http://dunia-listrik.blogspot.co.id/2013/04/short-circuit-calculation-using-mva.html
tgl 14/06/2017 jam 12.06
Maaf saya tulis dalam bahasa inggris, karena ini saya belajar dari literatur berbahasa inggris.
13.8KV Bus
Generator: 100MVA, X"d = 0.2
Transformer 2: 30 MVA, 13.8/6.6KV, 15% Z
6.6KV Bus
Transformer 3: 2MVA, 6.6KV/400V, 10% Z
Motor 1: 10 MVA (Lumped), 20% Z
400V Bus
Motor 2: 1000 KVA (Lumped), 20% Z
Motor 3: 600 KVA (Lumped), 10% Z
In the event of a short circuit, the sources of short circuit current are
1. Utility
2. Generators
3. Motors
Static loads such as heaters and lighting do not contribute to short circuit.
"EquivalentMVA" are:
Transformers and Motors
Generators
13.8KV Bus
Generator: MVAsc = 100 / 0.2 = 500 MVA
Transnformer 2: MVAsc = 30 / 0.15 = 200 MVA
6.6KV Bus
Transformer 3: MVAsc = 2 / 0.1 = 20 MVA
Motor 1: MVAsc = 10 / 0.2 = 50 MVA
400V Bus
Motor 2: MVAsc = 1 / 0.2 = 5 MVA
Motor 3: MVAsc = 0.6 / 0.1 = 6 MVA
At Transformer 3:
MVAsc @ 6.6KV = 167.51 + 50 = 217.51 MVA
MVAsc @ 400V = 1/ (1 / 217.51 + 1 / 20) = 18.31 MVA
At 400V Motors
Motor 3: MVAsc = 18.31 x 5 / ( 5 + 6 ) = 8.3 MVA
Motor 4: MVAsc = 18.31 x 6 / ( 5 + 6 ) = 9.98 MVA
The fault MVAsc @bus 400V = 18.31 + 5 + 6 = 29.31MVAsc
The three phase If = 29.31/(1.732*(0.4)) = 42.3 kA.
Examining the circuit in above, at the 400V Bus, on Transformer 3 contributes to the
zero sequence current.
For transformers, the negative sequence and zero sequence impedance are equal to the positive sequence
impedance.
Z1 = Z2 = Z0 or
MVA1 = MVA2 = MVA0
@bus 400V;
1 / MVAsc =1/3 (1 / MVAsc1 + 1 / MVAsc2 + 1 / MVAsc0)
1 / MVAsc = 1/3 (1 / 29.31 + 1 / 29.31 + 1 / 20 )
1/ MVAsc =