Water Chillers
Model CVGF
Water-Cooled Hermetic Centrifugal
Refrigeration Capacities From
400 to 1000 Tons (1400 kW-3510 kW)
50 and 60 Hz
Introduction 2
Features and Benefits 4
Application Considerations 9
General Data 10
Jobsite Connections 12
Controls 13
Physical Dimensions 17
Mechanical Specifications 19
Conversion Table 23
CTV-PRC001-GB 3
Features and
Benefits
CTV-PRC001-GB
4
Features and
Benefits
Microprocessor Controls with DynaView receives information from DynaView can be connected to the
and communicates information to the service tool using a standard 9-pin
CH530 other devices on the chillers male, 9-pin female RS-232 serial cable.
DynaView Operator Interface communications link. DynaView The serial connection is located at the
performs the Leaving Chilled Water bottom of the DynaView panel behind
DynaView is the unit-mounted control
Temperature and Limit Control a sliding door.
panel and also serves as the main
algorithms, arbitrating capacity against
processor and operator interface. It has
any operating limit against which the
a touch-sensitive overlay on a 1/4
chiller may find itself working.
VGA display.
Auto/Stop commands
DynaView presents information through
an intuitive, tabbed- navigation system. Status (all subsystems)
Alternate languages can be downloaded Setpoint adjustment
to the control panel, which can hold (daily user points)
English plus two other languages at
one time. 10 active diagnostics
Mode overrides
ASHRAE chiller log
Auto / Stop
Contrast Control
CTV-PRC001-GB 5
Features and
Benefits
CTV-PRC001-GB
6
Features and
Benefits
Feedforward Adaptive Building Automation and Time of day scheduling: allows the
end user to define the occupancy
Control Chiller Plant Control period, i.e. time of the day, holiday
The Tracer chiller controller allows the For a preprogrammable and flexible periods and exception schedules.
system designer to explore energy building automation and chiller plant Optimization of the start/stop time of
saving strategies and allows the control, Trane has developed the Tracer the installation: based on the
centrifugal chiller to be used in ways Summit. It can control the operation programmed schedule of occupancy
that were never thought possible. of the complete installation: chillers, and on the historical record of the
Feedforward Adaptive Control pumps, cooling towers, isolating behavior of the temperatures,
Feedforward is an open-loop, valves, air handlers and terminal units. calculates the optimal time of start
predictive control strategy designed to Trane can undertake full responsibility and stop of the installation to get the
anticipate and compensate for load for an optimized automation and best compromise between energy
changes. It uses evaporator entering- energy management for the entire savings and comfort of the occupants.
water temperature as an indication of chiller plant.
Soft loading: the soft loading function
load change. This allows the controller The main functions are: minimizes the number of chillers that
to respond faster and maintain stable
Chiller sequencing: equalizes the are operated to satisfy the building
leaving-water temperatures.
number of running hours of the morning pull down, thus preventing
Soft Loading chillers. Different control strategies are an overshoot of the actual capacity
The chiller controller uses soft loading available depending on the required. Unnecessary starts are
except during manual operation. Large configuration of the installation. avoided and the peak current demand
adjustments due to load or setpoint is lowered.
Control of the auxiliaries: includes
changes are made gradually,
input/output modules to control the
preventing the compressor from
operation of the various auxiliary
cycling unnecessarily. It does this by
equipments (water pumps, valves,
internally filtering the setpoints to avoid
cooling towers, etc.)
reaching the differential-to-stop or the
current limit. Soft loading applies to the
leaving chilled-water temperature and
current-limit setpoints.
Multi-Objective Limit Arbitration
There are many objectives that the
controller must meet, but it cannot
satisfy more than one objective at a
time. Typically, the controllers primary
objective is to maintain the evaporator
leaving-water temperature.
Whenever the controller senses that it
can no longer meet its primary
objective without triggering a
protective shutdown, it focuses on the
most critical secondary objective.
When the secondary objective is no
longer critical, the controller reverts to
its primary objective.
Fast Restart
While the inlet guide vanes are closing,
the controller will allow the centrifugal
chiller to restart and going to a
postlube operational mode. If the
chiller shuts down on a nonlatching
diagnostic, the diagnostic has 3060
seconds to clear itself and initiate a fast
restart. This includes momentary
power losses.
CTV-PRC001-GB 7
Features and
Benefits
CTV-PRC001-GB
8
Features and
Benefits
CTV-PRC001-GB 9
Application
Considerations
CTV-PRC001-GB
1 0
General
Data
Remote Mounted Wye-Delta, Solid-State Inside the Delta, *Across-the-line, *Primary Reactor, *Auto Transformer
*Medium Voltage (3300, 4160, 6600) Starter Types - Full Voltage (X-Line), Primary Reactor, Auto Transformer
CTV-PRC001-GB 1 1
General 50 and 60 Hz SI Units
Data and (English Units)
CTV-PRC001-GB
1 2
Jobsite
Connections
CTV-PRC001-GB 1 3
Controls Standard Features
CTV-PRC001-GB
1 4
Optional
Controls Features
Extended Operation Package condenser pressure rises too high, the maintain the setpoint. Heating is the
controllers Adaptive Control logic primary mission and cooling is a waste
Select the extended-operation package limits the loading of the chiller to product or a secondary mission.
for chillers that require external, hot prevent the chiller from shutting down This technique provides application
water control, and/or base-loading on a safety limit. These limits may flexibility, especially in multiple-chiller
capabilities. This package also includes prevent the chiller from reaching the plants in conjunction with undersized
a 4-20 mA or 0-10 Vdc analog input for load requested by the Base Loading heating plants.
a refrigerant monitor. signal.
External base-loading control input The chiller needs only one condenser
External base-loading setpoint An alternative and less radical for hot-water control, whereas Heat
External hot-water control input approach to Base Loading indirectly Recovery uses a secondary condenser.
Refrigerant monitor input controls chiller capacity. Artificially Refrigerant Monitor
load the chiller by setting the chilled- The Extended Operation package
Base-Loading Control water setpoint lower than it is capable
This feature allows an external allows for a refrigerant monitor to send
of achieving. Then, modify the chillers a 4-20 mA signal to the DynaView
controller to directly modulate the load by adjusting the current-limit
capacity of the chiller. It is typically used display. It can be calibrated to
setpoint. This approach provides correspond to either 0-100 ppm or 0-
in applications where virtually infinite greater safety and control stability
sources of evaporator load and 1,000 ppm concentration levels.
because it leaves the chilled-water The concentration level is displayed at
condenser capacity are available and it temperature-control logic in effect.
is desirable to control the loading of the DynaView, but the chiller will not take
The chilled-water temperature control any action based on the input from the
chiller. Two examples are industrial responds more quickly to dramatic
process applications and cogeneration refrigerant monitor.
system changes and limits chiller
plants. Industrial process applications loading prior to reaching an Adaptive Alternatively, a refrigerant monitor can
might use this feature to impose a Control limit. be connected to Tracer Summit, which
specific load on the facilitys electrical has the ability to increase ventilation in
system. Cogeneration plants might use Hot-Water Control the equipment room in response to
this feature to balance the systems This feature allows an external high refrigerant concentrations.
heating, cooling, and electrical controller to enable/disable and
generation. modulate the hot-water control mode.
Occasionally, centrifugal chillers are
All chiller safeties and Adaptive Control used to provide heating as a primary
functions are in full effect when Base mission. In this case the external
Loading is enabled. If the chiller controller or operator would select a
approaches full current, the evaporator hot-water temperature setpoint and the
temperature drops too low, or the chiller capacity would be modulated to
CTV-PRC001-GB 1 5
Standard
Controls Protections
CTV-PRC001-GB
1 6
Standard
Controls Protections
Momentary Power Loss and The chiller may shut down under the Surge Detection Protection
Distribution Fault Protection following conditions: Surge detection is based on current
Three-phase momentary power loss Line-voltage sags of 1.5 or more line fluctuations in one of three phases. The
(MPL) detection gives the chiller cycles for voltage dips of 30 percent default detection criterion is two
improved performance through many or more occurrences of RMS current change of
different power anomalies. MPLs of 2.5 30 percent within 0.8 seconds in 60 + 10
cycles or longer will be detected and Control-voltage sags of 3 or more line percent seconds. With the Tracer
cause the unit to shut down. The unit cycles for voltage dips of 40 percent chiller controller, the detection criterion
will be disconnected from the line or more is adjustable.
within 6 line cycles of detection. If Third-order or higher harmonic Overvoltage and Undervoltage
enabled, MPL protection will be active content on the line Protection
any time the compressor is running. The unit will be shut down with an
MPL is not active on reduced-voltage Current Overload Protection
The control panel will monitor the automatic reset if the line voltage is
starters from the initial start signal below or above 10 percent of nominal.
through transition. The MPL diagnostic current drawn by each line of the motor
is an automatic reset diagnostic. MPL and shut the chiller off when the Must trip = 15 percent of nominal.
protection can be disabled in TechView. highest of the three line currents
exceeds the trip curve. A manual reset Time to trip = minimum of 1 minute, 10
An MPL has occurred when the motor diagnostic describing the failure will be seconds and maximum of 5 minutes,
no longer consumes power. An MPL displayed. The current overload 20 seconds. Overvoltage and
may be caused by any drop or sag in protection does not prohibit the chiller undervoltage protection can be
the voltage that results in a change in from reaching its full-load amperage. disabled using TechView.
the direction of power flow. Different Power Factor and kW Measurement
operating conditions, motor loads, The chiller protects itself from damage
due to current overload during starting Three-phase measurement of kW and
motor size, inlet guide vane (IGV) unadjusted power factor yields higher
position, etc. may result in different and running modes, but is allowed to
reach full-load amps. accuracy during power imbalance
levels at which this may occur. It is conditions than with CH530.
difficult to define an exact voltage sag High Motor-Winding Temperature
or voltage level at which a particular Protection Short-Cycling Protection
motor will no longer consume power, This function monitors the motor Short-cycling protection is based on a
but we are able to make some general temperature and terminates chiller start-to-start time. This method uses a
statements concerning MPL protection: operation when the temperature is straight start-to-start timer to determine
excessive. The controller monitors each when to allow the next start.
The chiller will remain running under
the following conditions: of the three winding-temperature A Restart Inhibit Start-to-Start Time
sensors any time the controller is setpoint is used to set the desired start-
Line-voltage sag of 1.5 line cycles or powered up, and displays each of the to-start time. There is no free start on
less for any voltage magnitude sag temperatures at the service menu. a power up at DynaView. The real-time
Control-voltage sags of less than 3 Immediately prior to start, and while clock is used to determine when the
line cycles for any magnitude sag running, the controller will generate a next start will be allowed, based on the
latching diagnostic if the winding previous start.
Control-voltage sags of 40 percent or temperature exceeds 265 5F
less for any amount of time When the start is inhibited by the
(129.4 2.8C). restart-inhibit function, the time
Second-order or lower harmonic remaining is displayed along with the
content on the line restart-inhibit mode.
CTV-PRC001-GB 1 7
Physical 50 and 60 Hz SI
Dimensions (English Units)
Figure PD-1 Model CVGF Cooling Only Figure PD-2 Model CVGF Cooling Only Without Unit
With Unit Mounted Starter Mounted Starter (for Remote Mounted Starter)
HEIGHT HEIGHT
WIDTH WIDTH
457 mm (18')
RECOMMENDED
CLEARANCE
LENGTH
CTV-PRC001-GB
1 8
Physical
Dimensions
CTV-PRC001-GB 1 9
Mechanical
Specifications
The Trane CVGF packaged centrifugal Motor with steel tube sheets welded to each
water chillers using HFC-134a The motor is a hermetic, liquid end. Intermediate tube support sheets
refrigerant consist of a hermetic two refrigerant cooled, two-pole, low-slip positioned along the shell axis prevent
stage, gear-drive centrifugal squirrel cage induction motor. A radial relative tube motion. Individually
compressor, evaporator, condenser, hydrodynamic bearing and duplex replaceable externally finned and
interstage economizer, unit-mounted angular contact ball bearings support internally grooved 19 mm ( in.) and
microprocessor based control panel the rotor assembly. Winding- 25.4 mm (1.0 in.) nominal diameter
and compressor motor starter. The embedded sensors provide positive seamless copper tubes are
chiller is completely factory assembled. thermal protection. mechanically expanded into tube
sheets.
Compressor Lubrication System
Two-stage centrifugal compressor with The lubrication system consists of an Two or three pass water boxes rated at
high-strength aluminum alloy fully internal oil sump with heaters, positive 10.5 bar (150 psi) is standard. Grooved
shrouded impellers. The impellers are displacement oil pump, brazed plate pipe stubs for Victaulic couplings are
tested at 25 percent over design condenser-cooled oil cooler, and oil standard; flanged connections are
operating speed. The rotating distillation/return line. optionally available. The waterside is
assembly is dynamically balanced for hydrostatically tested at 1.5 times
Economizer/Orifice
vibration of less than 5.1 mm/s (0.2 ips The economizer consists of a carbon maximum working pressure.
peak velocities) at nominal operating steel shell with internal components Liquid refrigerant is admitted to the
speeds. The control system affords designed to prevent liquid carryover to evaporator through a single calibrated
100 - 20 percent capacity modulation the compressor. Liquid refrigerant is orifice (no moving parts) which
by electrically actuated guide vanes admitted through a single calibrated maintains a pressure differential
upstream of each impeller. orifice (no moving parts) which between the economizer and the
Drive Train maintains a pressure differential evaporator.
The drive train consists of helical bull between condenser and economizer. Condenser
and pinion gears. Gear tooth surfaces Evaporator The condenser is designed, tested and
are case hardened and precision The evaporator is designed, tested and stamped in accordance with the ASME
ground. The one-piece impeller shaft is stamped in accordance with ASME Boiler and Pressure Vessel Code or PED
supported by hydrodynamic thrust and Boiler and Pressure Vessel Code or PED (European Code) for a refrigerant side
radial bearings. (European Code) for refrigerant side working pressure of 15.2 bars (220
working pressure of 15.2 bars (220 psig). It consists of a carbon steel shell
psig). It consists of a carbon steel shell with steel tube sheets welded to each
end. Individually replaceable, externally
finned and internally grooved 19 mm
( in.) and 25.4 mm (1.0 in.) nominal
diameter seamless copper tubes are
mechanically expanded into the tube
sheets.
CTV-PRC001-GB
2 0
Mechanical
Specifications
Welded steel two pass water boxes are The microcomputer control system The service tool provides advanced
bolted to the tube sheets. Water processes the leaving evaporator fluid troubleshooting and access to
connections are steel pipe stubs temperature sensor signal to satisfy the sophisticated configuration settings not
grooved for Victaulic couplings; flanged system requirements across the entire needed during operation of the chiller.
connections are optionally available. load range. Any PC that meets the installation
Maximum waterside working pressure The controller will load and unload the requirements may be loaded with the
of 10.5 bars (150 psi) is standard. The chiller via control of the stepper- motor/ service tool software via download
waterside is hydrostatically tested at 1.5 actuator which drives the inlet guide from www.trane.com.
times maximum working pressure. vanes open and closed. The load range Unit mounted display is capable of
Unit Control Panel can be limited either by a control limit displaying chiller parameters in IP or SI
The Tracer CH.530 is a function such as motor current, low units, and language in English and any
microprocessor-based chiller controller evaporator temperature or high 2 downloadable and/or locally
that provides complete stand alone condenser pressure limit or by an inlet translated languages.
system control for water-cooled guide vane limit (whichever comes Compressor Motor Starter
centrifugals. It is a factory-mounted first). It will also control the evaporator Unit-mounted starters can either be a
packaged and tested on the CVGF unit. and condenser pumps to insure proper star-delta or solid state in NEMA1 type
All controls necessary for the safe and chiller operation. enclosure wired to compressor motor
reliable operation of the chiller are Status and 10 active diagnostics are up to 952 RLA at 380~480 volts (star-
provided including oil management, communicated to the operator via delta), 900 RLA at 481~600 Volts
interface to the starter, and three phase display with a tabbed navigation (star-delta), and 1472 RLA at 380~600
motor overload protection. It also system. Setpoints are entered through volts (solid-state).
includes comprehensive status and the touch-sensitive screen. Countdown
diagnostic monitoring controls. A Remote-mounted starters can either be
timer displays remaining time(s) during star-delta or solid state for low voltage.
control power transformer included in wait states and time out periods.
the starter panel powers the control Across-the-line, primary reactor, or
Nonvolatile memory saves unit set-up auto transformer for medium and high
system. information during power loss without voltage. All in a NEMA 1 type enclosure
The microprocessor controller is the need for batteries. Password up to 1402 RLA at 380~600 volts (star-
compatible with reduced voltage or full protection is provided to secure the delta), 1472 RLA at 380~600 volts
voltage electro-mechanical starters, operator interface. PC-based service (solid-state), and 360 RLA at 3300~6600
and solid state starter. Starter for tool software displays the last 60 active volts (x-line, primary reactor, and auto-
Europe with the CE mark is available. or 60 historic diagnostics, indicating the transformer).
time, date of occurrence, and system
parameters at the time of the diagnostic.
CTV-PRC001-GB 2 1
Mechanical
Specifications
CTV-PRC001-GB
2 2
Conversion
Table
To Convert From: To: Mulgpiy By: To Convert From: To: Multiply By:
Length Energy and Power and Capaclty
Feet (ft) meters (m) 0.30481 British Thermal Units (BTUH) KilowattIkW) 0.000293
Inches (In) millimeters (mm) 25.4 British Thermal Units (BTU) KCalorie (Kcal) 0.252
Arca Tons (refrig. effect) Kilowatt (refrig. effect) 3.516
Square Feet (ft2) square meters (m2) 0.093 Tons (refrig. effect) Kilocalories per hour (Kcal/hr) 3024
Square Inches (In2) square millimeters (mm2) 645.2 Horsepower Kilowatt(kW) 0.7457
Volume Pressure
Cubic Feet (ft3) Cubic meters (m2) 0.0283 Feet of water (ftH2O) Pascals (PA) 2990
Cubic Inches (In3) Cubic mm (mm3) 16387 Inches of water (inH2O) Pascals (PA) 249
Gallons (gal) litres (l) 3.785 Pounds per square inch (PSI) Pascals (PA) 689
Gallons (gal) cubic meters (m3) 0.003785 PSI Bar or KG/CM 2
6.895 x 10-2
Flow Weight
Cubic feet/min (cfm) cubic meters/second (m3/s) 0.000472 Ounches (oz) Kilograms (kg) 0.02835
Cubic Feet/min (cfm) cubic meters/hr (m3/hr) 1.69884 Pounds (lbs) Kilograms (Kg) 0.4536
Gallons/minute (GPM) cubic meters/hr (m3/hr) 0.2271 Fouling factors for heat exchanges
2 2
Gallons/minute (GPM) Iitres/second (Vs) 0.06308 0.00075 ft F hr/BTU = 0.132 m K/kM
Velocrty 0.00025 ft2 F hr/BTU = 0.044 m2 K/kW
Feet per minute (ft/m) meters per second (m/s) 0.00508
Feet per second (ft/s) meters per second (m/s) 0.3048
CTV-PRC001-GB 2 3
Literature Order Number CTV-PRC001-GB
File Number PL-RF-CTV-000-PRC001-0904
Supersedes CTV-PRC001-GB 103
Literature Stocking Location Europe
Trane has a policy of continuous product and product data improvement and reserves the right to change
design and specifications without notice. Only qualified technicians should perform the installation and
www.trane.com servicing of equipment referred to in this publication.