You are on page 1of 5

Type 2000

I/P & E/P Transducers

Description Principle of Operation


The Marsh Bellofram Type 2000 is a robust The Type 2000 I/P and E/P transducers utilize
electronic instrument that regulates an incom- closed-loop pressure feedback-control for precision
ing supply pressure down to a precise output pressure output and minimized effects of tem-
pressure which is directly proportional to an perature, supply pressure changes, supply voltage
changes, and mounting angle.
electrical control signal. The secret to the Type
2000s precise, reliable performance under a Supply pressure is reduced by the supply valve
variety of demanding environmental conditions to provide an output pressure which is internally
is a patented piezo-ceramic actuator with many routed to a precision temperature compensated
industry-wide firsts. piezo-resistive pressure sensor. Supply pressure
is also routed to an externally removable orifice
The Type 2000 has been designed to meet the which provides a reduced pilot pressure to a
electro-pneumatic needs of the world: chamber containing a servo diaphragm and nozzle.
Pilot pressure is controlled by modulating the gap
Field-selectable inputs and direct/reverse/
split ranging
between the face of a nozzle and an adjacent
piezo-ceramic actuator, which is part of a unique Type 2000
Multiple input/output/mounting patented mechanism. Transducers
configurations The piezo-ceramic actuator serves as a control link
Precise, reliable performance under extreme between electrical input and pressure output as Note
conditions of temperature, vibration, orienta- follows:
The combined adjustments of Gain, Zero and
tion, supply pressure changes, supply voltage The input current (I/P) or voltage (E/P) signal Span are all interactive. It may take several
changes, RFI/EMI, humid / oil-laden media, is conditioned to provide a normalized control adjustment attempts to accomplish final desired
and corrosive surroundings signal directly proportional to the desired pressure setting.
output.
Simultaneously the output of the pressure sensor Zero and Span Adjustments
Applications
is amplified and conditioned to produce a feedback The Type 2000 contains multi-turn Coarse-Zero,
The Type 2000s precisely regulated pneumatic signal. Fine-Zero, and Span adjustment potentiometers
output can be used to operate: The sum of the control signal and the feedback sig- which are clockwise positive. Adjustment of
nal produce a command signal which is delivered either Zero Pot changes the units minimum out-
Transducers

Valve Actuators
as a DC voltage to the piezo-ceramic actuator. put while the Span Pot changes the maximum
Louver and Damper Actuators
As voltage increases, the force applied by the output.
Valve Positioners actuator increases, so as to restrict nozzle bleed
Relays and thus increase pilot pressure. Wide Rangeability
Clutches and Brakes Increased pilot pressure applied to the servo The Type 2000 can be field calibrated to pres-
Controllers diaphragm directly causes opening of the supply sure ranges other than the standard ones by
valve and an increase in the output pressure until combinations of recalibration, pressure range
Air Cylinders the output feedback signal and control signal switching, and split high/low ranging. A unit
combine to produce the correct command signal. should not be switched to a range outside its
Industry Applications Include
pressure sensor family (eg., a 0-15 PSIG can be
Chemical and Petrochemical Industries Fine-Tuning Your Application
switched to a 3-15 PSIG, but not to 0-30 PSIG).
Petroleum Production For optimal performance in your application, the (Caution: Do not exceed the range of the on-
calibration of the Type 2000 can be fine-tuned
Pipeline Transmission board pressure sensor.) For example, the easiest
in the field. An easily-removable cover provides
Electric Utilities access to the isolated electronics. All potenti- way to recalibrate a 0-30 PSIG unit to 3-15 psig
Water and Wastewater Systems ometers, connections, jumpers, and switches would be to change the switch setting to 3-27
are clearly marked on the circuit board or on the PSIG, then switch to split range low.
Pulp and Paper
handy chart located on the inside of the cover. Field-Selectable Features
Textiles The three elements of calibration (Gain, Zero, and
Semiconductor Industry Span) are described below. Consult the Type 2000 Onboard switches allow the user to easily recon-
Food and Beverage Users Manual for detailed calibration procedures, figure the Type 2000 for any of several electrical
Environmental Control Systems cautions, and instrumentation requirements. inputs, direct/reverse acting, or output split-rang-
ing high/low. Fine tuning of the units calibration
Construction Equipment Gain (Damping) Adjustment
may be necessary after a reconfiguration.
Agricultural Equipment The output response of the Type 2000 can be
Machine Tool optimized for varying downstream volumes by
adjusting the system gain of the control circuit.
Material Handling Adjust the Gain Pot counterclockwise for increased
Automotive Testing and Assembly gain; clockwise for increased oscillation damping.
Medical Equipment For maximum allowable gain in your application,
the pot should be turned clockwise until oscilla-
tion just disappears.
72 800.727.5646 www.marshbellofram.com
Direct/Reverse Acting Split Ranging (High or Low)
Direct Acting transducers regulate to their minimum output when supplied The Type 2000 can be configured to regulate either half (top or bottom)
with minimum input; maximum out with maximum in. Reverse Acting of its normal output range, when supplied with its normal full-ranging
transducers regulate to their maximum output at minimum input. electrical input. For example, a 0-10V 0-30 PSI unit set to split range low
will regulate 0-15 PSI @ 0-10V. It will regulate 15-30 PSI @ 0-10V if set to
split range high.

Easy Access Top Cover Electrical Port Options


1) Isolated electronics 1) 1/2 NPT Conduit
2) Calibration adjustments 2) 20mm Conduit
3) Configuration switches 3) Hirschmann (DIN 43 650-A)
4) Switch information on 4) Terminal Block
inside of cover

Easy Access Orifice


Mounting Options
1) In-Line Output Port
2) Direct: Holes on left Same as Input Port
rear and bottom faces (Not shown; rear face)
3) Bracket Mounting options:
Panel, Pipe, Valve, DIN-Rail Input Port Options
1) 1/4 NPT
Integral Booster 2) 1/4 BSPP
Flows up to 21 scfm for quick 3) 1/4 BSPT
system response
Manifold-Mounting Option
Supply and Output ports on the
Gauge Port bottom face rather than through
1/8 NPT on all models the body
(Not shown; rear face)
It is mandatory for the user to install a
suitably rated NRTL Listed or Certified conduit seal

Agency Approvals - Applies only to units ordered with approvals

Transducers
Factory Mutual
E Model with F approval, Explosion Proof/Intrinsically Safe S Model with Terminal Block, Intrinsically Safe
Not for use with natural gas or other Non-inert Gases Intrinsically Safe: Class I, Div 1, Groups A, B, C, D; T4, Ta = 60C;
Explosion Proof: Class I, Div 1, Groups A, B, C&D; T6, Ta = 60C Non-Incendive: Class I, Div 2, Groups A, B, C & D; T4, Ta=60C
Dust-Ignition Proof: Classes II & III, Div 1, Groups E, F&G; T6, Ta = 60C Entity Parameters:
TYPE 4X, IP 66 I/P: VMAX=30V, IMAX=200 mA, PMAX=1W, Ci= 0, Li=0
Intrinsically Safe: Class I, II & III, Div 1, Groups A, B, C, D, E, F & G; T4, Ta = 60C; E/P: VMAX=30V, IMAX=100 mA, PMAX=0.75 W, Ci= 0, Li=0
TYPE 4X, IP 66
Non-Incendive: Class I, Div 2, Groups A, B, C & D; T4, Ta=60C CANADIAN STANDARD ASSOCIATION
Suitable: Class II, Div 2, Groups F & G; T4, Ta = 60C
Suitable: Class III, Div 2; T4, Ta = 60C E Model with F approval, Explosion Proof/Intrinsically
Type 4X, IP 66 Safe, Certified to Two Standards.
Certified to CLASS 2258 04 PROCESS CONTROL EQUIPMENT
Entity Parameters: Class I, Div 1&2, Groups A, B, C, D; Class II, Div1, Groups E, F and G; Div 2,
I/P: VMAX=30V, IMAX=200 mA, PMAX=1W, Ci= 0, Li=0 Groups F and G; Class III.
E/P: VMAX=30V, IMAX=100 mA, PMAX=0.75 W, Ci= 0, Li=0 Rated: 28Vdc, 8mA, T6; Enclosure TYPE 4X, IP66; Max Ambient Temperature 60C.

E Model with G approval, Explosion Proof, Entity Parameters:


United States and Canada I/P: V =30V IMAX=200mA PMAX=1.0W Ci=0F
Li=0H MAX
For use with natural gas or other non-inert gases as a process E/P: VMAX=30V IMAX=100mA PMAX=0.75W Ci=0F Li=0H
medium up to a maximum input pressure of 140 PSI when
installed with suitable NRTL listed, certified or approved conduit Certified to CLASS 2258 02 PROCESS CONTROL EQUIPMENT
seal installed at the enclosure. Class I, Div 1 & 2, Groups A,B,C,D; Class II, Div 1, Groups E, F, G; Div 2, Groups F & G; Class III
Explosion Proof: Class I, Div 1, Groups A, B, C & D, T6 Ta = 60C Rated: 28Vdc, 8mA, T6; Enclosure TYPE 4X, IP66; Max Ambient Temperature 60C.
Dust-Ignition Proof: Classes II&III, Div 1, Groups E, F & G, T6 Ta = 60C
NEMA 4X, IP 66 Entity Parameters:
I/P: VMAX=30V IMAX=200mA PMAX=1.0W Ci=0F Li=0H
S Model, Intrinsically Safe E/P: VMAX=30V IMAX=100mA PMAX=0.75W Ci=0F Li=0H
Intrinsically Safe: Class I, II & III, Div 1,
Groups A, B, C, D, E, F & G, T4 Ta = 60C; ATEX (European Model)
Non-Incendive: Class I, Div 2, Groups A, B, C & D, T4 Ta=60C
Suitable: Class II, Div 2, Groups F & G, T4 Ta=60C INTRINSIC SAFETY: II 1 G EEx ia IIC T4 (-20<Ta<+60) EN 50014: 1997 (A2) EN
Suitable: Class III, Div 2, T4 Ta=60C 50020:1994 EN 500284: 1999
Type 4X, IP 66
The Bellofram T-2000 Transducers were tested and found to comply with Electromagnetic
Entity Parameters: Compatibility Directive effective January 1, 1996. The relevant EMC specifications tested
I/P: VMAX=30V, IMAX=200 mA, PMAX=1W, Ci= 0, Li=0 were the following: EN 50081-1 (1992) and EN 50082-1 (1992). A Technical Construction File,
E/P: VMAX=30V, IMAX=100 mA, PMAX=0.75 W, Ci= 0, Li=0 Serial #107 was written and Certificate of Conformity issued by a Competent Body.

www.marshbellofram.com 800.727.5646 73
Type 2000 Specifications The secret to the Type 2000s
Accuracy
0.1% of full-scale output typical (0.25% guaranteed); includes effects of precise, reliable performance
hysteresis, dead band, and repeatability
under a variety of demanding
Electrical
Switch-Selectable environmental conditions
Inputs 4-20mA. 0-5, 1-5, 1-9, 1-10, or 0-10VDC is a patented piezo-ceramic
1/2 NPT or 20mm Conduit
Connections DIN Hirschmann (S model only) actuator with many
External Terminal Block (S model only) industry-wide firsts.
Power Supply 5-28VDC (with voltage inputs only)
Direct/Reverse Acting Switch-Selectable
Pneumatic
0-5, 0-15, 3-15, 1-17, 0-30, 6-30, 3-27, 0-60, 0-100, or 120 PSIG
Outputs 0-0.1, 0-0.3, 0-1.0, 0.2-1.0, 0.07-1.2, 0-2.1, 0.4-2.1, 0.2-1.9,
0-4.1, 0-6.9, 0-8.3 BAR
1/4" (NPT, BSPT, or BSPP threads)
Ports (Input/Output)
Bottom-ported for Manifold Mounting
Exhaust (Explosion proof only) 1/8 - 27 NPT
Ports (Gauge) 1/8 NPT
For 05 PSIG (0.3 BAR) Through 060 PSIG
From 5 PSIG (0.3 BAR) above maximum output to 100 PSIG maximum
Supply For 0-100 PSIG and 0120 PSIG Ranges
From 5 PSIG (0.3 BAR) above maximum output to 140 PSIG maximum
Split-Ranging Switch-Selectable, Full-Range or Split-Range High or Split-Range Low
Consumption 4 SCFH maximum (1.9 LPM)
Range Sensor Flow
PSIG BAR PSIG BAR SCFM LPM
0-5 0-0.3 5 0.3 11 312
0-15 0-1.0 15 1.0 15 423
3-15 0.2-1.0 15 1.0 15 423
1-17 0.07-1.2 15 1.0 15 423
0-30 0-2.1 30 2.1 15 423
Flow Capacity
3-27 0.2-1.9 30 2.1 15 423
6-30 0.4-2.1 30 2.1 15 423
0-60 0-4.1 50 3.5 17 480
Transducers

(Typical Flow @ 100 PSIG (6.9 BAR) in and maximum out)


0-100 0-6.9 100 6.9 21 595
0-120 0-8.3 100 6.9 21 595
(Typical Flow @ 140 PSIG (9.7 BAR) in and maximum out)
3 SCFM (85 LPM) @ 5 PSIG (0.3 BAR) above setpoint
Exhaust Capacity (0-15 PSIG range unit set at mid range)
Stability Air Quality
Supply Voltage Effect None Instrument-quality air consists of:
Supply Pressure Effect None a. A dew point less than 35 F
Vibration Effect <1% FS (+/-1G; 5-1000Hz) b. No particles larger than three microns
Mounting Position Effect None c. Maximum oil content of 1 ppm
RFI/EMI CE-Compliant
Temperature Effect 0.02% FS/F (-40 to 180F [-40 to 82C]) It is mandatory for the user to
Storage Temperature -40to 200F (-40 to 93C) install a suitably rated NRTL
Approximate Weight 3.0 lbs, 1.35 kg Listed or Certified conduit seal

TYPE 2000: REGULATED PRESSURE VS. FLOW Type 2000 Mounting Options
PSIG BAR 140 psig supply pressure
70 4.8 Mounting Method Intrinsically-Safe (S) Model Explosion-Proof (E) Model
In-Line Yes Yes
60 4.1
Direct Mounting Side or Bottom Holes Side or Bottom Holes
regulated Pressure

50 3.4 Panel Bracket Supplied Accessory


40 2.8 Valve Bracket Accessory Supplied
Pipe Bracket Accessory Accessory
30 2.1 DIN-Rail Bracket Accessory Accessory
20 1.4 Manifold Plate Accessory Accessory
Mounting: The Type 2000 can be mounted in-line, or directly to a panel via mounting
10 0.7
holes located in the side and bottom of the unit. In addition, the S model includes a panel-
0 0 mounting bracket; while the E model includes a valve-mounting bracket. Kits are available
for mounting of either model to panel, valve, pipe, or DIN-Rail. A custom plate is available
SCFM 0 2 4 6 8 10 12 14 16 18 20 22 24 for mounting of the bottom-ported version to a manifold. (See Accessories)
LPM 0 57 113 170 227 283 340 397 453 510 566 623 680
Forward Flow High Flow Med Flow Low Flow

74 800.727.5646 www.marshbellofram.com
Type 2000 Ordering Information Type 2000 Accessories
2 K Part Number
Enclosure
S Intrinsically Safe
Panel Mounting Kit 010-135-000
E Explosion Proof Valve Mounting Kit 010-134-000
Electrical Port1
N 1/2 NPT Conduit 2" Pipe Mounting Kit
010-143-000
M 20mm Conduit S Unit Only (Valve Mounting Kit is required)
H Hirschmann5 DIN Rail Adapter 010-115-000
T Terminal Block2 S Unit Only
Pneumatic Ports Manifold Adapter Kit 971-158-000
N NPT Filter Kit, 60 microns 010-139-000
T BSPT
P BSPP Pressure Gauge Kit
15 PSIG (1 BAR)
010-138-000
M Manifold Mount3
Agency Approval 6
Pressure Gauge Kit
F FM/CSA 30 PSIG (2.1 BAR)
010-138-001
C ATEX S Unit Only
FM Natural Gas Approved Pressure Gauge Kit
G 60 PSIG (4.1 BAR)
010-138-002
for US and Canada4
Electrical Input Pressure Gauge Kit
42 4-20 mA 160 PSIG (11 BAR)
010-138-003
05 0-5 V
15 1-5 V
19 1-9 V Type 2000 Notes
11 1-10 V Enclosure
01 0-10 V
1
Availability
Mode
S E
D Direct Acting N Yes Yes
R Reverse Acting Electrical Port M Yes Yes
Mode H Yes No
F Full Range T Yes No
H Split Range High 2
NEMA 4X / IP66 not available
L Split Range Low 3
Bottom O-Ring Ports
Pneumatic Output
NRTL listed or certified conduit seal installed by user

Transducers
4
005 0-5 PSIG 0-0.3 BAR
015 0-15 PSIG 0-1.0 BAR 5
Not Agency Approved
315 3-15 PSIG 0.2-1.0 BAR F C G
117 1-17 PSIG 0.07-1.2 BAR
Maximum Supply for 6
Agency Approval
these regulators is FM/CSA ATEX Gas
030 0-30 PSIG 0-2.1 BAR
S Intrinsic
100 PSIG
630 6-30 PSIG 0.4-2.1 BAR Yes Yes No
Safety
327 3-27 PSIG 0.2-1.9 BAR Enclosure
060 0-60 PSIG 0-4.1 BAR E Explosion Yes No Yes
Proof
100 0-100 PSIG 0-6.9 BAR Maximum Supply for
these regulators is
120 0-120 PSIG 0-8.3 BAR 140 PSIG Terminal Block I/P Transducer E/P Transducer
Special S N/C + Signal
00 None
+ + Signal + Power Supply
It is mandatory for the user to install a - - Signal Common
suitably rated NRTL Listed or Certified conduit seal
Type 2000 Wiring Connections and Switch Positions
Switch # 1: PSIG BAR 2 3 4 5 6: psig BAR 7 8 9
0-15 0-1.0
0-15 0-1.0
3-15 0.2-1.0
1-17 0.07-1.2
1-17 0.07-1.2 Voltage
1-5 VDC Split Low 0-30 0-2.1 Reverse
ON 0-30 0-2.1 Split Low Input Full I/P
0-5 VDC Full 0-60 0-4.1 Acting
3-27 0.2-1.9 (E/P)
0-100 0-6.9
6-30 0.4-2.1
0-120 0-8.3
0-100 0-6.9
Switch # 1: PSIG BAR 2 3 4 5 6: psig BAR 7 8 9
1-9 VDC 3-15 0.2-1.0
0-60 0-4.1 Full Current Direct Split Low
OFF 0-10 VDC Split High 3-27 0.2-1.9 E/P
0-120 0-8.3 Split High Input (I/P) Acting Split High
4-20 mA 6-30 0.4-2.1

www.marshbellofram.com 800.727.5646 75
Type 2000 Dimensions

1/2-14 NPT

.360
.716

2X M3X0.5
2X 8-32 UNC-2B X .250 DEEP
X .375 DEEP
4.780
MOUNTING HOLES

3.883

OUT 1.893 IN
.570 TYP

.550 1/4-18 NPT TYP


1.060
1.100

Bellofram
Type 2000 Explosion Proof Dimensions
2.307

Marsh
1.37

[34.7]

2.225
Transducers

2.939

3.92
1.10
[99.5]
[27.9]

0.55
[14.0]

6.01

[152.6]

2.06
1.78 OUT
[52.3]
[45.2]
0.68
[17.3]

Drawings and dimensions are for reference only. 2.12


0.57
[14.5]

[53.8]

76 800.727.5646 www.marshbellofram.com

You might also like