Professional Documents
Culture Documents
Water Chillers
Model CVGF
Water-Cooled Hermetic Centrifugal
Refrigeration Capacities From
400 to 1000 Tons (1400 kW-3510 kW)
50 and 60 Hz
Introduction 2
Features and Benefits 4
General Data 7
Dimensional Data 10
Mechanical Specifications 14
3
CTV-PRC001-EN
Features and
Benefits
CTV-PRC001-EN
4
Features and
Benefits
CTV-PRC001-EN 5
Features and
Benefits
Chiller Plant Control Several communication capabilities are Remote communication through a
provided: modem; as an option, a modem can
For chilled water plants, Trane has Local, through a PC workstation be connected to communicate the
developed the Tracer Summit. It can keyboard; the Tracer Summit can be plant operation parameters through
control the operation of the complete programmed to send messages to voice grade phone lines
installation: chillers, pumps, cooling the workstation in the following cases
towers, isolating valves, etc. It is a The remote station is a PC workstation,
- Analog parameter exceeding a a modem and software to display the
programmable module, configured programmed value
according to the requirements of the remote plant parameters.
- Maintenance warning
end user. Trane can undertake full - Component failure alarm
responsibility for an optimized - Critical alarm messages; in this
automation and energy management latter case, the message is
for the entire chiller plant. displayed until the operator
The main functions are: acknowledges the receipt of the
Chiller sequencing: equalizes the information; from the remote
number of running hours of the station it is also possible to access
chillers; different control strategies and modify the chiller plants
are available depending on the control parameters
configuration of the installation
Control of the auxiliaries: includes
input/output modules to control the
operation of the various auxiliary
equipments (water pumps, valves,
cooling towers, etc.)
Time of day scheduling: allows the
end user to define the occupancy
period, i.e. time of the day, holiday
periods and exception schedules
Optimization of the start/stop time of
the installation: based on the
programmed schedule of occupancy
and on the historical record of the
behavior of the temperatures,
calculates the optimal time of start
and stop of the installation to get the
best compromise between energy
savings and comfort of the occupants
Soft loading: the soft loading function
minimizes the number of chillers that
are operated to satisfy the building
morning pull down, thus preventing
an overshoot of the actual capacity
required; unnecessary starts are
avoided and the peak current
demand is lowered
CTV-PRC001-EN
6
General
Data
CTV-PRC001-EN 7
General 50 and 60 Hz
Data English Units
CTV-PRC001-EN
8
General 50 and 60 Hz
Data SI Units
CTV-PRC001-EN 9
Dimensional 50 and 60 Hz
Data English Units
Figure DD-1 Model CVGF Cooling Only With Unit Mounted Starter
CTV-PRC001-EN
10
Dimensional 50 and 60 Hz
Data English Units
Figure DD-2 Model CVGF Cooling Only Without Unit Mounted Starter
(For Remote Mounted Starter)
CTV-PRC001-EN 11
Dimensional 50 and 60 Hz
Data SI Units
Figure DD-3 Model CVGF Cooling Only With Unit Mounted Starter
CTV-PRC001-EN
12
Dimensional 50 and 60 Hz
Data SI Units
Figure DD-4 Model CVGF Cooling Only Without Unit Mounted Starter
(For Remote Mounted Starter)
CTV-PRC001-EN 13
Mechanical
Specifications
CTV-PRC001-EN
14
Mechanical
Specifications
Unit Control Panel The display also provides over 20 Run Test
The unit mounted microprocessor reports that are organized into four Prior to shipment, all chillers receive
based control panel is factory installed groupings: Custom Report, Chiller post-assembly pressure and leak tests
and tested on the CVGF unit. All Report, Refrigerant Report, and followed by a run test to verify
controls necessary for the safe and Compressor Report. Each report performance and to calibrate operating
reliable operation of the chiller are contains data that is accessed by and safety controls.
provided including oil management scrolling through the menu items. Each Isolation Pads
and interface to the starter. A control grouping will have a heading that Molded neoprene isolation pads are
power transformer included in the describes the type of data in that supplied with each chiller for
starter panel powers the control grouping. placement under all support points.
system. The microcomputer control All necessary settings and setpoints Spring isolators are optionally
system processes the leaving are programmed into the available.
evaporator fluid temperature sensor microprocessor controller via the
signal to satisfy the system Refrigerant and Oil Charge
keypad of the operator interface. The A full charge of refrigerant and oil is
requirements across the entire load controller is capable of receiving
range. supplied with each unit. The oil ships in
signals from a variety of control the units sump and the refrigerant
The microprocessor controller is sources and of being programmed at ships directly to the jobsite from
compatible with reduced voltage or full the keypad as to which control source refrigerant suppliers.
voltage electromechanical starters and has priority. These control sources are
may be factory unit-mounted or field not mutually exclusive, any Painting
remote mounted. A solid-state starter is combination of control sources can All painted CVGF surfaces are coated
available only as unit mounted (not coexist simultaneously. The control with two coats of air-dry beige primer-
available for Europe). panel will then set the active setpoints finisher prior to shipment.
The controller will load and unload the according to the priority signal. Insulation
chiller via control of the stepper-motor/ Compressor Motor Starter The chiller can be ordered with or
actuator which drives the inlet guide Unit-mounted starters can either be a without factory applied insulation.
vanes open and closed. The load range star-delta or solid-state in a NEMA 1 Factory supplied insulation is applied
can be limited either by a control limit enclosure wired to compressor motor to all low temperature surfaces
function such as motor current, low up to 1024 RLA (star-delta) and 1039 including the evaporator, water boxes
evaporator temperature or high RLA (solid-state). Unit mounted and suction elbow. Insulation material
condenser pressure limit or by an inlet starters for Europe will be star-delta is 19 mm ( in.) Armaflex II or equal
guide vane limit (whichever comes only in a IP54 enclosure wired to the (thermal conductivity = 0.04 W/mC;
first). It will also control the evaporator compressor motor up to 1024 RLA. 0.3 Btuin/hftF). The oil cooling lines
and condenser pumps to insure proper A steel panel door with optional are insulated with 9.5 mm (3/8 in.) and
chiller operation. mechanical interlock disconnects the 13 mm ( in.) insulation respectively.
Over 100 diagnostic checks are made system when the door is opened. The Rigging
on a continuous basis. When a fault is panel also contains three-phase Evaporator and condenser tube sheets
detected, the display indicates the fault, current transformer for overload provide rigging support points. A
the type of reset required, the time and protection, and an oil pump starter rigging diagram is affixed to the chiller.
date the diagnostic occurred, the mode with overloads. The starter is factory
mounted and wired to the compressor Quality
in which the machine was operating at The La Crosse chiller manufacturing
the time of the diagnostic, and a help motor and the control panel. The CVGF
chiller/starter assembly is factory facility is ISO 9001.
message. A diagnostic history will
display the last 20 diagnostics with the tested.
time and date of their occurrence. Optional remote mounted
electromechanical starters are
available.
CTV-PRC001-EN 15
Literature Order Number CTV-PRC001-EN
File Number PL-RF-CTV-000-PRC001-700
Supersedes CTV-PRC001-EN 1/00