Professional Documents
Culture Documents
Basic Principles
for planning and configuration
1.0 General 4
1.1 Important note about servicing and maintenance work 4
1.2 Course content 5
1.3 About this training manual 5
2.0 Basic Principles 6
2.1 Introduction 6
2.2 Network Structure 6
2.3 SecoNET Network - Terms 7
2.4 The SecoNET network principle 8
2.5 Connecting MAXIMA and Management Systems 9
2.6 Structure of the SecoNET network 10
2.7 The Main Control Unit 13
2.7.1 General 13
2.7.2 Actuation Concept 14
2.7.3 Indication and numbering 15
2.7.4 Area Filters 15
2.7.5 Hardware / Software 16
3.0 Configuration 17
3.1 Using several communications modules 17
3.2 SecoNET Network Extension 20
3.3 Small SecoNET Networks 21
3.4 Programming 22
3.5 Planning of the Service Interface(s) 22
3.6 Planning of Customer Texts 22
3.6.1 SecoNET with Management System 22
3.6.2 SecoNET with Main Control Unit 23
3.6.3 Network error number calculation 25
4.0 Information processing 28
4.1 Communications System Faults 28
4.2 Domains Concept 29
4.3 The Management System 30
4.4 The Main Control Unit 31
4.5 Routing 31
5.0 Connectivity Options with SecoNET 32
5.1 BMZ Integral or BMZ Integral C 32
5.2 BMZ Integral and a Management System 32
5.3 BMZ Integral, SecoNET Main Loop and Subordinated Loop 33
5.4 BMZ Integral Connecting two systems 33
6.0 The Relationship of the Fire Alarm Control Panel to the SecoNET Network 34
6.1 BMZ Integral 34
6.2 BMZ Maxima 34
6.3 Standard-Maxnet 35
6.4 Enhanced Maxnet 35
7.0 Training Examples 36
File name: SecoNET_PRJ-en.doc Version V 1.7 Page 2(42)
Doc. No. SPT/02:SecoNET_prj_2002 SPT/G. Porcher 30.09.2009
SecoNET CONFIGURATION
7.1 Example 1 36
7.1.1 Network Configuration 37
7.2 Example 2 38
7.2.1 Control Panel Configuration (only network modules) 39
7.2.2 Network Structure 40
7.3 Example 3 (with main control unit) 41
15.0 List of Document Versions 42
SCHRACK Seconet AG
Training in Vienna
Trainingscenter@schrack-seconet.com
Further information about this topic can be found in the relevant servicing information!!!
SCHRACK Seconet AG assumes no liability for technical or printing errors and omissions in this document. Furthermore, no liability is assumed for
damage which can be directly or indirectly traced back to usage of this documentation
2.1 Introduction
Decentralization of fire alarm control panels and the networking of control panels into snaller and
larger networks is becoming increasingly important. For this reason, when developing the BMZ
Integral, particular attention was paid from the outset to ensuring that the control panel could
support the decentralized structure and could be networked.
As the BMZ Integral was developed as a redundant system, one of the most important requirements
for networking was also to guarantee stability, failure prevention and functional security by using
redundant data transmission across the entire network. Since all the functions had already been
implemented at the outset, the same hardware could be used for the SecoNET network as for the
subcontrol unit loop.
The trend towards planning and realisation of industrial centres requires that ever more control
panels are networked, and an important factor is that the information for the entire system is
available in different locations by deploying management systems.
B3/B4 B3/B4
Node (Nodes) Every BMZ Integral communications module in a Subnet is called a Node.
Node-ID Every Node in the SecoNET network has a unique ID (physical address),
which is assigned when configuring a Node by List Generator. Logical
addresses are only configured once the network is operational.
Subcontrol unit loop Networking of individual BMZ Integral or BMZ Integral C control panels to
form a network. All the control panels together have the external appearance
of a single control panel.
Management system A superordinated computer system for operating SecoNET network network
control panels and for displaying information about events occurring at
individual SecoNET network control panels.
Main control unit A superordinated BMZ Integral unit for operating SecoNET network network
control panels and for displaying information about events occurring at
individual SecoNET network control panels.
B3/B4 B3 B3 B3/B4
SecoNET
Subnet 1
B3/B4 B3 B3 B3/B4
BMZ BMZ
Integral Integral
SecoNET
Subnet 1
BMZ BMZ
Integral Integral
When networking BMZ control panels, at least two of the control panels must be BMZ Integral
control panels.
The other connected control panels can be Integral C control panels.
File name: SecoNET_PRJ-en.doc Version V 1.7 Page 8(42)
Doc. No. SPT/02:SecoNET_prj_2002 SPT/G. Porcher 30.09.2009
SecoNET CONFIGURATION
The numbering of elements can begin with the number 1 for every control panel that it connected
into the SecoNET network. If the connected control panel is part of a subcontrol unit loop, then the
number of an element may only occur once in the subcontrol unit loop.
It must be possible to actuate the main detector output from every connected SecoNET control
panel (the only exception being for a network with a main control unit).
SecoNET
SecoLOG
BMZ BMZ
Integral Integral
N3 - ZZK-Protocol (Master)
N3 EZZK Protocol (Master) for connecting BMZ Maxima units, standard MaxNET and
enhanced MaxNET.
Redundant loops are assigned hierarchically in the SecoNET network. By definition a main loop
exists, to which one or more subordinate loops can be connected.
The hierarchical assignment of redundant loops means that the redundancy increases the more
nodes there are. This means that there is a considerable improvement in available compared with
there being an individual loop. The quantity of Subnets (subordinated loops) is theoretically limited
to a maximum of 63 (0 62).
SecoNET SecoNET
(subordinated loop) (subordinated loop)
SecoNET
(main loop)
BMZ BMZ
BMZ
Integral Integral
Integral
SecoNET
(subordinated loop)
BMZ BMZ
Integral Integral
The maximum number of the SecoNET devices (BMZ Integral, BMZ Integral C, main control unit,
main control unit) is 254.
BMZ BMZ
Integral Integral
SecoNET
(subordinated
loop)
BMZ BMZ BMZ BMZ
BMZ BMZ BMZ
Integral Integral Integral Integral
Integral Integral Integral
SecoNET SecoNET
(subordinated (subordinated SecoNET
loop) loop) (subordinated open loop)
BMZ BMZ BMZ BMZ
Integral Integral Integral Integral
SecoNET
(Main loop)
BMZ SecoLOG
BMZ BMZ
Integral
Integral Integral
SecoNET
(subordinated
loop)
BMZ BMZ
Integral Integral
The structure of the hierarchical loops (tree structure) must however always remain intact. The
configuration shown in the figure below is not permissible.
SecoNET SecoNET
(subordinated (subordinated
loop) loop)
BMZ BMZ BMZ BMZ
BMZ
Integral Integral Integral Integral
Integral
SecoNET SecoNET
(subordinated (subordinated
loop) loop)
SecoNET
(main loop)
BMZ
BMZ
Integral
Integral
SecoNET
(subordinated
loop)
BMZ
BMZ BMZ BMZ BMZ
Integral BMZ BMZ
Integral Integral Integral Integral
TZ 2 Integral Integral
TZ 3
SecoNET BMZ INTEGRAL
Subcontrol unit loop
(subordinated SecoNET
loop) SecoNET (subordinated open loop)
BMZ BMZ
BMZ BMZ
Integral Integral
Integral Integral
TZ 1 TZ 4
SecoNET
(main loop)
BMZ
BMZ BMZ
Integral
Integral Integral
SecoNET
(subordinated
loop)
BMZ BMZ
Integral Integral
This configuration can be used for transmitting SecoNET network data over a subcontrol unit loop.
In this case control panels TZ 1, TZ 3 and TZ 4 each require a B3 USI4 module and a B3 LPI
module. In this example a BMZ Integral C could be used for control panel TZ 2. Subcontrol unit
TZ1 is connected to the SecoNET network and serves simultaneously as a router.. Subcontrol units
TZ 3 and TZ 4 only function as routers. Additional Subnets are also formed in this configuration.
SecoNET
SecoNET
BMZ
BMZ
Integral
Integral
TZ 2
TZ 3
BMZ INTEGRAL
Subcontrol unit loop
SecoNET
SecoNET
BMZ BMZ
Integral Integral
TZ 1 TZ 4
SecoNET
2.7.1 General
The SecoNET main control unit is used for centralised operation and indication for a SecoNET
control panel network. It consists of a BMZ Integral subcontrol unit with a full door, to which a
remote SecoNET High End Operating Panel (from software version SW 5.1.x) has been attached
via the MMI-BUS.
In principle version C or later networking modules with larger memories (B3-LPI, B3-USI4) should
be used in the main control unit.
A centralized main detector is actuated from the main control unit.
SecoNET SecoNET
(subordinated loop) (subordinated loop)
SecoNET
(main loop)
BMZ
BMZ BMZ Integral
Integral Integral HZ
SecoNET
(subordinated loop)
BMZ BMZ
Integral Integral
Maximum 64 events (per subcontrol unit) from the main control unit to the subcontrol unit
Maximum of 512 links per main control unit (maximum of 256 controllers locally)
It is possible using Events to use linked results from subcontrol units and linked results in the main
control unit to trigger controllers in the main control unit or the subcontrol unit.
This assignment of numbers occurs during the configuration of the SecoNET network and has
nothing to do with the subcontrol unit number.
Standard text
AL ARM 1 0 1 - 1 0 0 0 7 / 0 2 3 001
SCU number
Subelement number
A maximum of 15 area filters can be programmed for SecoNET in the main control unit. The filters
are then assigned to the subcontrol units. One filter is possible per operating panel, if several
operating locations are connected to a single main control unit.
The assignment of the management system/main control unit to area filters is carried out based on
the number of the operating panel.
As standard:
External operating panel (25 character display) with printer (only up to software version
5.0.x)
N3 High End Operating Panel with or without a printer (from software version 5.1.x)
Optional:
The individual BMZ Integral units are independently configured from one another. Only the
interface to the SecoNET network or other required interfaces for connecting the management
system and MaxNet to the SecoNET network must be configured.
When configuring these interfaces only the required protocol (Integral Standard Protocol or ZZK
Protocol) as well as RS232, RS422, RS485 (redundant or non-redundant) and the bit rate or parity
require configuring.
BMZ INTEGRAL
B3 - B3 - B3 -
MCU USI4 USI4
Processor half A
SPI - BUS
Processor half B
B3 - B3 - B3 -
MCU USI4 USI4
SecoNet
SecoNet
In the event of a permanent failure of one half of the BMZ Integrals processor only one
communications module can continue to communicate with the SecoNET network (dependent on
which processor half has failed). In the instance shown here (processor half B has failed) only the
management system which is connected to the left B3-USI4 module can communicate with the
SecoNET network. A service PC which is connected to the right B3-USI4 module no longer has a
connection to the SecoNET network. Dependent on which B3-USI4 module is used for connecting
the BMZ Integral to the SecoNET network, the BMZ Integral may also no longer be connected to
the SecoNET network. To guarantee full redundancy of data transmission, a configuration as shown
should be avoided.
Processor half A
Processor half B
B3 -
USI4
SecoNet
SecoNet
Service
Assistant
G
SecoLO
USI 4
USI 4
SecoNET
SecoNET
Service
Assistant
G
SecoLO
SecoNET
B3 USI4
SecoNET
By taking this measure, it is no longer possible for a management system failure or a service PC
failure to happen.
a main loop, onto which the management system, the ServiceAssistant and an extended Maxnet
are connected
and of
several subordinated loops, to which only fire alarm control panels are connected.
When symmetrically formed (with 8 nodes on each Subnet) this configuration consists of 43 nodes.
As a BMZ Integral can be connected to every node (which can consist of up to 16 subcontrol units
in turn), this configuration can consist of up to 43 x 16 (=688) BMZ Integral subcontrol units (and
an extended Maxnet !).
SecoNET
(untergeordneter
SecoNET Ring) erweitertes
(untergeordneter Maxnet
Ring)
BMZ
BMZ BMZ
SecoNET
SecoNET
(untergeordneter BMZ BMZ
Ring) (Hauptring)
SecoLOG -
Leitsystem
BMZ BMZ
SecoNET BMZ
(untergeordneter
Ring)
SecoNET
(untergeordneter
Ring)
ServiceAssistant
UZ 4
UZ 1
SecoNET
Subnet 1
UZ 3
UZ 3 Main Control Unit
Programming of control panels which are connected into the SecoNET network consists of
one programming per unit
Texts should also be prepared for connection faults between the control panels (Country-specific
regulations should be observed with regard to the text formulation. For connection faults the text
must be assigned to so-called fault numbers. These fault numbers are made up of Subnet, Node and
Port numbers.
The main control unit only needs texts for the elements in the main control unit (exceptions: texts
for e.g.: UZ1, UZ2, ...). All texts in the main control unit and the required texts for the subcontrol
units are automatically compiled together when exported using the Integral-Text-Tool, so that they
can then be uploaded into the main control unit
Example: Project "SPT-Trainingsland" (One main control unit and 4 other subcontrol units)
Main central
Network error numbers
A Subnet "X" B
Between two centrals in a SecoNET network there can be two different error messages for the same
connection. Standard view of the network error number is the same as the calculated number of
subnet-node-port adress, but if the logging of the network error have an delay than the network
error number of the other central is viewed (e.g. central a shows as standard "xxxx" an with an
delay "yyyy".
Are previous points have been carried out, it can be definited each subnet address, node address
(per subnet for a communications card is always the same) and the port address.
3 = 1B(loop) 2 = 0B (loop)
Sub net 0
4 = PC
1 = 1A (loop)
B3/B5 Integral
0 = 0A (loop)
1 = 1A (loop)
4 = PC card
modem Interface
2 = 0B (loop)
2 = 0B (loop)
4 = PC card
3 = 1B (loop) 2 = 0B (loop) modem Interface
5 = 0A (PC)
Fire Alarm
Trainingcenter
Vienna
6 = 1A (PC)
5 = 0B (lPC)
6 = 1B (PC)
SecoNet SecoNet
Management
System
or
MaxNet
The information from a client reaches the node via the direct point-to-pint connection. The node
sends this information to all the other nodes in the SecoNET network. Information from the
SecoNET network is only transmitted from the node to a client if this client has been specifically
addressed.
On the whole, messages from fire alarm control panels are forwarded to all management systems. A
management system can directly address a client, in order to query or change the state of an element
of this client.
This type of information processing guarantees that a fire alarm control panel can be connected to
the SecoNET network reactionlessly (the fire alarm control panel's operations are not influenced by
the SecoNET network).
A message is only forwarded from a node to an addressed client, if the recipient has been assigned
to at least one domain, to which the sender of the message has also been assigned.
The assignment of Clients to domains is programmed when configuring the SecoNET network. For
this reason the domains structure should already be set during the planning phase
Example:
Management system 1 belongs to domains 1-3 => receives all information from domains 1-3
Management system 2 belongs to domain 2 => therefore only receives information from UZ6
Domains 1, 2, 3
Manage. Sys. 1
Domain 2 Domain 1
Manage. Sys 2 HZ (UZ) 2
During the configuration process it is possible to set which number the failure of a management
system is indicated on a BMZ Integral.
Example:
If there are several management systems deployed in the SecoNET network, then management
system failures are indicated with an additional number (e.g. management system 1/2). Only when
all management systems fail will the fault be displayed with only the management system number
(e.g. Management System 1).
Note:
Only those management systems which belong to the same domains as the control panels will
be displayed as having faults on the fire alarm control panels.
All control panels which belong to the same domain as the management system must be
programmed to the same management system number!
The first number (1) is set during the BMZ programming for the management system element.
The second number is generated from the order of the addressing of the Subnet and Node number.
The lowest combination assumes the number 1.
1.) Management system "1" Subnet number 2, Node 4 => automatically displayed as 1/1 when there
is a failure.
2.) Management system "2" Subnet number 2, Node 5 => automatically displayed as 1/2 when there
is a failure.
Example:
If there are several main control units deployed in the SecoNET network, then main control unit
failures are indicated with an additional number (e.g. main control unit 1/2). Only when all main
control units fail will the fault be displayed with only the main control unit number (e.g. main
control unit 1).
Note:
Only those main control units which belong to the same domains as the fire alarm control panels
will be displayed as having faults on the fire alarm control panels.
All fire alarm control panels which belong to the same domain as the main control unit must be
programmed to the same main control unit number!
The first number (1) is set during the BMZ programming for the main control unit element.
The second number is generated from the order of the addressing of the Subnet and Node number.
The lowest combination for the main control unit assumes the number 1.
1.) Main control unit "1" Subnet number 2, Node 3 => automatically displayed as 1/1 when there is
a failure.
2.) Main control unit "2" Subnet number 2, Node 8 => automatically displayed as 1/2 when there is
a failure.
4.5 Routing
If two Subnets are connected, then information received on one Subnet is only transferred on to the
second Subnet, if the information is also required by this Subnet.
SecoNet SecoNet
SecoNet SecoNet
Management
system,
MAXIMA,
MaxNet
SecoNet
SecoNet (main loop)
(main loop) SecoNet
(subordinated loop)
From a SecoNET network topology point of view, in this instance there are two nodes, with the first
node being connected to two clients (the BMZ Integral and the management system) and the second
node is connected to only one client (the second system).
SecoNet SecoNet
When a superordinated management system is directly connection to a BMZ Integral, then the
status of the connection between the communications module and the management system to the
BMZ Integral is displayed as follows:
The complete failure of the entire connection to the management system is displayed as a main
control unit fault.
When the BMZ Integral is connected to the SecoNET network, then SecoNET network faults are
displayed on the BMZ Integral as follows:
Transmission path faults in the SecoNET network are not displayed on the BMZ Integral.
The failure of the management system (or a fault in the connection between the BMZ Integral
and the management system) is displayed on the BMZ Integral as a main control unit fault.
If several management systems are connected to the SecoNET network, then the failure of
one/several management system(s) is displayed using SubElementNumbers, with the failure of
all management systems being displayed as a main control unit fault.
A transmission path fault between the BMZ Maxima and the communications module when
connected redundantly is displayed as a flat module fault #20 or #21.
The complete failure of the connection between the BMZ Maxima and the communications
module is displayed as falt module fault #25..
The fault indication on the BMZ Maxima which is connected to the communications module
corresponds to that of the BMZ Maxima.
Other BMZ Maximas in the Standard Maxnet do not indicate faults that affect the SecoNET
network.
The fault indication on the BMZ Maxima which is connected to the communications module
corresponded to that of the BMZ Maxima.
Other BMZ Maximas in the enhanced Maxnet do not indicate faults that affect the SecoNET
network.
7.1 Example 1
BMZ 4
ET NET Integral
o N co e t 3
Sec net 5 e
S bn
Sub NE) Su
(LI
BMZ 1
BMZ 7 Integral
Integral C
BMZ
SecoNET MAXIMA
Subnet 2
SecoNET
BMZ 6
Subnet 4
BMZ 2 (E-MAXNET)
Integral C Integral
SecoNET
Service
Subnet 1 PC
(main loop) LTS
BMZ 5 BMZ 3
Integral C Integral
SecoNET
Subnet 5
(LINE)
Service
PC
BMZ 3
BMZ 5 Integral
Integral C
LTS
BMZ "X"
Integral
SecoNET
BMZ 6 Subnet 1
Integral C (main loop)
BMZ 9
Integral
BMZ Integral
Subcontrol unit
BMZ BMZ 4
Integral loop
MAXIMA
BMZ 9
Integral C
SecoNET
Subnet 2
UZ1
(MAXNET)
B3-USI4 to Service PC
2 MAXIMA UZ1
In BMZ Integral Control Panels, B3 - LPI modules can also be used for communication.
Subnet 4
(LINE) BMZ 6
TZ 2
BMZ 8 Integral
Integral
BMZ 6
BMZ 4 TZ 1
Integral
Integral C
BMZ 1
Integral
BMZ 2
Integral
HZ
Service
PC
SecoLOG
BMZ 3 / UZ3:
1 pc B3-USI4
BMZ 4 / UZ4:
1 pc B4-USI
BMZ 5 / UZ5:
1 pc B3-USI4
BMZ 6 / UZ6:
1 pc B3-USI4
Ing. Gnter
Porcher
Austria,
Vienna
2009.09.30
13:48:18
+02'00'