You are on page 1of 7

See

discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/260705477

Thermal Sizing and Electric Shock Calculations


for Equipment Grounding Conductors

Article in IEEE Transactions on Industry Applications July 2013


DOI: 10.1109/TIA.2013.2258133

CITATIONS READS

3 97

3 authors, including:

Haijun Liu Massimo Mitolo


ETAP Engineering Systems Inc. (ESI)
101 PUBLICATIONS 1,009 CITATIONS 100 PUBLICATIONS 250 CITATIONS

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Currents flowing through the human body: the numerical viewpoint View project

Electrical Safety in Arc Welding Processes. View project

All content following this page was uploaded by Massimo Mitolo on 05 November 2015.

The user has requested enhancement of the downloaded file. All in-text references underlined in blue are added to the original document
and are linked to publications on ResearchGate, letting you access and read them immediately.
1720 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 49, NO. 4, JULY/AUGUST 2013

Thermal Sizing and Electric Shock Calculations


for Equipment Grounding Conductors
Haijun Liu, Senior Member, IEEE, Massimo Mitolo, Senior Member, IEEE, and Farrokh Shokooh, Fellow, IEEE

AbstractThis paper presents the thermal sizing procedure


of equipment grounding (protective) conductors and the electric
shock calculations as per the standard 60364 of the International
Electrotechnical Committee (IEC) that is used worldwide. The
application of IEC standards in the design of low-voltage systems
(i.e., not exceeding 1 kV) governed by the National Electrical Code
(NEC) and the American National Standards Institute (ANSI),
which are adopted in the U.S., is discussed and proposed in this
paper. The authors propose an interpretation of the NEC installa-
tions in light of the earthing definitions included in the IEC realm.
On this premises, IEC sizing criteria are applied to typical North
American installations to prove their general applicability and
their legitimacy to NEC/ANSI-based electrical systems. Examples
are also presented for both thermal sizing and electric shock
calculation of equipment grounding conductors.
Index TermsElectric shock, equipment grounding conductors
(EGCs), grounding, protective conductors (PEs), residual current
devices (RCDs), safety, thermal sizing.

I. I NTRODUCTION Fig. 1. Comparison between minimum sizes of PEs (NEC versus IEC) as a
function of standard trip ratings of overcurrent devices.

T HE TERM equipment grounding refers to the interconnec-


tion and grounding of the nonelectrical metallic elements
of system [1]. An equipment grounding conductor (EGC), In [1, Tables 2-2 and 2-5], shock voltage exposure is provided
which is also referred to as a protective conductor (PE) in the as a function of the spacing between the EGC and the phase
International Electrotechnical Committee (IEC) realm, must be conductor, of given sizes, at a presumed ground fault current.
run with circuit conductors inside the metal raceway or inside No detailed thermal sizing and electric shock calculation re-
the multiple-conductor cable jacket [2]. The grounding conduc- quirement are presented in this standard.
tor must function to conduct the available ground fault current In reference to the EGC sizing, it is stated in
that might be imposed on it, during the clearing time of protec- [2, Sec. 250.122A] that EGCs of the wire type shall not
tive devices, without excessive temperature rise or arcing [1]. be smaller than that shown in Table 250.122, but in no case
Electric shock injuries result from contact with metallic shall be they required to be larger than the circuit conductors
components that are normally not live but are unintentionally supplying the equipment. National Electrical Code (NEC)
energized. Effective equipment grounding practices, in con- Table 250.122 gives the minimum size of EGCs based on
junction with proper protective devices, can minimize these trip settings of protective devices. There is a warning note at
personal injuries. The impedance of the grounding conductor the bottom of Table 250.122, which calls attention to the fact
must be low enough to accept the available line-to-ground fault that the tabled minimum cross-sectional areas may not fulfill
current without creating a hazardous voltage drop [1], which all the code requirements; therefore, the size may need to be
appears as a perspective touch voltage at the far end of the increased. However, no detailed thermal sizing and electric
grounding conductor, in correspondence with the equipment. shock calculation requirement are presented in [2] either.
In [3], the tabular method of IEC standards is shown, which
yields larger cross-sectional areas S of PE than [2] in corre-
Manuscript received June 22, 2012; revised October 14, 2012; accepted spondence with the same values of trip settings of protective
November 30, 2012. Date of publication April 15, 2013; date of current version
July 15, 2013. Paper 2012-PSEC-251.R1, presented at the 2012 IEEE Industry devices. Fig. 1 provides a comparative chart for calculated
Applications Society Annual Meeting, Las Vegas, NV, USA, October 711, values of SPE (as per the IEC methodology detailed in the suc-
and approved for publication in the IEEE T RANSACTIONS ON I NDUSTRY ceeding sections) and of SEGC (as per the NEC Table 250.122)
A PPLICATIONS by the Power Systems Protection Committee of the IEEE
Industry Applications Society. as a function of standard trip ratings of overcurrent devices,
The authors are with Operation Technology, Inc., Irvine, CA 92618 USA ranging between 15 and 200 A. To determine the ampacities
(e-mail: haijunl@etap.com; mitolo@ieee.org; farrokh.shokooh@etap.com). of the line conductors per IEC and, hence, the size of PEs, it
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. has been assumed with a polyvinyl-chloride (PVC)-insulated
Digital Object Identifier 10.1109/TIA.2013.2258133 phase conductor or a single-core cable, in a conduit on a

0093-9994/$31.00 2013 IEEE


LIU et al.: THERMAL SIZING AND ELECTRIC SHOCK CALCULATIONS FOR EGCs 1721

wooden or masonry wall, and in the presence of only two loaded TABLE I
VALUES OF PARAMETERS FOR D IFFERENT
conductors in the conduit. C ONDUCTIVE M ATERIALS FOR PE/EGC S
In [4], in contrast with [1] and [2], the details of a thermal
sizing calculation for protective/EGCs is given. This paper
will explore the possibility of using such calculation to size
EGCs in NEC [American National Standards Institute (ANSI)]-
based installations. This paper investigates how the calculation
presented in [5] can be adapted to the given electrical systems.
Specifically, [5] provides a detailed guide for the calculation
of the line-to-ground fault-loop impedance. Such impedance
is crucial in the assessment of the magnitude of the actual
ground fault current, which must be of sufficient magnitude to
trip protective devices within a safe time, thereby preventing
electric shock hazard.
TABLE II
M AXIMUM P ERMISSIBLE D ISCONNECTION T IME
II. T HERMAL S IZING OF EGC S
In [4], a methodology to thermally size PEs is given, which
can be also used for EGCs calculation in NEC/ANSI-based
installations. In [4], methods that are both based on tables and
equations are given. The method from theoretical equations is
the main focus of this paper.
The cross-sectional areas of PEs (also referred to EGCs)
must not be less than the value determined by the following
formula (in adiabatic conditions that are applicable for discon-
nection times not exceeding 5 s) [4]:
IG 
S= tf (1) in a cable, bare, etc.) [6]. The PEs final temperatures, which
k
are the maximum temperatures that its insulation can withstand,
where slightly differ among standards (e.g., in [7][11]).
S cross-sectional area (in mm2 ); Note that, if (1) produces nonstandard cross sections, the
IG rms value (in amperes) of the prospective fault current for succeeding higher trade size must be selected for the PE.
a fault of negligible impedance that can flow through the Equations (1) and (2) are installation independent and can be
protective device; directly applied to NEC/ANSI installations.
tf clearing time (in seconds) of the protective device;
k factor dependent on the conductive material of the PE, III. E LECTRIC S HOCK C ALCULATIONS
its insulation, and other parts, and the initial and the final IN L OW-VOLTAGE I NSTALLATIONS
temperatures.
IEC specifies different earthing types (TNC, TNS, TNC
Factor k can be determined from the following formula:
S, TT, and IT) based on system grounding and equipment
  
c( + 20 ) M 0 grounding [3], [5], for which electric shock calculations vary.
k= ln 1 + (2)
20 + 0
A. TNCS Earthing System
where TNCS earthing systems are solidly grounded power sys-
c volumetric heat capacity of the PE conductive material tems, in which the EGC is directly connected to the grounded
(in J/ C mm3 ) at 20 C; point of the source (e.g., neutral point); in part of the system,
reciprocal of the temperature coefficient of resistivity at the PE/EGC and the neutral wire are combined in a single
0 C for the conductor (in C); conductor, defined as the PEN. A diagrammatic representation
20 electrical resistivity of conductor material at 20 C (in of a TNCS system is shown in Fig. 1.
mm); RN is the ground grid/ground electrode resistance of the sup-
0 temperature (in C) of the PE/EGC at the inception of the ply source (i.e., it is not an intentional resistance). The acronym
fault; ECP, i.e., exposed conductive part, identifies the conductive
M maximum temperature that the PE/EGC insulation can enclosures of electrical equipment. The dashed line represents
withstand. a fault between a phase conductor and the enclosure.
Table I lists the values of parameters for different conductive In [5], the maximum permissible disconnection time for final
materials of PEs to be used in the calculation of k. ac circuits not exceeding 32 A is listed, as shown in Table II for
The PE initial temperature varies according to its arrange- TT and TN systems.
ment in raceways (e.g., bunched with other cables, incorporated U0 indicates the system nominal voltage to earth.
1722 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 49, NO. 4, JULY/AUGUST 2013

Fig. 2. Diagrammatic representation of TNCS systems.

It is important to note that the given disconnection times have


been established by conventionally assuming that phase and PE
conductors have the same cross-sectional area (i.e., Sph = SPE ,
Fig. 3. IT systems.
when Sph 16 mm2 , in accordance to [5]); when SPE < Sph ,
the conventional disconnection time may not be safe.
In TN systems, a disconnection time not exceeding 5 s B. IT Earthing System
is permitted for circuit exceeding 32 A and for distribution IT earthing systems are characterized by a source with an
circuits, regardless of the possible values of the touch voltage; ungrounded neutral point or connected to earth through suffi-
however, fault potentials appearing on distribution circuits must ciently high impedance [e.g., high-resistance neutral grounding
not affect any final circuit they supply. resistor (HRG)] (see Fig. 3).
Fig. 2 can be a general representation of an NEC-based The enclosures of electrical equipment, however, must be
installation in buildings: The PEN splits into the neutral con- individually or, in group, collectively grounded through a local
ductor and the PE/EGC at the service entrance of the unit due ground electrode system of resistance that is low enough to
to the main bonding jumper. limit touch voltages to values not exceeding 50 V.
The four steps for the electric shock calculation, leading to a In the given safe conditions, protective devices will not
safe EGC size, for the system in Fig. 2 are as follows. have to trip in the event of a single fault within an ECP or
1) In correspondence with the maximum disconnection time earth, thereby guaranteeing the continuity of the service and yet
provided in Table II (or 5 s for distribution circuits), preserving the safety of people.
the minimum allowed line-to-ground fault current Ia to Ungrounded systems are prone to overvoltages and to the
clear the fault is obtained from the upstream protective occurrence of resonant faults to ground, which can severely
devices timecurrent curve (TCC) (e.g., a fuse). If the damage the system and set up fires. For this reason, high-
protective device is a residual current device (RCD), Ia resistance grounded systems are preferable as they offer the
is a rated residual current (e.g., 30 mA); in this case, the same benefits of the continuity of the service, without the
RCD is in compliance with the permissible disconnecting aforementioned risks.
times of Table II, as long as the prospective residual An example of an IT system, whose equipment enclosures
fault currents are at least five times higher than the rated are collectively grounded, as excerpted from [1], is the mine
residual operating current. installation shown in Fig. 4.
2) The maximum allowed fault-loop impedance ZM is cal- In [13], a high-resistance grounded system for substations
culated as U0 /Ia . supplying heavy portable electric machinery is mandated, such
3) The actual fault-loop impedance Z is obtained by adding as those found in surface mining [14], which is adopted in
the following: the U.S.
impedance of the faulty phase conductor; The two steps for the electric shock calculation for the given
impedance of the source (e.g., a Delta/Wye solidly ITcollective system are as follows.
grounded transformer and a primary network); 1) At the occurrence of the first ground fault, safety against
impedance of the EGC (PE); indirect contact is guaranteed if the prospective touch
impedance of the PEN conductor. voltage does not exceed 50 V [5]; thus, the following
4) If Z ZM , the EGC is acceptable from the electric conditions must be fulfilled:
shock point of view. Touch voltages on faulty enclosures,
in fact, will persist for a harmless period of time; other- ZPE IG 50 V (3)
wise, steps 3 and 4 must be repeated with a larger trade
size of the EGC. where ZPE is the impedance (in ohms) of the PE/EGC
Alternatively, RCDs, which guarantee a much faster clearing connecting the faulted ECP to the frame ground of the
time in correspondence with the same ground fault current, may substation, and IG is the magnitude (in amperes) of the
be employed. first fault-to-ground current.
LIU et al.: THERMAL SIZING AND ELECTRIC SHOCK CALCULATIONS FOR EGCs 1723

Fig. 5. Example of a solidly grounded system as per the NEC.

IV. C ALCULATION E XAMPLE : S OLIDLY


G ROUNDED S YSTEM
A simplified one line depicting a solidly grounded system as
in [2] is shown in Fig. 5.
The given arrangement is similar to the TNCS system,
as described in [3]. The neutral conductor and the EGC are
bonded together at the service entrance, and both are connected
Fig. 4. Example of an ITcollective system. U.S. mine installation.
to the building ground electrode (e.g., water pipe, ground rods,
2) At the inception of a subsequent second fault to ground, etc.). The multiple earth connections of the PEN, constituting
involving another phase, the ITcollective system evolves a multiple grounded neutral system [17] adopted in the U.S.,
into a TN system, and the following condition on the are lumped into RMGN . In this paper, the simulation of the
fault-loop impedance must be fulfilled (assuming that the path to the source of the ground fault current originating at
neutral wire is not distributed) [5], [12]: the consumer premises through the aforementioned multiple

3Vph earths is not carried out; it is assumed that the single-phase
ZS ZM = (4) fault current to ground at the service entrance of the facility
2Ia
is communicated by the utility.
where ZS is the fault-loop impedance comprising the In Fig. 5, a 208-V three-phase source (e.g., utility) supplies a
impedance of the phase conductor and of the PE/EGC of load through two segments. In segment 1, i.e., from the source
the faulted equipment, ZM is the maximum permissible to the service entrance of a building, the neutral wire and the
loop impedance, and Ia is the current causing the auto- PE/EGC are combined in one conductor to form the PEN. In
matic operation of protective devices within the safe times segment 2, the PE/EGC is separated from the neutral conductor,
specified in Table II for TN systems, or 5 s for distribution
and at the service entrance, a five-wire distribution system is
circuits.
originated. This arrangement can be considered as a TNCS
It is worth noting that IT systems, whose equipment enclo- earthing systems as in [5], as shown in Fig. 2. The final circuit
sures are individually, or in group, grounded, at the occurrence
supplying the load is protected with 15-A fuses.
of a second fault evolve into a TT system; therefore, the
following condition, in accordance to [5], applies:
A. PE/EGC Thermal Sizing
RG Ia 50 V (5)
The line-to-ground fault current at the load side of segment 2
where RG is the earth resistance of the local grounding elec- is 0.53 kA, and the fault clearing time tf of the fuse is 0.01 s.
trode of the faulted enclosures; Ia is the current causing the We also assume a copper PE/EGC, insulated in cross-linked
automatic disconnection of the supply in a time complying with polyethylene and bunched with other cables or insulated con-
that of Table II for TT systems, or 1 s for distribution circuits. ductors, with an initial temperature of 90 C and a maximum
admissible temperature of 200 C.
C. System Protected by GFCIs (RCDs) With the data from Table I, k can be calculated with (2),
The ground fault circuit interrupter (GFCI), defined as the which yields the result of k = 140.7 ((A s)1/2 /mm). The
RCD in the IEC world, can be only effectively used in TT and cross-sectional area of the PE/EGC can be determined through
TNS systems and not in TNC or IT systems. In TNC sys- (1), which yields S = 1.77 mm2 . This value corresponds to the
tems, in fact, the fault current may circulate through the toroid trade size of 14 AWG (i.e., 2.08 mm2 ). In [2, Table 250.122]
of the RCD via the PEN conductor, i.e., desensitizing it, unless mandates the same 14 AWG for the PE/EGC, It is worth noting
the connection of the PE/EGC to the PEN conductor is made on that, in the IEC realm, S = 2.04 mm2 is not a standard size;
the source side of the RCD. In IT systems, instead, the ground therefore, the next larger trade size for the PE/EGC would be
current would flow through the RCDs toroid due to the system 2.5 mm2 , which is greater that 14 AWG. This consideration
natural distributed capacitance. In both cases, the RCDs cannot confirms the tendency of the IEC calculations to provide larger
sense any current unbalance and therefore cannot operate. wire sizes.
1724 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 49, NO. 4, JULY/AUGUST 2013

Fig. 7. TCC of LV CB 2.

transformer T1. Under fault conditions, the presence of the


HRG does not pose any safety issue to people, as prospective
touch voltages appearing on the equipment on the secondary
side of the substation is in fact proportional to the PE/EGC
impedance and not to the ohmic value of the HRG [15].
The PE/EGC in question, with a length of 110 ft, offers
a complex impedance ZPE/EGC = 0.0539 + j0.0056 , of
magnitude ZPE = 0.054 . As a consequence, the prospec-
Fig. 6. Example of a high-resistance grounded system. tive touch voltage to which people are exposed, which is the
voltage drop across this conductor, is ZPE 5 A = 0.27 V.
B. Electric Shock Calculation This value is well below the threshold of 50 V, and the dis-
The maximum disconnection time for final circuits not ex- connection of the supply for safety upon the first fault is not
ceeding 32 A in TN systems is 0.4 s (120 < U0 230 V). necessary.
From the TCC curve of the fuse, in correspondence with Upon a subsequent second fault to ground, involving a differ-
0.4 s, we can obtain the minimum allowed line-to-ground fault ent phase of the distribution circuit, (4) must be fulfilled, where
current Ia to clear the fault, which is 27.5 A. Ia in correspondence of 5 s, is approximately 250 A, as shown
The allowed maximum loop impedance ZM = U0 /Ia = in the TCC of LV CB 2 of Fig. 7.
120 V/27.5 A = 4.36 . As a result, ZM = 0.96 , whereas ZS = Zph + ZPE/EGC ,
In this example, the source impedance is XU = j0.001 , of magnitude ZS = 0.139 ; the inequality (4) is therefore true,
the phase conductor impedance for segment 1 is Zph1 = and the protection against indirect contact is guaranteed.
0.032 + j0.017 , and the PEN conductor impedance is
ZPEN = 0.101 + j0.023 ; segment 2 has phase conductor
VI. C ONCLUSION
impedance Zph2 = 0.006 + j0.003 and PE/EGC impedance
ZPE/EGC = 0.081 + j0.006 . The calculated magnitude of The thermal sizing procedure of PE/EGCs based on IEC
the fault-loop impedance, including all the given above 60364-5-54 and the electric shock calculations based on IEC
impedance, is Z = 0.226 . Comparing Z with ZM , it is clear 60364-4-41 have been detailed in this paper. On this basis,
that this system is well in the electric shock hazard safety limits. it has been substantiated how NEC-based installations can be
studied and designed by using the aforementioned standards.
This paper, in fact, have shown that the calculation methods
V. C ALCULATION E XAMPLE :
provided by IEC might be used in the North American low-
H IGH -R ESISTANCE -G ROUNDED S YSTEM
voltage installations from both theoretical and legal points of
Fig. 6 shows a high-resistance-grounded system permitted by view as they substantially provide the same or even more
[2, Art. 250.36], modeled with [16], which can be considered as conservative end results.
an IT (collectively) earthed system, as in [5]. Table III offers a summary of more conservative changes
The neutral point of the transformer is earthed through an to the sizing of grounding conductors that would result from
HRG rated 5 A.1 following the IEC rather than the NEC. The comparison be-
An EGC of size #6 AWG connects the enclosure of LV Bus 2 tween the two sizing methodologies has been performed in
to the earthed side of the neutral grounding resistor at the correspondence with the same ratings of overcurrent devices;
it is assumed the case of single-core PVC-insulated conductors,
1 Monitoring equipment of the ground fault current, mandated to be used in in a conduit on a wooden or masonry wall, and in the presence
conjunction with HRGs in both NEC and IEC standards, is not shown. of only two loaded conductors in the conduit [18].
LIU et al.: THERMAL SIZING AND ELECTRIC SHOCK CALCULATIONS FOR EGCs 1725

TABLE III [11] Calculation of Thermally Permissible Short-Circuit Currents, Taking Into
C OMPARISON B ETWEEN M INIMUM S IZES OF Account Non-Adiabatic Heating Effects, IEC 60 949, 1988.
PE/EGC C ONDUCTORS (NEC V ERSUS IEC) [12] M. Mitolo, Electrical Safety of Low-Voltage Systems. New York, NY,
USA: McGraw-Hill, 2009.
[13] 30 CFR 75.801, Title 30 of the Code of Federal Regulations, Mineral
Resources.
[14] W. L. Cooley and R. L. King, Bureau of mines information circular/
1980, United States Dept. Interior, Washington, DC, USA, IC 8835,
1980.
[15] M. Mitolo, Grounding the neutral of electrical systems through low-
resistance grounding resistors: An application case, IEEE Trans. Ind.
Appl., vol. 44, no. 5, pp. 13111316, Sep./Oct. 2008.
[16] [Online]. Available: www.etap.com
[17] M. Mitolo, Of electrical distribution systems with multiple grounded
neutrals, IEEE Trans. Ind. Appl., vol. 46, no. 4, pp. 15411546,
Jul./Aug. 2010.
[18] Electrical Installations of BuildingsPart 5-52: Selection and Erection
of Electrical Equipment - Wiring Systems, IEC 60 634-5-52, 2001-08.

Haijun Liu (SM01) received the Bachelors


and Masters degrees from Chongqing University,
Chongqing, China, and the Doctoral degree from the
IZ in column 4 is the minimum current-carrying capacity of University of Wisconsin, Milwaukee, WI, USA, all
in electrical engineering.
the line conductor of size SLine to match, or exceed, the trip He was with the Thomas Edison Technical Center
rating IN of the protective device. Columns 5 and 6 list trade of Cooper Power Systems as a Senior Power Engi-
wire sizes per IEC; column 3 lists the equivalent cross-sectional neer. He is currently a Principal Electrical Engineer
and the Vice President of Operation Technology,
areas of AWG wires, as the result of the metrification of Inc., Irvine, CA, USA. His research interests in-
column 2. clude electric power system modeling, simulation,
A mandatory set of rules and minimum requirements in the and software development. One of his current focuses is low-voltage system
studies.
U.S. electrical engineering practice is given in [2], which cannot Dr. Liu is a Registered Professional Engineer in the State of California.
be replaced by any other standard. However, specific criteria for
the electric shock analysis, of paramount importance in order
Massimo Mitolo (SM03) received the Doctoral de-
to assess the electrical safety of systems, are not included in gree in electrical engineering from the University of
[2]; therefore, the engineers of record, who would inevitably Naples Federico II, Naples, Italy.
undergo a legal scrutiny of their work in the unfortunate event He is currently a Senior Principle Electrical En-
gineer with Operation Technology, Inc., Irvine, CA,
of accidents, has the choice to take advantage of the IEC safety USA. He is the author of over 60 journal papers and
criteria to enhance their design in this area, with the likely of the book Electrical Safety of Low-Voltage Systems
approval of local authorities having jurisdiction. (McGraw-Hill, 2009). His research interests include
the analysis and grounding of power systems.
Simplified examples were also provided to unequivocally Dr. Mitolo is a Registered Professional Engineer
show the correspondence between electrical systems NEC/IEC in Italy. He is active within the Industrial and Com-
and the related calculations. mercial Power Systems Department of the IEEE Industry Application Society,
where he is currently the Chair of the Power Systems Engineering Committee,
the Chair of the Power Systems Analysis Subcommittee, and the Chair of the
R EFERENCES Grounding Subcommittee. He also serves as an Associate Editor for the IEEE
Power Systems Engineering and Energy Systems Committees with ScholarOne
[1] IEEE Recommended Practice for Grounding of Industrial and Commer- Manuscripts. He was the recipient of the IEEE 2012 Outstanding Engineer
cial Power Systems, IEEE Std. 142-2007, 2007. Award, awarded by the Orange County Power Engineering/Industry Applica-
[2] National Electrical Code, NFPA 70, 2011. tion Society for the development of new technical concepts for the advancement
[3] M. Mitolo, M. Tartaglia, and S. Panetta, Of international terminology and of the electrical safety engineering of low-voltage systems, as well as of the
wiring methods used in the matter of bonding and earthing of low-voltage 2012 I&CPS Ralph H. Lee Department Prize Paper Award and of the Power
power systems, IEEE Trans. Ind. Appl., vol. 46, no. 3, pp. 10891095, Systems Engineering Committee 2012 Prize Paper Award.
May/Jun. 2010.
[4] Electrical Installations of BuildingsSelection and Erection of Electrical
EquipmentEarthing Arrangements, Protective Conductors and Protec- Farrokh Shokooh (F94) was associated with
tive Bonding Conductors, IEC 60 364-5-54, Jun. 2002. Barbay Engineers, Inc. for five years. He was an
[5] Low-Voltage Electrical InstallationsProtection for SafetyProtection Associate Professor with Louisiana State University
against Electric Shock, IEC 60 364-4-41, 2005-12. and was a Visiting Lecturer with the University of
[6] M. Mitolo and M. Tartaglia, An analytical evaluation of the factor k2 for California, Irvine, CA, USA. For six years, he was a
protective conductors, IEEE Trans. Ind. Appl., vol. 48, no. 1, pp. 211 Staff Engineer with Fluor Corporation before found-
217, Jan./Feb. 2012. ing Operation Technology, Inc., Irvine, in 1986. His
[7] Short-Circuit Temperature Limits of Electric Cables With Rated Volt- teaching and research interests include mathematical
ages of 1 kV (U m = 1.2 kV) and 3 kV (U m = 3.6 kV), IEC 60 724, modeling and dynamic analysis of electrical ma-
Oct. 2000. chines and power systems. His industrial experience
[8] Short-Circuit Temperature Limits of Electric Cables With Rated Voltages ranges from conceptual design, control, and opera-
From 6 kV (U m = 7.2 kV) up to 30 kV (U m = 36 kV), IEC 60 986, tion of power systems to computer software design and development. His areas
Oct. 2000. of expertise include cable systems, grounding, short circuit, transient stability,
[9] Short-Circuit Temperature Limits of Electric Cables With Rated Voltages and protective device coordination.
Above 30 kV (U m = 36 kV), IEC 61 443, Jul. 1999. Dr. Shokooh is an active member of a number of IEEE subcommittees
[10] Short Circuit Characteristics of Insulated Cable, ICEA P-32-382, and working groups. He is a Registered Professional Engineer in the state of
Jan. 2007. California.

View publication stats

You might also like