100-400)% 3I0 5% of Ir

Table 13: Options Earth Fault Protection


Directional Overcurrent Earth Fault Protection
Setting range Accuracy
Basic current 3I0 (5-300)% Ir 5% Iset
Independent time delay (0-6,0) s < 1% + 10 ms
Rated voltage 110 / 3 V
Min. polarising voltage 1% Ur 5% at 50 Hz
-15% to 5% at 60 Hz
Characteristic angle 65 lag 3 at 20 V
Coordination timer Acc T0 (0-150) ms 10 ms
Current reversal ON - OFF
Weak end infeed
voltage check 3U 0 (5-70)% Ur 5% Uset

Table 14: Option Fault Locator


Function Setting range Nominal range Accuracy
Distance to fault locator 2% typical
reach for Ir = 1 A in
resistive direction (0-1500) ohm
reactive direction (0-1500) ohm
min. measuring cycle 1,75 or 1,25 cycle
phase selection internal
Service values
frequency (0,95-1,05) fr < 0,1 Hz
voltage (0,1-1,8) U r < 2%
current (0,2-4) Ir < 2%
active power at cos = 1,0 < 2%
at cos = 0,9 < 6%
reactive power at cos = 0,8 < 6%
ABB Line protection REL 100
1MDB06308-YN
Page 17

Ordering Ordering Table


Sl.No. Version D.C. Voltage CT,PT Ordering No. Circuit Diagram
Type Rating
(Secondary)
1. Option 1 110-125 VDC 1A,110V 1MYN743209-A 7433-1477-AA
+RLKG100
2. Option 1 220-250 VDC 1A,110V 1MYN743209-B 7433-1477-AA
+RLKG100
3. Option 1+3 110-125 VDC 1A,110V 1MYN743210-A 7433-1477-AA
+RLKG100
4. Option 1+3 220-250 VDC 1A,110V 1MYN743210-B 7433-1477-AA
+RLKG100
5. Option 1+3 110-125 VDC 1A,110V 1MYN743210-C 1MYN743210-CA
+RLKG100
6. Option 1+3 220-250 VDC 1A,110V 1MYN743210-D 7433-1477-AA
+RLKG100
7. Option 1+3 110-125 VDC 5A,110V 1MYN743210-E 7433-1477-AA
+RLKG100
8. Option 1+3 220-250 VDC 5A,110V 1MYN743210-F 7433-1477-AA
+RLKG100
9. Option 1+3 110-125 VDC 5A,110V 1MYN743210-G 1MYN743210-CA
+RLKG100
10. Option 1+3 220-250 VDC 5A,110V 1MYN743210-H 7433-1477-AA
+RLKG100

Optional Units
1.RTDC100
For plastic fibre - 1MYN571001-A
For glass fibre - 1MYN571001-B
2. Communication program - SM/REL100
3. For ordering optical fibres and other communication equipment belonging to SCS200 or
SMS200, please refer to document 1MDB06004-EN (Type REL100/RELZ 100 line protec-
tion)page 11

Sample Line protection terminal with full scheme dis- The distance protection function should con-
Specification tance protection function as main protection tain up to six independent impedance measur-
function and directional or non directional ing zones with quadrilateral characteristic and
earth fault overcurrent protection function as independent settings of reach in the reactive
an optional complement. Optionally included and resistive directions for phase to earth
fault location function should have accuracy faults and for multi-phase faults. Zero
better than 2% and should not depend on fault sequence compensating factor should be set-
resistance, load current and supply of fault table independently for each impedance zone
from different sources. Design should be in order to suit requirements on distance pro-
multi-processor based with at least one tection of multi-circuit parallel operating
microprocessor for each basic protection lines.
function.
Line protection terminal should also be suit-
Remote communication with the line protec- able for the protection of lines within com-
tion terminal should be possible from two dif- plex network configurations. Full scheme
ferent locations and independent of one design must assure correct and phase selec-
another. tive operation for simultaneous and inter-sys-
tem faults on multi-circuit lines as well as for
different evolving faults.
ABB Line protection REL 100
1MDB06308-YN
Page 18

The minimum operating time of the protec- The line protection terminal shall provide the
tion must not be more than 13 ms. The typical user with complete information on the last
operating time shall be less than 30 ms. The three disturbances locally and remotely with
characteristic of distance zone 1 in the reac- at least 150 time tagged events per distur-
tive direction must be compensated for load bance when optionally combined with SCS/
current. SMS. Local human machine communication
should be based on a user friendly menu
The memory voltage for proper directional structured programs and performed via a per-
discrimination at close in three phase faults manently installed human machine communi-
shall be based on positive sequence voltage. cation unit, type tested together with the line
protection terminal.
Earth fault overcurrent protection function
must be selectable between directional and Pre-fault and fault values of currents and volt-
non directional version. Its operation should ages must be available for fault analyzing
be based on the measurement of zero purposes. Remote communication should be
sequence quantities on the protected line. possible via local fibre optical network and
Time delay should be selectable between standard CCITT telephone network. Corre-
independent and all standardized dependent sponding computer programs must be avail-
time characteristics. able. Remote setting of different setting
parameters within at least four groups of set-
A wide range of permissive tripping and ting parameters must be possible. Monitoring
blocking scheme communication logics of all input and output logic signals as well as
should be available for the distance protection tripping signals must be possible locally and
as well as for the directional earth fault over- remotely. A continuous self supervision func-
current protection function. Scheme commu- tion with self diagnostic possibilities must be
nication logics should be independent for included in the line protection terminal.
both protection schemes. Standard logics like
current reversal, weak end infeed echo and
trip should be provided for both protection
functions. Logic operating without separate
reverse directed measuring elements are not
acceptable.

References REL 100 Users Guide 1MDU06028-EN

REOR 100/ RCRA 100 1MRK 511 013-BEN

REXA autorecloser 1MDB10306-YN

Panorama Station Automation 1MRK 500 016-BEN

SM/REL 100 1MRK 511 014-BEN


ABB Line protection REL 100
1MDB06308-YN
Page 19

Asea Brown Boveri Limited


Protection & Substation Automation
Plot nos.5 & 6, II Phase .Peenya Indl. Estate,
Bangalore-560058
Tel:080-8395181. Telefax:080-8396121
Marketing Offices :
Southern Reg.Offices Western Regional Offices Northern Regional Offices Eastern Regional Offices
Sona Towers, 77,Harrington Road Vaswani Chambers 1st Floor,Qutab 9,Lala Lajpat Rai
71 Miller Road, Chetput 264/265, Dr.A.B.Road Institutional Area, Guru Sarani, (Elgin Road)
Bangalore-560 052 Chennai-600 031 Worli,Mumbai-400 025 Nanak Foundation Building Calcutta-700 020
Tel:080-2256315 Tel:044-8261167 Tel:022-4308231 New Delhi-110 067 Tel:033-2479162
Telefax:080-2254147 Telefax:044-8257221 Telefax:022-4300143 Tel:011-6515966 Telefax:033-2472427
Telefax :011-6851721

Hyderabad Coimbatore Bhopal Chandigarh Bhilai


Tel:040-3344024 Tel:0422-432431 Tel:0755-586548 Tel:0172-606093 Tel:0788-324783
Visakapatnam Kochi Jabalpur Jaipur Bhubaneswar
Tel:0891-550183 Tel:0484-318301 Tel:0761-316469 Tel:0141-382023 Tel:0674-470955
Neyveli Nagpur Lucknow Jamshedpur
Tel:04142-52728 Tel:0712-553811 Tel:0522-281395 Tel:0657-426782
Pune Ludhiana
Tel:0212-659055 Tel:0161-452848
Vadodara
Tel:0265-336486

You might also like