Professional Documents
Culture Documents
Application Note
Current transformer testing
This application note gives examples on how to per-
Wiring check and visual inspection
form some typical tests on current transformers (CTs)
with TRAX Manual control. These tests are common 1] Check that the primary and secondary side
to perform for instance during commissioning. are connected for correct ratio according to
system requirements.
Subject to change without notice. Printed matter No. ZR-AJ01E Doc. AJ034139AE V01a 2017
Polarity and ratio test with 11] For Polarity use calculation 2, select Phase
between Gen U and Ch 1.
AC voltage 12] Select an appropriate test voltage, best accu-
racy is achieved at about 75% of saturation
Polarity test and ratio test voltage.
1] Isolate the CT secondary from the load and
make connections as shown in the figure 13] Start the generating.
below. 14] Wait for results to stabilize
15] Press stop and read results. Ratio should be
IMPORTANT close to 1 and polarity should be close to 0
Make sure that one side of primary and deg.
secondary windings are connected to
ground at all times. Otherwise, the mea- 16] Repeat the test for all phases and cores.
surement results will be affected and the
Tip!
instrument may be damaged.
If saturation voltage is unknown: start
energizing with a low voltage, approxi-
mately 1% of generator max voltage.
Increase the voltage slowly until excita-
tion current starts increasing considerably
(e.g. to 100 mA) and the lower voltage to
about 75% of its value result in high cur-
rent. Now a high accuracy measurement
of ratio with voltage is achieved.
Burden impedance test 9] Wait until current and voltage reach stabile
value.
A burden test is made to ensure that the load (VA) is
10] Stop the test
not more than specified on nameplate.
11] Evaluate that the measured VA is below the
1] Connect according to picture below.
VA rating for the CT.
IMPORTANT 12] Repeat the test for all phases and cores.
Make sure that one side of primary and
secondary windings are connected to
ground at all times. Otherwise, the mea-
surement results will be affected and the
instrument may be damaged.
2] Select 16 A DC output.
3] Activate Int Gen I and make sure it is set to
DC.
4] Activate R R1 and make sure it is set to DC.
5] Activate the Hold function.
6] Press
7] For winding resistance use calculation 1,
select / division R1 and Gen I.
8] Set the current to 10% of secondary nominal
current rating, Is normally 1 A or 5 A.
9] Start the generating.
Connection L1-L2
Connection L2-L3