FIRE-FIGHTING UNITS

50 Hz
EBARA Pumps Europe network

Head Office Italian Sales Network Export Network


EBARA Pumps Europe S.p.A. NORTH-EAST Region: EBARA Pumps Europe S.p.A. UNITED KINGDOM
Via Pacinotti, 32 (Trentino Alto Adige, Veneto, Friuli Venezia Giulia, Unit 7 - Zodiac Business Park
36040 Brendola (VI), Italy Emilia Romagna) High Road - Cowley Uxbridge
Phone +39 0444 706811 - Fax +39 0444 405811 Regional Manager mobile: +39 335 6423308 Middlesex - UB8 2GU, United Kingdom
e-mail: nord@ebaraeurope.com Phone +44 1895 439027 - Fax +44 1895 439028
Italian Sales (for order only): Phone +39 0444 706811 - Fax +39 0444 405811 e-mail: mktguk@ebaraeurope.com
e-mail: ordini@ebaraeurope.com
NORTH-WEST Region: EBARA ESPAA BOMBAS S.A.
Export Sales (for order only): (Valle dAosta, Piemonte, Lombardia, Liguria) C/Cormoranes 6 Y 8
e-mail: exportsales@ebaraeurope.com Regional Manager mobile: +39 335 5327276 Poligono Ind. La Estacin
e-mail: mrtgmi@ebaraeurope.com 28320 Pinto (Madrid), Spain
Technical Customer Service (TCS): Phone +39 0444 706811 - Fax +39 0444 405975 Phone +34 916.923.630 - Fax +34 916.910.818
e-mail: tcs@ebaraeurope.com e-mail: marketing@ebara.es
Phone +39 0444 706869/902/923/833 CENTRAL Region:
(Toscana, Umbria, Marche, Lazio, Abruzzo, Molise) EBARA Pumps Europe S.p.A. FRANCE
Marketing & Marketing Communication: Regional Manager mobile: +39 335 6423286 555, Rue Juliette Recamier
e-mail: marketing@ebaraeurope.com e-mail: centro@ebaraeurope.com 69970 Chaponnay, France
Phone +39 0444 706811 - Fax +39 0444 405811 Phone +33 4 72769482 - Fax +33 805101071
e-mail: mktgf@ebaraeurope.com
SOUTH Region:
(Campania, Basilicata, Puglia, Calabria, Sicilia) EBARA Pumps Europe S.p.A. GERMANY
Regional Manager mobile: +39 335 6423316 Ferdinand-Porsche-Ring 7
e-mail: sud@ebaraeurope.com 63110 Rodgau-Jgesheim, Germany
Phone +39 0444 706811 - Fax +39 0444 405811 Phone +49 (0) 6106-660 99-0
Fax +49 (0) 6106-660 99-45
INDUSTRIAL Division: e-mail: mktgd@ebaraeurope.com
Manager mobile: +39 335 6423302
e-mail: industry@ebaraeurope.com EBARA POMPY POLSKA Sp. z o.o.
Phone +39 0444 706811 - Fax +39 0444 405811 ul. Dziakowa 115
02-234 Warszawa, Poland
WASTEWATER Division: Phone +48 22 3909920 - Fax +48 22 3909929
Manager mobile: +39 335 6423290 e-mail: mktgpl@ebaraeurope.com
e-mail: ses@ebaraeurope.com
Phone +39 0444 706811 - Fax +39 0444 405811 EBARA Pumps Europe S.p.A. SAUDI ARABIA
Phone +966 11 810 4561
CAGLIARI Branch: Fax +966 11 810 4562
Via del Fangario, 29
09122 Cagliari EBARA Pumps Europe S.p.A INDIA LIAISON OFFICE
Phone +39 070 274281 - Fax +39 0444 405960 1503,Bhumiraj Costarica,
Branch Manager mobile: +39 335 6423320 Sector-18, Palm Beach Rd.
e-mail: mktgca@ebaraeurope.com Sanpada, Navi Mumbai
Maharashtra, Pin: 400705 - India
PALERMO Branch: Phone +91 22 2781 2862
Via Don L. Sturzo, 181/183 Fax +91 22 2781 2865
Z.I. - 90044 Carini (PA) e-mail: mktgind@ebaraeurope.com
Phone +39 091 8669790 - Fax +39 0444 405980
Branch Manager mobile: +39 335 6423316 EBARA Pumps RUS Ltd.
e-mail: mktgpa@ebaraeurope.com Prospekt Andropov 18, building 7, floor 11
115432 Moscow
Phone +7 499 6830133
e-mail: mktgrus@ebaraeurope.com

The content of this publication should not be considered mandatory. EBARA Pumps Europe S.p.A. reserves the right to change the content without prior notice. Cod. 479705532 09/14

EBARA Pumps EuropeS.p.A. EBARA Corporation


Via Pacinotti, 32 11-1, Haneda Asahi-cho, Ohta-ku,
36040 Brendola (Vicenza), Italy Tokyo 144-8510
Phone +39 0444 706811 - Fax +39 0444 405811 Japan
e-mail: marketing@ebaraeurope.com Phone +81 3 6275 7598 - Fax +81 3 5736 3193
www.ebaraeurope.com www.ebara.com
INDEX

Fire-Fighting Overview of Standard UNI EN 12845 2


Fire-Fighting introduction 4
BASE-JOINT PUMPS (3PS - ENRS) FFS-FFBE electric pump 14
FFBD motor pump 38
FFBD electric pump + motor pump 43

BOREHOLE PUMPS (SF6 - WINNER 4N15 - BHE) FFS-S hydraulic kits 46

WITH EXTERNAL PROTECTION R60 Cabinets 63

Electrical panels 64

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 1 Fire-Fighting


UNI EN 12845 FIRE-PREVENTION
INTRODUCTION TO STANDARD EN 12845

Introduction
System standard UNI EN 12845 regulates the design, installation and As required by the standard, the EBARA supply pumps used in FFS-FFB
maintenance of fixed sprinkler fire extinguishing systems. pumping units, are fitted with motors that provide: the power required
The pump unit indicated in section 10 of the standard is comprised of: at the peak of the power curve in the event of pumps with non-
a supply pump that meets the system's specifications (or several pumps overloading curves; for pumps with power curves that increase with the
operating in parallel), and a jockey pump for small system leaks. flow rate, however, they provide the power required up to a flow rate
The operation of the supply pump, which may be electrical or diesel- that corresponds with a NPSH pump demand of no less than 16 m.
fuelled, is governed by Standard UNI EN 12845 point 10.2, based on In the first instance (Fig.1) the power peak may occur within the
the type of water supply. operating range (curve A) or outside it (curve B).
In the second instance (Fig.2), the power curve increases in line with
the flow rate (curve C). The motor is selected based on a flow rate that
corresponds with a pump NPSHr of 16 m or greater.

160 160 32

140
A 140 28
B C
120 120 24
Head H [%]

100 100 20
Head H [%]

NPSHr [m]
80 80 16

60 60 12

40 40 8
NPSHr
20 20 4

0 0 0
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
120 120
Ab. power P2 [%]

Ab. power P2 [%]

100 100

80 A 80 C
60 60
B
40 40

20 20
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Flow rate Q [%] Flow rate Q [%]

Fig. 1 Definition of the power requested Fig. 2 Definition of the power requested
on the basis of the peak value on the basis of the NPSH
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Hazard classes Type of water supply used


(UNI EN 12845 paragraph 6 and annex A) Mains water supplies should automatically provide the pressure
The hazard class and water supply class (described below), are chosen and flow rate required by the system and should be able to ensure
by the designer of the fire extinguishing system. continuity and reliability.
The standard requires that fire-extinguishing systems that protect The standard recognises four different types of water supply (UNI EN
businesses and buildings are designed and built in accordance with 12845 paragraph 9.6):
hazard classes, which are divided into three types:
Light Hazard - LH; Single water supplies (9.6.1);
Ordinary Hazard - OH, divided into the categories: OH1, OH2, OH3, Superior single water supplies (9.6.2);
OH4 Dual water supplies (9.6.3);
High Hazard - HH, divided into the categories: Combined water supplies (9.6.4);
> High Hazard, Process - HHP, in turn divided into the categories:
- HHP1 - High Hazard - Process Group 1 In a UNI EN 12845 fire-extinguishing pumping system, in the event
- HHP2 - High Hazard - Process Group 2 of Superior or dual water supplies, no more than one supply pump
- HHP3 - High Hazard - Process Group 3 should be operated by an electric motor (point 10.2). In practice, if a
- HHP4 - High Hazard - Process Group 4 unit with several supply pumps is installed on one of these water supply
> High Hazard, Storage - HHS, in turn divided into the categories: systems, only one of them is operated by an electric motor, the others
- HHS1 - High Hazard - Storage Category I are operated by diesel motors.
- HHS2 - High Hazard - Storage Category II
- HHS3 - High Hazard - Storage Category III
- HHS4 - High Hazard - Storage Category IV

Your Life, our Quality. Worldwide. 2 Fire-Fighting


UNI EN 12845 FIRE-PREVENTION
INTRODUCTION TO STANDARD EN 12845

Performance specifications - Pre-calculated systems General conditions of use


The system performance specifications for selecting the pumps must Use:
comply with that set out in paragraph 10.7 of Standard UNI EN 12845. Fixed fire-extinguishing systems, automatic sprinkler systems in
Statement 16 of the Standard sets out the minimum specifications for accordance with Standard UNI EN 12845
pressure and flow rate, based on pre-calculated systems for hazard Fire-extinguishing systems, hydrant lines in accordance with Standard
classes LH and OH, with water drawn from storage tanks. UNI 10779
For pre-calculated systems in hazard classes HHP-HHS, the pump
specifications are defined in accordance with paragraph 7.3.2 of Area of installation and operation:
Standard UNI EN 12845. In these instances the pump must be able to Dedicated area for pumping unit, enclosed and protected, with a level
supply 140% of the flow rate at a pressure of no less than 70% of the of fire resistance of no less than 60 minutes
specified pressure at the pump's rated flow rate. (UNI EN 12845 point 10.3)
The choice of performance specifications and the number of pumps Protected via sprinkler (UNI EN 12845 point 10.3.2)
installed is the responsibility of the system designer. The pumping unit should not be positioned in buildings or parts of
buildings where dangerous processes or explosion risks are present
Operating principle (UNI EN 12845 point 8.4)
The supply pump in the UNI EN 12845 fire-extinguishing pumping Protected from frost (UNI EN 12845 point 8.4)
unit, in the event it is triggered, is started by the operation of two Protected from tampering (UNI EN 12845 point 8.4)
pressure switches controlled by the electrical control panel (each pump
has its own electrical panel), and must operate continuously until it is Ambient temperature:
stopped. This can only take place manually (UNI EN 12845 10.7.5.2). The ambient temperature for operation is 4- 40C for electrical
The activation of the supply pump simultaneously causes the activation pumps at an altitude of no higher than 1000m a.s.l.
of an acoustic alarm signal via an alarm remote control unit installed in Ambient temperature for motor pumps is +10- 40C
a manned area. Max. relative humidity is 50% at +40C
The jockey pump, with a low flow rate, is activated in the event of small
leaks in the system (in order to prevent the supply pump from activating Temperature of water supply:
needlessly). It is activated automatically via its own electrical control The temperature of the channelled water should be 0- 40C
panel and associated pressure switch, which is calibrated to a pressure The temperature of the channelled water should be 0- 25C if
value slightly higher than that of the supply pump pressure switch. submerged pumps are used
The jockey pump is stopped automatically once the system pressure is
restored. The channelled water should be free of fibrous substances or other
suspended materials or vegetation which could cause deposits inside
Standards and directives the pipes (UNI EN 12845 point 8.1.2).
UNI EN 12845, fixed fire-extinguishing systems - automatic sprinkler The water pressure should not exceed 12 bar, except in systems with
systems a high vertical trend (difference in height between highest and lowest

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
UNI 10779, fire-extinguishing systems - hydrant lines sprinkler > 45 metres)
UNI EN ISO 9906 Attachment A - Rotodynamic pumps - Hydraulic (UNI EN 12845 8.2.1, 8.2.2).
performance tests and acceptance criteria
Machinery Directive 2006/42/CE
Low Voltage 2006/95/CE
Electromagnetic Compatibility 2004/108/CE

Your Life, our Quality. Worldwide. 3 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

Endothermic diesel motor


Direct injection or turbocharged; start-up without preheating
Forced lubrication with geared pump
Full-flow oil filter
Oil pre-heater for cold starting at maximum power, located under the
casing
Cooling (based on power rating): air-cooled with dual drive belt,
glycol water-cooled with closed-loop radiator; with water/water heat
exchanger on request
Electrical start-up via dual battery able to reach full power within 15
seconds from any sequence at a minimum temperature of 10 C in
the pumping area
Electrical motor for jockey pump
Three-phase asynchronous motor with external self-ventilation with
squirrel cage rotor
2900 rpm
Insulation Class F
Main power supply 400V
Voltage 50 Hz
MAIN MATERIALS OF MAIN/RESERVE PUMP
ENR
Pump body made of cast iron
Impeller made of cast iron
FFS - FFB Shaft made of AISI 420 steel
UNI EN 12845 FIRE-FIGHTING UNITS Mechanical seal made of SiC/Carbon/EPDM
EBARA type FFS-FFB fire-extinguishing units are applied to water
supplies for automatic fire-extinguishing systems in accordance with 3 SERIES
European Standard UNI EN 12845. Pump body made of AISI 304 steel
Impeller made of AISI 304 steel
APPLICATIONS: Shaft made of AISI 304 steel
The units are suitable for water supply and pressure boosting in Mechanical seal made of Ceramics/Carbon/NBR
automatic sprinkler systems, fire hydrants or fire hoses or for controlling
the same. MAIN MATERIALS FOR JOCKEY PUMP
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

AGA
DESCRIPTION Pump body made of cast iron
These water supply units for fire-extinguishing systems are built in Impeller made of brass
accordance with Standard EN 12845. Based on the model, they are Shaft made of AISI 303 steel (part in contact with liquid)
comprised of from 1 to 3 base-joint horizontal pumps EN 733 Mechanical seal made of Ceramics/Carbon/NBR
coupled together via an elastic spacer joint with associated joint cover.
The pumps have electrical/diesel motors and a jockey pump. COMPACT
With pump in polypropylene reinforced with glass fibre
GENERAL TECHNICAL DATA Impeller made of Noryl
Usable liquids Shaft made of AISI 316 steel
Clean water with no aggressive or fibrous substances or other Mechanical seal made from graphite/ceramics
suspended abrasive material.
MATRIX
Field of use Pump body made of AISI 304 steel
Fluid temperature range: +25 to +40 C Impeller made of AISI 304 steel
Min. ambient temperature 4 C (10C) Shaft made of AISI 304 steel (part in contact with liquid)
Max. operating pressure 12 bar Standard mechanical seal made from Ceramics/Carbon/EPDM
Electrical motor for main/reserve pump MATERIALS USED FOR METAL STRUCTURE
Self-ventilating asynchronous three-phase enclosed motor with external The base is made from zinc-plated section steel
self-ventilation The manifolds are made from zinc-plated steel
2900 rpm Throttle-type shut-off valves (made from EN GJL 250 treated cast iron)
Protection rating IP 55 Inspectable clapet-type non-return valves (made from EN GJL 250
Insulation Class F treated cast iron)
Main power supply 400V
Voltage 50 Hz

Your Life, our Quality. Worldwide. 4 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

GENERAL TECHNICAL DATA


Use - Auto - 0 - Man. selector key with safety shut-off
Water supply and water pressure boosting in residential, commercial - Shutdown signal
and public buildings, hotels, hospitals, supermarkets, and in industrial - Failed start-up signal
and process applications. With water for fire-extinguishing use with no - Pump operating signal
aggressive chemical or mechanical agents that could damage the materials - Power supply signal
used and with no suspended abrasive or fibrous substances. - Phase sequence/failure signal
- Start-up request signal
Operation - 1 lamp test button
The system is kept under pressure without the need to start the main - 1 manual operation button
pump via a jockey pump with automatic start-up and shut-off via - 1 pump shut-off button
pressure switch. This pump is sized so as not to be able to provide - 1 status information graphic display
transformer for low voltage auxiliary circuits.
sufficient pressure and flow rate to supply a single open sprinkler. In the
start-up contactor (direct up to 7.5 kW, star-delta for higher power
event that the pressure is lowered following a demand for water that
ratings).
cannot be compensated for by the jockey pump, the main pump and
high blow potential protection fuses that allow for the passage of
emergency pump (where fitted) are activated in sequence. Both these starting current within 20 seconds
pumps are activated automatically and shut-off manually via a switch detection system for phase failure or inverted phase conditions.
on the control panel. clean contacts for remote signalling: pump in operation, phase failure,
start-up request, start-up failure, electrical power supply present.
Build
Preassembled unit with a single base up to 90 kW, made from welded Motor pump electrical panel
and coated strong section steel, with support feet for facilitating On the front panel: door lock main switch with suitable "machine stop"
handling. Based on the type of build, the unit is comprised of the knob; electronic control unit for managing motor pump in accordance
following: with Standards UNI EN 12845 and UNI 10779:
Auto - 0 - Man. selector key with safety shut-off
Main pump 1 power supply indicator light
Horizontal axis base-joint normalised unidirectional centrifugal pump 1 manual operation enablement indicator light
with end suction and back pull out axial suction and radial delivery. 1 independent manual operation button (single button for emergency
This is coupled to an oversized electrical or endothermic motor that start-up associated with a power diode to avoid the influence of one
exceeds the power demand of pump under any load condition, from start-up battery on another)
zero load to a flow rate equal to an NPSHr of 16 mca, in accordance 1 Diesel motor shut-off button
with Standard EN 12845. The coupling is achieved via a lantern, - Inside
support, flexible joint with spacer, alignment support and anchor. Transformer for low voltage auxiliary circuits
Protection fuses
Included motor pump accessories Clean contacts for remote signalling:

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
- 2 batteries Pump in operation
- 1 fuel tank (with a capacity suitable for the specific requirements), Motor pump general alarm
Start-up request
with fuel level indicator and collection basin (up to 16L). For larger
Start-up failure
sizes the tank is equipped with a dual chamber
2 battery chargers (dedicated to each individual battery)
- 1 manual pump for loading fuel (tank capacity >50 l)
- 1 engine oil gauge Jockey pump electrical panel
On the front panel:
Jockey pump Auto - 0 - Man. selector
Horizontal multi-stage pump or self-priming pump with suitable thermal shutdown red indicator light (and voltage present indicator
performance to maintain system pressure, from the AGA, COMPACT based on the model)
or MATRIX range. pump in operation green (or yellow, based on model) indicator light
door lock main switch with suitable "machine stop" knob
Control panels - Inside:
Built in accordance with applicable CEI Standards and Standards UNI transformer
EN 12845 and UNI 10779 for the main/jockey pumps, in coated sheet direct start-up contactor
metal casing. Protection grade IP 54. Each pump is equipped with a thermal relay
control panel housed on a dedicated support (this can be separate on protection fuses
request for wall installation)
Pressure-switch circuits
Electrical panel for electric pump 2 circuits comprised of a dual-stage pressure switch, pressure gauge,
On the front panel: door lock main switch with suitable "machine pressure gauge holder, non-return valve, tap, both for the main pump
stop" knob; electronic control unit for managing electric pump in and emergency pump, for automatic start-up.
accordance with Standards UNI EN 12845 and UNI 10779: 1 pressure switch for the automatic start-up and shut-off of the
jockey pump.

Your Life, our Quality. Worldwide. 5 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

Expansion cones ACCESSORIES


Concentric cones inserted onto the delivery column to limit the speed Suction eccentric reducer with max. inclination of 20
within the parameters set out by the standard. Lug valve with limit switch contact, version with lever handle or
handwheel based on unit model
Ball-type or throttle-type valves Flow rate gauge kit
Can be locked, with position indicator, on the delivery column, in 500 litre horizontal priming reservoir (one for each service pump),
combination with the concentric cone. ON/OFF status monitoring with mechanical float valve and electrical float for filling command via
device included. service pump.
Non-return valves Vibration-damping joint kit
Clapet-type valves that can be inspected, fitted onto the delivery Remote panel for alarm notifications
column. Spare parts kit for diesel motors
Water/water heat exchanger kit
Vibration-damping joints
On the delivery column in the event of a diesel motor.
Stub pipe for flow rate gauge attachment
On the delivery manifold with a suitable ND. (included in the flow rate
gauge kit, see accessories)
Recirculation circuit
Attachments for continuous water flow circuit to prevent overheating
with the pump operating with the delivery line closed, complete with
calibrated diaphragm fitted to the main pump delivery line.
Attachments for priming reservoir
In accordance with Standard UNI EN 12845, fitted to the delivery
column, obligatory for overhead installations.

HYDRAULIC DIAGRAM SHOWING OVERHEAD SURFACE PUMPS


TEST PORT DISCHARGE

KEY FILLING
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

1 Supply pump
2 Jockey pump
3 Throttle-type shut-off valve TOO FULL
4 Pump supply tank
6 Ball-type shut-off valve
7 Recirculation circuit attachment
8 Pressure gauge
9 Automatic air relief valve SYSTEM
10 Non-return valve CONNECTION

11 Blind flange/closure cap


12 Pump control pressure switch
DRAINAGE

13 Membrane-based expansion vessel


PUMP ROOM SPRINKLER SUPPLY

14 Gauge attachment
15 Extension stub pipe upstream of gauge
16 Flow rate gauge
17 Filter
18 Pump priming reservoir
PRIMING

19 Low-level switch for pump start-up


20 Base valve
RECIRCULATION

N.B.: Components marked with an asterisk are supplied separately on


request (*3, *15, *16, full flow rate measuring kit) (13 expansion
vessel), fitting and testing to be carried out by the manufacturer of the
fire-extinguishing system.
N.B.: Components given between brackets and the associated mains
TEST AND DISCHARGE

water supplies marked with a dotted line are not part of the pressure
boosting unit. These are the responsibility of the manufacturer of the
fire-extinguishing system.

Your Life, our Quality. Worldwide. 6 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

HYDRAULIC DIAGRAM SHOWING UNDERHEAD SURFACE PUMPS

TEST PORT DISCHARGE


KEY
1 Supply pump
2 Jockey pump
3 Throttle-type shut-off valve
4 Pump supply tank
6 Ball-type shut-off valve
7 Recirculation circuit attachment
8 Pressure gauge
9 Automatic air relief valve
10 Non-return valve
11 Blind flange/closure cap SYSTEM
12 Pump control pressure switch CONNECTION
13 Membrane-based expansion vessel
14 Gauge attachment

PUMP ROOM SPRINKLER SUPPLY


15 Extension stub pipe upstream of gauge
16 Flow rate gauge
17 Filter

N.B.: Components marked with an asterisk are only supplied separately on


request (*3, *14, *15, *16, full flow rate measuring kit) (*13 expansion

TEST AND DISCHARGE


vessel). Fitting and testing are to be carried out by the manufacturer of
the system.

RECIRCULATION
N.B.: Components given between brackets and the associated mains water
supplies marked with a dotted line are not part of the fire-extinguishing
pressure boosting unit. These are the responsibility of the manufacturer
of the fire-extinguishing system.

HYDRAULIC DIAGRAM SHOWING SUBMERGED PUMPS

KEY

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
1 Supply pump
2 Jockey pump
3 Throttle-type shut-off valve
4 Pump supply tank
5 -
6 Ball-type shut-off valve
7 Recirculation circuit attachment
8 Pressure gauge SYSTEM
CONNECTION
9 Automatic air relief valve
10 Non-return valve
11 Blind flange/closure cap
PUMP ROOM SPRINKLER SUPPLY

12 Pump control pressure switch


13 Membrane-based expansion vessel
14 T connector, measurement attachment
15 Extension stub pipe upstream of gauge
16 Flow rate gauge
17 Safety valve
18 Minimum-level switch for pump start-up
19 Float valve for filling

N.B.: Accessories and sections of pipe from the mouth of the pump outlet
up to the connectors upstream of the clapet valves, including electrical
TEST PORT DISCHARGE

connections, are the responsibility of the manufacturer of the fire-


extinguishing system.
N.B.: Components marked with an asterisk are supplied separately on
TEST AND DISCHARGE

request (*3,*14,*15,*16, full flow rate measuring kit) (*13 expansion


RECIRCULATION

vessel) (*17, safety valve). Fitting and testing are to be carried out by
the manufacturer of the fire-extinguishing system.
N.B.: Components given between brackets and the associated mains
water supplies marked with a dotted line are not part of the pressure
boosting unit. These are the responsibility of the manufacturer of the
fire-extinguishing system

Your Life, our Quality. Worldwide. 7 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

DIAGRAM OF FFS FIRE-FIGHTING UNIT WITH BASE-JOINT ELECTRICAL PUMPS

KEY 34 Expansion vessel


1 Connector upstream of non-return valve (*) Supply pump flow rate gauge kit
2 Inspectable clapet-type non-return valve 36 (*) Stabilising stub pipe
3 Connection stub pipe 37 (*) Shut-off valve
4 Throttle-type shut-off valve with electrical signal for failure to open 38 Flow meter
5 Delivery manifold 39 Electrical supply pump (supplied separately for submerged pump unit kits)
6 Connection pipe for jockey pump (not provided for submerged pumps) Conical diffuser for reducing pump delivery speed (for units with 3PS pumps)
7 T connector, jockey pump line 40 Counter flange (for submerged pump unit kits)
8 Inspectable clapet-type non-return valve, jockey pump line 41 Jockey pump (supplied separately for submerged pump unit kits)
9 Ball-type shut-off valve, jockey pump line 43 (*) Eccentric conical diffuser (not provided for submerged pump unit kits)
10 Ball-type shut-off valve 44 (*) Throttle-type shut-off valve for suction with electrical signal for failure to open (excluding
11 Automatic air relief valve submerged pumps)
14 Angle valve / diaphragm, recirculation circuit (*) Priming kit (not provided for submerged pump unit kits)
15 /15A Closure cap / Priming kit 45 Ball-type shut-off valve
16 /16A Closure cap / Set-up for pump room sprinkler supply attachment 46 Priming kit clapet-type non-return valve
18 Pressure switch test circuit valves 47 Base (not provided for submerged pump unit kits)
19 Supply electrical pump start-up pressure switches 48 Frame
24 Pressure gauge, pressure switch circuit 49 Eyebolts for lifting
25 Pressure gauge, jockey pump line 50 3-piece connector, jockey pump line
26 Ball-type shut-off valve, jockey pump pressure switch circuit 51 Attachment for flow rate gauge
27 Jockey pump start-up pressure switch
28 Blind flange (*) Supplied separately on request
29 Counter flange
30 Electrical control panel for supply electrical pump
31 Electrical control panel for jockey electrical pump
32 Alarm panel for manned area
33 Alarm siren control unit

PUMP CONTROL PANELS


ALARM CONTROL UNIT
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

SUCTION CONE FLOW RATE GAUGE KIT

PRIMING KIT

SUCTION VALVE

CONTROL WITH
HANDWHEEL REDUCER
DN 125-150-200-250

Your Life, our Quality. Worldwide. 8 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

DIAGRAM OF FFB FIRE-FIGHTING UNIT WITH ELECTRICAL PUMP AND BASE-JOINT MOTOR PUMP

KEY
1 Vibration-damping joint 27 Jockey pump start-up pressure switch
2 Inspectable clapet-type non-return valve 28 Blind flange
3/3A- Blind flange (cap)/ flow rate gauge kit 29 Counter flange
4 Shut-off valve with electrical signal for failure to open 30 Electrical control panel for supply motor pump
5 Delivery manifold 30A Electrical control panel for supply electrical pump
6 Jockey pump connection pipe 31 Electrical control panel for jockey electrical pump
7 Connector with closure cap, jockey pump line 32 (*) Alarm panel for manned area
8 Inspectable clapet-type non-return valve, jockey pump line 33 (*) Alarm siren control unit
9 Ball-type shut-off valve, jockey pump line 34 (*) Expansion vessel
10 Ball-type shut-off valve for expansion vessels (*) Supply pump flow rate gauge kit
11 Automatic air relief valve 36 Stabilising stub pipe
12 T connector, recirculation circuit 37 Shut-off valve
13 Pressure switch test circuit non-return valve 38 Flow meter
14 Angle valve / diaphragm, recirculation circuit 39 Supply motor pump
15/15A Closure cap / Priming kit 39A Supply electrical pump
16/16A Closure cap / Set-up for pump room sprinkler supply attachment 40 Conical diffuser for reducing pump delivery speed
17 T connector, pressure switch test circuit 41 Jockey pump
18 Ball-type shut-off valve, pressure switch outlet circuit 42 Ball-type shut-off valve, jockey pump suction line
19 Supply electrical pump start-up pressure switches 43 (*) Eccentric conical diffuser
20 Closure cap connector, pressure switch test circuit 44 (*) Throttle-type shut-off valve with electrical signal for failure to open (supply pump suction line)
21 Fuel tank (*) Priming kit
22 Collection tank 45 Ball-type shut-off valve
23 Batteries 46 Priming kit clapet-type non-return valve
24 Pressure gauge, pressure switch test circuit 47 Base
25 Pressure gauge, jockey pump line 48 Manifold supports
26 Ball-type shut-off valve, jockey pump pressure switch circuit 49 3-piece connector, jockey pump line

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
ALARM CONTROL UNIT
PUMP CONTROL PANELS

FLOW RATE GAUGE KIT

VERSION WITH FLANGED VALVE


VERSION WITH THREADED VALVE

SUCTION VALVE SUCTION CONE


CONTROL WITH
HANDWHEEL REDUCER
DN 125-150-200-250

VIBRATION-DAMPING JOINT PRIMING KIT

Your Life, our Quality. Worldwide. 9 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

DIAGRAM OF FFS-S FIRE-FIGHTING UNIT KIT WITH SUBMERGED ELECTRICAL PUMPS

KEY
1 Connector upstream of non-return valve 26 Ball-type shut-off valve, jockey pump pressure switch circuit
2 Inspectable clapet-type non-return valve 27 Jockey pump start-up pressure switch
3 Connection stub pipe 28 Blind flange
4 Throttle-type shut-off valve with electrical signal for failure to open 29 Counter flange
5 Delivery manifold 30 Electrical control panel for supply electrical pump
7 T-connector, jockey pump line 31 Electrical control panel for jockey electrical pump
8 Inspectable clapet-type non-return valve, jockey pump line 32 (*) Alarm control unit for manned area
9 Ball-type shut-off valve, jockey pump line 33 (*) Alarm siren control unit
10 Ball-type shut-off valve 34 (*) Expansion vessel
11 Automatic air relief valve (*) Supply pump flow rate gauge kit
14 Angle valve / diaphragm, recirculation circuit 36- Stabilising stub pipe
15 /15A- Closure cap / Priming kit 37- Shut-off valve
16 /16A- Closure cap / Set-up for pump room sprinkler supply attachment 38- Flow meter
18 Ball-type shut-off valve, pressure switch test and outlet circuit 40 Counter flange
19 Supply electrical pump start-up pressure switches 48 Frame
24 Pressure gauge, pressure switch test circuit 49 Eyebolts for lifting
25 Pressure gauge, jockey pump line 50 3-piece connector, jockey pump line
51 Attachment for flow rate gauge

ALARM CONTROL UNIT


The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

FLOW RATE GAUGE KIT

Your Life, our Quality. Worldwide. 10 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

FFS-FFB FIRE EXTINGUISHING UNIT CONFIGURATION IN ACCORDANCE WITH STANDARD UNI EN 12845

ATTACHMENT FOR fuel tank with containment


FIRE-FIGHTING ROOM tank
SPRINKLER
flow meter
flow rate gauge
adjustment valves independent control panels
lockable delivery valve with for each pump with signals
status indicator for remote and controls
alarm

stub pipe for flow


rate gauge

concentric cone

attachment for
priming circuit

lockable shut-off
valves with status control pressure
switches

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
signal for remote
alarm
recirculation circuit
attachment

COMPENSATION membrane tanks


JOINT
eccentric reduction
adaptors

Your Life, our Quality. Worldwide. 11 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

IDENTIFICATION CODE - UNITS WITH BASE-JOINT PUMPS


FF B D 1 1 1 ENR S 50-200 - 222 / 18.5E / 18.8D + 2.2P
0,75
Jockey pump power rating 0,9
1,1
2,2

Diesel motor rated power (1) 4.6D


28.6D
110D

Electric motor rated power (1) 3E


22E
90E

Supply pump impeller diameter 166


222
255

Pump size 32-160


50-200
100-250
Spacer joint
S

Supply pump 3PS


3PF
ENR
Jockey pump number 0
1

Supply motor pump number 0 (2)

1
2

Supply electrical pump number 0 (2)

1
2
Type of power supply (3) electrical E
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

diesel D (4)

Unit with 3PS pumps S


Unit with 3PF - ENR pumps B
UNI EN 12845 fire-extinguishing pumping unit
(1)
Not given in the absence of the specific pump
(2)
0 quantity not indicated
(3)
Not indicated for units with 3PS pumps
(4)
Also in case of dual motorisation E+D

Your Life, our Quality. Worldwide. 12 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

IDENTIFICATION CODE - UNITS WITH ELECTRICAL SUBMERGED PUMPS


FFS KIT 2 1 S DN100x80x1 + 11
Power rating [kW] Power supply panel

Dimensions: DN1xDN2xDNJP

Submerged Pump Identification Code

Jockey pump number

Supply pump number

UNI EN 12845 fire-extinguishing pumping unit

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 13 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

BASE - JOINT 32-40 (3PF - ENR) PERFORMANCE TABLE


Series Size Q=Flow rate
pump pump l/min 100 150 200 250 300 333 360 370 400 450 500 590 660 700 710
m3/h 6 9 12 15 18 20 21 22 24 27 30 35 40 42 43
H=Head [m]
3PF 32-160-166 35,5 34,0 32,0 30,0 27,0 25,0 - - - - - - - - -
3PF 32-200-186 42,0 40,0 37,5 35,1 31,0 28,0 - - - - - - - - -
3PF 32-200-200 53,5 52,0 49,5 46,5 43,5 40,5 38,0 - - - - - - - -
3PF 32-200-224 69,0 67,5 65,0 62,5 58,5 55,5 53,0 52,0 49,0 44,0 - - - - -
ENR 32-250-245 82,5 82,0 80,0 76,5 71,0 66,0 60,5 - - - - - - - -
ENR 32-250-255 92,3 91,5 89,5 86,0 80,5 75,5 70,0 68,0 - - - - - - -
3PF 40-160-166 - - 38,5 37,5 36,8 36,0 35,5 35,2 34,5 33,2 31,9 29,2 26,9 25,5 -
3PF 40-200-183 - - 45,5 44,5 44,0 43,0 42,5 42,0 41,0 39,5 38,0 35,1 32,5 31,0 -
3PF 40-200-200 - - 57,0 56,5 55,5 55,0 54,6 54,5 53,5 52,5 51,0 48,0 45,5 44,0 -
3PF 40-200-224 - - 71,0 70,5 70,2 70,0 69,5 69,0 68,5 67,5 66,0 63,0 60,5 59,0 -
ENR 40-250-220 - - 65,5 65 63,5 62,5 61,5 61,0 60,0 57,5 54,5 47,0 - - -
ENR 40-250-239 - - 79,8 79,5 78,5 78,0 77,5 77,0 76,0 74,0 71,5 65,5 59,5 - -
ENR 40-250-252 - - 91,0 90,5 90,0 89,0 88,5 88,3 87,5 86,0 83,5 78,5 73,5 70,0 69,0
BASE - JOINT 50-65 (3PF - ENR) PERFORMANCE TABLE
Series Size Q=Flow rate
pump pump l/min 400 450 500 590 660 700 800 1050 1150 1200 1320 1600 2200 2300 2400
m3/h 24 27 30 35 40 42 48 63 69 72 79 96 132 138 144
H=Head [m]
3PF 50-160-154 31,0 30,4 29,9 28,7 27,7 27,1 25,5 21,0 19,0 18,0 - - - - -
3PF 50-160-166 38,5 38,0 37,5 36,3 35,4 35,0 33,5 29,0 27,0 26,0 - - - - -
3PF 50-200-197 - - 53,0 52,0 50,5 50,0 48,0 42,0 38,7 37,0 - - - - -
3PF 50-200-212 - - 63,0 62,0 61,5 61,0 59,0 54,0 51,0 49,5 - - - - -
3PF 50-200-224 - - 70,0 69,0 68,5 68,0 66,0 61,0 58,5 57,0 - - - - -
ENR 50-250-222 67,0 66,5 66,0 64,5 63,0 62,0 59,5 49,5 - - - - - - -
ENR 50-250-235 76,0 75,5 75,0 74,0 73,0 72,0 69,5 61,0 56,0 - - - - - -
ENR 50-250-252 90,0 89,8 89,5 88,5 87,5 87,0 85,0 77,5 73,5 71,5 65,0 - - - -
3PF 65-200-190 - - - - - 51,0 50,0 47,5 46,0 45,5 44,0 40,0 30,0 - -
3PF 65-200-201 - - - - - 58,5 57,5 55,0 53,5 53,0 51,5 47,5 38,0 36,5 -
3PF 65-200-208 - - - - - 62,0 61,0 58,5 57,0 56,5 55,0 51,0 41,5 40,0 -
3PF 65-200-212 - - - - - 65,5 65,0 62,5 61,0 59,5 59,0 55,5 46,5 45,0 -
ENR 65-250-226 - - - - - - 66,5 65,5 65,0 64,9 64,0 61,0 50,5 - -
ENR 65-250-237 - - - - - - 75,5 75,0 74,5 74,0 73,0 70,0 60,5 58,5 -
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

ENR 65-250-252 - - - - - - 89,0 88,0 87,5 87,0 86,5 83,5 74,5 72,5 70,5
BASE - JOINT 80-100 (ENR) PERFORMANCE TABLE
Series Size Q=Flow rate
pump pump l/min 1200 1600 2000 2300 2600 3000 3150 3300 3500 3600 3800 4400 4700 5000 5200
m3/h 72 96 120 138 156 180 189 198 210 216 228 264 282 300 312
H=Head [m]
ENR 80-200-190 47,5 45,5 43,0 40,0 36,4 30,5 - - - - - - - - -
ENR 80-200-199 54,0 53,0 50,5 47,5 44,0 38,8 36,5 34,0 - - - - - - -
ENR 80-200-207 61,0 60,0 58,0 56,0 53,0 48,0 46,0 44,0 41,0 39,1 - - - - -
ENR 80-200-214 66,5 66,0 64,5 63,0 60,5 56,5 55,0 53,0 50,0 48,5 45,5 - - - -
ENR 80-250-222 64,0 62,5 60,0 56,5 52,0 45,0 - - - - - - - - -
ENR 80-250-234 73,5 72,5 70,0 67,0 63,0 55,5 52,5 - - - - - - - -
ENR 80-250-243 82,5 82,0 80,0 77,0 72,5 65,0 61,5 58,5 - - - - - - -
ENR 80-250-255 93,0 92,5 91,0 88,5 85,0 78,5 75,5 72,0 67,5 - - - - - -
ENR 100-200-182 - 39,5 38,5 37,5 36,0 33,5 32,5 31,3 29,7 28,9 27,2 21,8 - - -
ENR 100-200-190 - 44,5 43,5 43,0 41,5 40,0 38,9 37,9 36,5 35,7 34,0 28,5 25,5 - -
ENR 100-200-194 - 47,0 46,5 45,5 45,0 43,0 42,0 41,5 39,9 39,2 37,6 32,5 29,5 - -
ENR 100-200-197 - 49,5 49,0 48,5 47,5 46,0 45,0 44,0 43,0 42,0 40,5 35,5 33,0 30,0 -
ENR 100-200-201 - 52,0 51,5 51,0 50,0 48,5 48,0 47,0 46,0 45,5 44,0 39,3 36,7 33,5 -
ENR 100-200-209 - 56,5 56,0 55,5 55,0 53,5 53,0 52,5 51,0 50,5 49,5 45,0 42,5 39,8 38,0
ENR 100-200-213 - 59,0 58,5 58,0 57,5 56,0 55,5 55,0 54,0 53,0 52,0 47,5 45,5 43,0 41,0
ENR 100-250-221 - 62,0 61,0 60,0 59,0 56,5 56,0 55,0 53,5 52,5 50,5 44,0 - - -
ENR 100-250-225 - 65,5 64,5 63,5 62,5 60,5 59,5 58,5 57,0 56,0 54,5 48,0 44,0 - -
ENR 100-250-232 - 71,0 70,5 69,5 68,5 66,5 65,5 64,5 63,0 62,0 60,5 54,0 50,0 - -
ENR 100-250-242 - 80,0 79,0 78,5 77,5 76,0 75,5 74,5 73,0 72,0 70,5 64,0 60,0 56,0 -
ENR 100-250-248 - 85,0 84,5 84,0 83,0 81,5 81,0 80,5 79,0 78,5 77,0 71,0 67,5 64,0 61,0
ENR 100-250-255 - 91,0 90,5 90,0 89,5 88,5 88,0 87,0 86,0 85,5 84,0 78,0 75,0 71,5 68,5

Your Life, our Quality. Worldwide. 14 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

AGA SUR (JOCKEY) PERFORMANCE TABLE


Model P 2 Q=Flow rate
l/min 10 20 30 40 50 60 70 80
[HP] [kW] m3/h 0,6 1,2 1,8 2,4 3 3,6 4,2 4,8
H=Head [m]
AGA 300T SUR 3 2,2 73,5 68,0 63,5 58,8 54,5 50,9 47,3 44,0

PERFORMANCE TABLE FOR COMPACT (JOCKEY) PUMP


Model P 2 Q=Flow rate
l/min 20 30 40 50 60 80
[HP] [kW] m3/h 1,2 1,8 2,4 3 3,6 4,8
H=Head [m]
COMPACT A/10 1 0,75 56,5 53,0 48,5 43,5 37,1 20,0
COMPACT A/12 1,2 0,9 67,5 63,5 58,5 52,5 45,0 24,0
COMPACT A/15 1,5 1,1 79,0 74,5 69,0 62,5 54,0 28,0

PERFORMANCE TABLE FOR MATRIX (JOCKEY) PUMP


Model P 2 Q=Flow rate
l/min 30 45 60 80 100 130
[HP] [kW] m3/h 1,8 2,7 3,6 4,8 6 7,8
H=Head [m]
MATRIX 5-9T/2.2 3 2,2 97,0 92,0 87,0 78,0 66,0 39,6

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 15 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series 3PS 32-160 (impeller diameter - 166 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 16 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series 3PS 32-200 (impeller diameter - from 186 to 224 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 17 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series ENR 32-250 (impeller diameter - from 245 to 255 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 18 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series 3PS 40-160 (impeller diameter - 166 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 19 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series 3PS 40-200 (impeller diameter - from 183 to 224 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 20 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series ENR 40-250 (impeller diameter - from 220 to 252 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 21 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series 3PS 50-160 (impeller diameter - from 154 to 166 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 22 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series 3PS 50-200 (impeller diameter - from 197 to 224 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 23 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series ENR 50-250 (impeller diameter - from 222 to 252 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 24 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series 3PS 65-200 (impeller diameter - from 190 to 212 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 25 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series ENR 65-250 (impeller diameter - from 226 to 252 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 26 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series ENR 80-200 (impeller diameter - from 190 to 214 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 27 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series ENR 80-250 (impeller diameter - from 222 to 255 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 28 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series ENR 100-200 (1/2) (impeller diameter - from 182 to 194 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 29 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series ENR 100-200 (2/2) (impeller diameter - from 197 to 213 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 30 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series ENR 100-250 (1/2) (impeller diameter - from 221 to 232 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 31 Fire-Fighting


FFS-FFB
FIRE-FIGHTING UNITS

PERFORMANCE CURVES for series ENR 100-250 (2/2) (impeller diameter - from 242 to 255 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 32 Fire-Fighting


FFS-FFB
FFS/FFBE FIRE-FIGHTING UNITS

TABLE OF BASE-JOINT ELECTRICAL MODELS


Pump Size Motor FFS11/FFBE11 Pump FFS21/FFBE21 Pump
diameter electric pilot pilot
impeller [kW]
3PF 32-160-166 3 FFS 11 3PS 32-160-166/3 COMPACT A/10 FFS 21 3PS 32-160-166/3 COMPACT A/10
3PF 32-200-186 4 FFS 11 3PS 32-200-186/4 COMPACT A/10 FFS 21 3PS 32-200-186/4 COMPACT A/10
3PF 32-200-200 5,5 FFS 11 3PS 32-200-200/5.5 COMPACT A/12 FFS 21 3PS 32-200-200/5.5 COMPACT A/12
3PF 32-200-224 7.5 FFS 11 3PS 32-200-224/7.5 COMPACT A/15 FFS 21 3PS 32-200-224/7.5 COMPACT A/15
ENR 32-250-245 11 FFBE 11 ENRS 32-250-245/11 MATRIX 5-9T/2.2 FFBE 21 ENRS 32-250-245/11 MATRIX 5-9T/2.2
ENR 32-250-255 15 FFBE 11 ENRS 32-250-255/15 MATRIX 5-9T/2.2 FFBE 21 ENRS 32-250-255/15 MATRIX 5-9T/2.2
3PF 40-160-166 5,5 FFS 11 3PS 40-160-166/5.5 COMPACT A/10 FFS 21 3PS 40-160-166/5.5 COMPACT A/10
3PF 40-200-183 7,5 FFS 11 3PS 40-200-183/7.5 COMPACT A/10 FFS 21 3PS 40-200-183/7.5 COMPACT A/10
3PF 40-200-200 9,2 FFS 11 3PS 40-200-200/9.2 COMPACT A/12 FFS 21 3PS 40-200-200/9.2 COMPACT A/12
3PF 40-200-224 15 FFS 11 3PS 40-200-224/15 COMPACT A/15 FFS 21 3PS 40-200-224/15 COMPACT A/15
ENR 40-250-220 11 FFBE 11 ENRS 40-250-220/11 MATRIX 5-9T/2.2 FFBE 21 ENRS 40-250-220/11 MATRIX 5-9T/2.2
ENR 40-250-239 15 FFBE 11 ENRS 40-250-239/15 MATRIX 5-9T/2.2 FFBE 21 ENRS 40-250-239/15 MATRIX 5-9T/2.2
ENR 40-250-252 18,5 FFBE 11 ENRS 40-250-252/18.5 MATRIX 5-9T/2.2 FFBE 21 ENRS 40-250-252/18.5 MATRIX 5-9T/2.2
3PF 50-160-166 9,2 FFS 11 3PS 50-160-166/9.2 COMPACT A/10 FFS 21 3PS 50-160-166/9.2 COMPACT A/10
3PF 50-200-197 11 FFS 11 3PS 50-200-197/11 COMPACT A/12 FFS 21 3PS 50-200-197/11 COMPACT A/12
3PF 50-200-212 15 FFS 11 3PS 50-200-212/15 COMPACT A/15 FFS 21 3PS 50-200-212/15 COMPACT A/15
3PF 50-200-224 18,5 FFS 11 3PS 50-200-224/18.5 COMPACT A/15 FFS 21 3PS 50-200-224/18.5 COMPACT A/15
ENR 50-250-222 18,5 FFBE 11 ENRS 50-250-222/18.5 MATRIX 5-9T/2.2 FFBE 21 ENRS 50-250-222/18.5 MATRIX 5-9T/2.2
ENR 50-250-235 22 FFBE 11 ENRS 50-250-235/22 MATRIX 5-9T/2.2 FFBE 21 ENRS 50-250-235/22 MATRIX 5-9T/2.2
ENR 50-250-252 30 FFBE 11 ENRS 50-250-252/30 MATRIX 5-9T/2.2 FFBE 21 ENRS 50-250-252/30 MATRIX 5-9T/2.2
3PF 65-200-190 15 FFS 11 3PS 65-200-190/15 COMPACT A/12 FFS 21 3PS 65-200-190/15 COMPACT A/12
3PF 65-200-201 18,5 FFS 11 3PS 65-200-201/18.5 COMPACT A/12 FFS 21 3PS 65-200-201/18.5 COMPACT A/12
3PF 65-200-208 22 FFS 11 3PS 65-200-208/22 COMPACT A/15 FFS 21 3PS 65-200-208/22 COMPACT A/15
3PF 65-200-212 30 FFS 11 3PS 65-200-212/30 COMPACT A/15 FFS 21 3PS 65-200-212/30 COMPACT A/15
ENR 65-250-226 30 FFBE 11 ENRS 65-250-226/30 MATRIX 5-9T/2.2 FFBE 21 ENRS 65-250-226/30 MATRIX 5-9T/2.2
ENR 65-250-237 37 FFBE 11 ENRS 65-250-237/37 MATRIX 5-9T/2.2 FFBE 21 ENRS 65-250-237/37 MATRIX 5-9T/2.2
ENR 65-250-252 45 FFBE 11 ENRS 65-250-252/45 MATRIX 5-9T/2.2 FFBE 21 ENRS 65-250-252/45 MATRIX 5-9T/2.2
ENR 80-200-190 22 FFBE 11 ENRS 80-200-190/22 AGA 300T SUR FFBE 21 ENRS 80-200-190/22 AGA 300T SUR
ENR 80-200-199 30 FFBE 11 ENRS 80-200-199/30 AGA 300T SUR FFBE 21 ENRS 80-200-199/30 AGA 300T SUR
ENR 80-200-207 37 FFBE 11 ENRS 80-200-207/37 AGA 300T SUR FFBE 21 ENRS 80-200-207/37 AGA 300T SUR
ENR 80-200-214 45 FFBE 11 ENRS 80-200-214/45 AGA 300T SUR FFBE 21 ENRS 80-200-214/45 AGA 300T SUR
ENR 80-250-222 37 FFBE 11 ENRS 80-250-222/37 MATRIX 5-9T/2.2 FFBE 21 ENRS 80-250-222/37 MATRIX 5-9T/2.2
ENR 80-250-234 45 FFBE 11 ENRS 80-250-234/45 MATRIX 5-9T/2.2 FFBE 21 ENRS 80-250-234/45 MATRIX 5-9T/2.2
ENR 80-250-243 55 FFBE 11 ENRS 80-250-243/55 MATRIX 5-9T/2.2 FFBE 21 ENRS 80-250-243/55 MATRIX 5-9T/2.2

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
ENR 80-250-255 75 FFBE 11 ENRS 80-250-255/75 MATRIX 5-9T/2.2 FFBE 21 ENRS 80-250-255/75 MATRIX 5-9T/2.2
ENR 100-200-182 22 FFBE 11 ENRS 100-200-182/22 AGA 300T SUR FFBE 21 ENRS 100-200-182/22 AGA 300T SUR
ENR 100-200-194 30 FFBE 11 ENRS 100-200-194/30 AGA 300T SUR FFBE 21 ENRS 100-200-194/30 AGA 300T SUR
ENR 100-200-201 37 FFBE 11 ENRS 100-200-201/37 AGA 300T SUR FFBE 21 ENRS 100-200-201/37 AGA 300T SUR
ENR 100-200-209 45 FFBE 11 ENRS 100-200-209/45 AGA 300T SUR FFBE 21 ENRS 100-200-209/45 AGA 300T SUR
ENR 100-200-213 55 FFBE 11 ENRS 100-200-213/55 AGA 300T SUR FFBE 21 ENRS 100-200-213/55 AGA 300T SUR
ENR 100-250-221 45 FFBE 11 ENRS 100-250-221/45 MATRIX 5-9T/2.2 FFBE 21 ENRS 100-250-221/45 MATRIX 5-9T/2.2
ENR 100-250-232 55 FFBE 11 ENRS 100-250-232/55 MATRIX 5-9T/2.2 FFBE 21 ENRS 100-250-232/55 MATRIX 5-9T/2.2
ENR 100-250-248 75 FFBE 11 ENRS 100-250-248/75 MATRIX 5-9T/2.2 FFBE 21 ENRS 100-250-248/75 MATRIX 5-9T/2.2
ENR 100-250-255 90 FFBE 11 ENRS 100-250-255/90 MATRIX 5-9T/2.2 FFBE 21 ENRS 100-250-255/90 MATRIX 5-9T/2.2
For performance data refer to pages 14 to 32.

Your Life, our Quality. Worldwide. 33 Fire-Fighting


FFS-FFB
FFS11 FIRE-FIGHTING UNITS

FFS11 DIMENSIONS - 3PS ELECTRICAL PUMP+PILOT

SUCTION CONE

DIMENSIONS CHART
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Model Pilot pump Dimensions [mm] Weight


A B C C1 D E H DN1 DN2 DN3 R M N O Q HQ S T DN1-SK B2 C2 [kg]
[1] [2] [1] [2] [1] [2]
FFS11 3PS 32-160-166/3 COMPACT A 10 1075 280 80 165 1215 1035 330 50 65 G1 1690 65 450 1040 - 1230 400 1150 65 80 10 15 72 120 237
FFS11 3PS 32-200-186/4 COMPACT A 10 1125 310 80 165 1215 1035 330 50 65 G1 1740 65 450 1040 - 1230 400 1150 65 80 10 15 72 120 254
FFS11 3PS 32-200-200/5.5 COMPACT A/12 1125 310 80 165 1215 1035 330 50 65 G1 1740 65 450 1040 - 1260 400 1150 65 80 10 15 72 120 270
FFS11 3PS 32-200-224/7.5 COMPACT A/15 1125 310 80 165 1215 1035 330 50 65 G1 1740 65 450 1040 - 1260 400 1150 65 80 10 15 72 120 276
FFS11 3PS 40-160-166/5.5 COMPACT A/10 1165 280 80 170 1220 1040 330 65 80 G2 1780 70 450 1040 - 1230 400 1150 100 80 20 15 135 120 270
FFS11 3PS 40-200-183/7.5 COMPACT A/10 1210 310 100 170 1220 1040 330 65 80 G3 1825 70 450 1040 - 1260 400 1150 100 80 20 15 135 120 289
FFS11 3PS 40-200-200/9.2 COMPACT A/12 1210 310 100 170 1220 1040 330 65 80 G4 1825 70 450 1040 - 1360 500 1150 100 80 20 15 135 120 303
FFS11 3PS 40-200-224/15 COMPACT A/15 1210 310 100 170 1240 1040 330 65 80 G5 1825 70 450 1040 20 1410 500 1150 100 80 20 15 135 120 349
FFS11 3PS 5Q-160-166/9.2 COMPACT A/10 1425 310 100 180 1230 1040 330 65 100 G2 2055 80 450 1040 - 1360 500 1150 125 80 30 15 205 120 329
FFS11 3PS 5Q-200-197/11 COMPACT A/12 1445 310 100 180 1250 1040 330 65 100 G2 2075 80 450 1040 20 1410 500 1150 125 80 30 15 205 120 360
FFS11 3PS 5Q-200-212/15 COMPACT A/12 1445 310 100 180 1250 1040 330 65 100 G2 2075 80 450 1040 20 1410 500 1150 125 80 30 15 205 120 377
FFS11 3PS 5Q-200-224/18.5 COMPACT A/15 1445 310 100 180 1295 1040 330 65 100 G2 2075 80 450 1040 65 1410 500 1150 125 80 30 15 205 120 391
FFS11 3PS 65-200-190/15 COMPACT A/12 1555 330 100 230 1340 1040 330 80 125 DN80 2200 130 450 1040 60 1430 500 1150 150 200 35 60 235 375 421
FFS11 3PS 65-200-201/18.5 COMPACT A 12 1555 330 100 230 1385 1040 330 80 125 DN81 2200 130 450 1040 105 1530 600 1150 150 200 35 60 235 375 435
FFS11 3PS 65-200-208/22 COMPACT A 15 1555 330 100 230 1420 1040 330 80 125 DN82 2200 130 450 1040 140 1530 600 1150 150 200 35 60 235 375 519
FFS11 3PS 65-200-212/30 COMPACT A 15 1585 360 100 230 1580 1255 445 80 125 DN83 2230 130 550 1255 140 1630 600 1450 150 200 35 60 235 375 628
[1]= Underhead
[2]= Overhead

Your Life, our Quality. Worldwide. 34 Fire-Fighting


FFS-FFB
FFBE11 FIRE-FIGHTING UNITS

FFBE11 DIMENSIONS - ENRS ELECTRICAL PUMP+PILOT

TYPE A WITH THROTTLE VALVE


TYPE B WITH THREADED VALVE

SUCTION CONE

DIMENSIONS CHART
Model Pilot pump Dimensions [mm]
Type A B B1 C D D1 E H N DN1 DN1-JP DN2 DN3 R HQ O T DN1-SK B2 C2
[1] [2] [1] [2] [1] [2]

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
FFBE11 ENRS32-250-245/11E+2.2P MATRIX 5-9T/2.2 B 973 385 330 65 12281203 890 315 310 50 G1 65 G1 1066 1505 910 1200 65 80 8 14 180 185
FFBE11 ENRS32-250-255/15E+2.2P MATRIX 5-9T/2.2 B 973 385 330 65 12281203 890 315 310 50 G1 65 G1 1066 1505 910 1200 65 80 8 14 180 185
FFBE11 ENRS40-250-220/11E+2.2P MATRIX 5-9T/2.2 B 1034 385 330 65 12351214 894 315 310 65 G1 80 G2 1134 1505 910 1200 100 100 19 19 197 197
FFBE11 ENRS40-250-239/15E+2.2P MATRIX 5-9T/2.2 B 1034 385 330 65 12351214 894 315 310 65 G1 80 G2 1134 1505 910 1200 100 100 19 19 197 197
FFBE11 ENRS40-250-252/18.5E+2.2P MATRIX 5-9T/2.2 B 1034 385 330 65 12351214 894 315 310 65 G1 80 G2 1134 1505 910 1200 100 100 19 19 197 197
FFBE11 ENRS50-250-222/18.5E+2.2P MATRIX 5-9T/2.2 B 1232 385 330 65 12451232 898 315 310 65 G1 100 G2 1232 1505 910 1200 100 125 19 32 197 227
FFBE11 ENRS50-250-235/22E+2.2P MATRIX 5-9T/2.2 B 1154 417 350 65 14451432 998 370 340 65 G1 100 G2 1264 1517 1020 1400 100 125 19 32 197 227
FFBE11 ENRS50-250-252/30E+2.2P MATRIX 5-9T/2.2 B 1174 437 350 65 14451432 998 370 340 65 G1 100 G2 1284 1517 1020 1400 100 125 19 32 197 227
FFBE11 ENRS65-250-226/30E+2.2P MATRIX 5-9T/2.2 A 1443 437 350 65 146014851002 370 340 80 G1 125 80 1568 1517 1020 1400 150 200 40 65 340 550
FFBE11 ENRS65-250-237/37E+2.2P MATRIX 5-9T/2.2 A 1443 437 350 65 146014851102 370 340 80 G1 125 80 1568 1517 1020 1400 150 200 40 65 340 550
FFBE11 ENRS65-250-252/45E+2.2P MATRIX 5-9T/2.2 A 1521 515 480 125 170017251102 450 430 80 G1 125 80 1646 1535 1160 1700 150 200 40 65 340 550
FFBE11 ENRS80-200-190/22E+2.2P AGA 300T SUR A 1517 417 430 65 147815011002 370 340 100 G1 150 100 1660 1517 1020 1400 200 250 52 80 450 650
FFBE11 ENRS80-200-199/30E+2.2P AGA 300T SUR A 1537 437 430 65 147815011002 370 340 100 G1 150 100 1680 1517 1020 1400 200 250 52 80 450 650
FFBE11 ENRS80-200-207/37E+2.2P AGA 300T SUR A 1537 490 430 65 147815011002 370 430 100 G1 150 100 1680 1517 1020 1400 200 250 52 80 450 650
FFBE11 ENRS80-200-214/45E+2.2P AGA 300T SUR A 1615 515 560 125 171817411102 450 430 100 G1 150 100 1758 1535 1160 1700 200 250 52 80 450 650
FFBE11 ENRS80-250-222/37E+2.2P MATRIX 5-9T/2.2 A 1567 437 350 65 171015011002 370 340 100 G1 150 100 1710 1517 1020 1400 200 250 53 80 450 450
FFBE11 ENRS80-250-234/45E+2.2P MATRIX 5-9T/2.2 A 1645 515 480 125 178817411102 450 430 100 G1 150 100 1788 1535 1160 1700 200 200 53 80 450 450
FFBE11 ENRS80-250-243/55E+2.2P MATRIX 5-9T/2.2 A 1670 540 480 125 181317411102 450 430 100 G1 150 100 1813 1535 1160 1700 200 200 53 80 450 450
FFBE11 ENRS80-250-255/75E+2.2P MATRIX 5-9T/2.2 A 1700 570 480 125 184317411102 450 430 100 G1 150 100 1843 1535 1160 1700 200 200 53 80 450 450
FFBE11 ENRS100-200-182/22E+2.2P AGA 300T SUR A 1685 437 430 65 185515291006 370 340 125 G1 200 125 1855 1517 1020 1400 250 250 52 52 550 550
FFBE11 ENRS100-200-194/30E+2.2P AGA 300T SUR A 1685 437 430 65 185515291006 370 340 125 G1 200 125 1855 1517 1020 1400 250 250 52 52 550 550
FFBE11 ENRS100-200-201/37E+2.2P AGA 300T SUR A 1685 437 430 65 185515291106 370 340 125 G1 200 125 1855 1517 1020 1400 250 250 52 52 550 550
FFBE11 ENRS100-200-209/45E+2.2P AGA 300T SUR A 1763 515 560 125 193317691106 450 430 125 G1 200 125 1933 1535 1160 1700 250 250 52 52 550 550
FFBE11 ENRS100-200-213/55E+2.2P AGA 300T SUR A 1788 540 560 125 195817691106 450 430 125 G1 200 125 1958 1535 1160 1700 250 250 67 67 550 550
FFBE11 ENRS100-250-221/45E+2.2P MATRIX 5-9T/2.2 A 1793 515 480 125 193317691106 450 430 125 G1 200 125 1933 1535 1160 1700 250 250 67 67 550 550
FFBE11 ENRS100-250-232/55E+2.2P MATRIX 5-9T/2.2 A 1788 540 480 125 195817691106 450 430 125 G1 200 125 1958 1535 1160 1700 250 250 67 67 550 550
FFBE11 ENRS100-250-248/75E+2.2P MATRIX 5-9T/2.2 A 1818 570 480 125 198817691106 450 430 125 G1 200 125 1988 1535 1160 1700 250 250 67 67 550 550
FFBE11 ENRS100-250-255/90E+2.2P MATRIX 5-9T/2.2 A 1818 570 480 125 198817691106 450 430 125 G1 200 125 1988 1535 1160 1700 250 250 67 67 550 550
[1]= Underhead
[2]= Overhead

Your Life, our Quality. Worldwide. 35 Fire-Fighting


FFS-FFB
FFS21 FIRE-FIGHTING UNITS

FFS21 DIMENSIONS - 3PS ELECTRICAL PUMP+PILOT

SUCTION CONE

DIMENSIONS CHART
Model Pilot pump Dimensions [mm] Weight
A B C C1 D E H DN1 DN2 DN3 R M N O Q HQ S T DN1-SK B2 C2 [kg]
[1] [2] [1] [2] [1] [2]
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

FFS21 3PS 32-160-166/3 COMPACT A 10 1075 280 80 165 12151035 330 50 65 G1 1690 65 450 1040 - 1230 400 1150 65 80 10 15 72 120 359
FFS21 3PS 32-200-186/4 COMPACT A 10 1125 310 80 165 12151035 330 50 65 G1 1740 65 450 1040 - 1230 400 1150 65 80 10 15 72 120 393
FFS21 3PS 32-200-200/5.5 COMPACT A/12 1125 310 80 165 12151035 330 50 65 G1 1740 65 450 1040 - 1260 400 1150 65 80 10 15 72 120 426
FFS21 3PS 32-200-224/7.5 COMPACT A/15 1125 310 80 165 12151035 330 50 65 G1 1740 65 450 1040 - 1260 400 1150 65 80 10 15 72 120 437
FFS21 3PS 40-160-166/5.5 COMPACT A/10 1165 280 80 170 12201040 330 65 80 G2 1780 70 450 1040 - 1230 400 1150 100 80 20 15 135 120 422
FFS21 3PS 40-200-183/7.5 COMPACT A/10 1210 310 100 170 12201040 330 65 80 G3 1825 70 450 1040 - 1260 400 1150 100 80 20 15 135 120 459
FFS21 3PS 40-200-200/9.2 COMPACT A/12 1210 310 100 170 12201040 330 65 80 G4 1825 70 450 1040 - 1360 500 1150 100 80 20 15 135 120 486
FFS21 3PS 40-200-224/15 COMPACT A/15 1210 310 100 170 12401040 330 65 80 G5 1825 70 450 1040 20 1410 500 1150 100 80 20 15 135 120 577
FFS21 3PS 50-160-166/9.2 COMPACT A/10 1425 310 100 180 12301040 330 65 100 G2 2055 80 450 1040 - 1360 500 1150 125 80 30 15 205 120 521
FFS21 3PS 50-200-197/11 COMPACT A/12 1445 310 100 180 12501040 330 65 100 G2 2075 80 450 1040 20 1410 500 1150 125 80 30 15 205 120 582
FFS21 3PS 50-200-212/15 COMPACT A/12 1445 310 100 180 12501040 330 65 100 G2 2075 80 450 1040 20 1410 500 1150 125 80 30 15 205 120 616
FFS21 3PS 50-200-224/18.5 COMPACT A/15 1445 310 100 180 12951040 330 65 100 G2 2075 80 450 1040 65 1410 500 1150 125 80 30 15 205 120 644
FFS21 3PS 65-200-190/15 COMPACT A/12 1555 330 100 230 13401040 330 80 125 DN802200 130 450 1040 60 1430 500 1150 150 200 35 60 235 375 715
FFS21 3PS 65-200-201/18.5 COMPACT A 12 1555 330 100 230 13851040 330 80 125 DN812200 130 450 1040 105 1530 600 1150 150 200 35 60 235 375 735
FFS21 3PS 65-200-208/22 COMPACT A 15 1555 330 100 230 14201040 330 80 125 DN822200 130 450 1040 140 1530 600 1150 150 200 35 60 235 375 881
FFS21 3PS 65-200-212/30 COMPACT A 15 1585 360 100 230 15801255 445 80 125 DN832230 130 550 1255 140 1630 600 1450 150 200 35 60 235 375 1113
[1]= Underhead
[2]= Overhead

Your Life, our Quality. Worldwide. 36 Fire-Fighting


FFS-FFB
FFBE21 FIRE-FIGHTING UNITS

FFBE21 DIMENSIONS - ENRS ELECTRICAL PUMP+PILOT

TYPE A WITH THROTTLE VALVE


TYPE B WITH THREADED VALVE

SUCTION CONE

DIMENSIONS CHART
Model Pilot pump Dimensions [mm]
Type A B B1~ C D D1 E H N DN1 DN1-JP DN2 DN3 R HQ O T DN1-SK B2 C2
[1] [2] [1] [2] [1] [2]

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
FFBE21 ENRS32-250-245/11E+2.2P MATRIX 5-9T/2.2 B 973 385 330 65 122812031230 315 310 50 G1 65 G11066150512501200 65 80 8 14 180 185
FFBE21 ENRS32-250-255/15E+2.2P MATRIX 5-9T/2.2 B 973 385 330 65 122812031230 315 310 50 G1 65 G11066150512501200 65 80 8 14 180 185
FFBE21 ENRS40-250-220/11E+2.2P MATRIX 5-9T/2.2 B 1034 385 330 65 123512141234 315 310 65 G1 80 G2 1134150512501200 100 100 19 19 197 197
FFBE21 ENRS40-250-239/15E+2.2P MATRIX 5-9T/2.2 B 1034 385 330 65 123512141234 315 310 65 G1 80 G2 1134150512501200 100 100 19 19 197 197
FFBE21 ENRS40-250-252/18.5E+2.2P MATRIX 5-9T/2.2 B 1034 385 330 65 123512141234 315 310 65 G1 80 G2 1134150512501200 100 100 19 19 197 197
FFBE21 ENRS50-250-222/18.5E+2.2P MATRIX 5-9T/2.2 B 1122 385 330 65 124512321238 315 310 65 G1 100 G21232150512501200 100 125 19 32 197 227
FFBE21 ENRS50-250-235/22E+2.2P MATRIX 5-9T/2.2 B 1154 417 350 65 144514321403 370 340 65 G1 100 G21264151714201400 100 125 19 32 197 227
FFBE21 ENRS50-250-252/30E+2.2P MATRIX 5-9T/2.2 B 1174 437 350 65 144514321403 370 340 65 G1 100 G21284151714201400 100 125 19 32 197 227
FFBE21 ENRS65-250-226/30E+2.2P MATRIX 5-9T/2.2 A 1443 437 350 65 146014851407 370 340 80 G1 125 80 1568151714201400 150 200 40 65 340 550
FFBE21 ENRS65-250-237/37E+2.2P MATRIX 5-9T/2.2 A 1443 437 350 65 146014851407 370 340 80 G1 125 80 1568151714201400 150 200 40 65 340 550
FFBE21 ENRS65-250-252/45E+2.2P MATRIX 5-9T/2.2 A 1521 515 480 125170017251697 450 430 80 G1 125 80 1646153517601700 150 200 40 65 340 550
FFBE21 ENRS80-200-190/22E+2.2P AGA 300T SUR A 1517 417 430 65 147815011407 370 340 100 G1 150 100 1660151714201400 200 250 52 80 450 650
FFBE21 ENRS80-200-199/30E+2.2P AGA 300T SUR A 1537 437 430 65 147815011407 370 340 100 G1 150 100 1680151714201400 200 250 52 80 450 650
FFBE21 ENRS80-200-207/37E+2.2P AGA 300T SUR A 1537 437 430 65 147815011407 370 340 100 G1 150 100 1680151714201400 200 250 52 80 450 650
FFBE21 ENRS80-200-214/45E+2.2P AGA 300T SUR A 1615 515 560 125171817411697 450 430 100 G1 150 100 1758153517601700 200 250 52 80 450 650
FFBE21 ENRS80-250-222/37E+2.2P MATRIX 5-9T/2.2 A 1567 437 350 65 147815011407 370 340 100 G1 150 100 1710151714201400 200 200 200 200 450 450
FFBE21 ENRS80-250-234/45E+2.2P MATRIX 5-9T/2.2 A 1645 515 480 125171817411697 450 430 100 G1 150 100 1788153517601700 200 200 200 200 450 450
FFBE21 ENRS80-250-243/55E+2.2P MATRIX 5-9T/2.2 A 1670 540 480 125171817411697 450 430 100 G1 150 100 1813153517601700 200 200 200 200 450 450
FFBE21 ENRS80-250-255/75E+2.2P MATRIX 5-9T/2.2 A 1700 570 480 125171817411697 450 430 100 G1 150 100 1843153517601700 200 200 200 200 450 450
FFBE21 ENRS100-200-182/22E+2.2P AGA 300T SUR A 1685 437 430 65 150515291411 370 340 125 G1 200 125 1855151714201400 250 250 67 67 550 550
FFBE21 ENRS100-200-194/30E+2.2P AGA 300T SUR A 1685 437 430 65 150515291411 370 340 125 G1 200 125 1855151714201400 250 250 67 67 550 550
FFBE21 ENRS100-200-201/37E+2.2P AGA 300T SUR A 1685 437 430 65 150515291411 370 340 125 G1 200 125 1855151714201400 250 250 67 67 550 550
FFBE21 ENRS100-200-209/45E+2.2P AGA 300T SUR A 1763 515 560 125174517691701 450 430 125 G1 200 125 1933153517601700 250 250 67 67 550 550
FFBE21 ENRS100-200-213/55E+2.2P AGA 300T SUR A 1788 540 560 125174517691701 450 430 125 G1 200 125 1958153517601700 250 250 67 67 550 550
FFBE21 ENRS100-250-225E+2.2P MATRIX 5-9T/2.2 A 1763 515 480 125174517691701 450 430 125 G1 200 125 1933153517601700 250 250 67 67 620 620
FFBE21 ENRS100-250-232/55E+2.2P MATRIX 5-9T/2.2 A 1788 540 480 125174517691701 450 430 125 G1 200 125 1958153517601700 250 250 67 67 620 620
FFBE21 ENRS100-250-248/75E+2.2P MATRIX 5-9T/2.2 A 1818 570 480 125174517691701 450 430 125 G1 200 125 1988153517601700 250 250 67 67 620 620
FFBE21 ENRS100-250-255/90E+2.2P MATRIX 5-9T/2.2 A 1818 570 480 125174517691701 450 430 125 G1 200 125 1988153517601700 250 250 67 67 620 620
[1]= Underhead
[2]= Overhead

Your Life, our Quality. Worldwide. 37 Fire-Fighting


FFS-FFB
FFBD FIRE-FIGHTING UNITS

TABLE OF BASE-JOINT DIESEL MODELS


Pump Size Motor FFBD11 Pump FFBD21 Pump
diameter diesel pilot pilot
impeller [kW]
3PF 32-200-186 4,6 FFBD11 3PFS 32-200-186/4.6 COMPACT A/10 FFBD21 3PFS 32-200-186/4.6 COMPACT A/10
3PF 32-200-200 6,8 FFBD11 3PFS 32-200-200/6.8 COMPACT A/12 FFBD21 3PFS 32-200-200/6.8 COMPACT A/12
3PF 32-200-224 7,8 FFBD11 3PFS 32-200-224/7.8 COMPACT A/15 FFBD21 3PFS 32-200-224/7.8 COMPACT A/15
ENR 32-250-255 14,9 FFBD11 ENRS 32-250-255/14.9 MATRIX 5-9T/2.2 FFBD21 ENRS 32-250-255/14.9 MATRIX 5-9T/2.2
3PF 40-160-166 6,8 FFBD11 3PFS 40-160-166/6.8 COMPACT A/10 FFBD21 3PFS 40-160-166/6.8 COMPACT A/10
3PF 40-200-183 7,8 FFBD11 3PFS 40-200-183/7.8 COMPACT A/10 FFBD21 3PFS 40-200-183/7.8 COMPACT A/10
3PF 40-200-224 14,9 FFBD11 3PFS 40-200-224/14.9 COMPACT A/15 FFBD21 3PFS 40-200-224/14.9 COMPACT A/15
ENR 40-250-239 14,9 FFBD11 ENRS 40-250-239/14.9 MATRIX 5-9T/2.2 FFBD21 ENRS 40-250-239/14.9 MATRIX 5-9T/2.2
ENR 40-250-252 18,8 FFBD11 ENRS 40-250-252/18.8 MATRIX 5-9T/2.2 FFBD21 ENRS 40-250-252/18.8 MATRIX 5-9T/2.2
3PF 50-160-154 7,8 FFBD11 3PFS 50-160-154/7.8 COMPACT A/10 FFBD21 3PFS 50-160-154/7.8 COMPACT A/10
3PF 50-200-212 14,9 FFBD11 3PFS 50-200-212/14.9 COMPACT A/12 FFBD21 3PFS 50-200-212/14.9 COMPACT A/12
3PF 50-200-224 18,8 FFBD11 3PFS 50-200-224/18.8 COMPACT A/15 FFBD21 3PFS 50-200-224/18.8 COMPACT A/15
ENR 50-250-222 18,8 FFBD11 ENRS 50-250-222/18.8 MATRIX 5-9T/2.2 FFBD21 ENRS 50-250-222/18.8 MATRIX 5-9T/2.2
ENR 50-250-252 28,6 FFBD11 ENRS 50-250-252/28.6 MATRIX 5-9T/2.2 FFBD21 ENRS 50-250-252/28.6 MATRIX 5-9T/2.2
3PF 65-200-190 18,8 FFBD11 3PFS 65-200-190/18.8 COMPACT A/12 FFBD21 3PFS 65-200-190/18.8 COMPACT A/12
3PF 65-200-212 28,6 FFBD11 3PFS 65-200-212/28.6 COMPACT A/15 FFBD21 3PFS 65-200-212/28.6 COMPACT A/15
ENR 65-250-226 28,6 FFBD11 ENRS 65-250-226/28.6 MATRIX 5-9T/2.2 FFBD21 ENRS 65-250-226/28.6 MATRIX 5-9T/2.2
ENR 65-250-237 35 FFBD11 ENRS 65-250-237/35 MATRIX 5-9T/2.2 FFBD21 ENRS 65-250-237/35 MATRIX 5-9T/2.2
ENR 65-250-252 53 FFBD11 ENRS 65-250-252/53 MATRIX 5-9T/2.2 FFBD21 ENRS 65-250-252/53 MATRIX 5-9T/2.2
ENR 80-200-199 28,6 FFBD11 ENRS 80-200-199/28.6 AGA 300T SUR FFBD21 ENRS 80-200-199/28.6 AGA 300T SUR
ENR 80-200-207 35 FFBD11 ENRS 80-200-207/35 AGA 300T SUR FFBD21 ENRS 80-200-207/35 AGA 300T SUR
ENR 80-200-214 53 FFBD11 ENRS 80-200-214/53 AGA 300T SUR FFBD21 ENRS 80-200-214/53 AGA 300T SUR
ENR 80-250-222 35 FFBD11 ENRS 80-250-222/35 MATRIX 5-9T/2.2 FFBD21 ENRS 80-250-222/35 MATRIX 5-9T/2.2
ENR 80-250-243 53 FFBD11 ENRS 80-250-243/53 MATRIX 5-9T/2.2 FFBD21 ENRS 80-250-243/53 MATRIX 5-9T/2.2
ENR 80-250-255 73,5 FFBD11 ENRS 80-250-255/73.5 MATRIX 5-9T/2.2 FFBD21 ENRS 80-250-255/73.5 MATRIX 5-9T/2.2
ENR 100-200-190 28,6 FFBD11 ENRS 100-200-190/28.6 AGA 300T SUR FFBD21 ENRS 100-200-190/28.6 AGA 300T SUR
ENR 100-200-197 35 FFBD11 ENRS 100-200-197/35 AGA 300T SUR FFBD21 ENRS 100-200-197/35 AGA 300T SUR
ENR 100-200-213 53 FFBD11 ENRS 100-200-213/53 AGA 300T SUR FFBD21 ENRS 100-200-213/53 AGA 300T SUR
ENR 100-250-225 53 FFBD11 ENRS 100-250-225/53 MATRIX 5-9T/2.2 FFBD21 ENRS 100-250-225/53 MATRIX 5-9T/2.2
ENR 100-250-242 73,5 FFBD11 ENRS 100-250-242/73.5 MATRIX 5-9T/2.2 FFBD21 ENRS 100-250-242/73.5 MATRIX 5-9T/2.2
ENR 100-250-255 110 FFBD11 ENRS 100-250-255/110 MATRIX 5-9T/2.2 FFBD21 ENRS 100-250-255/110 MATRIX 5-9T/2.2
For performance data refer to pages 14 to 32.
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 38 Fire-Fighting


FFS-FFB
FFBD11 FIRE-FIGHTING UNITS

FFBD11 DIMENSIONS - 3PFS-ENRS MOTOR PUMP+PILOT

TYPE A WITH THROTTLE VALVE

TYPE B WITH THREADED VALVE

SUCTION CONE

DIMENSIONS CHART

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
Model Pilot pump Dimensions [mm]
Type A B B1 C D D1 E H N DN1DN1-JPDN2 DN3 R HQ O T DN1-SK B2 C2
[1] [2] [1] [2] [1] [2]
FFBD11 3PFS32-160-166/4.6D+0.75P COMPACT A/10 B 983 365 ~364 65 12281203 890 315 310 50 G1 65 G1 1076 1505 910 1200 65 80 8 14 180 185
FFBD11 3PFS32-200-186/4.6D+0.75P COMPACT A/10 B 1003 365 ~364 65 12281203 890 315 310 50 G1 65 G1 1096 1505 910 1200 65 80 8 14 180 185
FFBD11 3PFS32-200-200/6.7D+0.9P COMPACT A/12 B 1003 365 ~364 65 12281203 890 315 310 50 G1 65 G1 1096 1505 910 1200 65 80 8 14 180 185
FFBD11 3PFS32-200-224/7.8D+1.1P COMPACT A/15 B 1003 365 ~364 65 12281203 890 315 310 50 G1 65 G1 1096 1505 910 1200 65 80 8 14 180 185
FFBD11 3PFS40-160-166/6.7D+0.75P COMPACT A/10 B 1044 365 ~364 65 12351214 894 315 310 65 G1 80 G 2 1144 1505 910 1200 100 100 19 19 197 197
FFBD11 3PFS40-200-183/7.8D+0.75P COMPACT A/10 B 1064 365 ~364 65 12351214 894 315 310 65 G1 80 G 2 1164 1505 910 1200 100 100 19 19 197 197
FFBD11 3PFS40-200-224/14.9D+1.1P COMPACT A/15 B 1089 390 ~364 65 12351214 894 315 310 65 G1 80 G 2 1189 1505 910 1200 100 100 19 19 197 197
FFBD11 3PFS50-160-154/7.8D+0.75P COMPACT A/10 B 1162 365 ~364 65 12451232 898 315 310 65 G1 100 G 2 1272 1505 910 1200 100 125 19 32 197 227
FFBD11 3PFS50-200-212/14.9D+0.9P COMPACT A/12 B 1207 390 ~364 65 12451232 898 315 310 65 G1 100 G 2 1317 1505 910 1200 100 125 19 32 197 227
FFBD11 3PFS50-200-224/18.8D+1.1P COMPACT A/15 B 1234 417 ~384 65 14451432 998 370 340 65 G1 100 G 2 1344 151710201400 100 125 19 32 197 227
FFBD11 3PFS65-200-190/18.8D+0.9P COMPACT A/12 A 1398 417 ~384 65 14601485 1002 370 340 80 G1 125 DN80 1523 151710201400 150 200 40 65 340 550
FFBD11 3PFS65-200-212/28.6D+1.1P COMPACT A/15 A 1432 451 ~384 65 14601485 1002 370 340 80 G1 125 DN80 1557 151710201400 150 200 40 65 340 550
FFBD11 ENRS32-250-255/14.9D+2.2P MATRIX 5-9T/2.2 B 1073 390 ~330 65 12281203 890 315 310 50 G 1 65 G 1 1166 1505 910 1200 65 80 8 14 180 185
FFBD11 ENRS40-250-239/14.9D+2.2P MATRIX 5-9T/2.2 B 1134 390 ~330 65 12351214 894 315 310 65 G 1 80 G 2 1234 1505 910 1200 100 100 19 19 197 197
FFBD11 ENRS40-250-252/18.8D+2.2P MATRIX 5-9T/2.2 B 1161 417 ~350 65 14351414 994 370 340 65 G 1 80 G 2 1261 151710201400 100 100 19 19 197 197
FFBD11 ENRS50-250-222/18.8D+2.2P MATRIX 5-9T/2.2 B 1259 417 ~350 65 14451432 994 370 340 65 G 1 100 G 2 1369 151710201400 100 125 19 32 197 227
FFBD11 ENRS50-250-252/28.6D+2.2P MATRIX 5-9T/2.2 B 1293 451 ~350 65 14451432 998 370 340 65 G 1 100 G 2 1403 151710201400 100 125 19 32 197 227
FFBD11 ENRS65-250-226/28.6D+2.2P MATRIX 5-9T/2.2 A 1457 451 ~350 65 14601485 1002 370 340 80 G 1 125 DN80 1582 151710201400 150 200 40 65 340 550
FFBD11 ENRS80-200-199/28.6D+2.2P AGA 300T SUR A 1551 451 ~430 65 14781501 1002 370 340 100 G 1 150 DN1001694 151710201400 200 250 52 80 450 650
FFBD11 ENRS100-200-190/28.6D+2.2P AGA 300T SUR A 1699 451 ~430 65 15051529 1006 370 340 125 G 1 200 DN1251869 151710201400 250 250 67 67 550 550
[1]= Underhead
[2]= Overhead

Your Life, our Quality. Worldwide. 39 Fire-Fighting


FFS-FFB
FFBD11 FIRE-FIGHTING UNITS

FFBD11 DIMENSIONS - ENRS MOTOR PUMP+PILOT

SUCTION CONE

DIMENSIONS CHART
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Model Pilot pump Dimensions [mm]


A B B1 C D D1 E H N DN1 DN1-JP DN2 DN3 R HQ O T DN1-SK B2 C2
[1] [2] [1] [2] [1] [2]
FFBD11 ENRS65-250-237/35D+2.2P MATRIX 5-9T/2.2 1526 520 ~480 125 1700 1725 1697 450 430 80 G 1 125 DN80 1651 1830 1760 1700 150 200 40 65 340 550
FFBD11 ENRS65-250-252/53D+2.2P MATRIX 5-9T/2.2 1526 520 ~480 125 1700 1725 1697 450 430 80 G 1 125 DN80 1651 1830 1760 1700 150 200 40 65 340 550
FFBD11 ENRS80-200-207/35D+2.2P AGA 300T SUR 1620 520 ~560 125 1718 1741 1697 450 430 100 G 1 150 DN100 1763 1830 1760 1700 200 250 80 80 720 650
FFBD11 ENRS80-200-214/53D+2.2P AGA 300T SUR 1620 520 ~560 125 1718 1741 1697 450 430 100 G 1 150 DN100 1763 1830 1760 1700 200 250 80 80 720 650
FFBD11 ENRS80-250-222/35D+2.2P MATRIX 5-9T/2.2 1650 520 ~480 125 1718 1741 1697 450 430 100 G 1 150 DN100 1793 1830 1760 1700 200 200 52 52 450 450
FFBD11 ENRS80-250-243/53D+2.2P MATRIX 5-9T/2.2 1650 520 ~480 125 1718 1741 1697 450 430 100 G 1 150 DN100 1793 1830 1760 1700 200 200 52 52 450 450
FFBD11 ENRS80-250-255/73,5D+2.2P MATRIX 5-9T/2.2 1700 570 ~480 125 1718 1741 1697 450 430 100 G 1 150 DN100 1843 1830 1760 1700 200 200 52 52 450 450
FFBD11 ENRS100-200-197/35D+2.2P AGA 300T SUR 1768 520 ~560 125 1745 1769 1701 450 430 125 G 1 200 DN125 1938 1830 1760 1700 250 250 67 67 620 620
FFBD11 ENRS100-200-213/53D+2.2P AGA 300T SUR 1768 520 ~560 125 1745 1769 1701 450 430 125 G 1 200 DN125 1938 1830 1760 1700 250 250 67 67 620 620
FFBD11 ENRS100-250-225/53D+2.2P MATRIX 5-9T/2.2 1768 520 ~480 125 1745 1769 1701 450 430 125 G 1 200 DN125 1938 1830 1760 1700 250 250 67 67 620 620
FFBD11 ENRS100-250-242/73,5D+2.2P MATRIX 5-9T/2.2 1788 540 ~480 125 1745 1769 1701 450 430 125 G 1 200 DN125 1958 1830 1760 1700 250 250 67 67 620 620
FFBD11 ENRS100-250-255/110D+2.2P MATRIX 5-9T/2.2 1848 600 ~480 125 2045 2069 1701 450 430 125 G 1 200 DN125 2018 1830 1760 2000 250 250 67 67 620 620
[1]= Underhead
[2]= Overhead

Your Life, our Quality. Worldwide. 40 Fire-Fighting


FFS-FFB
FFBD21 FIRE-FIGHTING UNITS

FFBD21 DIMENSIONS - 3PFS-ENRS MOTOR PUMPS+PILOT

TYPE A WITH THROTTLE VALVE

TYPE B WITH THREADED VALVE

SUCTION CONE

DIMENSIONS CHART

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
Model Pilot pump Dimensions [mm]
Type A B B1 C D D1 E H N DN1DN1-JPDN2 DN3 R HQ O T DN1-SK B2 C2
[1] [2] [1] [2] [1] [2]
FFBD21 3PFS32-160-166/4.6D+0.75P COMPACT A/10 B 983 365 ~364 65 12281203 1230 315 310 50 G1 65 G1 1076 150512501200 65 80 8 14 180 185
FFBD21 3PFS32-200-186/4.6D+0.75P COMPACT A/10 B 1003 365 ~364 65 12281203 1230 315 310 50 G1 65 G1 1096 150512501200 65 80 8 14 180 185
FFBD21 3PFS32-200-200/6.7D+0.9P COMPACT A/12 B 1003 365 ~364 65 12281203 1230 315 310 50 G1 65 G1 1096 150512501200 65 80 8 14 180 185
FFBD21 3PFS32-200-224/7.8D+1.1P COMPACT A/15 B 1003 365 ~364 65 12281203 1230 315 310 50 G1 65 G1 1096 150512501200 65 80 8 14 180 185
FFBD21 3PFS40-160-166/6.7D+0.75P COMPACT A/10 B 1044 365 ~364 65 12351214 1234 315 310 65 G1 80 G 2 1144 150512501200 100 100 19 19 197 197
FFBD21 3PFS40-200-183/7.8D+0.75P COMPACT A/10 B 1064 365 ~364 65 12351214 1234 315 310 65 G1 80 G 2 1164 150512501200 100 100 19 19 197 197
FFBD21 3PFS40-200-224/14.9D+1.1P COMPACT A/15 B 1089 390 ~364 65 12351214 1234 315 310 65 G1 80 G 2 1189 150512501200 100 100 19 19 197 197
FFBD21 3PFS50-160-154/7.8D+0.75P COMPACT A/10 B 1162 365 ~364 65 12451232 1238 315 310 65 G1 100 G 2 1272 150512501200 100 125 19 32 197 227
FFBD21 3PFS50-200-212/14.9D+0.9P COMPACT A/12 B 1207 390 ~364 65 12451232 1238 315 310 65 G1 100 G 2 1317 150512501200 100 125 19 32 197 227
FFBD21 3PFS50-200-224/18.8D+1.1P COMPACT A/15 B 1234 417 ~384 65 14451432 1403 370 340 65 G1 100 G 2 1344 151714201400 100 125 19 32 197 227
FFBD21 3PFS65-200-190/18.8D+0.9P COMPACT A/12 A 1398 417 ~384 65 14601485 1407 370 340 80 G1 125 DN80 1523 151714201400 150 200 40 65 340 550
FFBD21 3PFS65-200-212/28.6D+1.1P COMPACT A/15 A 1432 451 ~384 65 14601485 1407 370 340 80 G1 125 DN80 1557 151714201400 150 200 40 65 340 550
FFBD21 ENRS32-250-255/14.9D+2.2P MATRIX 5-9T/2.2 B 1073 390 ~330 65 12281203 1230 315 310 50 G 1 65 G1 1166 150512501200 65 80 8 14 180 185
FFBD21 ENRS40-250-239/14.9D+2.2P MATRIX 5-9T/2.2 B 1129 385 ~330 65 12351214 1234 315 310 65 G 1 80 G 2 1229 150512501200 100 100 19 19 197 197
FFBD21 ENRS40-250-252/18.8D+2.2P MATRIX 5-9T/2.2 B 1161 417 ~350 65 14351414 1399 370 340 65 G 1 80 G 2 1261 151714201400 100 100 19 19 197 197
FFBD21 ENRS50-250-222/18.8D+2.2P MATRIX 5-9T/2.2 B 1259 417 ~350 65 14451432 1403 370 340 65 G 1 100 G 2 1369 151714201400 100 125 19 32 197 227
FFBD21 ENRS50-250-252/28.6D+2.2P MATRIX 5-9T/2.2 B 1293 451 ~350 65 14451432 1403 370 340 65 G 1 100 G 2 1403 151714201400 100 125 19 32 197 227
FFBD21 ENRS65-250-226/28.6D+2.2P MATRIX 5-9T/2.2 A 1457 451 ~350 65 14601485 1407 370 340 80 G 1 125 DN80 1582 151714201400 150 200 40 65 340 550
FFBD21 ENRS80-200-199/28.6D+2.2P AGA 300T SUR A 1551 451 ~430 65 14781501 1407 370 340 100 G 1 150 DN1001694 151714201400 200 250 52 80 450 650
FFBD21 ENRS100-200-190/28.6D+2.2P AGA 300T SUR A 1699 451 ~430 65 15051529 1407 370 340 125 G 1 200 DN1251869 151714201400 250 250 67 67 550 550
[1]= Underhead
[2]= Overhead

Your Life, our Quality. Worldwide. 41 Fire-Fighting


FFS-FFB
FFBD21 FIRE-FIGHTING UNITS

FFBD21 DIMENSIONS - ENRS MOTOR PUMPS+PILOT

SUCTION CONE

DIMENSIONS CHART
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Model Pilot pump Dimensions [mm]


A B B1 C D D1 E H N DN1 DN1-JP DN2 DN3 R HQ O T DN1-SK B2 C2
[1] [2] [1] [2] [1] [2]
FFBD21 ENRS65-250-237/35D+2.2P MATRIX 5-9T/2.2 1556 550 ~480 125 1700 1725 2037 450 430 80 G 1 125 DN80 1681 1830 2100 1700 150 200 40 65 340 550
FFBD21 ENRS65-250-252/53D+2.2P MATRIX 5-9T/2.2 1556 550 ~480 125 1700 1725 2037 450 430 80 G 1 125 DN80 1681 1830 2100 1700 150 200 40 65 340 550
FFBD21 ENRS80-200-207/35D+2.2P AGA 300T SUR 1650 550 ~560 125 1718 1741 2037 450 430 100 G 1 150 DN100 1793 1830 2100 1700 200 250 52 80 450 650
FFBD21 ENRS80-200-214/53D+2.2P AGA 300T SUR 1650 550 ~560 125 1718 1741 2037 450 430 100 G 1 150 DN100 1793 1830 2100 1700 200 250 52 80 450 650
FFBD21 ENRS80-250-222/35D+2.2P MATRIX 5-9T/2.2 1680 550 ~480 125 1718 1741 2037 450 430 100 G 1 150 DN100 1823 1830 2100 1700 200 200 52 52 450 450
FFBD21 ENRS80-250-243/53D+2.2P MATRIX 5-9T/2.2 1680 550 ~480 125 1718 1741 2037 450 430 100 G 1 150 DN100 1823 1830 2100 1700 200 200 52 52 450 450
FFBD21 ENRS80-250-255/73,5D+2.2P MATRIX 5-9T/2.2 1730 600 ~480 125 1718 1741 2037 450 430 100 G 1 150 DN100 1873 1830 2100 1700 200 200 52 52 450 450
FFBD21 ENRS100-200-197/35D+2.2P AGA 300T SUR 1798 550 ~560 125 1745 1769 2041 450 430 125 G 1 200 DN125 1968 1830 2100 1700 250 250 67 67 550 550
FFBD21 ENRS100-200-213/53D+2.2P AGA 300T SUR 1798 550 ~560 125 1745 1769 2041 450 430 125 G 1 200 DN125 1968 1830 2100 1700 250 250 67 67 550 550
FFBD21 ENRS100-250-225/53D+2.2P MATRIX 5-9T/2.2 1798 550 ~480 125 1745 1769 2041 450 430 125 G 1 200 DN125 1968 1830 2100 1700 250 250 67 67 550 550
FFBD21 ENRS100-250-242/73,5D+2.2P MATRIX 5-9T/2.2 1818 570 ~480 125 1745 1769 2041 450 430 125 G 1 200 DN125 1988 1830 2100 1700 250 250 67 67 550 550
FFBD21 ENRS100-250-255/110D+2.2P MATRIX 5-9T/2.2 1848 600 ~480 125 2045 2069 2041 450 430 125 G 1 200 DN125 2018 1830 2100 2000 250 250 67 67 550 550
[1]= Underhead
[2]= Overhead

Your Life, our Quality. Worldwide. 42 Fire-Fighting


FFS-FFB
FFBD111 FIRE-FIGHTING UNITS

TABLE OF BASE-JOINT ELECTRICAL-DIESEL MODELS


Pump Size Motor Motor FFBD111 Pump
diameter electric diesel pilot
impeller [kW] [kW]
3PF 32-160-166 3 4,6 FFBD111 3PFS 32-160-166/3/4.6 COMPACT A/10
3PF 32-200-186 4 4,6 FFBD111 3PFS 32-200-186/4/4.6 COMPACT A/10
3PF 32-200-200 5,5 6,8 FFBD111 3PFS 32-200-200/5.5/6.8 COMPACT A/12
3PF 32-200-224 7.5 7,8 FFBD111 3PFS 32-200-224/7.5/7.8 COMPACT A/15
ENR 32-250-245 11 14,9 FFBD111 ENRS 32-250-245/11/14.9 MATRIX 5-9T/2.2
ENR 32-250-255 15 14,9 FFBD111 ENRS 32-250-255/15/14.9 MATRIX 5-9T/2.2
3PF 40-160-166 5,5 6,8 FFBD111 3PFS 40-160-166/5.5/6.8 COMPACT A/10
3PF 40-200-183 7,5 7,8 FFBD111 3PFS 40-200-183/7.5/7.8 COMPACT A/10
3PF 40-200-200 9,2 14,9 FFBD111 3PFS 40-200-200/11/14.9 COMPACT A/12
3PF 40-200-224 15 14,9 FFBD111 3PFS 40-200-224/15/14.9 COMPACT A/15
ENR 40-250-239 15 14,9 FFBD111 ENRS 40-250-239/15/14.9 MATRIX 5-9T/2.2
ENR 40-250-252 18,5 18,8 FFBD111 ENRS 40-250-252/18.5/18.8 MATRIX 5-9T/2.2
3PF 50-160-154 7,5 7,8 FFBD111 3PFS 50-160-154/7.5/7.8 COMPACT A/10
3PF 50-200-197 11 14,9 FFBD111 3PFS 50-200-197/11/14.9 COMPACT A/12
3PF 50-200-212 15 14,9 FFBD111 3PFS 50-200-212/15/14.9 COMPACT A/12
3PF 50-200-224 18,5 18,8 FFBD111 3PFS 50-200-224/18.5/18.8 COMPACT A/15
ENR 50-250-222 18,5 18,8 FFBD111 ENRS 50-250-222/18.5/18.8 MATRIX 5-9T/2.2
ENR 50-250-235 22 28,6 FFBD111 ENRS 50-250-235/22/28.6 MATRIX 5-9T/2.2
ENR 50-250-252 30 28,6 FFBD111 ENRS 50-250-252/30/28.6 MATRIX 5-9T/2.2
3PF 65-200-190 15 18,8 FFBD111 3PFS 65-200-190/15/18.8 COMPACT A/12
3PF 65-200-208 22 28,6 FFBD111 3PFS 65-200-208/22/28.6 COMPACT A/15
3PF 65-200-212 30 28,6 FFBD111 3PFS 65-200-212/30/28.6 COMPACT A/15
ENR 65-250-226 30 28,6 FFBD111 ENRS 65-250-226/30/28.6 MATRIX 5-9T/2.2
ENR 65-250-237 37 35 FFBD111 ENRS 65-250-237/37/35 MATRIX 5-9T/2.2
ENR 65-250-252 45 53 FFBD111 ENRS 65-250-252/45/53 MATRIX 5-9T/2.2
ENR 80-200-190 22 28,6 FFBD111 ENRS 80-200-190/22/28.6 AGA 300T SUR
ENR 80-200-199 30 28,6 FFBD111 ENRS 80-200-199/30/28.6 AGA 300T SUR
ENR 80-200-207 37 35 FFBD111 ENRS 80-200-207/37/35 AGA 300T SUR
ENR 80-200-214 45 53 FFBD111 ENRS 80-200-214/45/53 AGA 300T SUR
ENR 80-250-222 37 35 FFBD111 ENRS 80-250-222/37/35 MATRIX 5-9T/2.2
ENR 80-250-234 45 53 FFBD111 ENRS 80-250-234/45/53 MATRIX 5-9T/2.2
ENR 80-250-243 55 53 FFBD111 ENRS 80-250-243/55/53 MATRIX 5-9T/2.2
ENR 80-250-255 75 73,5 FFBD111 ENRS 80-250-255/75/73.5 MATRIX 5-9T/2.2
ENR 100-200-182 22 28,6 FFBD111 ENRS 100-200-182/22/28.6 AGA 300T SUR

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
ENR 100-200-190 30 28,6 FFBD111 ENRS 100-200-190/30/28.6 AGA 300T SUR
ENR 100-200-194 30 35 FFBD111 ENRS 100-200-194/30/35 AGA 300T SUR
ENR 100-200-197 37 35 FFBD111 ENRS 100-200-197/37/35 AGA 300T SUR
ENR 100-200-209 45 53 FFBD111 ENRS 100-200-209/45/53 AGA 300T SUR
ENR 100-200-213 55 53 FFBD111 ENRS 100-200-213/55/53 AGA 300T SUR
ENR 100-250-221 45 53 FFBD111 ENRS 100-250-221/45/53 MATRIX 5-9T/2.2
ENR 100-250-225 55 53 FFBD111 ENRS 100-250-225/55/53 MATRIX 5-9T/2.2
ENR 100-250-232 55 73,5 FFBD111 ENRS 100-250-232/55/73.5 MATRIX 5-9T/2.2
ENR 100-250-242 75 73,5 FFBD111 ENRS 100-250-242/75/73.5 MATRIX 5-9T/2.2
ENR 100-250-255 90 110 FFBD111 ENRS 100-250-255/90/110 MATRIX 5-9T/2.2
For performance data refer to pages 14 to 32.

Your Life, our Quality. Worldwide. 43 Fire-Fighting


FFS-FFB
FFBD111 FIRE-FIGHTING UNITS

FFBD111 DIMENSIONS - 3PFS-ENRS ELECTRICAL PUMP-MOTOR PUMP+PILOT

TYPE A WITH THROTTLE VALVE

TYPE B WITH THREADED VALVE

SUCTION CONE

DIMENSIONS CHART
Model Pilot pump Dimensions [mm]
Type A B B1 C D D1 E H N DN1 DN1-JP DN2 DN3 R HQ O T DN1-SK B2 C2
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

[1] [2] [1] [2] [1] [2]


FFBD111 3PFS32-160-166/3E/4.6D+0.75P COMPACT A/10 B 983 365 ~364 65 1228 1203 1230 315 310 50 G1 65 G1 1076 150512501200 65 80 8 14 180 185
FFBD111 3PFS32-200-186/4E/4.6D+0.75P COMPACT A/10 B 1003 365 ~364 65 1228 1203 1230 315 310 50 G1 65 G1 1096 150512501200 65 80 8 14 180 185
FFBD111 3PFS32-200-200/5.5E/6.7D+0.9P COMPACT A/12 B 1003 365 ~364 65 1228 1203 1230 315 310 50 G1 65 G1 1096 150512501200 65 80 8 14 180 185
FFBD111 3PFS32-200-224/7.5E/7.8D+1.1P COMPACT A/15 B 1003 365 ~364 65 1228 1203 1230 315 310 50 G1 65 G1 1096 150512501200 65 80 8 14 180 185
FFBD111 3PFS40-160-166/5.5E/6.7D+0.75P COMPACT A/10 B 1044 365 ~364 65 1235 1214 1234 315 310 65 G1 80 G 2 1144 150512501200 100 100 19 19 197 197
FFBD111 3PFS40-200-183/7.5E/7.8D+0.75P COMPACT A/10 B 1064 365 ~364 65 1235 1214 1234 315 310 65 G1 80 G 2 1164 150512501200 100 100 19 19 197 197
FFBD111 3PFS40-200-200/9.2E/14.9D+0.9P COMPACT A/12 B 1089 390 ~364 65 1235 1214 1234 315 310 65 G1 80 G 2 1189 150512501200 100 100 19 19 197 197
FFBD111 3PFS40-200-224/15E/14.9D+1.1P COMPACT A/15 B 1089 390 ~364 65 1235 1214 1234 315 310 65 G1 80 G 2 1189 150512501200 100 100 19 19 197 197
FFBD111 3PFS50-160-154/7.5E/7.8D+0.75P COMPACT A/10 B 1162 365 ~364 65 1245 1232 1238 315 310 65 G1 100 G 2 1272 150512501200 100 125 19 32 197 227
FFBD111 3PFS50-200-197/11E/14.9D+0.9P COMPACT A/12 B 1207 390 ~364 65 1245 1232 1238 315 310 65 G1 100 G 2 1317 150512501200 100 125 19 32 197 227
FFBD111 3PFS50-200-212/15E/14.9D+0.9P COMPACT A/12 B 1207 390 ~364 65 1245 1232 1238 315 310 65 G1 100 G 2 1317 150512501200 100 125 19 32 197 227
FFBD111 3PFS50-200-224/18,5E/18.8D+1.1P COMPACT A/15 B 1234 417 ~384 65 1445 1432 1403 370 340 65 G1 100 G 2 1344 151714201400 100 125 19 32 197 227
FFBD111 3PFS65-200-190/15E/18.8D+0.9P COMPACT A/12 A 1398 417 ~384 65 1460 1485 1407 370 340 80 G1 125 DN80 1523 151714201400 150 200 40 65 340 550
FFBD111 3PFS65-200-208/22E/28.6D+1.1P COMPACT A/15 A 1432 451 ~384 65 1460 1485 1407 370 340 80 G1 125 DN80 1557 151714201400 150 200 40 65 340 550
FFBD111 3PFS65-200-212/30E/28.6D+1.1P COMPACT A/15 A 1432 451 ~384 65 1460 1485 1407 370 340 80 G1 125 DN80 1557 151714201400 150 200 40 65 340 550
FFBD111 ENRS32-250-245/11E/14.9D+2.2P MATRIX 5-9T/2.2 B 1073 390 ~330 65 1228 1203 1230 315 310 50 G1 65 G 2 1166 150512501200 65 80 8 14 180 185
FFBD111 ENRS32-250-255/15E/14.9D+2.2P MATRIX 5-9T/2.2 B 1073 390 ~330 65 1228 1203 1230 315 310 50 G1 65 G 2 1166 150512501200 65 80 8 14 180 185
FFBD111 ENRS40-250-239/15E/14.9D+2.2P MATRIX 5-9T/2.2 B 1129 385 ~330 65 1235 1214 1234 315 310 65 G1 80 G2 1229 113212501200 100 100 19 19 197 197
FFBD111 ENRS40-250-252/18.5E/18.8D+2.2P MATRIX 5-9T/2.2 B 1161 417 ~350 65 1435 1414 1399 370 340 65 G1 80 G2 1261 115914201400 100 100 19 19 197 197
FFBD111 ENRS50-250-222/18.5E/18.8D+2.2P MATRIX 5-9T/2.2 B 1259 417 ~350 65 1445 1432 1403 370 340 65 G1 100 G 2 1369 151714201400 100 125 19 32 197 227
FFBD111 ENRS50-250-235/22E/28.6D+2.2P MATRIX 5-9T/2.2 B 1293 451 ~350 65 1445 1432 1403 370 340 65 G1 100 G 2 1403 151714201400 100 125 19 32 197 227
FFBD111 ENRS50-250-252/30E/28.6D+2.2P MATRIX 5-9T/2.2 B 1293 451 ~350 65 1445 1432 1403 370 340 65 G1 100 G 2 1403 151714201400 100 125 19 32 197 227
FFBD111 ENRS65-250-226/30E/28.6D+2.2P MATRIX 5-9T/2.2 A 1457 451 ~350 65 1460 1485 1407 370 340 80 G1 125 DN80 1582 151714201400 150 200 40 65 340 550
FFBD111 ENRS80-200-190/22E/28.6D+2.2P AGA 300T SUR A 1551 451 ~430 65 1478 1501 1407 370 340 100 G1 150 DN1001694 151714201400 200 250 52 80 450 650
FFBD111 ENRS80-200-199/30E/28.6D+2.2P AGA 300T SUR A 1551 451 ~430 65 1478 1501 1407 370 340 100 G1 150 DN1001694 151714201400 200 250 52 80 450 650
FFBD111 ENRS100-200-182/22E/28.6D+2.2P AGA 300T SUR A 1699 451 ~430 65 1505 1529 1411 370 340 125 G1 200 DN1251869 151714201400 250 250 67 67 550 550
FFBD111 ENRS100-200-190/30E/28.6D+2.2P AGA 300T SUR A 1699 451 ~430 65 1505 1529 1411 370 340 125 G1 200 DN1251869 151714201400 250 250 67 67 550 550
[1]= Underhead
[2]= Overhead

Your Life, our Quality. Worldwide. 44 Fire-Fighting


FFS-FFB
FFBD111 FIRE-FIGHTING UNITS

FFBD111 DIMENSIONS - ENRS ELECTRICAL PUMP-MOTOR PUMP+PILOT

SUCTION CONE

DIMENSIONS CHART

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
Model Pilot pump Dimensions [mm]
A B B1~ C D D1 E H N DN1 DN1-JP DN2 DN3 R HQ O T DN1-SK B2 C2
[1] [2] [1] [2] [1] [2]
FFBD111 ENRS65-250-237/37E/35D+2.2P MATRIX 5-9T/2.2 1556 550 480 125 170017252037 450 430 80 G1 125 DN80 1681183021001700 150 200 40 65 340 550
FFBD111 ENRS65-250-252/45E/53D+2.2P MATRIX 5-9T/2.2 1556 550 480 125 170017252037 450 430 80 G1 125 DN80 1681183021001700 150 200 40 65 340 550
FFBD111 ENRS80-200-207/37E/35D+2.2P AGA 300T SUR 1650 550 560 125 171817412037 450 430 100 G1 150 DN100 1793183021001700 200 250 52 80 450 650
FFBD111 ENRS80-200-214/45E/53D+2.2P AGA 300T SUR 1650 550 560 125 171817412037 450 430 100 G1 150 DN100 1793183021001700 200 250 52 80 450 650
FFBD111 ENRS80-250-222/37E/35D+2.2P MATRIX 5-9T/2.2 1680 550 480 125 171817412037 450 430 100 G1 150 DN100 1823183021001700 200 200 52 52 450 450
FFBD111 ENRS80-250-234/45E/53D+2.2P MATRIX 5-9T/2.2 1680 550 480 125 171817412037 450 430 100 G1 150 DN100 1823183021001700 200 200 52 52 450 450
FFBD111 ENRS80-250-243/55E/53D+2.2P MATRIX 5-9T/2.2 1700 570 480 125 171817412037 450 430 100 G1 150 DN100 1843183021001700 200 200 52 52 450 450
FFBD111 ENRS80-250-255/75E/73.5D+2.2P MATRIX 5-9T/2.2 1730 600 480 125 171817412037 450 430 100 G1 150 DN100 1873183021001700 200 200 52 52 450 450
FFBD111 ENRS100-200-194/30E/35D+2.2P AGA 300T SUR 1798 550 560 125 174517692041 450 430 125 G1 200 DN125 1968183021001700 250 250 67 67 550 550
FFBD111 ENRS100-200-197/37E/35D+2.2P AGA 300T SUR 1798 550 560 125 174517692041 450 430 125 G1 200 DN125 1968183021001700 250 250 67 67 550 550
FFBD111 ENRS100-200-209/45E/53D+2.2P AGA 300T SUR 1798 550 560 125 174517692041 450 430 125 G1 200 DN125 1968183021001700 250 250 67 67 550 550
FFBD111 ENRS100-200-213/55E/53D+2.2 AGA 300T SUR 1818 570 560 125 174517692041 450 430 125 G1 200 DN125 1988183021001700 250 250 67 67 550 550
FFBD111 ENRS100-250-221/45E/53D+2.2P MATRIX 5-9T/2.2 1793 545 480 125 174517692041 450 430 125 G1 200 DN125 1963183021001700 250 250 67 67 550 550
FFBD111 ENRS100-250-225/55E/53D+2.2P MATRIX 5-9T/2.2 1818 570 480 125 174517692041 450 430 125 G1 200 DN125 1988183021001700 250 250 67 67 550 550
FFBD111 ENRS100-250-232/55E/73.5D+2.2P MATRIX 5-9T/2.2 1818 570 480 125 174517692041 450 430 125 G1 200 DN125 1988183021001700 250 250 67 67 550 550
FFBD111 ENRS100-250-242/75E/73.5D+2.2P MATRIX 5-9T/2.2 1848 600 480 125 174517692041 450 430 125 G1 200 DN125 2018183021001700 250 250 67 67 550 550
FFBD111 ENRS100-250-255/90E/110D+2.2P MATRIX 5-9T/2.2 1848 600 480 125 204520692041 450 430 125 G1 200 DN125 2018183021002000 250 250 67 67 550 550
[1]= Underhead
[2]= Overhead

Your Life, our Quality. Worldwide. 45 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

SUBMERGED PUMP PERFORMANCE TABLE (SF6 - WINNER 4N15)


Model P2 Q=Flow rate
Three-phase l/min 200 250 300 400 500 550
400V
[HP] [kW] m3/h 12 15 18 24 30 33
H=Head [m]
SF6 S25-3 4 3 40,0 38,0 35,5 29,5 21,5 16,5
SF6 S25-4 5,5 4 53,0 50,5 47,5 39,5 29,0 22,0
SF6 S25-6 7,5 5,5 80,0 76,0 71,0 59,0 43,0 33,0
Model P 2 Q=Flow rate
Three-phase l/min 300 400 500 550 600 700 750
400V
[HP] [kW] m3/h 18 24 30 33 36 42 45
H=Head [m]
SF6 S32-2 4 3 28,5 26,5 23,5 22,0 19,7 14,6 11,4
SF6 S32-3 5,5 4 43,0 40,0 35,5 32,5 29,5 22,0 17,1
SF6 S32-4 7,5 5,5 57,0 53,0 47,0 43,5 39,5 29,0 23,0
SF6 S32-5 10 7,5 71,5 66,5 59,0 54,5 49,5 36,5 28,5
SF6 S32-6 12,5 9,2 86,0 80,0 71,0 65,5 59,0 44,0 34,0
Model P 2 Q=Flow rate
Three-phase l/min 400 500 600 700 750 800 900 1000
400V
[HP] [kW] m3/h 24 30 36 42 45 48 54 60
H=Head [m]
SF6 S42-2 5,5 4 22,5 21,0 19,2 17,1 16,0 14,5 11,4 8,0
SF6 S42-3 7,5 5,5 33,5 31,5 29,0 25,5 24,0 22,0 17,2 12,0
SF6 S42-4 10 7,5 45,0 42,0 38,5 34,0 31,5 29,0 23,0 16,0
SF6 S42-5 12,5 9,2 56,0 52,5 48,0 42,5 39,5 36,5 28,5 20,0
SF6 S42-6 15 11 67,0 63,0 57,5 51,0 47,5 43,5 34,5 24,0
SF6 S42-8 20 15 89,5 84,0 77,0 68,0 63,5 58,0 46,0 32,0
SF6 S42-9 20 15 101,0 94,5 86,5 77,0 71,5 65,5 51,5 36,0
Model P 2 Q=Flow rate
Three-phase l/min 100 130 160 200 240 280 320 350
400V
[HP] [kW] m3/h 6 8 10 12 14 17 19 21
H=Head [m]
WINNER 4N15-13 4 3 64,0 60,0 56,0 49,0 43,0 35,0 27,0 21,0
WINNER 4N15-17 5,5 4 83,0 78,0 73,0 64,0 56,0 46,0 36,0 27,0
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

WINNER 4N15-24 7,5 5,5 118,0 110,0 103,0 91,0 78,0 65,0 50,0 38,0
Model P 2 Q=Flow rate
Three-phase l/min 100 150 200 250 300
400V
[HP] [kW] m3/h 6 9 12 15 18
H=Head [m]
SF6 R13-4 3 2,2 60,5 57,0 51,0 42,0 29,5
SF6 R13-5 4 3 75,5 71,5 64,0 52,5 37,0
SF6 R13-6 5,5 4 90,5 85,5 76,5 63,0 44,5
SF6 R13-7 7,5 5,5 106,0 100,0 89,5 73,5 52,0
PERFORMANCE TABLE FOR IDROGO (JOCKEY) PUMP PERFORMANCE TABLE FOR WINNER 4N (JOCKEY) PUMP
Model P 2 Q=Flow rate Model P2 Q=Flow rate
l/min 20 30 40 60 80 l/min 10 15 20 30 35 45 55 95
[HP] [kW] m3/h 1,2 1,8 2,4 3,6 4,8 [HP] [kW] m3/h 0,6 0,9 1,2 1,8 2,1 2,7 3,3 5,7
H=Head [m] H=Head [m]
IDROGO 40/08 0,8 0,6 43,3 40,2 36,3 26,1 13,4 WINNER 4N1- 18 0,7 0,55 95,0 89,0 80,0 54,0 38,0 - - -
IDROGO 40/10 1 0,75 54,1 50,2 45,4 32,6 16,8 WINNER 4N1- 24 1 0,75 127,0 119,0 107,0 72,0 50,0 - - -
IDROGO 40/12 1,2 0,9 64,9 60,2 54,5 39,2 20,2 WINNER 4N2- 20 1,5 1,1 - 131,0 127,0 113,0 103,0 75,0 38,0 -
IDROGO 40/15 1,5 1,1 75,7 70,3 63,6 45,7 23,5 WINNER 4N4- 18 2 1,5 - - - 114,0 111,0 104,0 96,0 32,0

Your Life, our Quality. Worldwide. 46 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

PERFORMANCE TABLE FOR BHE(L) SUBMERGED PUMPS


Model P 2 Q=Flow rate
Three-phase l/min 100 150 200 250 300 400 450
400V
[HP] [kW] m3/h 6 9 12 15 18 24 27
H=Head [m]
6BHE(L) 13-8 5,5 4 81,1 77,5 72,7 66,3 50,0 29,7 -
Model P 2 Q=Flow rate
l/min 100 133 167 200 250 300 350 400 450
[HP] [kW] m3/h 6 8 10 12 15 18 21 24 27
H=Head [m]
6BHE(L) 20-6 5,5 4 68,0 66,4 64,0 62,0 57,6 51,6 43,2 32,9 20,5
6BHE(L) 20-9 7,5 5,5 102,0 99,6 96,0 93,0 86,4 77,4 64,8 49,4 30,8
6BHE(L) 20-10 10 7,5 113,7 110,7 106,7 103,3 96,0 86,0 72,0 54,9 34,2
Model P 2 Q=Flow rate
l/min 83,5 166,5 250 333,5 416,5 500 583,5 666,5 750
[HP] [kW] m3/h 5 10 15 20 25 30 35 40 45
H=Head [m]
6BHE(L) 32-3 5 4 43,9 41,4 38,9 36,0 33,3 30,2 26,7 21,7 15,3
6BHE(L) 32-4 7,5 5,5 59,5 56,0 52,6 48,8 45,2 41,1 36,5 30,0 21,4
6BHE(L) 32-5 10 7,5 74,2 70,2 66,2 61,5 56,9 51,8 46,1 38,0 27,4
6BHE(L) 32-6 10 7,5 88,4 83,4 78,4 72,6 67,1 61,0 54,0 44,1 31,2
6BHE(L) 32-7 12,5 9,3 104,2 98,4 92,6 86,0 79,7 72,6 64,6 53,3 38,4
Model P 2 Q=Flow rate
l/min 416,5 500 583,5 666,5 750 833,5 916,5 1000
[HP] [kW] m3/h 25 30 35 40 45 50 55 60
H=Head [m]
6BHE(L) 48-2 4 3 22,6 20,9 19,3 17,8 16,6 15,1 13,4 11,3
6BHE(L) 48-3 5,5 4 33,8 31,2 28,8 26,6 24,7 22,5 19,9 16,8
6BHE(L) 48-4 7,5 5,5 45,0 41,5 38,3 35,5 32,9 29,9 26,5 22,3
6BHE(L) 48-5 10 7,5 56,8 52,3 48,3 44,7 41,5 37,8 33,6 28,4
6BHE(L) 48-6 12,5 9,3 70,0 65,2 60,4 55,5 50,3 46,0 41,6 35,7
6BHE(L) 48-7 12,5 9,3 80,4 74,8 69,3 63,5 57,6 52,7 47,5 40,5
6BHE(L) 48-8 15 11 91,6 85,1 78,9 72,2 65,5 59,9 54,0 46,0
6BHE(L) 48-9 20 15 105,5 98,2 91,0 83,7 75,9 69,5 62,9 54,1
Model P 2 Q=Flow rate
l/min 666,5 750 833,5 916,5 1000 1083,5 1166,5 1250

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
[HP] [kW] m3/h 40 45 50 55 60 65 70 75
H=Head [m]
6BHE(L) 64-2 5 4 21,1 19,0 17,3 16,5 15,7 14,9 13,9 12,4
6BHE(L) 64-3 7,5 5,5 31,8 28,8 26,2 24,9 23,7 22,5 21,0 18,9
6BHE(L) 64-4 10 7,5 42,5 38,4 35,0 33,2 31,6 30,1 28,0 25,2
6BHE(L) 64-5 12,5 9,3 53,8 48,7 44,3 41,9 40,1 38,2 35,6 32,2
6BHE(L) 64-6 15 11 64,0 57,9 52,7 50,0 47,7 45,3 42,3 38,1
6BHE(L) 64-7 20 15 76,2 70,1 65,2 61,7 58,6 55,7 52,1 46,1
6BHE(L) 64-8 20 15 86,0 79,1 73,5 69,7 66,1 62,8 58,5 51,6
6BHE(L) 64-9 20 15 95,5 87,8 81,5 77,4 73,4 69,6 64,6 56,8
Model P2 Q=Flow rate Model P2 Q=Flow rate
Three-phase l/min 600 700
1000 1250 1500 1700 2100 Three-phase l/min 700 1000
1250 1500 1700 1900 2100
400V 400V
[HP] [kW] m3/h 36 42
60 75 90 102 126 [HP] [kW] m3/h 42 60
75 90 102 114 126
H=Head [m] H=Head [m]
86 BHEL 77-2 10 7,5 37,0 35,7 30,6 26,3 21,1 16,4 13,6 86 BHEL 95-2 12,5 9,2 38,8 34,0 30,2 26,4 22,8 18,4 13,6
86 BHEL 77-3 15 11 55,5 53,5 46,0 39,5 31,6 24,6 20,4 86 BHEL 95-3 20 15 58,0 51,0 45,5 39,6 34,2 27,6 20,4
86 BHEL 77-4 20 15 74,0 71,5 61,0 52,5 42,0 32,8 27,2 86 BHEL 95-4 25 18,5 77,5 68,0 60,5 53,0 45,5 36,8 27,2
86 BHEL 77-5 25 18,5 92,5 89,5 76,5 66,0 52,5 41,0 34,0 86 BHEL 95-5 30 22 97,0 85,0 75,5 66,0 57,0 46,0 34,0
86 BHEL 77-6 30 22 111,0 107,0 92,0 79,0 63,0 49,0 41,0 86 BHEL 95-6 40 30 116,0 102,0 90,5 79,0 68,5 55,0 41,0
PERFORMANCE TABLE FOR IDROGO (JOCKEY) PUMP PERFORMANCE TABLE FOR WINNER 4N (JOCKEY) PUMP
Model P2 Q=Flow rate Model P2 Q=Flow rate
l/min 20 30 40 60 80 l/min 10 15 20 30 35 45 55 95
[HP] [kW] m3/h 1,2 1,8 2,4 3,6 4,8 [HP] [kW] m3/h 0,6 0,9 1,2 1,8 2,1 2,7 3,3 5,7
H=Head [m] H=Head [m]
IDROGO 40/08 0,8 0,6 43,3 40,2 36,3 26,1 13,4 WINNER 4N1- 18 0,7 0,55 95,0 89,0 80,0 54,0 38,0 - - -
IDROGO 40/10 1 0,75 54,1 50,2 45,4 32,6 16,8 WINNER 4N1- 24 1 0,75 127,0 119,0 107,0 72,0 50,0 - - -
IDROGO 40/12 1,2 0,9 64,9 60,2 54,5 39,2 20,2 WINNER 4N2- 20 1,5 1,1 - 131,0 127,0 113,0 103,0 75,0 38,0 -
IDROGO 40/15 1,5 1,1 75,7 70,3 63,6 45,7 23,5 WINNER 4N4- 18 2 1,5 - - - 114,0 111,0 104,0 96,0 32,0

Your Life, our Quality. Worldwide. 47 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

PERFORMANCE CURVES for series SF6 S25 (impeller diameter - 111.5 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 48 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

PERFORMANCE CURVES for series SF6 S32 (impeller diameter - 113.7 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 49 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

PERFORMANCE CURVES for series SF6 S42 (impeller diameter - 114 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 50 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

PERFORMANCE CURVES for series WINNER 4N15 (impeller diameter - 75.5 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 51 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

PERFORMANCE CURVES for series SF6 R13 (impeller diameter - 117 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 52 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

PERFORMANCE CURVES for series 6BHE13-20 (impeller diameter - 104 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 53 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

PERFORMANCE CURVES for series 6BHE 32 (impeller diameter - 104 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 54 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

PERFORMANCE CURVES for series 6BHE 48 (impeller diameter - 110.5 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 55 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

PERFORMANCE CURVES for series 6BHE 64 (impeller diameter - 103 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 56 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

PERFORMANCE CURVES for series 8BHEL 77 (impeller diameter - 114 mm) in accordance with ISO 9906 Annex A

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 57 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

PERFORMANCE CURVES for series 8BHEL 95 (impeller diameter - 117 mm) in accordance with ISO 9906 Annex A
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 58 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

FFS11S DIMENSIONS - MULTI-STAGE SUBMERGED ELECTRICAL PUMPS (SF6 - WINNER 4N15) + PILOT

PANEL ATTACHMENTS

ELECTRICAL PANEL NOT FITTED ONTO UNIT AND SUPPLIED


SEPARATELY FOR UNITS WITH 22Kw PUMP

DIMENSIONS CHART
Model Pilot pump Dimensions [mm]
DN1 DN2 DN3 H1 H2 H3

WINNER 4N15 13 3 IDROGO 40/12 65 50 1 1950 525 1340


WINNER 4N15 17 4 WINNER 4N2-14 65 50 1 1950 525 1340
WINNER 4N15 24/5.5 WINNER 4N2-20 65 50 1 1950 525 1340
SF6 25-3 3 IDROGO 40 10 80 65 2 1965 440 1345
SF6 25-4 4 IDROGO 40 12 80 65 2 1965 440 1345

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
SF6 25-6/5.5 WINNER 4N2-14 80 65 2 1965 440 1345
SF6 25-8 17.5 WINNER 4N4-18 80 65 2 1965 440 1345
SF6 32-2 3 IDROGO 40 08 80 80 2 1965 420 1345
SF6 32-3 4 IDROGO 40 10 80 80 2 1965 420 1345
SF6 32-4/5.5 IDROGO 40/12 80 80 2 1965 420 1345
SF6 32-5/7.5 IDROGO 40/15 80 80 2 1965 420 1345
SF6 32-6/9.2 WINNER 4N2-14 80 80 2 1965 420 1345
SF6 32-8/11 WINNER 4N4-18 80 80 2 1965 420 1345
SF6 42-4/7.5 IDROGO 40/10 100 80 2 1990 420 1355
SF6 42-6/9.2 IDROGO 40/15 100 80 2 1990 420 1355
SF6 42-7 11 WINNER 4N2-14 100 80 2 1990 420 1355
SF6 42-8 13 WINNER 4N4-18 100 80 2 1990 420 1355
SF6 42-9 15 WINNER 4N4-18 100 80 2 1990 420 1355

Your Life, our Quality. Worldwide. 59 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

FFS11S DIMENSIONS - MULTI-STAGE SUBMERGED ELECTRICAL PUMPS (BHE) + PILOT

PANEL ATTACHMENTS

ELECTRICAL PANEL NOT FITTED ONTO UNIT AND SUPPLIED


SEPARATELY FOR UNITS WITH 22Kw PUMP

DIMENSIONS CHART
Model Pilot pump Dimensions [mm]
DN1 DN2 DN3 H1 H2 H3

6 BHE 13-8 WINNER 4N2-14 65 50 1 1950 525 1340


6 BHE 20-6 IDROGO 40/12 65 65 2 1950 440 1340
6 BHE 20-9 WINNER 4N4-18 65 65 2 1950 440 1340
6 BHE 20-10 WINNER 4N4-18 65 65 2 1950 440 1340
6 BHE 32-3 IDROGO 40/08 100 80 2 1990 420 1355
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

6 BHE 32-4 IDROGO 40/12 100 80 2 1990 420 1355


6 BHE 32-5 IDROGO 40/15 100 80 2 1990 420 1355
6 BHE 32-6 IDROGO 40/15 100 80 2 1990 420 1355
6 BHE 32-7 WINNER 4N4-18 100 80 2 1990 420 1355
6 BHE 48-2 IDROGO 40/08 100 80 2 1990 420 1355
6 BHE 48-3 IDROGO 40/08 100 80 2 1990 420 1355
6 BHE 48-4 IDROGO 40/12 100 80 2 1990 420 1355
6 BHE 48-5 IDROGO 40/12 100 80 2 1990 420 1355
6 BHE 48-6 WINNER 4N4-18 100 80 2 1990 420 1355
6 BHE 48-7 WINNER 4N2-14 100 80 2 1990 420 1355
6 BHE 48-8 WINNER 4N4-18 100 80 2 1990 420 1355
6 BHE 48-9 WINNER 4N4-18 100 80 2 1990 420 1355
6 BHE 64-2 IDROGO 40/08 100 80 2 1990 420 1355
6 BHE 64-3 IDROGO 40/08 100 80 2 1990 420 1355
6 BHE 64-4 IDROGO 40/12 100 80 2 1990 420 1355
6 BHE 64-5 IDROGO 40/12 100 80 2 1990 420 1355
6 BHE 64-6 WINNER 4N2-14 100 80 2 1990 420 1355
6 BHE 64-7 WINNER 4N2-14 100 80 2 1990 420 1355
6 BHE 64-8 WINNER 4N4-18 100 80 2 1990 420 1355
6 BHE 64-9 WINNER 4N4-18 100 80 2 1990 420 1355
86 BHE 77-2 IDROGO 40/08 125 100 80 2015 375 1370
86 BHE 77-3 IDROGO 40 12 125 100 80 2015 375 1370
86 BHE 77-4 IDROGO 40 15 125 100 80 2015 375 1370
86 BHE 77-5 WINNER 4N4-18 125 100 80 2015 375 1370
86 BHE 77-6 WINNER 4N4-18 125 100 80 2015 375 1370
86 BHE 95-2 IDROGO 40/08 125 100 80 2015 375 1370
86 BHE 95-3 IDROGO 40/12 125 100 80 2015 375 1370
86 BHE 95-4 WINNER 4N2-14 125 100 80 2015 375 1370
86 BHE 95-5 WINNER 4N4-18 125 100 80 2015 375 1370
86 BHE 95-6 WINNER 4N2-20 125 100 80 2015 375 1370

Your Life, our Quality. Worldwide. 60 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

FFS21S DIMENSIONS - MULTI-STAGE SUBMERGED ELECTRICAL PUMPS (SF6 - WINNER 4N15) + PILOT

PANEL ATTACHMENTS

ARRANGEMENT 3: ELECTRICAL PANEL NOT FITTED ONTO UNIT AND


SUPPLIED SEPARATELY FOR UNITS WITH > 22Kw PUMP

DIMENSIONS CHART
Model Pilot pump Dimensions [mm]
DN1 DN2 L1 H1 H2 H3

WINNER 4N15 13/3 IDROGO 40/12 65 50 1 1950 525 1340


WINNER 4N15 17/4 WINNER 4N2-14 65 50 1 1950 525 1340
WINNER 4N15 24/5.5 WINNER 4N2-20 65 50 1 1950 525 1340
SF6 25-3/3 IDROGO 40/10 80 65 2 1965 440 1345
SF6 25-4/4 IDROGO 40/12 80 65 2 1965 440 1345

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
SF6 25-6/5.5 WINNER 4N2-14 80 65 2 1965 440 1345
SF6 25-8/7.5 WINNER 4N4-18 80 65 2 1965 440 1345
SF6 32-2/3 IDROGO 40/08 80 80 2. 1965 420 1345
SF6 32-3/4 IDROGO 40/10 80 80 2. 1965 420 1345
SF6 32-4/5.5 IDROGO 40/12 80 80 2. 1965 420 1345
SF6 32-5/7.5 IDROGO 40/15 80 80 2. 1965 420 1345
SF6 32-6/9.2 WINNER 4N2-14 80 80 2. 1965 420 1345
SF6 32-8/11 WINNER 4N4-18 80 80 2. 1965 420 1345
SF6 42-4/7.5 IDROGO 40/10 100 80 2.1/2 1990 420 1355
SF6 42-6/9.2 IDROGO 40/15 100 80 2.1/2 1990 420 1355
SF6 42-7/11 WINNER 4N2-14 100 80 2.1/2 1990 420 1355
SF6 42-8/13 WINNER 4N4-18 100 80 2.1/2 1990 420 1355
SF6 42-9/15 WINNER 4N4-18 100 80 2.1/2 1990 420 1355

Your Life, our Quality. Worldwide. 61 Fire-Fighting


FFS-FFB
FFS-S FIRE-FIGHTING UNIT KITS

FFS21S DIMENSIONS - MULTI-STAGE SUBMERGED ELECTRICAL PUMPS (BHE) + PILOT

PANEL ATTACHMENTS

ARRANGEMENT 3: ELECTRICAL PANEL NOT FITTED ONTO UNIT AND


SUPPLIED SEPARATELY FOR UNITS WITH > 22Kw PUMP

DIMENSIONS CHART
Model Pilot pump Dimensions [mm]
DN1 DN2 L1 H1 H2 H3

6 BHE 13-8 WINNER 4N2-14 65 50 1 1950 525 1340


6 BHE 20-6 IDROGO 40/12 65 65 2 1950 440 1340
6 BHE 20-9 WINNER 4N4-18 65 65 2 1950 440 1340
6 BHE 20-10 WINNER 4N4-18 65 65 2 1950 440 1340
6 BHE 32-3 IDROGO 40/08 100 80 2 1990 420 1355
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

6 BHE 32-4 IDROGO 40/12 100 80 2 1990 420 1355


6 BHE 32-5 IDROGO 40/15 100 80 2 1990 420 1355
6 BHE 32-6 IDROGO 40/15 100 80 2 1990 420 1355
6 BHE 32-7 WINNER 4N4-18 100 80 2 1990 420 1355
6 BHE 48-2 IDROGO 40/08 100 80 2 1990 420 1355
6 BHE 48-3 IDROGO 40/08 100 80 2 1990 420 1355
6 BHE 48-4 IDROGO 40/12 100 80 2 1990 420 1355
6 BHE 48-5 IDROGO 40/12 100 80 2 1990 420 1355
6 BHE 48-6 WINNER 4N4-18 100 80 2 1990 420 1355
6 BHE 48-7 WINNER 4N2-14 100 80 2 1990 420 1355
6 BHE 48-8 WINNER 4N4-18 100 80 2 1990 420 1355
6 BHE 48-9 WINNER 4N4-18 100 80 2 1990 420 1355
6 BHE 64-2 IDROGO 40/08 100 80 2 1990 420 1355
6 BHE 64-3 IDROGO 40/08 100 80 2 1990 420 1355
6 BHE 64-4 IDROGO 40/12 100 80 2 1990 420 1355
6 BHE 64-5 IDROGO 40/12 100 80 2 1990 420 1355
6 BHE 64-6 WINNER 4N2-14 100 80 2 1990 420 1355
6 BHE 64-7 WINNER 4N2-14 100 80 2 1990 420 1355
6 BHE 64-8 WINNER 4N4-18 100 80 2 1990 420 1355
6 BHE 64-9 WINNER 4N4-18 100 80 2 1990 420 1355
86 BHE 77-2 IDROGO 40/08 125 100 80 2015 375 1370
86 BHE 77-3 IDROGO 40/12 125 100 80 2015 375 1370
86 BHE 77-4 IDROGO 40/15 125 100 80 2015 375 1370
86 BHE 77-5 WINNER 4N4-18 125 100 80 2015 375 1370
86 BHE 77-6 WINNER 4N4-18 125 100 80 2015 375 1370
86 BHE 95-2 IDROGO 40/08 125 100 80 2015 375 1370
86 BHE 95-3 IDROGO 40/12 125 100 80 2015 375 1370
86 BHE 95-4 WINNER 4N2-14 125 100 80 2015 375 1370
86 BHE 95-5 WINNER 4N4-18 125 100 80 2015 375 1370
86 BHE 95-6 WINNER 4N2-20 125 100 80 2015 375 1370

Your Life, our Quality. Worldwide. 62 Fire-Fighting


CABINETS
FIRE-FIGHTING UNITS WITH EXTERNAL PROTECTION R60

STRUCTURAL SPECIFICATIONS PHOTO OF FFBDC 111 - OVERHEAD VERSION


Exterior cases designed to house fire-extinguishing units compliant
with Standards UNI EN 12845 and UNI 10779 are made in accordance
with the structural and functional specifications set out in Standard
UNI 11292. The protective cases are made from structures that are fire
resistant for up to 60 minutes. They can be inspected from all sides in
that they are equipped with REI60 doors and have light interior walls
to improve brightness. The dimensions are sufficient to allow for the
insertion/removal of the pumping unit parts. The protective cases are
equipped with a natural ventilation system with shutters that open
automatically by force of gravity equipped with protective grilles. The
protective cases provide all the necessary properties to ensure both
the management of the pumping unit during the operation of the fire-
extinguishing system as well as routine and non-routine maintenance.

The protective cases have the following structural specifications:


Load-bearing structure in electro-welded and coated section steel
filled with mineral wool for fire-resistance R60;
Smooth roof R60; PHOTO OF FFBDC 111 - UNDERHEAD VERSION
R60 doors equipped with 180 hinges and locks with unique codes;
Compartment for electrical panels and electrical equipment with
concealed roof to protect against atmospheric agents;
Base made from hot-galvanised electro-welded steel (to be built inside
CCA frame to protect base);
Hydraulic and electrical connections located on the bottom of the
cabinet (floor outlets)
Standard illumination for cabinet and electrical panel compartment
(200lux) operational even in the event of mains power failure (25lux
for 60 minutes);
One single-phase 230V 50Hz power socket;
Control electrical panel and protection for lighting and power sockets;
Convector heater complete with environmental thermostat to
maintain temperature above 15C inside the cabinet;
Ventilation system with shutters controlled by gravity with opposing

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
protective grilles;
Sprinkler system with flow switch and test valve for alarm (optional); PHOTO OF FFBC 11S-FFBC 21S UNITS WITH SUBMERGED PUMPS
Priming tanks located in the upper part already connected to the
pumps anchored with galvanised and electro-welded section steel
structure, as necessary for the overhead version;
Gravity-operated shutter with protective grille and fan supplied
directly from the diesel motor alternator, for forced ventilation (motor
pumps only);
Exhaust system with vibration-damping pipe, exhaust pipe and piping,
protected in a thermally isolated compartment ventilated from the
outside at half terminal with dual wall and rain guard (motor pumps
only);
Fuel tank with external pressure relief pipe and collection basin (dual
chamber) for any diesel leaks (motor pumps only);
Combined with electrical or diesel pumping units compliant with
Standards UNI EN12845 and UNI 10779, connected to the structures
via flexible supports and pipes with vibration-damping joints,
electrically and hydraulically assembled and tested at the factory.

Your Life, our Quality. Worldwide. 63 Fire-Fighting


ELECTRICAL PANELS
FFP SERIES (MAIN PUMP FOR FFS UNITS)

Control panels for fire-extinguishing units compliant with Standards UNI


EN 12845 and UNI 10779.
Each panel is set up to control one electrical pump.
The panels are equipped with a circuit board that controls incorrect
phase sequence, phase failure, undervoltage and measures the current
taken up by the motor. There is also a terminal board for all electrical
connections: pressure switches, external floats and notifications to be
sent to the DFFRP control unit, installed in the supervised area.
These are set up for direct pump start-up for power ratings of up
to 7.5 kW. Star delta starting is used for higher power ratings. They
come complete with a graphic display for viewing system electrical
parameters and menu settings.
The front of the panel features indicators lights for alarm signals in
accordance with Standards UNI EN 12845 and UNI 10779. Fuses
protecting the motor line and auxiliary lines and the phase failure
monitoring device are housed inside.
Any faults in the relay and display circuit board DO NOT block the
electrical pump start-up request in any way, both in the event of
MANUAL or AUTOMATIC operation triggered by the pressure switches.

FUNCTIONS
Automatic or manual control of the supply pump
Alarm signal with the ability for remote replication

TECHNICAL DATA
Door lock main disconnection switch
Electrical pump control ON/OFF switch
Pre-programmed electronic control unit for managing the electrical
pump in accordance with Standards UNI EN 12845 and UNI 10779
Pump in operation indicator
Start-up request indicator
Start-up failure indicator
Power supply available indicator
Phase/voltage failure indicator
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Lamp test button


Manual start-up button
Pump stop button
Transformer for low voltage auxiliary circuit with protective fuses
Start-up contactors (for direct start-up up to 7.5 kW. Star delta
starting is used for higher power ratings.)
High potential protective fuses for the passage of starting current for
up to 20 seconds
Terminal board for the connection of pressure switches and priming
float
Alarm output terminal board
Set up in accordance with Standard UNI 10779
Power supply: 400V 10- 50/60 Hz
Temperature limits: -10C +40C
Protection rating IP55
Reference standards: EN 60204-1, EN 60439-1, EN 61000-6-1, EN
61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 60529, EN 12845

Your Life, our Quality. Worldwide. 64 Fire-Fighting


ELECTRICAL PANELS
FFJP SERIES (PILOT PUMP FOR FFS UNITS)

Control panels for fire-extinguishing units compliant with Standards UNI


EN 12845 and UNI 10779 for electrical jockey pump
Each panel is set up to control one electrical pump.
Operation is enabled by the minimum pressure level in the system, on
the signal of a pressure switch. The pump is stopped automatically
once the calibrated pressure is restored.
The triggering of protection fuses FU1 on the motor line is signalled
by the electronic relay which is triggered in the event of phase failure
and indicated by an indicator light on the control panel and remotely.
Motor overloading is monitored by the electronic relay and signalled
by a lamp on the panel and remotely.
All protective devices (including the triggering of fuses FU2, FU3) are
signalled remotely via contacts with no potential.

TECHNICAL DATA
"Clean" contacts for indicating pump operation and end block
Set up for the connection of a float or minimum pressure switch to
protect against dry operation
Power supply: 400V 10- 50/60 Hz
Temperature limits: -10C +40C
Protection rating IP55
Reference standards: EN 60204-1, EN 60439-1, EN 61000-6-1, EN
61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 60529, EN 12845

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 65 Fire-Fighting


ELECTRICAL PANELS
FFSA SERIES (ACOUSTIC CONTROL UNIT ON-BOARD UNIT)

Acoustic signal control unit on board unit

The control unit is a piezoelectric two-tone siren with a battery-


charging power supply unit and a 12 V d.c. battery. The control unit
draws its power supply from the mains power supply at 230 V and is
controlled by both panels on the SUPPLY pump and is activated in the
following cases:
SUPPLY pump operation request due to pressure drop in the system in
the event of a fire
Phase or power supply failure or incorrect phase at SUPPLY pump
electrical panels
Triggering of fuses protecting motor, auxiliary circuits, pump start-up
failure, SUPPLY pump electrical panels
Triggering of protective devices on JOCKEY pump electrical panel
No water in the suction tanks
The control unit has a siren silencing button and a red LED for alarm
signalling
In the event of a power supply failure the piezoelectric siren is activated
and supplied autonomously by the battery for 20 hours of continuous
operation.

TECHNICAL DATA
Power supply: 230 10% - 50/60 Hz
Temperature limits: -10C +40C
Protection rating IP55
Sound power level: 75 dB A
Reference standards: EN 60204-1, EN 60439-1, EN 12845
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 66 Fire-Fighting


ELECTRICAL PANELS
DFFRP SERIES (REMOTE CONTROL UNIT FOR MANNED AREA)

Digital remote control panel for monitoring alarms in the manned area
to be connected to the electrical panels and micro switch contacts for
the fire-extinguishing unit supply suction valves.
Simultaneously manages the alarm signals from the two main pumps
(electrical and/or diesel) as well as the jockey pump.

FUNCTIONS
The control unit displays, monitors and signals alarms deriving from the
fire-extinguishing unit on a display panel.
It includes a battery with a charge that lasts up to 20 hours to allow the
alarm signals to operate in the event of a power failure.
Contacts are available for remote alarm signalling, for forwarding the
same to a local or remote PC and for the connection of a GSM module
(optional).
Communication with the electrical panels can be analogue (via cable
connection) or digital via RS 485 connection (optional conversion
module for FFB units).

TECHNICAL DATA
Power supply: 230 10% - 50/60 Hz
Temperature limits: -10C +40C
Protection rating IP55
Sound power level: 75 dB A
Reference standards: EN 60204-1, EN 60439-1, EN 61000-6-1, EN
61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 60529, EN 12845

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 67 Fire-Fighting


ELECTRICAL PANELS
FFBP SERIES (MAIN PUMP FOR FFB UNITS)

Control panels for fire-extinguishing units compliant with Standards UNI


EN 12845 and UNI 10779.
Each panel is set up to control one electrical pump.
The electrical panels are equipped with a type CEA ELCOS electronic
circuit board able to monitor and control the contactors for automatic
start-up (start-up via pressure switch).
The presence of any alarms does not cause the pump to stop, they are
indicated via the associated cumulative LED signal, a description on the
display and they switch the contact for the remote control of the signal
at the DFFRP control unit installed in the manned area.
These are set up for direct pump start-up for power ratings of up
to 7.5 kW. Star delta starting is used for higher power ratings. They
come complete with a graphic display for viewing system electrical
parameters and menu settings.
The front of the panel features indicators lights for alarm signals in
accordance with Standards UNI EN 12845 and UNI 10779. Fuses
protecting the motor line and auxiliary lines and the phase failure
monitoring device are housed inside.

FUNCTIONS
Automatic or manual control of the supply pump
Alarm signal with the ability for remote replication

TECHNICAL DATA
Door lock main disconnection switch
Electrical pump control ON/OFF switch
Pre-programmed electronic control unit for managing the electrical
pump in accordance with Standards UNI EN 12845 and UNI 10779
Pump in operation indicator
Start-up request indicator
Start-up failure indicator
Power supply available indicator
Phase/voltage failure indicator
Lamp test button
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Manual start-up button


Pump stop button
Transformer for low voltage auxiliary circuit with protective fuses
Start-up contactors (for direct start-up up to 7.5 kW. Star delta
starting is used for higher power ratings.)
High potential protective fuses for the passage of starting current for
up to 20 seconds
Terminal board for the connection of pressure switches and priming
float
Alarm output terminal board
Set up in accordance with Standard UNI 10779
Power supply: 400V 10- 50/60 Hz
Temperature limits: -10C +40C
Protection rating IP55
Reference standards: EN 60204-1, EN 60439-1, EN 61000-6-1, EN
61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 60529, EN 12845

Your Life, our Quality. Worldwide. 68 Fire-Fighting


ELECTRICAL PANELS
FFBM SERIES (MAIN MOTOR PUMP FOR FFB UNITS)

Control panels for fire-extinguishing units compliant with Standards UNI


EN 12845 and UNI 10779.
Each panel is set up to control one motor pump.
The electrical panels are equipped with a type CEA ELCOS electronic
circuit board able to monitor and control the contactors for automatic
start-up (start-up via pressure switch).
The circuit board monitors the operating status of the motor pump via
voltmeter for batteries A and B, ammeter for batteries A and B, hour
meter, rev counter, fuel level indicator and oil thermometer.
The presence of any alarms does not cause the pump to stop, they are
indicated via the associated cumulative LED signal, a description on the
display and they switch the contact for the remote control of the signal
at the DFFRP control unit installed in the manned area.
The electrical panel maintains the charge of batteries A and B using
dedicated battery chargers installed inside it.
They come complete with a graphic display for viewing system electrical
parameters and menu settings.
The front of the panel features indicators lights for alarm signals in
accordance with Standards UNI EN 12845 and UNI 10779. Fuses
protecting the motor line and auxiliary lines are housed inside.

FUNCTIONS
Automatic or manual control of the supply pump
Alarm signal with the ability for remote replication

TECHNICAL DATA
Door lock main disconnection switch
Motor pump control ON/OFF switch
Pre-programmed electronic control unit for managing the motor
pump in accordance with Standards UNI EN 12845 and UNI 10779
Pump in operation indicator
Start-up request indicator
Start-up failure indicator
Power supply available indicator

The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.
Voltage failure signal
Lamp test button
Pair of buttons for emergency manual start-up from batteries
Motor pump stop button
2 Battery chargers for charging and monitoring each battery
Terminal board for the connection of pressure switches and priming
float
Alarm output terminal board
Power supply: 230 single phase 50/60 Hz, 8-32 VDC
Temperature limits: -10C +50C
Protection rating IP55
Reference standards: EN 60204-1, EN 60439-1, EN 61000-6-1, EN
61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 60529, EN 12845

Your Life, our Quality. Worldwide. 69 Fire-Fighting


ELECTRICAL PANELS
FFBJP SERIES (PILOT PUMP FOR FFB UNITS)

Control panels for fire-extinguishing units compliant with Standards UNI


EN 12845 and UNI 10779 for electrical jockey pump
Each panel is set up to control one electrical pump.
Operation is enabled by the minimum pressure level in the system, on
the signal of a pressure switch. The pump is stopped automatically
once the calibrated pressure is restored.
The triggering of protection fuses FU1 on the motor line is signalled
by the electronic relay which is triggered in the event of phase failure
and indicated by an indicator light on the control panel and remotely.
Motor overloading is monitored by the electronic relay and signalled
by a lamp on the panel and remotely.
All protective devices (including the triggering of fuses FU2, FU3) are
signalled remotely via contacts with no potential.

TECHNICAL DATA
Power supply: 400V 10- 50/60 Hz
Temperature limits: -10C +40C
Protection rating IP55
Reference standards: EN 60204-1, EN 60439-1, EN 61000-6-1, EN
61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 60529, EN 12845
The contents of this publication should not be regarded as binding. EBARA Pumps Europe S.p.A. reserves the right to effect any modification it deems necessary, without prior notice.

Your Life, our Quality. Worldwide. 70 Fire-Fighting


PERFORMANCE SPECIFICATIONS
The specifications given refer to the curves provided in our catalogues and Data Books (see www.ebaraeurope.com).
All performance curves are calculated in accordance with ISO 9906 Annex A.

Tolerances in accordance with ISO 9906 Annex A.


The curves refer to an effective asynchronous motor speed at 50 Hz.
The measurements were taken at a water temperature of 20C and a kinematic viscosity of = 1 mm2/s (1 cSt).
In order to avoid the risk of overheating, the pumps should not be used at a flow rate below 10% of the maximum flow rate.

Symbols: Q = Flow rate [m3/h]


H = Head [m]
P 1 = Power uptake from electrical line
P 2 = Power delivered at motor shaft (power uptake of pump)