You are on page 1of 17

Energy and Buildings 122 (2016) 6379

Contents lists available at ScienceDirect

Energy and Buildings


journal homepage: www.elsevier.com/locate/enbuild

Experimental investigation of the thermal performances of an


extensive green roof in the Mediterranean area
Piero Bevilacqua , Domenico Mazzeo, Roberto Bruno, Natale Arcuri
Department of Mechanical, Energy and Management Engineering, University of Calabria, Ponte P. Bucci 46/C, ZIP 87036 Arcavacata di Rende, Cosenza, Italy

a r t i c l e i n f o a b s t r a c t

Article history: Nowadays green roofs are a well-consolidated technology used in several countries since these systems
Received 11 January 2016 can be employed both to generate considerable energy savings and to improve the thermal performances
Received in revised form 22 March 2016 of buildings. This paper deals with an experimental analysis of an extensive green roof, installed on a
Accepted 23 March 2016
building of the University of Calabria (Italy, Lat. 39.3 N). The thermal performances of different layering
Available online 31 March 2016
solutions are analysed under typical Mediterranean climate conditions with reference to a traditional
roof system. The analysis showed that the green roof is able to reduce the temperature at the interface
Keywords:
with the structural roof, on average, by 12 C with respect to a black bituminous roof in summer and to
Green roof
Experimental analysis
maintain, on average, a value that is 4 C higher in winter. The measured temperatures allowed to calculate
Dynamic properties the transferred heat through the building roof, showing negative heat uxes for the whole period and a
Heat uxes reduction of the thermal energy entering the indoor environment of 100% in summer, proving the passive
Energy savings cooling effect of the green roof, and a reduction between 30% and 37% of the thermal energy exiting the
Mediterranean climate indoor environment in winter. The experimental data have been employed also to conduct a dynamic
characterization of the different vegetated solutions, showing that the different green roofs solutions are
able to generate values of decrement factor varying between 0.135 and 0.193 and a time lag between
3.1 h and 4.8 h, which can substantially improve the dynamic properties of traditional roof structures,
especially in the case of roofs with limited dynamic performances.
2016 Elsevier B.V. All rights reserved.

1. Introduction the improvement of stormwater management. Nevertheless, these


systems allow the achievement of several other benets, such as
In recent decades, the increasing awareness of the indefensibil- the reduction of rainwater runoff [35], the mitigation of urban
ity of the actual model of economic growth has led to new concepts heat island effect (UHI) [6,7], the improvement of membrane dura-
of sustainable development. In the building sector, which is respon- bility and extension of roof life [8,9] and the reduction of heating
sible for a relevant demand of primary energy, the trend in the quest and cooling demands for the buildings air-conditioning [1015].
of adequate technical solutions is continuously increasing. Many Finally, green roofs sequester carbon dioxide and reduce local-
systems have been investigated to evaluate performances in terms ized air pollution [1619], increase the water runoff quality [20],
of environmental, economic and energy benets. Passive systems create habitat for wildlife and recreational opportunities [2124]
such as green roofs, also named eco-roofs, living roofs or roof gar- and decrease urban noise pollution [25,26]. Therefore, green roofs
dens [1], belong to the studied systems. Nowadays green roofs are a actually represent an innovative construction system that can
well-consolidated technology used in several countries around the increase the sustainability of buildings and cities.
world as an innovative roong solution. Vegetated roofs have been Vegetated roofs are categorised as intensive, simple intensive
used since ancient times with the most famous example being the (or semi-intensive) and extensive greenings according to the level
Babylonian gardens in Mesopotamia [2], but more recent examples of maintenance required, but often only the extensive and inten-
can be found especially in Northern European countries. Indeed sive categories are considered. Intensive roofs are deep, heavy,
this technology has historically proven validity in the improve- require a high level of maintenance and, usually, they are designed
ment of the building envelope insulation in cold climates and in for complete accessibility. This type of roof is usually applied to
new buildings in which the extra weight is kept in considera-
tion during the design of the structural components. The extensive
Corresponding author. ones, instead, are characterized by lightweight growing media
E-mail address: piero.bevilacqua@unical.it (P. Bevilacqua). of reduced depth; they require low maintenance and are less

http://dx.doi.org/10.1016/j.enbuild.2016.03.062
0378-7788/ 2016 Elsevier B.V. All rights reserved.
64 P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379

likely to be designed for frequent human access. Typical extensive penalizing the scarce heating demand, and in cold climates they
green roofs are equipped with self-sustaining and native species are useful for reducing the thermal losses in winter. However the
of plants, therefore they require low irrigation since the vege- thermal transmittance value in the study was not varied, since they
tation is well adapted to local climatic conditions [2729]. The considered as a case study a well-insulated building.
plants represent a necessary element to realize the evapotranspi- Other researchers have evaluated the performance of green
ration process in the substrate layer, crucial for the achievement of roofs through experimental analysis. The results obtained by Liu
cooling effects [30]. Moreover, the reduced system weight makes and Minor [9] in the city of Toronto showed that green roofs are
them suitable for installation on existing buildings. A typical exten- effective in reducing heat uxes through the roong system, thus
sive green roof layering, together with the materials generally lowering the energy demand for space conditioning in the build-
employed, can be found in [3134]. Different constructive solutions ing. The additional green roof systems, compared to the reference
are nowadays available, that are often not standardized and may roof consisting of steel deck, gypsum board, vapor retarder, ther-
be composed of different types of layers, materials, thicknesses and mal insulation, breboard and modied bituminous membrane,
vegetation. Consequently a more comprehensive datasets to report reduced the heat uxes through the roof by 7090% in summer and
quantitative information about the performance for the different 1030% in winter. The green roofs also reduced the roof membrane
technologies adopted is required [29]. maximum temperature in summer by more than 20 C and daily
From an energetic point of view, as the surface of the roof temperature uctuations experienced by the roof membranes by
increases, in relation to external walls surface, the heat ux through about 30 C. Their results refer to a humid continental climate local-
the building cover assumes a more relevant contribution in the ity, and in the study the temperature inside the building was kept
energy requirements of the building upper oor air-conditioning constant so that any heat ow between the building and its environ-
[35]. In this regard, the physical phenomena involved in the energy ment created energy demand for space conditioning. Therefore, the
balance of the several layers of an extensive green, such as veg- energy demand due to the roof was estimated by the sum of the heat
etation, substrate and drainage roof, lead to the reduction of the entering and leaving through the roof. In similar climatic condi-
thermal loads of the indoor environment, both in summer and tions another study, conducted by Teemusk and Mandar in Estonia,
winter. Regarding the vegetation layer, the heat uxes with the out- compared experimentally the temperature regime of a lightweight
door environment involve absorption of solar radiation, long-wave aggregates based roof garden with a modied bituminous mem-
radiative exchange with the sky, convective exchange with external brane roof in different season [8]. The results of their study revealed
air, precipitation and evapotranspiration processes. Similar physi- that the roof garden can decrease the temperature uctuations sig-
cal phenomena are involved in the thermal balance of the soil, with nicantly in summer, protecting roof membrane from rapid cooling
the addition of the conductive heat ux and the sensible heat stored and freezing in autumn and spring, and provide effective thermal
in the structure. The theoretical investigation of these systems insulation in winter. In a Midwestern U.S. climate Getter et al. [46]
is very difcult due also to the strong variation of the thermo- quantied the thermal properties of an inverted 325 m2 extensive
physical properties of the soil and drainage layer with the water green roof installed over a traditional gravel insulated roof, taken
content (WC) [36]. In summer, the shading effect of vegetation, as reference. Their results demonstrated how an extensive green
the increased thermal mass of the system and evapotranspiration roof inuences temperatures and heat uxes in the roof during dif-
phenomena, permit the reduction of heat uxes entering the build- ferent seasons of the year, with a reduction of heat uxes, through
ing through the roof. In winter, the green roof offers additional the building envelope, by an average percentage of 13% in winter
insulation to reduce heat losses from indoor spaces to the outdoor and 167% in summer. In terms of maximum and minimum temper-
environment. ature, the monthly average values over the course of the year were
In the recent literature many researchers focused their stud- consistently higher for the gravel-ballasted roof than the green roof,
ies on the mathematical modelling of the heat and mass transfer with values up to 20 C warmer during summer. The study reported
in a green roof in order to be able to assess the resulting ben- in [47], regarding ve typical days, showed that a green roof test
ets [3642]. Such topic, given the complexity of the physical bed in Singapore (China), can reduce the internal air temperature
phenomena involved, is still under development. Consequently by an average value of 0.5 C if compared with a bare roof.
many authors addressed the problem by using mathematical model Even though many examples of experimental analysis can be
solved with a numerical approach; however the results obtained found in the literature, most of the available researches on green
provide only a qualitative accuracy. Niachou et al. [43] estimated roofs rely on simulated data. Furthermore one of the main factors
the impact of a green roof on the total energy consumption of affecting the performance of a green roof is the climatic conditions,
buildings with various types of roofs, with and without insula- therefore generalizable results are difcult to assess. In this regard
tions, through a simplied mathematical approach, simulating the the performance of green roofs in winter period is still a matter
presence of the vegetated roof by properly modifying the thermal of debate where some scientists claimed it as a medium to save
conductance of the building cover. They observed that the great- energy and some viewed it as a cause of more energy consumption
est yearly energy saving, in the case of non-insulated buildings, [1].
was of 37%. Spala et al. [44], using the dynamic simulation pro- Other experimental studies have been conducted in Mediter-
gram TRNSYS, calculated the energy consumption of a two-storey ranean climate conditions. Coma et al. [48] evaluated the energy
building in Athens. They observed a remarkable reduction in the consumption and thermal behaviour of three identical house-like
cooling load with a maximum of 39% for the whole building, and of cubicles located in Puigverd de Lleida (Spain): two of them were
58% for the last oor. Moreover, they observed a maximum decre- equipped with extensive green systems with different drainage
ment of heating loads of 8% for the whole building, and 17% for the layer materials, pozzolana and rubber crumbs, installed on a tradi-
last oor. However, not many details were given about the math- tional non insulated at roof, and one with a traditional insulated
ematical approach used. Another group of researchers, by using a roof. They measured the electrical energy consumption of a heat
more detailed green roof model based on the numerical procedure pump system for more than one year. Their results indicated that
implemented in EnergyPlus, calculated the energy performances both extensive green roof cubicles generated less energy con-
of an ofce building with various typologies of green roof and a sumption (16.7% and 2.2%, respectively) than the reference one
high reective coating, in different European climate conditions during warm periods, whereas higher energy consumption (6.1%
[45]. They concluded that in warm climates green roofs are suit- and 11.1%, respectively) during heating periods were detected.
able for reducing the energy demand for the space cooling, without DOrazio et al. [49] assessed the yearly thermal performance of
P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379 65

Table 1
Climatic data of Cosenza.

Units Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Monthly average C 8.1 8.8 11.3 14.4 18.1 23.1 26.0 25.8 22.7 17.8 13.4 9.4
daily temperature

Maximum monthly C 17.3 18.0 21.6 26.6 30.1 32.5 36.5 34.8 34.1 27.0 22.0 18.0
average daily temperature

Minimum monthly C 1.8 1.9 0.4 2.4 6.3 9.5 11.9 13.0 10.2 5.3 0.6 1.3
average daily temperature
Average monthly mm/month 139.4 119.3 95.2 72.5 52.1 26.3 14.9 22.7 56.3 99.4 140.2 151.4
daily rainfall
Number of Rainy Days days 10 9 8 10 6 4 3 3 8 8 10 13
Monthly average MJ/m2 7.7 11.8 17.3 21.8 25.7 29.6 28.9 26.0 20.0 12.9 9.4 7.7
daily solar radiation on the
horizontal surface

an extensive green roof and compared it with that of six other of either brick or metal, with a slab in either pinewood or con-
type of roof, of similar size. The roof systems were installed on a crete and with or without under covering ventilation. Their results
real-scale high-insulated experimental building under temperate highlighted that when the roof has dense vegetation the entering
climate in the vicinity of Ancona (Italy) and the study was con- thermal gain went down by about 60% compared with the roof with
ducted in absence of air conditioning. Their results demonstrated no vegetation. Moreover the roof with vegetation acted as a passive
that in winter the green roof is able to guarantee further insu- cooling system since the outgoing energy throughout the summer
lation even in saturation conditions while, in summer, the green was about 9% greater than the incoming energy during the same
roof mitigates incoming heat uxes and ceiling temperatures, even period.
though its performance is partially hindered by high insulation. In In this study, an experimental analysis of an extensive green roof
another work, a 2 C decrement in summer internal air temperature installed on a real-scale University building in Cosenza (Italy, Lat.
by the installation of a green roof on buildings located in Athens was 39.3 N) is presented. The paper concerns the evaluation of the tem-
determined [43]. For the same climatic condition and in absence of perature levels and the thermal performances of different layering
air-conditioning, in [50] are presented the results of a long-term solutions compared to a reference conguration representing the
experimental analysis to identify the thermal behaviour of a green original conguration of the roof surface before the installation of
roof installed over a bare at roof with a low thermal insulation, the green roof. The external coating of the reference roof is made of a
that was considered as reference. During the experiment, in both black bituminous waterproof layer, which is a solution still adopted
buildings, the storey under the roof remained unoccupied during for at roof buildings even though does not represent the majority
summer while in the rest of the year, only the last storey under of the roofs in the area of the study. The analysis was conducted
the green roof was occupied by one person during ofce hours. both in summer and winter seasons in a typical Mediterranean
Their result showed that the green roof cannot provide consider- climate. The analysis showed the thermal behaviour of the green
able additional thermal insulation in order to minimise heat loss roof in terms of average values and temperature uctuation in the
within the roof during the cold season, while it can contribute sub- layers of the different stratigraphies, demonstrating the ability of
stantially to building energy conservation during the warm period this system to provide benets both in summer and winter. More-
of the year. Schweitzer and Erell [51] evaluated the energy per- over the effect of the green roof on the conditions of the indoor
formances and assessed the cooling effect of extensive green roofs environment was assessed for three internal rooms of the last
through reduced-scale models of buildings equipped with planted oor of the building properly monitored. Furthermore, the mea-
roofs in the campus of Tel Aviv University (Israel). They monitored surements of layers temperature have permitted the assessment
the daily evaporated water and calculated the associated latent of the heat uxes through the structural roof, and to quantify the
heat. Their results highlighted that the cooling efciency of all roof achievable energy savings for the air-conditioning of the consid-
variants studied was very low, since the reduction of the building ered building per square meter of roof. Finally the experimental
energy load attributed to the green roof system was less than 5% data were used in an innovative way to perform a dynamic charac-
of the calculated evapotranspiration heat. Olivieri et al. [52] con- terization of different green roof solutions, by means the evaluation
ducted an experimental measurements for the assessment of the of the decrement factor and the time lag of the thermal wave trans-
summer performance of extensive green roofs in a locality near ferring through this roong solutions, providing data hardly found
Ancona (Italy). The roof cover of the real-scale experimental build- in the literature.
ing was insulated with a double layer of expanded polystyrene.
The whole roof was divided into six types of roof covering, made

Fig. 1. Plots layering and position of the installed sensors.


66 P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379

2. Methodology

m2 K/W

m2 K/W
W/m K

W/m K

W/m K

W/m K
kg/m3

kg/m3

kg/m3
J/kg K

J/kg K

J/kg K
Unit
2.1. Climatic conditions

Value

0.034

0.098
The University of Calabria is located in Southern Italy, where the

1307
1210

1200
1400

1000
0.27

0.71
0.16

400
0.4
climatic conditions are typically Mediterranean, dened as subtype
Csa according to the Kppen climate classication. The summers are

Thermal Conductivity

Thermal Conductivity

Thermal Conductivity

Thermal Conductivity
hot and dry, while winters are rather wet. Cosenza is situated in a

Thermal Resistance

Thermal Resistance
valley surrounded by mountains, so it shows a particular micro-
climate. The temperature excursion, both at a daily and at a yearly

Specic heat

Specic heat

Specic heat
level, is very high. In particular, the minimum temperatures reach

Property

Density

Density

Density
low values during the night due to the heat exchange and the ther-
mal inversion, while in summer the temperatures are very high,
especially in non windy conditions. Precipitations are heavier dur-
ing the colder months. The monthly average daily values of the

Thickness [mm]
main climatic parameters are reported in Table 1.

2.2. Experimental set-up and monitoring system

Plot 3

1.8
55

75
80

30
3
The investigated building has a square plan with side of 21.30 m

m2 K/W

m2 K/W
and a height of 18 m; it consists of ve oors and one underground.

W/m K

W/m K

W/m K
kg/m3

kg/m3

kg/m3
J/kg K

J/kg K

J/kg K
The experimental extensive green roof with a surface of 200 m2 was

Unit


installed in October 2012 on the 380 m2 of the available plane sur-
face in the Department of Mechanical, Energetic and Management

Value

0.098
1925
1307
1210

1000
0.27

0.71

900

400
Engineering of the University of Calabria. The structural part of the

0.4

0.2

plane roof consists of reinforced concrete joists and polystyrene
lightening elements, with a total thickness of 31 cm. Four plots

Thermal Conductivity

Thermal Conductivity

Thermal Conductivity
Thermal Resistance

Thermal Resistance
were installed on the building roof for a total green roof area of
about 150 m2 . In particular three green roof plots, with a surface of

Specic heat

Specic heat

Specic heat
approximately 50 m2 each, were built with specic layering (Plots

Property
13 of Fig. 1) whereas one plot was left as the reference traditional

Density

Density

Density
roof (RR). Plot 1 and Plot 2 are made of the following layering, start-
ing from the bottom to the top: an additional recovery waterproof


layer; a lightweight concrete layer to provide a 1% slope for rainfall
Thickness [mm]

water management (from 10 cm to 5 cm); a root-barrier waterproof


layer (INDEX Italia Defend and ZINCO Harpoplan ZD UV); a water
storage and protection layer (ZINCO TSM32 and ZINCO BSM64); a
Plot 2

drainage and water storage layer (CLIMAGRN Climadrain 55 and

75
80

40

7
4
CLIMAGRN FKD 40); a lter sheet (ZINCO TG and CLIMAGRN Fil-
ter sheet 105); growing media (HARPOSEIC Terra Mediterranea)
m2 K/W

m2 K/W
W/m K

W/m K

W/m K
Thermal properties and geometrical characteristics of the materials of the different plots.

kg/m3

kg/m3

kg/m3
J/kg K

J/kg K

J/kg K
and Mediterranean vegetation. The main difference between Plot 1
Unit

and Plot 2 lies in the hydraulic properties of the material installed


since they are made of different commercial materials; however


Value

0.098
1925
1307
1210

1000

this aspect is not investigated in the study. Plot 3 was made with the
0.27

0.71

900

400
0.4

0.2

same layers but additional insulation layer of 3 cm (ISOLKAPPA Isol-


plan 120) was placed under the water storage layer and vegetation
Thermal Conductivity

Thermal Conductivity

Thermal Conductivity

was not planted. The thermal properties and geometrical character-


Thermal Resistance

Thermal Resistance

istics of the different layers of the plots, provided by manufacturers


of the different layers, are reported in Table 2. The growing medium
Specic heat

Specic heat

Specic heat

is mainly constituted by of lapillus of different grain size, a reduced


Property

Density

Density

Density

content of pumice and a percentage of organic matter of less than


6%. The planted species in Plot 1 and Plot 2 are sedum type, in partic-

ular Dianthus grantianopolitanus, Carpobrotus edulis and Cerastium


tomentosum.
Thickness [mm]

The last plot, with a surface of approximately 50 m2 , is the


Reference Roof and represents the original conguration of the
roof surface, before the installation of the green roof, with an
Plot 1

55

75
80

external coating made of a bituminous waterproof. The surface is



3
4

dark-coloured and the estimated value of the reection coefcient


Drainage and storage

(albedo) according to [6] is 0.05. Such a roof cover solution, even if


does not represent the totality of roofs in the area, is of great inter-
est from a thermal point of view because it induces high solar gain
Lightweight
Waterproof

in winter but also high loadings due to solar radiation in summer.


Protection
Insulation
Substrate

Meteorological data are monitored by a weather station, shown


Table 2

Layer

crete
con-

in Fig. 2, placed at the south-eastern corner of the roof, that mea-


sures: ambient air temperature, relative humidity, precipitations,
P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379 67

Fig. 2. Experimental site and meteorological station.

atmospheric pressure, wind direction and speed. The tempera- layer, and between the traditional roof surface and the lightweight
ture sensor with solar shield has an operative range from 40 C concrete. A further RTD was placed on the top of the insulation layer
to +80 C with an accuracy of 0.4 C, the relative humidity sen- in Plot 3 (Fig. 1). In the reference Roof, accordingly, only surface
sor works in the range of 0 100% with an accuracy of 3%. The temperature is measures by RTDs properly shielded and positioned
wind speed sensor has an operative range from 1.5 m/s to 79 m/s in two acquisition point.
and an accuracy of 5%. The rain gauge sensor has a resolution of The soil probe has accuracy of 2% for the measurement of soil
0.2 mm. For the measurement of total horizontal solar radiation a moisture in an operative range from 0% to saturation and an accu-
secondary standard EPLAB pyranometer is used whereas the ther- racy of 1% for the measurement of temperature with an output
mal infrared sky radiation is measured with an EPLAB precision from 50 C to +50 C. The RTD sensors are four wires PT100 class
infrared radiometer. 1/3 with accuracy of 0.1 C at 0 C and 0.27 at 100 C.
In each plot two acquisition point (A and B), properly spaced The green roof is equipped with a drip irrigation system man-
from their edges to avoid boundary effects, were installed for the aged by modules that operate the activation and shut-down
monitoring of the main layers variables. In each point, along the according to the values provided by adequate water presence sen-
vertical prole, a probe simultaneously measure the temperature sors installed in the drainage layers. The irrigation is provided
and volumetric water content (WC) in the substrate. Two resis- during hotter months in summer to prevent water stress of plants.
tance temperature detectors (RTD) were installed at the interface In Plot 1 irrigation operates from 22:00 to midnight while in Plot
between the lightweight concrete and the root-barrier waterproof 2 it operates from midnight to 2:00. The articial daily watering

Fig. 3. Roof plan with Plots and Monitored internal rooms of the building.
68 P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379

amount is 3.56 kg/m2 day in both plots. Plot 3 does not require irri- stored for each channel and saved into the PC le system, in a matrix
gation since the vegetation is absent. Irrigation water is taken from structure.
a dedicated storage tank that collect rainfall for grey water reuse
for the watering of soil and plants. When the tank does not contain
3. Thermal behaviour analysis
a sufcient level of water, irrigation is provided by water from the
supply network.
The investigations were carried out with reference to a repre-
The effect of the green roof on the internal conditions have been
sentative period in the hottest and in coldest weeks of the year, by
assessed by considering only the top oor of the building, since
analysing the response of the different layers of the plots. Present-
it mostly benets from the presence of the green roof. For this
ing one-week results rather than daily ones allows for misleading
purpose, sensors for the monitoring of internal air temperature, rel-
conclusions related to short-term events such as brief rainfall
ative humidity and room ceiling surface temperature were installed
episodes and temporary overcast sky conditions to be eliminated.
in the internal environments in three rooms located directly below
Furthermore, the effect of green roofs on indoor environment con-
the three green roof plots (Room 1 is positioned beneath Plot 1
ditions was assessed to demonstrate its inuence in improving the
and so on). The same measurements were made in the Reference
thermal conditions of indoor spaces.
Room, located in correspondence of the reference roof. Tempera-
tures were measured with RTD sensors with an operative range
from 40 C to +75 C and an accuracy of 0.5 C. The relative 3.1. Summer behaviour
humidity sensor work in the range 0100% with an accuracy of 2%.
These sensors are equipped with an internal data logger that stores Fig. 4 reports the climatic conditions for the selected summer
the measurements with a sample rate of 5 min. period in 2013 (from 22/08/2013 to 28/08/2013), identied by clear
From Fig. 3 it is possible to observe that the four rooms have sky condition, high external air temperature and an absence of
different expositions since they are located on different sides precipitations. Total horizontal solar radiation reached a peak of
of the building. Such an aspect would make any comparison 862 W/m2 , the external air temperature varied between 19.9 C and
between indoor conditions of internal rooms difcult since oth- 32.8 C, relative humidity between 35% and 80% and atmospheric
ers parameters, such as solar radiation incident to the wall and pressure between 974.8 hPa and 980.6 hPa.
penetrating glazed surfaces, contribute to the thermal balance of Temperatures in the substrate and volumetric WC in the acquisi-
the indoor air temperature nodes. However in this particular case tion points (A and B) of Plot 1 are shown in Fig. 5a. The temperature
the south-facing building wall is shaded by the adjacent building in the growing media follows the pattern of external air temper-
and consequently is not exposed to direct solar irradiation during ature and ranges between 19.3 C and 35.3 C with a mean value
the day. Furthermore Room 1, Room 3 and Reference Room do not of 26.1 C in point A and 25.1 C in point B. The peculiarity of the
present east and west exposed windows whereas Room 2 has an irrigation system allows for an evaluation of the spatial inuence of
east-facing window that is located in a lodge and partially shielded WC on soil temperature proles. It is clear from Fig. 5a that higher
by an external window grate; therefore the solar radiation pene- WC is related to lower temperatures. Acquisition point B is more
trating trough this glazed surface is limited. Considering also that affected by the dropped water so that when irrigation starts, the
the four rooms have comparable plan surfaces it can be assumed water content abruptly rises to 13.7% and then declines during the
that, with a certain margin of error, a comparison between indoor day due to the evapotranspiration effects. As a consequence of WC
conditions can be conducted to evaluate the benets obtainable growth, an immediate drop in substrate temperature (TsB ), which
by means of the different green roof congurations compared to falls to the minimum daily value, is observed. In point A, where WC
the reference case. In this regard, considering that in every room showed more limited daily variations, of between 10% and 12%,
the external wall surface is small compared to the roof surface, the correspondent substrate temperature showed slightly higher
heat uxes through the roof cover assume a cardinal role in the values, especially during the irrigation time schedule. However, a
determination of indoor room air temperature. correlation between the WC and temperature in the growing media
The last oor of the investigated buildings, including the four appears; a greater WC can lead to more appreciable temperature
investigated rooms, is dedicated to work activities and occupied differences. Accordingly, Jim et al. [53] indicated the substrate-
by research and teaching personnel. The building is occupied from moisture effect in delaying temperature rise in soil in their results.
9:00 AM to 6:00 PM with one hour time break for lunch, so The pattern on the top of the lightweight concrete layer evi-
accordingly, occupants schedule is mainly dictated by the work dently indicates the ability of upper layers (substrate and drainage)
regulations. The electric appliances and lighting use follows conse- to attenuate temperature oscillations (Fig. 5b). The maximum daily
quently the work time schedule. In the considered academic year temperature excursion, dened as the range between maximum
Room 1, Room 3 and Reference Room were occupied by one person and minimum temperatures, is considerably lower and the tem-
each whereas Room 2 was not occupied. The rooms are equipped perature varies between 22.2 C and 26.1 C in point A with a steady
with one desktop laptop with a nominal power of about 150 W and component equal to 24.1 C and between 21.3 C and 25.7 C in
are lighted by surface mounted luminaires equipped with uores- point B with a steady component equal to 23.2 C. A further notable
cent lamp with a total power approximately of 230 W per room. contribution in attenuation of the maximum daily temperature is
However, it must be highlight that, the investigated periods given by the lightweight concrete, and the temperature measured
were chosen during holidays, or during suspended work activities. on the bottom of this layer can be considered fairly stable around
For this reason, as a consequence, the measured indoor variables the steady value of 24.9 C in point A and 24.0 C in point B. The
are representative of free oating conditions with the absence of effect of substrate moisture in suppressing the vertical tempera-
internal heat gains. In this regard, the occupant behaviour does not ture gradients is also detected in the lower layers of the layering.
affect the results of the analysed winter and summer periods. The time lag of the temperature peak produced by the lightweight
A dedicated data acquisition system DAQ acquires all the moni- concrete is 5 h, whereas the total time lag due to the presence of
tored variables. Every sensor is connected to the acquisition board the additional green stratigraphy is approximately 10 h.
by dedicated modules. A proper acquisition software generates Similar results were found in Plot 2 where a different irriga-
a data structure (values array), where one sample per minute is tion schedule was set. In this case, the greater WC values produce
a lower temperature in the growing media but the drastic drop
detected in plot 1 is not observable. However, in acquisition point
P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379 69

Fig. 4. Climatic condition of the selected summer period. Solar radiation, sky temperature and external air temperature (a). Rainfall, windspeed and relative humidity (b).

B, where a lower WC is registered, again temperature tends to be the value of 3.5% and insignicant differences were measured
higher either in minimum and maximum daily values. The range between the different acquisition points, so that only the proles of
is between 20.9 C and 36.0 C around a mean value of 27.6 C in point A are displayed (Fig. 6a). Such a low water level could not be
point A and between 19.3 C and 34.3 C around a mean value of sufcient to produce relevant cooling effects linked to evaporation,
25.7 C in point B. This difference is reected in lower layers; again, a further element that contributes to increment the growing media
the temperature measured under the lightweight concrete is lower temperature that reached 50 C with a maximum daily temperature
in point B yet the deviation is not so accentuated. excursion of 25 C and a steady value of 36.4 C. The temperature
In Plot 3 the combined effect of absence of the vegetation above the insulation layer ranges between 24.4 C and 37.3 C: the
and presence of an additional insulation layer determines rela- effect of this additional layer in dampening the temperature uc-
tively higher temperatures value in the growing media that exceed tuation is detected clearly in the prole of the temperature above
the operative temperature range of the sensor. Furthermore, the the lightweight concrete layer, which varies between 27.4 C and
absence of irrigation induces low levels of WC that varies around 30.4 C. Again, the temperature under this layer can be considered

Fig. 5. Temperature proles in the layers. Substrate temperature and water content in acquisition points of Plot1 (a). Temperature at the bottom and top of the lightweight
layer in acquisition points of Plot1 (b).

Fig. 6. Temperature proles in the layers. Substrate temperature and water content in Plot3 (a). Temperatures underlying the substrate in Plot 3 (b).
70 P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379

reasonably constant, oscillating around 28.8 C (Fig. 6b). In the ref- 36.5 C. Due to the incidence of solar radiation, the membrane tem-
erence roof, owing to the high values of external air temperature, perature rises, reaching the peak at the same time of the maximum
of incident solar radiation and of the solar absorption coefcient value of solar radiation. Then, the temperature decline with a lower
of the black-coloured external surface, high values of the external slope since the external air temperature predominates the pattern
surface temperature peak were detected and the maximum daily of the supercial temperature when solar radiation assumes lower
temperature excursion reached extremely high values (Fig. 7a). The values. At night, the longwave radiative heat exchange with the sky
temperature ranges from 17.7 C to 64.8 C with a mean value of permits membrane cooling and allows attainment of the minimum

Fig. 7. Surface temperature in Reference Roof, air temperature and solar radiation in the selected summer period (a). Comparison between average external surface
temperature in Reference Roof and temperature below the lightweight concrete on the other plots (b).

Fig. 8. Evapotranspiration heat and solar radiation incident on Plot 1 in the considered summer period.

Fig. 9. Trend of internal air temperature of the four rooms located underneath the roof plots for the considered summer period (a). Inverse cumulative distribution of internal
air temperature in August 2013 (b).
P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379 71

daily value that is found before sunrise. Similar ndings regarding China, 58% of the heat from a green roof was lost by evapotran-
the temperature values of a reference roof are reported in [54,55]. spiration.
In Fig. 7b a comparison between the average external surface To assess the effectiveness of green roofs in producing energy
temperature of the reference roof and the temperature below the saving in the building, the effect on the indoor environment was
lightweight concrete of the other plots is made. It is evident that considered. Fig. 9a reports the trend of the internal air temperature
the green roof is able to produce lower temperature levels at the together with the external air temperature trend for the same sum-
interface with the structural roof, due to the shading effect of mer period considered in the thermal analysis of the layering for
vegetation, evapotranspiration phenomena and thermal resistance the four rooms located just beneath the correspondent plots. It is
growth. Plot 1 and Plot 2 present very similar temperature values important to underline that for all the analysed period, the building
at the bottom of the green stratigraphy that is approximately 12 C was not occupied, therefore, the measured variables are represen-
lower than the average supercial temperature of the reference tative of free oating conditions. The gure clearly shows that the
roof. Due to the presence of insulation, as expected, Plot 3 guaran- reference room presents the highest values of internal air temper-
tees a temperature level that is, on average 4 C higher than Plot 1 ature followed by Room 2, Room 3 and nally Room 1, where the
and Plot 2. temperatures are lower than 28 C for the whole period. Room 2
The plots irrigation enhances the cooling effect by means of is evidently affected by other factors since it presents a more pro-
an evapotranspiration phenomenon. This aspect is an important nounced daily temperature excursion, due to the major presence of
contribution to the energy balance of the green roof. Therefore a glazed surfaces and to the greater vertical dispersing walls surface
qualitative estimation of the energy associated with evapotranspi- whereas in the other rooms the pattern of air temperature is much
ration has been conducted. From Fig. 5a it is possible to observe less variable with limited daily excursion. On average, Room 1 pre-
that in point B the irrigation of the vegetation causes an imme- sented an internal air temperature 2.3 C lower than the Reference
diate growth of the substrate water content. This value however, Room, whereas Room 2 and Room 3 were respectively 0.8 C and
decreases during the following hours until the irrigation system 1.2 C lower.
starts to operate again. The minimum daily value remains fairly A further conrmation of the benecial effect of the green roof
constant in all the day of the considered period. From these obser- derives from the analysis of the temperature cumulative distri-
vations it can be concluded that the quantity of water provided by bution for the entire month of August 2013, as shown in Fig. 9b.
irrigation is eventually converted into latent heat through evapo- The graph reports on the y axis the percentage of time, to which
transpiration. In this case considering the difference between the corresponds a value of internal air temperature greater than the
maximum and minimum WC daily value, the amount of evapo- correspondent value in the x axis. The curve relative to the Ref-
transpirated water and the associated energy can be determined. erence Room reports temperature levels signicantly greater than
According to [37] the water ux in a green roof can be expressed the other rooms, denoting an undisputed benecial effect of the
as: green roof on the indoor environment. Temperatures higher than
28 C are observed with the time percentage of 95% for Reference
ET
= (1) Room, 89% for Room 2, 75% for Room 3 and 60% for Room 1.


where is the latent heat of vaporization (2422 kJ kg1 at 35 C) and 3.2. Winter behaviour
ET is the thermal ux due to the evapotranspiration process. Rear-
ranging the equation, the heat associated with evapotranspiration Fig. 10 reports the climatic conditions for the selected winter
LET in kWh, can be expressed as: week in 2014 (from 24/01/2014 to 30/01/2014) characterized by
low values of solar radiation with a peak of 569 W/m2 , external air
LET = Vw   (2) temperature variable between 1.4 C and 15.3 C, relative humidity
between 40.3% and 90.8%, atmospheric pressure between 820 hPa
where Vw in m3 , is the daily amount of water loss in the substrate and 992 hPa and the presence of two rainfall events.
and is the water density. The last term was then compared to the In the substrate, greater values of WC are related to lower tem-
solar radiation incident on the plot surface, since this is the main perature values. In Plot 2 the temperature in the substrate, in
loading of the thermal balance in summer condition. The measure- agreement with the pattern of external air, varied between 4.0 C
ments of the pyranometer provide hourly values of global radiation and 15.3 C. However, the difference in WC between the two dif-
on the horizontal surface; the integral of such values over the day- ferent acquisition points does not produce a relevant difference in
light period provides the daily energy collected by the green roof the values of substrate temperature for the same points. In winter,
plot surface. Results of the calculation are provided as an average the main force that drives the evapotranspiration phenomena is
of the evapotranspiration heat for both acquisition point A and B. solar radiation, which is more limited in magnitude; furthermore,
Similar results were obtained in Plot 2, whereas in Plot 3, as already the high external relative humidity values restrain the evaporation
observed in the layers temperature gures, the evapotranspiration potential, therefore the overall effect does not allow for appreci-
effects are of negligible account. For these reasons only the values ation of substantial differences in the temperature trend. Similar
obtained for Plot 1 in are indicated Fig. 8. results are found in Plot 1. In the layers below the growing media,
Evapotranspiration accounts for from 26% to 35% of the inci- the temperature showed a variable trend but, nevertheless, the
dent solar radiation on the plot surface. The results, in terms of temperature at the bottom of the lightweight concrete were rela-
latent heat, are in agreement with [51] who performed experiments tively high if compared to the external air, as can be seen in Fig. 11b.
in a reduced-scale models of buildings equipped with planted Similar results were found for the substrate in Plot 3, so that only
roofs, monitoring the total daily amount of water evaporated and the pattern of the variables below this layer is shown. The presence
calculating the latent heat from the latent heat of vaporization; fur- of the insulation layer is undoubtedly benecial since in this plot the
thermore, they are also in agreement with [38] which, through a temperature at the bottom of the lightweight concrete maintained
quasi-steady state heat and mass transfer green roof model val- the highest values of the plots, for the considered period presenting
idated with robust experimental data obtained from laboratory values that were always higher than the external air temperature
experiments, calculated the evapotranspiration term of the energy (Fig. 12). In the reference roof, again the surface temperature was
balance for different simulation cases. Conversely in [39] using a strongly inuenced by the external air temperature and solar radi-
mathematical model it was found that for a typical summer in ation and shows a variable trend, reaching a maximum value of
72 P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379

Fig. 10. Climatic condition of the selected winter period. Solar radiation, sky temperature and external air temperature (a). Rainfall, wind speed and relative humidity (b).

34.6 C. The minimum value, on a daily level, is considerably lower 4 C higher than the surface of the reference roof, whereas in Plot 1
and fell below 0 C, due to longwave heat exchange with the sky. was 2.5 C higher. Plot 2 showed the worst performance of all the
A comparison between the temperatures registered at the bottom three considered layering as for part of the week the temperature
of the lightweight concrete and the average surface temperature was almost coincident with the average surface temperature of the
measured on the reference roof, is shown in Fig. 13, observing how reference roof.
the green roof can maintain a higher temperature than the average Regarding the internal air conditions, Room 3 showed the high-
surface temperature of the reference roof. In particular, in Plot 3 est time percentage of temperature for each temperature shown in
the temperature at the base of the green layering was on average the x axis (Fig. 14); this behaviour is due to the presence of the insu-

Fig. 11. Temperature and water content in Plot 2 substrate (a) and temperatures of the underlying layer in Plot 2 (b) for the selected winter period.

Fig. 12. Temperature underlying substrate in Plot 3 in the selected winter period.
P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379 73

lation layer. Room 1 and Room 2 showed performances close to that priory tested, running simulations with different numbers of nodes.
of the Reference Room. The worst results were achieved in Room 2, In particular, in a preliminary test phase, simulations varying the
which did not demonstrate a different behaviour compared to the number of nodes from 10 to 20 with a step of 2 were performed.
Reference Room, in agreement with the result of the winter ther- From the results it was possible to conclude that fteen is a suf-
mal analysis of the layering. However, if temperature values higher cient number of nodes to carry out subsequent simulations.
than the winter comfort condition level (20 C) are considered, Plot With this procedure the capacitance effect of the structural roof
1 and Plot 2 were able to produce air temperature values on the is properly taken into account. The solution of the nite differ-
correspondent room that are higher, or at least similar, to that of ence scheme provides the temperatures values in each considered
the Reference Room. Even though winter performances are limited node, as shown in Fig. 15. The conductive heat ux was evaluated
if compared to the results of the summer period, the green roof can between the ceiling surface node and the previous one. Once the
contribute to thermal insulation of the building envelope, reducing hourly heat uxes are known, the integral in the considered period
heat losses toward the outdoor environment. provides the energy delivered to the indoor rooms, allowing for
the determination of the possible energy saving per square meter
of roof due to the presence of the green cover.
4. Heat uxes evaluation
4.1. Summer evaluation
In this section an assessment of the heat uxes entering and
exiting the indoor environment through the structural roof of the Fig. 16a reports the heat uxes for the considered summer
building, for the same summer and winter periods analysed in the period. In Plot 1 and Plot 2 the resulting heat uxes are always
previous sections, has been conducted. The heat uxes delivered negative indicating that the rooms are cooled by the ceiling that
through the roof cover allow a quantication of the energy benets disperses heat in the upper layers. The minimum value reached
related to the green roof installation. The temperature measured is 5.3 W/m2 for Plot 1 and 6.7 W/m2 for Plot 2. In Plot 3, as
at the indoor ceiling surface of each room, the temperature at conrmed by the thermal analysis, the additional insulation layer
the bottom of the lightweight concrete layer of each plot and the worsens the performance of the green layering with resultant pos-
surface temperature in the reference plot were used as boundary itive conductive heat ux in most part of the period, indicating that
conditions in a nite difference scheme. Grid independence was energy is entering the indoor environment. In the reference roof

Fig. 13. External surface temperature in Reference Roof, air temperature and solar radiation in the selected winter period (a). Comparison between average external surface
temperature in Reference Roof and temperature below the lightweight concrete on the other plots (b).

Fig. 14. Inverse cumulative distribution of internal air temperature for January 2014.
74 P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379

the pattern of the heat ux is highly variable, in agreement with lower conductive heat ux than Plot 1; however they both nullify
the surface temperature of the plot, with peaks of about 50 W/m2 , the ingoing heat ux showing only outgoing uxes.
considerably greater than other plots. During night time, when the
surface temperature falls to the minimum daily value, an inver-
sion of the heat uxes occurs, but the entity is quite limited with a 4.2. Winter evaluation
minimum value that does not exceed 14 W/m2 .
The integration of the quantied heat uxes in the considered The same considerations were conducted for the considered
period provides the specic energy, expressed in Wh per square winter period. Fig. 17 shows the results of the nite elements sim-
meter of roof surface, that enters or leaves the correspondent ulations. For the three plots and the reference roof, the calculated
indoor rooms. As summarized in Table 3, in the reference roof heat uxes are always negative in the winter period and with an
the total entering energy is 3025 Wh/m2 , one order of magnitude extreme variable pattern. This is a consequence of the variable trend
higher than Plot 3, where it results as being only 547 Wh/m2 with of the temperatures in the green roofs layers, as discussed in the
a reduction of about 82%. In particular, Plot 2 is able to produce previous paragraphs. Fig. 16b demonstrate how, in cold weather
conditions, the indoor rooms disperse heat through the roof, nev-

Fig. 15. Temperature distribution of the nodes in the four plots for the summer period. T5, T7, T9, T11 and T13 are the temperatures of the correspondent nodes; Tbot is the
temperature at the bottom of the lightweight concrete layer; Tceil is the internal ceiling temperature and Tsup is the surface temperature of Reference Roof.

Fig. 16. Conductive heat ux calculated between the last two nodes of the structural in summer (a) and winter (b).
P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379 75

Table. 3
Specic thermal energy entering and exiting the indoor rooms through the structural roof in summer and in winter.

Summer Winter
2 2
Eout [Wh m ] Ein [Wh m ] in [%] Eout [Wh m2 ] Ein [Wh m2 ] out [%]

Plot 1 1211 0 100 3447 0 30


Plot 2 1828 0 100 3406 0 31
Plot 3 16 547 82 3124 0 37
Ref. Roof 235 3025 4954 0

ertheless in the reference roof the heat ux is notably higher, in lated with reference to maximum temperature peaks in summer as
absolute value, than the green plots, by indicating the advantageous dened in [56].
effect of the presence of a green cover on the roof. In particular in
Plot 1 the minimum value reached by the heat ux is 42 W/m2 ,
in Plot 2 it is 37 W/m2 , in Plot 3 it is 32 W/m2 and in Reference Ti,max Ti,min
f = (3)
Roof it is 49 W/m2 . With reference to the energy loss through the Te,max Te,min
roof, Table 3 shows how Plot 1 and Plot 2 can reduce the loss by
30% and 31% respectively, whereas Plot 3, due to the presence of an
insulation layer, can provide a higher reduction of approximately  = tTi,max tTe,max (4)
37%.
where the subscripts i and e refer to internal and external conditions
and min and max refer to the daily maximum and minimum values.
In this section, a theoretical and experimental evaluation in
5. Dynamic characterization of the extensive green roof order to quantify the values assumed by these parameters for
the vegetation-substrate-drainage system was conducted for the
In order to assess dynamic thermal properties of building enve- investigated green roof plots.
lope elements, as traditional roof, it is usual to dene proper In theoretical analysis, the dynamic parameters were evaluated
parameters. These are, for the steady periodic regime, the heat stor- considering the sol-air temperature as the external boundary con-
age capacity, expressed in terms of decrement factor and time lag. dition, which is usually employed to schematize the joint action
In non-sinusoidal conditions, the decrement factor is dened as of the external loads [57,58] whereas, the temperature at the bot-
the ratio between the maximum daily excursions of the internal tom of the drainage layer was considered as the internal boundary
and external temperature uctuations [56]. The time lag is calcu- condition in the three plots. The sol-air temperature is obtainable

Fig. 17. Temperature distribution of the nodes in the four plots for the winter period. T5, T7, T9, T11 and T13 are the temperatures of the correspondent nodes; Tbot is the
temperature at the bottom of the lightweight concrete layer; Tceil is the internal ceiling temperature and Tsup is the surface temperature of Reference Roof.
76 P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379

from the external surface energy balance and, for a traditional roof, where 1 is dened as [10]:
is given by [57,58]:
1 = g + f g f (14)
hc hr 1
Tas = T + T + (5)
hc + hr amb hc + hr sky hc + hr The obtained values of mean absorption coefcient, mean con-
vective heat transfer coefcient and mean radiative heat transfer
The physical phenomena involved in a green roof are more com-
coefcient are: = 0.35, hc = 11.01 and hr = 5.09 for Plot 1; = 0.36,
plex than a traditional roof and the evapotranspiration contribution
hc = 11.35 and hr = 5.12 for plot 2; = s = 0.83, hc = hc,s = 9.42 and
plays an important role in the energy balance. The evapotran-
hr = 5.69 for Plot 3.
spiration phenomenon leads to benets due to cooling of the
Fig. 18 shows the trend of the calculated sol-air temperature
external ambient air with a consequent reduction of the equiva-
for the three plots. As expected, the sol-air temperature is affected
lent external temperature. In such conditions, the decrement factor
by solar radiation and sky temperature; from the graphs it can be
decreases and the time lag increases. The theoretical analysis was
clearly observed how for Plot 1 and Plot 2 the curves are very similar
conducted, similar to a traditional roof, without taking into account
with daily peaks of about 44 C, whereas in Plot 3 it reaches much
the contribution related to evapotranspiration, obtaining there-
higher values than the other plots with daily peaks of about 72 C.
fore precautionary values of the dynamic parameters. However,
According to the procedure described and considering the same
the absorption coefcient and the convective and radiative heat
acquisition points used in the thermal behaviour analysis, for each
transfer coefcients of the external surface of the green roof were
plot the decrement factor and the time lag were evaluated in the
appropriately modied for the considered surfaces.
investigated summer period on a daily basis. In particular, in the
In Eq. (5), the sky temperature is obtained assuming it as a black
theoretical analysis the sol-air temperature describes the external
body. The foliage and soil absorption coefcients for the three plots
environment and only the effect of the additional green layers is
are calculated according to Del Barrio relations [40], properly mod-
considered. Fig. 19a and Fig. 19b shows the daily values of the decre-
ied to consider the fractional vegetation coverage of the plots:
ment factor and of the time lag for the acquisition points of the three
f = (1 s s )(1 + s s )f (6) plots. For the considered summer period, the decrement factor of
   the two acquisition points ranges between 0.100 and 0.178 in Plot
s = (1 s ) s f + 1 g 1 f (7)
1 and between 0.131 and 0.185 in Plot 2, whereas in Plot 3, since
where the fractional vegetation coverage (f ) and the Leaf Area there is not the effect of the vegetation, this ranges between 0.154
Index (LAI) have been estimated through direct measurements on and 0.226. Regarding the time lag, Plot 3 always has lower values
the experimental site, obtaining a value of f = 0.59 and LAI = 1.5 than the other plots ranging from 2 h to 4 h, whereas Plot 1 and Plot
for plot 1 and f = 0.56 and LAI = 1.5 for plot 2. The longwave trans- 2 show almost identical daily values for the analysed seven days in
mittance s represents the short wave transmittance related to the the range 4 h to 6 h.
vegetation as a function of the LAI index and was assumed equal The average values obtained in the investigated period, accord-
to 0.41 according to the values provided in [40]. The albedo of the ing to the theoretical analysis, are listed in Table 4.
vegetation s was assumed equal to 0.26, that is a value proposed The relatively high time lag values observed conrm the positive
in literature for short glass plants [38]. The albedo of the soil g effect of the green stratigraphy in summer conditions. Plot 1 and
was measured in laboratory, obtaining a value of 0.17. The mean Plot 2 present very close time lag values, which are slightly lower
absorption coefcient for each plot is calculated as: than ve hours since they consist of similar layer materials. In Plot 3,
  the time lag value is even more reduced highlighting the important
= f f + 1 f s (8) role played by vegetation plays in the dynamic characterization of
The foliage and soil convective heat transfer coefcients are pro- a green roof. For the same reason, the decrement factor in Plot 3 is
vided by the relation [10]: higher than the other two plots. However, the ability of the system
  to suppress the temperature oscillations is conrmed by the results
hc,f = 1.1LAI a cp,a Cf Waf (9) of this analysis.
hc,s = a cp,a Cs Waf (10) The results of the experimental evaluations were obtained
considering the temperature in the substrate as upper boundary
where a (1.23 kg/m3 ) is air density, cp,a (1005.6 J/kg K) is air specic condition and that below the drainage layer, as the lower boundary
heat capacity, Cf e Cg are the bulk heat transfer coefcients respec- condition. Since the effect of the vegetation layer and of a part of the
tively in the vegetation and in the soil and Waf the wind speed in the substrate is excluded, these evaluations are more conservative. In
canopy. This formulation is more appropriate for a green roof since Fig. 19c and Fig. 19d the daily values of decrement factor and of time
takes into account the wind speed, the foliage and soil roughness. lag are shown for the acquisition points of the three plots. For the
Considering the contemporaneous presence of vegetation and soil considered summer period, the decrement factor varies between
on the green roof plots, the mean convective heat transfer coef- 0.234 and 0.325 in Plot 1, where the differences between point A
cient is calculated as a weighted average, in function of the foliage and B are more evident, but are, however, contained. In Plot 2, in
coverage, between soil and vegetation heat transfer coefcients, as all the investigated period, the values of the decrement factor for
shown by the following relation: the acquisition points are fairly similar, varying between 0.295 and
  0.336. In plot 3, substantially higher values from 0.403 to 0.524
hc = f hc,f + 1 f hc,s (11)

The mean radiative heat transfer coefcient for each plot is cal-
Table 4
culated as [59]:
 3
 Time lag and decrement factors for the green roof Plots according to the theoretical
hr = fg 4Ths (12) and experimental analysis.

where  is the Stefan-Boltzmann constant, Ths is the average


temperature between the plot surface temperature and the sky
temperature and fg , according to [10], is dened as:
f g
fg = (13)
1
P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379 77

were observed, owing to the absence of vegetation. The time lag the vegetation in summer, especially considering the decrement
was also variable during the days and ranges between 2 h and 6 h in factors, which in the last case, are almost double compared to the
Plot 1, between 3 h and 5 h in Plot 2 and between 1 h and 3 h in Plot results of the theoretical investigation.
3. The average values obtained in the investigated period, according A nal assessment of the dynamic properties results from a com-
to the experimental analysis, are reported in Table 4. As expected, parison with time lag and decrement factor values in presence and
time lags are smaller and decrement factors greater since in this absence of the green roof. For the reference roof, decrement factor
case the analysis excludes the effect of the vegetation layer and of and time lag were evaluated considering the experimental exter-
a part of the substrate, with a consequent reduction of the temper- nal and internal surface temperature. The mean values obtained in
ature uctuation that represents the external boundary condition the investigated summer period are 0.157 for the decrement factor
of the system. The results of Table 4 conrm the importance of and 6.571 h for the time lag. Multiplying such decrement factor to

Fig. 18. Sol-air temperature for the three Plots in the considered period.

Fig. 19. Theoretical daily values of decrement factor (a) and time lag (b) in the summer period for the three plots. Experimental daily values of decrement factor (c) and time
lag (d) in the summer period for the three plots.
78 P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379

the experimental ones reported in Table 4 for the additional green the considered climatic conditions, the different green roofs solu-
layers, we can obtain the total decrement factor of the whole roofs. tions, with a minimum average decrement factor value of 0.135
The total time lag is obtained instead by adding the experimental and a maximum average time lag of 4.8 h, can generate a substan-
time lags in Table 4 to that of the reference roof. The total experi- tial improvement of dynamic properties of the envelope, especially
mental decrement factor is equal to 0.045, 0.050 and 0.071 for Plot in the case of roofs with limited dynamic performance.
1, Plot 2 and Plot 3 respectively while the total experimental time
lag is equal to 10.79 h, 10.57 h and 8.29 h, respectively.
Such a procedure allows to predict, known the dynamic proper- Acknowledgements
ties of any traditional roof, as they are modied after the installation
of the green roof analysed in the present study. For instance, con- This research was supported by the Italian National Operational
sidering the dynamic properties of two type of roofs (R1 and R2) Programme (PON) Research and Competitiveness for conver-
studied by Kaska et al. [60], with a decrement factor of 0.035 and gency regions 2007/2013 Axis I Support to structural change
0.48 and a time lag of 5.12 h and 2 h, the additional green layering operational objective 4.1.1.1. Scientic-technological areas gener-
allows to reach values of 0.005 (R1) and 0.075 (R2) for the decre- ating processes of transformation of the production system and the
ment factor and of 11.69 h (R1) and 8.57 h (R2) for the time lag. creating new sectors Action II: Interventions supporting indus-
These results highlight the substantial improvement of dynamic trial research through the project PON01 02543. Integrated and
properties, especially in the case of traditional roofs with limited sustainable management service for the water-energy cycle in urban
dynamic performance (such as roof R2), that can be achieved with drainage systems.
the installation of extensive green roofs.

References
6. Conclusions
[1] O. Saadatian, K. Sopian, E. Salleh, C.H. Lim, S. Riffat, E. Saadatian, A. Toudeshki,
M.Y. Sulaiman, A review of energy aspects of green roofs, Renew. Sustain.
An experimental analysis of an extensive green roof consisting of Energy Rev. 23 (2013) 155168.
three different 50 m2 surface plots installed on a University build- [2] T. Ayata, P.C. Tabares-Velasco, J. Srebric, An investigation of sensible heat
uxes at a green roof in a laboratory setup, Build. Environ. 46 (2011)
ing in South Italy, was presented. The study was conducted both 18511861.
in summer and winter seasons in a typical Mediterranean climate, [3] J. Mentens, D. Raes, M. Hermy, Green roofs as a tool for solving the rainwater
analysing the thermal performances of different layering solutions runoff problem in the urbanized 21st century? Landscape Urban Plann. 77
(2006) 217226.
compared to a reference traditional roof of same area. The reference
[4] J.Y. Lee, H.J. Moon, T.I. Kim, H.W. Kim, M.Y. Han, Quantitative analysis on the
roof is a black bituminous cover that represent the original cong- urban ood mitigation effect by the extensive green roof system, Environ.
uration of the roof surface. Results obtained allowed a comparison Pollut. 181 (2013) 257261.
with a low albedo roof that, even if does not represent the totality [5] M. Carbone, G. Garofalo, G. Nigro, P. Piro, Green roofs in the mediterranean
area: interaction between native plant species and sub-surface runoff, Appl.
of roofs in the area, is of great interest from a thermal point of view. Mech. Mater. 737 (2015) 749753.
The results showed that in summer the green roof was able to main- [6] T. Susca, S.R. Gafn, G.R. Dellosso, Positive effects of vegetation: urban heat
tain a noticeable lower temperature at the base of the additional island and green roofs, Environ. Pollut. 159 (2011) 21192126.
[7] D.E. Bowler, L. Buyung-Ali, T.M. Knight, A.S. Pullin, Urban greening to cool
green stratigraphy. The plots without thermal insulation were able towns and cities: a systematic review of the empirical evidence, Landscape
to produce a temperature approximately 12 C lower than the aver- Urban Plann. 97 (2010) 147155.
age surface temperature of the reference roof at the interface with [8] A. Teemusk, . Mander, Greenroof potential to reduce temperature
uctuations of a roof membrane: a case study from Estonia, Build. Environ. 44
the structural roof. The presence of an insulation layer determined (2009) 643650, http://dx.doi.org/10.1016/j.buildenv.2008.05.011.
a worsening of the performances, with a temperature at the same [9] K. Liu, J. Minor, Performance Evaluation of an Extensive Green Roof, Greening
position approximately 4 C lower than the reference roof. In the Rooftops for Sustainable Communities, Washington, D.C, 2005, pp. 111.
[10] D, Sailor A green roof model for building energy simulation programs, Energy
selected winter period, the green layering with thermal insulation Build. 40 (2008) 14661478, http://dx.doi.org/10.1016/j.enbuild.2008.02.001.
demonstrated that it could guarantee a temperature 4 C higher [11] T.G. Theodosiou, Summer period analysis of the performance of a planted roof
than the average of the surface of the reference roof at the base of as a passive cooling technique, Energy Build. 35 (2003) 909917.
[12] M. Zinzi, S. Agnoli, Cool and green roofs. An energy and comfort comparison
the additional layers.
between passive cooling and mitigation urban heat island techniques for
The presence of the green roof determined also a reduction of the residential buildings in the Mediterranean region, Energy Build. 55 (2012)
internal environment temperature on average of 2.3 C in the inves- 6676.
tigated summer period, demonstrating the quality of this solution [13] I. Jaffal, S.-E. Ouldboukhitine, R. Belarbi, A comprehensive study of the impact
of green roofs on building energy performance, Renew. Energ. 43 (2012)
to decrease the cooling demand for the building air-conditioning. 157164.
In winter, if temperature values higher than the winter comfort [14] S. Parizotto, R. Lamberts, Investigation of green roof thermal performance in
condition level (20 C) are considered, the green roof can produce temperate climate: a case study of an experimental building in Florianpolis
city, Southern Brazil, Energy Build. 43 (2011) 17121722.
indoor room air temperature that is higher or at least similar to that [15] J. Coma, G. Prez, C. Sol, A. Castell, L.F. Cabeza, Thermal assessment of
of the reference room. extensive green roofs as passive tool for energy savings in buildings, Renew.
The monitored quantities permitted to calculate the heat uxes Energ. 85 (2016) 11061115.
[16] O. Saadatian, K. Sopian, E. Salleh, C.H. Lim, S. Riffat, E. Saadatian, A. Toudeshki,
through the structural roof of the building in the analysed peri- M.Y. Sulaiman, A review of energy aspects of green roofs, Renew. Sustain.
ods. The green roof plots generated negative heat uxes during Energy Rev. 23 (2013) 155168.
the investigated summer period, producing a passive cooling of the [17] B.A. Currie, B. Bass, Estimates of air pollution mitigation with green plants and
green roofs using the UFORE model, Urban Ecosyst. 11 (2008) 409422.
building room through the structural roof, and provided a reduction [18] D.B. Rowe, Green roofs as a means of pollution abatement, Environ. Pollut.
of the ingoing thermal energy of 100% in summer when compared 159 (2011) 21002110.
to the ingoing energy into the reference room. In winter, an atten- [19] J.-J. Baik, K.-H. Kwak, S.-B. Park, Y.-H. Ryu, Effects of building roof greening on
air quality in street canyons, Atmos. Environ. 61 (2012) 4855.
uation between 30% and 37% of the outgoing heat ux has been
[20] K. Vijayaraghavan, U.M. Joshi, R. Balasubramanian, A eld study to evaluate
obtained; therefore in both analysed seasons it is possible to obtain runoff quality from green roofs, Water Res. 46 (2012) 13371345.
considerable energy savings for the air-conditioning of the involved [21] B. Dvorak, A. Volder, Green roof vegetation for North American ecoregions: a
building. The experimental data were nally employed to conduct literature review, Landscape Urban Plann. 36 (2010) 351360.
[22] S. Schrader, M. Boning, Soil formation on green roofs and its contribution to
a dynamic characterization of the different green roofs solutions. urban biodiversity with emphasis on Collembolans, Pedobiologia 50 (2006)
The results of the dynamic characterization indicated that, under 347356.
P. Bevilacqua et al. / Energy and Buildings 122 (2016) 6379 79

[23] N. Williams, J. Rayner, K. Raynor, Green roofs for a wide brown land: [44] A. Spala, H.S. Bagiorgas, M.N. Assimakopoulos, J. Kalavrouziotis, On the green
opportunities and barriers for rooftop greening in Australia, Urban For. Urban roof system. Selection, state of the art and energy potential investigation of a
Green. 9 (2010) 245251. system installed in an ofce building in Athens, Greece, Renew. Energ. 33
[24] M. Ignatieva, G.H. Stewart, C. Meurk, Planning and design of ecological (2008) 173177, http://dx.doi.org/10.1016/j.renene.2007.03.022.
networks in urban areas, Landsc. Ecol. Eng. 7 (2010) 1725, http://dx.doi.org/ [45] F. Ascione, N. Bianco, F. de Rossi, G. Turni, G.P. Vanoli, Green roofs in
10.1007/s11355-010-0143-y. European climates. Are effective solutions for the energy savings in
[25] T. Van Renterghem, D. Botteldooren, In-situ measurements of sound air-conditioning? Appl. Energ. 104 (2013) 845859, http://dx.doi.org/10.
propagating over extensive green roofs, Build. Environ. 46 (2011) 729738, 1016/j.apenergy.2012.11.068.
http://dx.doi.org/10.1016/j.buildenv.2010.10.006. [46] K.L. Getter, D.B. Rowe, J.A. Andresen, I.S. Wichman, Seasonal heat ux
[26] T. Van Renterghem, M. Hornikx, J. Forssen, D. Botteldooren, The potential of properties of an extensive green roof in a Midwestern U. S. climate, Energy
building envelope greening to achieve quietness, Build. Environ. 61 (2013) Build. 43 (2011) 35483557, http://dx.doi.org/10.1016/j.enbuild.2011.09.018.
3444, http://dx.doi.org/10.1016/j.buildenv.2012.12.001. [47] X. Qin, X. Wu, Y. Chiew, Y. Li, A green roof test bed for stormwater
[27] U. Berardi, A. GhaffarianHoseini, A. GhaffarianHoseini, State-of-the-art management and reduction of urban heat island effect in Singapore, Br. J.
analysis of the environmental benets of green roofs, Appl. Energ. 115 (2014) Environ. Clim. Change 2 (2012) 410420.
411428, http://dx.doi.org/10.1016/j.apenergy.2013.10.047. [48] J. Coma, G. Prez, C. Sol, A. Castell, L.F. Cabeza, Thermal assessment of
[28] T. Theodosiou, Green roofs in buildings: thermal and environmental extensive green roofs as passive tool for energy savings in buildings, Renew.
behaviour, Adv. Build. Energy Res. 31 (2009) 271288. Energ. 85 (2016) 11061115, http://dx.doi.org/10.1016/j.renene.2015.07.074.
[29] R. Fioretti, A. Palla, L.G. Lanza, P. Principi, Green roof energy and water related [49] M. DOrazio, C. Di Perna, E. Di Giuseppe, Di Giuseppe Green roof yearly
performance in the Mediterranean climate, Build. Environ. 45 (2010) performance: a case study in a highly insulated building under temperate
18901904, http://dx.doi.org/10.1016/j.buildenv.2010.03.001. climate, Energy Build. 55 (2012) 439451, http://dx.doi.org/10.1016/j.
[30] P. Bevilacqua, J. Coma, G. Prez, C. Chocarro, A. Jurez, C. Sol, M. De Simone, enbuild.2012.09.009.
L.F. Cabeza, Plant cover and oristic composition effect on thermal behaviour [50] T. Theodosiou, D. Aravantinos, K. Tsikaloudaki, Thermal behaviour of a green
of extensive green roofs, Build. Environ. 92 (2015) 305316, http://dx.doi.org/ vs. a conventional roof under Mediterranean climate conditions, Int. J.
10.1016/j.buildenv.2015.04.026. Sustain. Energy 33 (2014) 227241, http://dx.doi.org/10.1080/14786451.
[31] K. Liu, Engineering performance of rooftop gardens through eld, in: RCI 18th 2013.772616.
International Convention and Trade Show, Tampa, Florida, 2003, pp. 115. [51] O. Schweitzer, E. Erell, Evaluation of the energy performance and irrigation
[32] C.J. Molineux, C.H. Fentiman, A.C. Gange, Characterising alternative recycled requirements of extensive green roofs in a water-scarce Mediterranean
waste materials for use as green roof growing media in the U.K, Ecol. Eng. 35 climate, Energy Build. 68 (2014) 2532, http://dx.doi.org/10.1016/j.enbuild.
(2009) 15071513, http://dx.doi.org/10.1016/j.ecoleng.2009.06.010. 2013.09.012.
[33] L. Rincn, J. Coma, G. Prez, A. Castell, D. Boer, L.F. Cabeza, Cabeza [52] F. Olivieri, C. Di Perna, M. DOrazio, L. Olivieri, J. Neila, Experimental
Environmental performance of recycled rubber as drainage layer in extensive measurements and numerical model for the summer performance assessment
green roofs. A comparative Life Cycle Assessment, Build. Environ. 74 (2014) of extensive green roofs in a Mediterranean coastal climate, Energy Build. 63
2230, http://dx.doi.org/10.1016/j.buildenv.2014.01.001. (2013) 114, http://dx.doi.org/10.1016/j.enbuild.2013.03.054.
[34] S.B. Mickovski, K. Buss, B.M. McKenzie, B. Skmener, Laboratory study on the [53] C.Y. Jim, L.L.H. Peng, Substrate moisture effect on water balance and thermal
potential use of recycled inert construction waste material in the substrate regime of a tropical extensive green roof, Ecol. Eng. 47 (2012) 923, http://dx.
mix for extensive green roofs, Ecol. Eng. 61 (2013) 706714, http://dx.doi.org/ doi.org/10.1016/j.ecoleng.2012.06.020.
10.1016/j.ecoleng.2013.02.015. [54] D. Morau, T. Libelle, F. Garde, Performance evaluation of green roof for
[35] R. Martens, B. Bass, S. Saiz Alcazar, Roofenvelope ratio impact on green roof thermal protection of buildings in Reunion island, Energy Procedia 14 (2012)
energy performance, Urban Ecosyst. 11 (2008) 399408, http://dx.doi.org/10. 10081016, http://dx.doi.org/10.1016/j.egypro.2011.12.1047.
1007/s11252-008-0053-z. [55] M.T. Simmons, B. Gardiner, S. Windhager, J. Tinsley, Green roofs are not
[36] D.J. Sailor, M. Hagos, An updated and expanded set of thermal property data created equal: the hydrologic and thermal performance of six different
for green roof growing media, Energy Build. 43 (2011) 22982303, http://dx. extensive green roofs and reective and non-reective roofs in a sub-tropical
doi.org/10.1016/j.enbuild.2011.05.014. climate, Urban Ecosyst. 11 (2008) 339348, http://dx.doi.org/10.1007/
[37] R.M. Lazzarin, F. Castellotti, F. Busato, Experimental measurements and s11252-008-0069-4.
numerical modelling of a green roof, Energy Build. 37 (2005) 12601267, [56] K.J. Kontoleon, D.K. Bikas, The effect of south walls outdoor absorption
http://dx.doi.org/10.1016/j.enbuild.2005.02.001. coefcient on time lag, decrement me viewed it as a cause of more energy
[38] P.C. Tabares-Velasco, J. Srebric, A heat transfer model for assessment of plant consumpt http://dx.doi.org/10.1016/j.enbuild.2006.11.006.
based roong systems in summer conditions, Build. Environ. 49 (2012) [57] G. Oliveti, N. Arcuri, D. Mazzeo, M. De Simone, A new parameter for the
310323, http://dx.doi.org/10.1016/j.buildenv.2011.07.019. dynamic analysis of building walls using the harmonic method, Int. J. Therm.
[39] C. Feng, Q. Meng, Y. Zhang, Theoretical and experimental analysis of the Sci. 88 (2015) 96109, http://dx.doi.org/10.1016/j.ijthermalsci.2014.09.006.
energy balance of extensive green roofs, Energy Build. 42 (2010) 959965, [58] D. Mazzeo, G. Oliveti, N. Arcuri, Inuence of internal and external boundary
http://dx.doi.org/10.1016/j.enbuild.2009.12.014. conditions on the decrement factor and time lag heat ux of building walls in
[40] E. Palomo, D. Barrio, Barrio Analysis of the green roofs cooling potential in steady periodic regime, Appl. Energ. 164 (2016) 509531, http://dx.doi.org/
buildings, Energy Build. 27 (1998) 179193, http://dx.doi.org/10.1016/S0378- 10.1016/j.apenergy.2015.11.076.
7788(97)00029-7. [59] G. Oliveti, N. Arcuri, S. Ruffolo, Experimental investigation on thermal
[41] S.E. Ouldboukhitine, R. Belarbi, I. Jaffal, A. Trabelsi, Assessment of green roof radiation exchange of horizontal outdoor surfaces, Build. Environ. 8 (2003)
thermal behavior: a coupled heat and mass transfer model, Build. Environ. 46 8389, http://dx.doi.org/10.1016/S0360-1323(02)00010-0.
(2011) 26242631, http://dx.doi.org/10.1016/j.buildenv.2011.06.021. [60] O. Kaska, R. Yumrutas, O. Arpa, Theoretical and experimental investigation of
[42] R. Djedjig, S.E. Ouldboukhitine, R. Belarbi, E. Bozonnet, Development and total equivalent temperature difference (TETD) values for building walls and
validation of a coupled heat and mass transfer model for green roofs, Int. at roofs in Turkey, Appl. Energ. 86 (2009) 737747, http://dx.doi.org/10.
Commun. Heat Mass Transfer 39 (2012) 752761, http://dx.doi.org/10.1016/j. 1016/j.apenergy.2008.09.010.
icheatmasstransfer.2012.03.024.
[43] A. Niachou, K. Papakonstantinou, M. Santamouris, A. Tsangrassoulis, G.
Mihalakakou, Analysis of the green roof thermal properties and investigation
of its energy performance, Energy Build. 33 (2001) 719729, http://dx.doi.
org/10.1016/S0378-7788(01)00062-7.

You might also like