FIRE DAMPERS

MODEL K75 TYPE A


UL CLASSIFIED 1-1/2 HOURS RATING

MODEL K75 AH FEATURES.

*Each damper is marked with a 1-1/2 hours


UL 555 Classified fire damper label.
ORDER HEIGHT *Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
(H) HORIZONTAL MOUNT ratings of less than 3 hours.
APPLICATION

MODEL K75 IS APPROVED FOR USE


IN WALLS, FLOORS AND PARTITIONS
WITH FIRE RESISTANCE RATINGS
LESS THAN 3 HOURS. Order Height
(Damper supplied 1/4"
less than order height)

STANDARD CONSTRUCTION
FRAME.
4-1/4 " Maximum X 22 gauge Galvanized steel channel. (D
AM
PE
BLADES. RS
UP
22 gauge Galvanized steel curtain type in the air stream. PL
IED OR
1/4 DE
RW
FINISH. "L
ES
ST
IDT
H
Mill. HA
NO
RD
CLOSURE SPRINGS. ER
WI
DT
301 Stainless Steel Spring. H)
(For Horizontal mount only, optional on vertical mount)
4-1/4"
FUSIBLE LINK. VARIATION.
Standard 165 F. Other available. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MOUNTING. procedures. Approved variations available at
ORDER HEIGHT

Vertical or Horizontal . additional cost are :


*Factory furnished sleeves.
MINIMUM SIZE. Sleeves are available in 10 through 20 gauge steel
Vertical Installation ---- 4"Wx 4"H.
MODEL and in lengths required for the specific application.
K75 AV
Horizontal Installation ---- 4"Wx 4"H. NOTE.
* Dampers furnished approximately 1/4" smaller
MAXIMUM SIZE. than given duct dimension
Single Section * Refer to the KBE Installation Instruction and
Vertical Installation ---- 60"Wx 60"H. (V) VERTICAL MOUNT supplements for complete installation details.
Horizontal Installation ---- 60"Wx 60"H.
Multiple Section S I F I
AS E UNDERWRITERS LABORATORIES (UL 555)
Vertical Installation ---- 120"Wx 120"H. L
D
C

CLASSIFIED FIRE DAMPERS.


Horizontal Installation ---- 120"Wx 120"H. UL R
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS

MODEL K75-T TYPE A


UL CLASSIFIED 1-1/2 HOURS RATING

MODEL K75-T AH FEATURES.

*Each damper is marked with a 1-1/2 hours


UL 555 Classified fire damper label.
ORDER HEIGHT *Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
(H) HORIZONTAL MOUNT ratings of less than 3 hours.
APPLICATION

MODEL K75 IS APPROVED FOR USE


IN WALLS, FLOORS AND PARTITIONS
WITH FIRE RESISTANCE RATINGS Order Height
LESS THAN 3 HOURS. (Damper supplied 1/4"
less than order height)

STANDARD CONSTRUCTION
FRAME.
4-3/8 " Maximum X 20 gauge Galvanized steel channel. (D
AM
PE
BLADES. RS
UP
22 gauge Galvanized steel curtain type in the air stream. PL
IED OR
1/4 DE
RW
FINISH. "L
ES
ST
IDT
H
Mill. HA
NO
RD
CLOSURE SPRINGS. ER
WI
DT
301 Stainless Steel Spring. H)
(For Horizontal mount only, optional on vertical mount)
4-3/8"
FUSIBLE LINK. VARIATION.
Standard 165 F. Other available. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MOUNTING. procedures. Approved variations available at
ORDER HEIGHT

Vertical or Horizontal . additional cost are :


*Factory furnished sleeves.
MINIMUM SIZE. Sleeves are available in 10 through 20 gauge steel
Vertical Installation ---- 4"Wx 4"H.
MODEL and in lengths required for the specific application.
K75-T AV
Horizontal Installation ---- 4"Wx 4"H. NOTE.
* Dampers furnished approximately 1/4" smaller
MAXIMUM SIZE. than given duct dimension
Single Section * Refer to the KBE Installation Instruction and
Vertical Installation ---- 60"Wx 60"H. (V) VERTICAL MOUNT supplements for complete installation details.
Horizontal Installation ---- 60"Wx 60"H.
Multiple Section S I F I
AS E UNDERWRITERS LABORATORIES (UL 555)
Vertical Installation ---- 120"Wx 120"H. L
D
C

CLASSIFIED FIRE DAMPERS.


Horizontal Installation ---- 120"Wx 120"H. UL R
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS
MODEL K75 TYPE B
UL CLASSIFIED 1-1/2 HOURS RATING

ORDER HEIGHT
FEATURES.

*Each damper is marked with a 1-1/2 hours


MODEL K75 BH UL 555 Classified fire damper label.
*Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
ratings of less than 3 hours.
OVERALL HEIGHT

(H) HORIZONTAL MOUNT

APPLICATION
MODEL K75 IS APPROVED FOR USE
IN WALLS, FLOORS AND PARTITIONS ORDER HEIGHT
DAMPER SUPPLIED 1/4"
WITH FIRE RESISTANCE RATINGS LESS THAN ORDER HEIGHT
LESS THAN 3 HOURS.

STANDARD CONSTRUCTION
FRAME. OVERALL HEIGHT
4-1/4 " Maximum X 22 gauge Galvanized steel channel. IS ORDER HEIGHT
PLUS "B" PAN TABLE
HEIGHT LESS 1/4".
BLADES.
22 gauge Galvanized steel curtain type out of the air stream. (D
AM OR
TH PER D
FINISH. AN SU ER
OR PP W
DE LIE IDTH
Mill. R D1
WI /4
DT " L
CLOSURE SPRINGS. H) ES
S
301 Stainless Steel Spring.
(For Horizontal mount only, optional on vertical mount)
FUSIBLE LINK. 4-1/4" VARIATION.
Standard 165 F. Other available. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MOUNTING. procedures. Approved variations available at
OVERALL DAMPER HEIGHT

Vertical or Horizontal . additional cost are :


*Factory furnished sleeves.
ORDER HEIGHT

MINIMUM SIZE. Sleeves are available in 10 through 20 gauge steel


Vertical Installation ---- 4"Wx 4"H. MODEL and in lengths required for the specific application.
K75 BV
Horizontal Installation ---- 4"Wx 4"H.
NOTE.
* Dampers furnished approximately 1/4" smaller
MAXIMUM SIZE. than given duct dimension
Single Section
* Refer to the KBE Installation Instruction and
Vertical Installation ---- 60"Wx 53"H.
(V) VERTICAL MOUNT supplements for complete installation details.
Horizontal Installation ---- 60"Wx 53"H.
Multiple Section L
AS
S I F I
E UNDERWRITERS LABORATORIES (UL 555)
D
C

CLASSIFIED FIRE DAMPERS.


Vertical Installation ---- 120"Wx 120"H.
Horizontal Installation ---- 120"Wx 120"H.
UL R
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS
MODEL K75-T TYPE B
UL CLASSIFIED 1-1/2 HOURS RATING
ORDER HEIGHT
FEATURES.

*Each damper is marked with a 1-1/2 hours


MODEL K75-T BH UL 555 Classified fire damper label.
*Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
ratings of less than 3 hours.
OVERALL HEIGHT

(H) HORIZONTAL MOUNT

APPLICATION
MODEL K75 IS APPROVED FOR USE
IN WALLS, FLOORS AND PARTITIONS ORDER HEIGHT
WITH FIRE RESISTANCE RATINGS DAMPER SUPPLIED 1/4"
LESS THAN ORDER HEIGHT
LESS THAN 3 HOURS.

STANDARD CONSTRUCTION
FRAME. OVERALL HEIGHT
4-3/8 " Maximum X 20 gauge Galvanized steel channel. IS ORDER HEIGHT
PLUS "B" PAN TABLE
BLADES. HEIGHT LESS 1/4".

22 gauge Galvanized steel curtain type out of the air stream. (D


AM OR
TH PER D
FINISH. AN SU ER
OR PP W
Mill. DE LIE IDTH
R D1
WI /4
DT " L
CLOSURE SPRINGS. H) ES
S
301 Stainless Steel Spring.
(For Horizontal mount only, optional on vertical mount)
FUSIBLE LINK. 4-3/8" VARIATION.
Standard 165 F. Other available. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MOUNTING. procedures. Approved variations available at
OVERALL DAMPER HEIGHT

Vertical or Horizontal . additional cost are :


*Factory furnished sleeves.
ORDER HEIGHT

MINIMUM SIZE. Sleeves are available in 10 through 20 gauge steel


Vertical Installation ---- 4"Wx 4"H. MODEL and in lengths required for the specific application.
K75-T BV
Horizontal Installation ---- 4"Wx 4"H.
NOTE.
MAXIMUM SIZE. * Dampers furnished approximately 1/4" smaller
Single Section than given duct dimension
Vertical Installation ---- 60"Wx 53"H. * Refer to the KBE Installation Instruction and
Horizontal Installation ---- 60"Wx 53"H. (V) VERTICAL MOUNT supplements for complete installation details.
Multiple Section L
AS
S I F I
E UNDERWRITERS LABORATORIES (UL 555)
Vertical Installation ---- 120"Wx 120"H.
D
C

CLASSIFIED FIRE DAMPERS.

Horizontal Installation ---- 120"Wx 120"H. UL R


FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS
MODEL K75 TYPE C, CR & CO
UL CLASSIFIED 1-1/2 HOURS RATING
Overall Damper Height
Order Height
Damper Supplied 1/4" Less
FEATURES.
Than Order Height

1" *Each damper is marked with a 1-1/2 hours


UL 555 Classified fire damper label.
Models
K75 CH *Meets all UL and NFPA criteria for primary fire
K75 CRH dampers in walls and floors with fire resistance
K75 COH ratings of less than 3 hours.
Typical
2-1/2"

(H) HORIZONTAL MOUNT OR


DE "C
R O"
HE
APPLICATION IG
HT OV
AL

MODEL K75 IS APPROVED FOR USE IN WALLS,


FLOORS AND PARTITIONS WITH FIRE RESISTANCE
OR "
RATINGS LESS THAN 3 HOURS. DE CO"
R
WI
DT
H
STANDARD CONSTRUCTION RE
OR CT
DE "C AN RO
R "
FRAME. HE
IG
GL
E UN
D
HT
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type out of the air stream.
OR
FINISH. DE "C"
R
WI
Mill. DT
H "
OR CR"
CLOSURE SPRINGS. DE
R
DI
301 Stainless Steel Spring. A.
(For Horizontal mount only, optional on vertical mount)
4-1/4"
FUSIBLE LINK.
Standard 165 F. Other available. VARIATION.
All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
MOUNTING. are limited to those incorporated in the approved
Vertical or Horizontal .
procedures. Approved variations available at
additional cost are :
Damper Supplied 1/4" Les

MINIMUM SIZE.
Overall Damper Height

Than Order Height


Order Height

Model K75 C ---- 4"Wx 4"H. *Factory furnished sleeves.


Model K75 CR ---- diameter 3". Models
Sleeves are available in 10 through 20 gauge steel
Model K75 CO ---- diameter 3". K75 CV and in lengths required for the specific application.
K75 CRV
MAXIMUM SIZE. K75 COV NOTE.
* Dampers furnished approximately 1/4" smaller
Model K75C Single Section: than given duct dimension
Vertical Installation ---- 58"Wx 52"H. * Refer to the KBE Installation Instruction and
Typical
Horizontal Installation ---- 58"Wx 52"H. 2-1/2" supplements for complete installation details.
Model K75CR & CO Single Section L
AS
S I F I
E UNDERWRITERS LABORATORIES (UL 555)
D

1"
C

CLASSIFIED FIRE DAMPERS.


Vertical Installation ---- Diameter 53"
Horizontal Installation ---- Diameter 53". (V) VERTICAL MOUNT UL R
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS
MODEL K75-T TYPE C, CR & CO
UL CLASSIFIED 1-1/2 HOURS RATING
Overall Damper Height
Order Height
Damper Supplied 1/4" Less
FEATURES.
Than Order Height

1" *Each damper is marked with a 1-1/2 hours


UL 555 Classified fire damper label.
Models
K75-T CH *Meets all UL and NFPA criteria for primary fire
K75-T CRH dampers in walls and floors with fire resistance
K75-T COH ratings of less than 3 hours.
Typical
2-1/2"

(H) HORIZONTAL MOUNT OR


DE "C
R O"
HE
IG OV
APPLICATION HT AL

MODEL K75 IS APPROVED FOR USE IN WALLS,


FLOORS AND PARTITIONS WITH FIRE RESISTANCE
OR "
RATINGS LESS THAN 3 HOURS. DE CO"
R
WI
DT
H
STANDARD CONSTRUCTION OR RE
DE "C CT
R " AN RO
GL
FRAME. HE
IG E UN
D
HT
4-3/8 " Maximum X 20 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type out of the air stream.
OR
FINISH. DE "C"
R
WI
Mill. DT
H "
OR CR"
CLOSURE SPRINGS. DE
R
DI
301 Stainless Steel Spring. A.
(For Horizontal mount only, optional on vertical mount)
4-3/8"
FUSIBLE LINK.
Standard 165 F. Other available.
VARIATION.
All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
MOUNTING. are limited to those incorporated in the approved
Vertical or Horizontal .
procedures. Approved variations available at
Damper Supplied 1/4" Less

additional cost are :


MINIMUM SIZE.
Overall Damper Height

Than Order Height


Order Height

*Factory furnished sleeves.


Model K75-T C ---- 4"Wx 4"H.
Sleeves are available in 10 through 20 gauge steel
Model K75-T CR ---- diameter 3". Models
K75-T CV and in lengths required for the specific application.
Model K75-T CO ---- diameter 3".
K75-T CRV

MAXIMUM SIZE.
K75-T COV NOTE.
* Dampers furnished approximately 1/4" smaller
Model K75-T C Single Section: than given duct dimension
Vertical Installation ---- 58"Wx 52"H. * Refer to the KBE Installation Instruction and
Typical
Horizontal Installation ---- 58"Wx 52"H. 2-1/2" supplements for complete installation details.
Model K75-T CR & CO Single Section L
AS
S I F I
E UNDERWRITERS LABORATORIES (UL 555)
D

1"
C

CLASSIFIED FIRE DAMPERS.


Vertical Installation ---- Diameter 53"
Horizontal Installation ---- Diameter 53". (V) VERTICAL MOUNT UL R
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS
MODEL K75 SC TYPE A or B
(304 STAINLESS STEEL CONSTRUCTION)
UL CLASSIFIED 1-1/2 HOURS RATING

MODEL K75 SC AH FEATURES.

*Each damper is marked with a 1-1/2 hours


UL 555 Classified fire damper label.
ORDER HEIGHT *Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
(H) HORIZONTAL MOUNT ratings of less than 3 hours.
APPLICATION

MODEL K75 IS APPROVED FOR USE


IN WALLS, FLOORS AND PARTITIONS
WITH FIRE RESISTANCE RATINGS
LESS THAN 3 HOURS. Order Height
(Damper supplied 1/4"
less than order height)
STANDARD CONSTRUCTION
FRAME.
4-3/8 " Maximum X 22 gauge 304 stainless steel channel.
(D
AM
BLADES. PE
RS
22 gauge 304 stainless steel curtain type in the air stream. UP
PL
IED OR
FINISH. 1/4
"L
DE
RW
IDT
ES
Mill. ST
HA
H

NO
CLOSURE SPRINGS. RD
ER
301 Stainless Steel Spring. WI
DT
H)
(For Horizontal mount only, optional on vertical mount)
FUSIBLE LINK. 4-3/8" 4-3/8"
VARIATION.
Standard 165 F. Other available. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MOUNTING. procedures. Approved variations available at
Vertical or Horizontal .
ORDER HEIGHT
ORDER HEIGHT

additional cost are :


*Factory furnished sleeves.
MINIMUM SIZE. Sleeves are available in 10 through 20 gauge steel
Vertical Installation ---- 4"Wx 4"H. MODEL MODEL and in lengths required for the specific application.
Horizontal Installation ---- 4"Wx 4"H. K75 SC AV K75 SC BV

NOTE.
MAXIMUM SIZE. * Dampers furnished approximately 1/4" smaller
Single Section than given duct dimension
Vertical Installation ---- 60"Wx 60"H. * Refer to the KBE Installation Instruction and
Horizontal Installation ---- 60"Wx 60"H. (V) VERTICAL MOUNT (V) VERTICAL MOUNT supplements for complete installation details.
Multiple Section
Vertical Installation ---- 120"Wx 120"H. L
AS
S I F I
E UNDERWRITERS LABORATORIES (UL 555)
D
C

CLASSIFIED FIRE DAMPERS.


Horizontal Installation ---- 120"Wx 120"H.
UL R
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS
MODEL K75 SB TYPE A or B
(304 STAINLESS STEEL BLADES)
UL CLASSIFIED 1-1/2 HOURS RATING

MODEL K75 SB AH FEATURES.

*Each damper is marked with a 1-1/2 hours


UL 555 Classified fire damper label.
ORDER HEIGHT *Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
(H) HORIZONTAL MOUNT ratings of less than 3 hours.
APPLICATION

MODEL K75 IS APPROVED FOR USE


IN WALLS, FLOORS AND PARTITIONS
WITH FIRE RESISTANCE RATINGS
LESS THAN 3 HOURS.
Order Height
(Damper supplied 1/4"
less than order height)

STANDARD CONSTRUCTION
FRAME.
4-1/4 " Maximum X 22 gauge galvanized steel channel.
(D
AM
BLADES. PE
RS
22 gauge 304 stainless steel curtain type in the air stream. UP
PL
IED OR
DE
FINISH. 1/4
"L
ES
RW
IDT
H
Mill. ST
HA
NO
CLOSURE SPRINGS. RD
ER
301 Stainless Steel Spring. WI
DT
H)
(For Horizontal mount only, optional on vertical mount)
4-1/4" 4-1/4"
FUSIBLE LINK. VARIATION.
Standard 165 F. Other available. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MOUNTING. procedures. Approved variations available at
ORDER HEIGHT

Vertical or Horizontal .
ORDER HEIGHT

additional cost are :


*Factory furnished sleeves.
MINIMUM SIZE. Sleeves are available in 10 through 20 gauge steel
Vertical Installation ---- 4"Wx 4"H. MODEL MODEL and in lengths required for the specific application.
K75 SB AV K75 SB BV
Horizontal Installation ---- 4"Wx 4"H.
NOTE.
MAXIMUM SIZE. * Dampers furnished approximately 1/4" smaller
Single Section than given duct dimension
Vertical Installation ---- 60"Wx 60"H. * Refer to the KBE Installation Instruction and
Horizontal Installation ---- 60"Wx 60"H. (V) VERTICAL MOUNT (V) VERTICAL MOUNT supplements for complete installation details.
Multiple Section
Vertical Installation ---- 120"Wx 120"H. L
AS
S I F I
E UNDERWRITERS LABORATORIES (UL 555)
D
C

CLASSIFIED FIRE DAMPERS.


Horizontal Installation ---- 120"Wx 120"H.
UL R
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

MODEL K75
CURTAIN TYPE FIRE DAMPER PERFORMANCE DATA
Free Area and Static Friction Loss at various velocities.
DAMPER FREE AREA (SQ FT)
HEIGHT WIDTH (INCHES) HEIGHT WIDTH (INCHES)
(INCHES) (INCHES)
6" 12" 18 " 24 " 30" 36 " 42 " 48" 54" 60 " 6" 12" 18 " 24 " 30 " 36 " 42 " 48" 54" 60 "
6" .14 .33 .52 .70 .89 1.1 1.3 1.5 1.7 1.8 6" .16 .38 .60 .81 1.0 1.3 1.5 1.7 1.9 2.1
12" .31 .72 1.1 1.5 1.9 2.4 2.8 3.2 3.5 4.0 12" .34 .81 1.3 1.8 2.2 2.7 3.2 3.6 4.1 4.6

18 " .48 1.1 1.7 2.4 3.0 3.7 4.3 4.9 5.6 6.2 18 " .53 1.3 2.0 2.7 3.4 4.1 4.8 5.6 5.6 7.0

24 " .65 1.5 2.4 3.2 4.1 5.0 5.8 6.7 7.5 8.4 24 " .72 1.7 2.7 3.6 4.6 5.6 6.5 7.5 7.5 9.4
30 " .82 1.9 3.0 4.1 5.2 6.3 7.3 8.4 9.5 10.6 30 " .91 2.1 3.3 4.6 5.8 7.0 8.2 9.4 10.7 11.9

36 " .99 2.3 3.6 4.9 6.3 7.6 8.9 10.2 11.5 12.8 36 " 1.1 2.6 4.0 5.5 7.0 8.4 9.9 11.4 12.8 14.3
42 " 1.2 2.7 4.2 5.8 7.3 8.8 10.4 11.9 13.4 15.0 42 " 1.3 3.0 4.7 6.4 8.2 9.9 11.6 13.3 15.0 16.8
48 " 1.3 3.1 4.9 6.6 8.4 10.2 11.9 13.7 15.5 17.2 48 " 1.5 3.4 5.4 7.4 9.3 11.3 13.3 15.3 17.2 19.2

54 " 1.5 3.5 5.5 7.5 9.5 11.5 13.5 15.5 17.5 19.4 54 " 1.7 3.9 6.1 8.3 10.5 12.8 15.0 17.2 19.4 21.6

60 " 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.4 21.7
TYPE B
TYPE A

Free Area is Equal to Nominal Duct Area for Type-C dampers.


To find pressure drop compute FREE AREA VELOCITY
intersect desired damper type curve and extend line
perpendicular to velocity lines down to Static Pressure Drop (in.wg.)

cfm = Free Area Velocity (FAV)


PRESSURE DROP CURVE free area
4000 in feet per min
EXAMPLE:
TYPE "C" A 24" x 24" type-A damper is required for a
TYPE "B" 3,000 cfm application:

FAV= 3,000 = 937 fpm


3.2 Square Feet
3000
TYPE "A"
by locating 937 fpm on the
FREE AREA VELOCITY

"A" damper curve and following


the vertical intersection point
down to the bottom of the
graph, read .041 in.wg. static pressure drop.

2000 cfm= cubic feet per minute


fpm= feet per minute
FAV= free area velocity
SP= Static Pressure
1500 P= Pressure difference or pressure drop
FA= Free Area
1000
Metric system conversions:
800
Multiply cfm by .4719 to obtain liters per second
600 fpm by .00508 for meters per second
in. wg. by .2486 to obtain kilopascals
400 sq.ft. by .0929 for square meters
200 Test data in accordance with AMCA Std 500
.01
.02
.03
.04
.05
.06
.07
.08
.09
0.1

0.2

0.3

0.4

Static Pressure Drop (in. wg.)


kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS


INSTALLATION AND MAINTENANCE INSTRUCTIONS
1-1/2 HOUR RATED, UL CLASSIFIED FIRE DAMPER
FOR USE IN FIRE BARRIERS WITH RATINGS OF LESS THAN 3 HOURS

INSPECTION INSTALLATION
Inspect for shipping damage. The basic intent of a proper installation is to secure
Inspect for proper size and model. the fire damper in, not to, the opening in such a
Inspect installed damper for proper orientation, as stated manner as to prevent distortion and disruption of the
on damper label. damper operation by allowing the fire damper in
Inspect for obstructions which could interfere with free openings to expand and the connecting duct to
operation and complete closure. separate in the event of the collapse of the hanging
Manually cycle the damper to verify proper operation. system. The fire damper must be positioned within
the masonry, block or gypsum wallboard fire barrier.

TYPICAL WALL INSTALLATION


DAMPER TO SLEEVE ATTACHMENT
A Sleeve shall be used of sufficient length to
MIN. 1" OVERLAP
permit direct attachment of perimeter mounting angles.
ON ALL SIDES AND This damper can be supplied with factory mounted
CORNERS
sleeve. If the sleeve is not factory supplied, it
SEE NOTE ON
CLEARANCE
must be attached on both sides of the damper by one
SEE NOTE ON
of the following methods:
REVERSE ANGLE Secure with 1/4" dia. bolts and nuts or by welding with
beads 1/2" in length, or with No. 10 steel sheet metal
screws, or 3/16" steel rivets. Fasteners shall be 8"
maximum on centers. Fasteners cannot be placed
where they will interfere with damper operation.
Gaps at corners between the damper and its sleeve
must be small enough to prohibit the passage of an
1/8" diameter rod through the entire depth of the
gap and between two damper panels and its sleeve.

SLEEVE THICKNESS
Sleeves shall be the same gauge or heavier as the
SEE NOTE ON duct to which it is attached. Gauges shall conform to
DAMPER TO SLEEVE SMACNA or ASHRAE duct standards. Damper sleeve
ATTACHMENT AND
SLEEVE GAUGE can be no thicker than 10 GA steel. On type
REQUIREMENTS C dampers, the sleeve must be 18 GA. or heavier.

EXPANSION CLEARANCE
The opening in the wall or floor for the fire damper
shall be sized so as to provide expansion clearance
SEE NOTE between the sleeve and opening. Clearances do not
ON DUCT
CONNECTION vary with walls constructed of different materials. A
minimum of 1/8" per foot of overall damper/sleeve
width and height is required. The maximum opening
3" MIN. FOR DUCT
CONNECTION AND
size shall not exceed 1/8" per foot plus 1", minimum
MTG. ANGLES total clearance shall be at least 1/4" larger than the
overall assembly.
6" MAX.
S I F I
AS E
L
16" MAX. WHEN INSTALLATION INSTRUCTIONS
D
C

FACTORY INSTALLED

WALL MOUNT SHOWN


ACCESS DOOR
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
FLOOR MOUNT SIMILAR
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS

MODEL K75 TYPE L


UL CLASSIFIED 3 HOURS RATING

APPLICATION FEATURES.

MODEL K75 L IS APPROVED FOR USE *Each damper is marked with a 3 hours
IN WALLS, FLOORS AND PARTITIONS UL 555 Classified fire damper label.
WITH FIRE RESISTANCE RATINGS *Meets all UL and NFPA criteria for primary fire
FOR 4 HOURS AND LESS. dampers in walls and floors with fire resistance
ratings of 4 hours and less.

STANDARD CONSTRUCTION
FRAME.
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES. Order Height
22 gauge Galvanized steel curtain type in the air stream. (Damper supplied 1/4"
less than order height)
FINISH.
Mill.
CLOSURE SPRINGS (Optional) .
301 Stainless Steel Spring .
(D
AM
PE
RS
UP
PL
FUSIBLE LINK. IED OR
DE
1/4 RW
Standard 165 F. Other available. "L
ES IDT
ST H
HA
NO
RD
ER
MOUNTING. WI
DT
H)
Vertical .
4-1/4"
MINIMUM SIZE. VARIATION.
Vertical Installation ---- 4"Wx 4"H. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MAXIMUM SIZE. procedures. Approved variations available at
ORDER HEIGHT

Single Section additional cost are :


Vertical Installation ---- 60"Wx 60"H. *Factory furnished sleeves.
Sleeves are available in 10 through 20 gauge steel
MODEL and in lengths required for the specific application.
K75 LV

NOTE.
AS
S I F I
E
* Dampers furnished approximately 1/4" smaller
L UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTANCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
* Refer to the KBE Installation Instruction and
(V) VERTICAL MOUNT supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS

MODEL K75-T TYPE L


UL CLASSIFIED 3 HOURS RATING

FEATURES.
APPLICATION
*Each damper is marked with a 3 hours
MODEL K75-T L IS APPROVED FOR USE UL 555 Classified fire damper label.
IN WALLS, FLOORS AND PARTITIONS *Meets all UL and NFPA criteria for primary fire
WITH FIRE RESISTANCE RATINGS dampers in walls and floors with fire resistance
4 HOURS AND LESS. ratings of 4 hours and less.

STANDARD CONSTRUCTION
FRAME.
4-3/8 " Maximum X 20 gauge Galvanized steel channel. Order Height
BLADES. (Damper supplied 1/4"
less than order height)
22 gauge Galvanized steel curtain type in the air stream.
FINISH.
Mill.
CLOSURE SPRINGS. (Optional)
(D
301 Stainless Steel Spring. AM
PE
RS
UP
PL
IED OR
1/4 DE
FUSIBLE LINK. "L
ES
RW
IDT
ST H
Standard 165 F. Other available. HA
NO
RD
ER
WI
DT
H)
MOUNTING.
Vertical .
4-3/8"
VARIATION.
MINIMUM SIZE. All UL Classified fire dampers must be fabricated in
Vertical Installation ---- 4"Wx 4"H. accordance with UL procedures. Available variation
are limited to those incorporated in the approved
procedures. Approved variations available at
MAXIMUM SIZE.
ORDER HEIGHT

additional cost are :


Single Section *Factory furnished sleeves.
Vertical Installation ---- 60"Wx 60"H. Sleeves are available in 10 through 20 gauge steel
MODEL and in lengths required for the specific application.
K75-T LV

L
AS
S I F I
E UNDERWRITERS LABORATORIES (UL 555) NOTE.
D
C

CLASSIFIED FIRE DAMPERS.


* Dampers furnished approximately 1/4" smaller
UL R
FIRE RESISTANCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS. than given duct dimension
* Refer to the KBE Installation Instruction and
(V) VERTICAL MOUNT supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS

MODEL K75 TYPE LB


UL CLASSIFIED 3 HOURS RATING

APPLICATION FEATURES.

MODEL K75 L IS APPROVED FOR USE *Each damper is marked with a 3 hours
IN WALLS, FLOORS AND PARTITIONS UL 555 Classified fire damper label.
WITH FIRE RESISTANCE RATINGS *Meets all UL and NFPA criteria for primary fire
OF 4 HOURS AND LESS. dampers in walls and floors with fire resistance
ratings of 4 hours and less.

STANDARD CONSTRUCTION
FRAME.
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type out of the air stream.
ORDER HEIGHT
FINISH. DAMPER SUPPLIED 1/4"
LESS THAN ORDER HEIGHT
Mill.
CLOSURE SPRINGS. (Optional)
301 Stainless Steel Spring.

FUSIBLE LINK. OVERALL HEIGHT


IS ORDER HEIGHT
Standard 165 F. Other available. PLUS "B" PAN TABLE
HEIGHT LESS 1/4".

(D
AM OR
TH PER
MOUNTING. AN SU ER
OR PP
D
W
Vertical . DE LIE IDTH
R D1
WI /4
DT " L
H) ES
S
MINIMUM SIZE.
Vertical Installation ---- 4"Wx 4"H.
4-1/4"
MAXIMUM SIZE. VARIATION.
Single Section All UL Classified fire dampers must be fabricated in
Vertical Installation ---- 60"Wx 53"H. accordance with UL procedures. Available variation
are limited to those incorporated in the approved
OVERALL DAMPER HEIGHT

procedures. Approved variations available at


additional cost are :
ORDER HEIGHT

*Factory furnished sleeves.


S I F I
AS
L E UNDERWRITERS LABORATORIES (UL 555)
MODEL
Sleeves are available in 10 through 20 gauge steel
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTANCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
K75 LBV and in lengths required for the specific application.

NOTE.
* Dampers furnished approximately 1/4" smaller
than given duct dimension
(V) VERTICAL MOUNT * Refer to the KBE Installation Instruction and
supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS
MODEL K75-T TYPE LB
UL CLASSIFIED 3 HOURS RATING

APPLICATION FEATURES.

MODEL K75-T L IS APPROVED FOR USE *Each damper is marked with a 3 hours
IN WALLS, FLOORS AND PARTITIONS UL 555 Classified fire damper label.
WITH FIRE RESISTANCE RATINGS *Meets all UL and NFPA criteria for primary fire
OF 4 HOURS AND LESS. dampers in walls and floors with fire resistance
ratings of 4 hours and less.

STANDARD CONSTRUCTION
FRAME.
4-3/8 " Maximum X 20 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type out of the air stream. ORDER HEIGHT
DAMPER SUPPLIED 1/4"
FINISH. LESS THAN ORDER HEIGHT

Mill.
CLOSURE SPRINGS. (Optional)
301 Stainless Steel Spring

OVERALL HEIGHT
FUSIBLE LINK. IS ORDER HEIGHT
PLUS "B" PAN TABLE
Standard 165 F. Other available. HEIGHT LESS 1/4".

(D
AM OR
TH PER D
AN SU ER
MOUNTING. OR PP W
DE LIE IDTH
R D1
Vertical . WI /4
DT " L
H) ES
S

MINIMUM SIZE.
Vertical Installation ---- 4"Wx 4"H. VARIATION.
4-3/8"
All UL Classified fire dampers must be fabricated in
MAXIMUM SIZE. accordance with UL procedures. Available variation
are limited to those incorporated in the approved
Vertical Installation ---- 60"Wx 53"H. procedures. Approved variations available at
additional cost are :
OVERALL DAMPER HEIGHT

*Factory furnished sleeves.


Sleeves are available in 10 through 20 gauge steel
ORDER HEIGHT

and in lengths required for the specific application.


MODEL
K75-T BV NOTE.
S I F I
* Dampers furnished approximately 1/4" smaller
AS E UNDERWRITERS LABORATORIES (UL 555)
L
than given duct dimension
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTANCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
* Refer to the KBE Installation Instruction and
supplements for complete installation details.
(V) VERTICAL MOUNT
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS
MODEL K75 TYPE LC, LCR & LCO
UL CLASSIFIED 3 HOURS RATING

APPLICATION FEATURES.

MODEL K75 L IS APPROVED FOR USE IN *Each damper is marked with a 3 hours
WALLS, FLOORS AND PARTITIONS WITH UL 555 Classified fire damper label.
FIRE RESISTANCE RATINGS OF 4 HOURS *Meets all UL and NFPA criteria for primary fire
AND LESS. dampers in walls and floors with fire resistance
ratings of 4 hours and less.

STANDARD CONSTRUCTION OR
DE "C
R O"
HE
FRAME. IG
HT OV
AL
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type out of the air stream.
OR "
FINISH. DE CO"
R
WI
Mill. DT
H
CLOSURE SPRINGS. (Optional) RE
OR
301 Stainless Steel Spring. DE "C CT
AN RO
R " GL UN
HE E
IG D
HT
FUSIBLE LINK.
Standard 165 F. Other available.
OR
DE "C"
MOUNTING. R
WI
DT
Vertical . H "
OR CR"
DE
R
DI
MINIMUM SIZE. A.
4-1/4"
Model K75L C ---- 4"Wx 4"H.
VARIATION.
Model K75L CR ---- diameter 3".
All UL Classified fire dampers must be fabricated in
Model K75L CO ---- diameter 3".
accordance with UL procedures. Available variation
MAXIMUM SIZE. are limited to those incorporated in the approved
procedures. Approved variations available at
Model K75LC Single Section:
Damper Supplied 1/4" Less

additional cost are :


Overall Damper Height

Than Order Height


Order Height

Vertical Installation ---- 60"Wx 60"H. *Factory furnished sleeves.


Models
Sleeves are available in 10 through 20 gauge steel
Model K75LCR & LCO Single Section K75 LCV and in lengths required for the specific application.
Vertical Installation ---- Diameter 53" K75 LCRV
K75 LCOV NOTE.
* Dampers furnished approximately 1/4" smaller
than given duct dimension
L
AS
S I F I
E UNDERWRITERS LABORATORIES (UL 555) * Refer to the KBE Installation Instruction and
Typical
D
C

CLASSIFIED FIRE DAMPERS.


supplements for complete installation details.
UL R
FIRE RESISTANCE RATED 3 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
2-1/2"

1"
(V) VERTICAL MOUNT
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS
MODEL K75-T TYPE LC, LCR & LCO
UL CLASSIFIED 3 HOURS RATING

FEATURES.
APPLICATION
*Each damper is marked with a 3 hours
MODEL K75-T L IS APPROVED FOR USE IN UL 555 Classified fire damper label.
WALLS, FLOORS AND PARTITIONS WITH *Meets all UL and NFPA criteria for primary fire
FIRE RESISTANCE RATINGS OF 4 HOURS dampers in walls and floors with fire resistance
AND LESS. ratings of 4 hours and less.

STANDARD CONSTRUCTION
OR
FRAME. DE "C
R O"
HE
4-3/8 " Maximum X 20 gauge Galvanized steel channel. IG OV
HT AL
BLADES.
22 gauge Galvanized steel curtain type out of the air stream.
FINISH.
OR "
Mill. DE CO"
R
WI
CLOSURE SPRINGS. (Optional) DT
H
301 Stainless Steel Spring.
OR RE
DE "C CT
R " AN RO
GL
FUSIBLE LINK. HE
IG E UN
D
HT
Standard 165 F. Other available.

MOUNTING.
OR
Vertical . DE "C"
R
WI
DT
H
MINIMUM SIZE. "
OR CR"
DE
Model K75-T LC ---- 4"Wx 4"H. R
DI
A.
Model K75-T LCR ---- diameter 3".
Model K75-T LCO ---- diameter 3".
4-3/8" VARIATION.
MAXIMUM SIZE. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
Model K75-T LC Single Section:
are limited to those incorporated in the approved
Vertical Installation ---- 58"Wx 52"H.
procedures. Approved variations available at
Model K75-T LCR & LCO Single Section additional cost are :
Damper Supplied 1/4" Less

Vertical Installation ---- Diameter 53" *Factory furnished sleeves.


Overall Damper Height

Than Order Height


Order Height

Sleeves are available in 10 through 20 gauge steel


Models and in lengths required for the specific application.
K75-T LCV
K75-T LCRV NOTE.
L
AS
S I F I
E UNDERWRITERS LABORATORIES (UL 555) K75-T LCOV * Dampers furnished approximately 1/4" smaller
D
C

CLASSIFIED FIRE DAMPERS.

UL FIRE RESISTANCE RATED 3 HOURS.


FOR USE IN UL CLASSIFIED BUILDING
than given duct dimension
R

MATERIALS RATED 4 HOURS OR LESS. * Refer to the KBE Installation Instruction and
Typical
supplements for complete installation details.
2-1/2"

1"
(V) VERTICAL MOUNT
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS

MODEL K75 SC TYPE L & LB


(304 STAINLESS STEEL CONSTRUCTION)
UL CLASSIFIED 3 HOURS RATING

APPLICATION FEATURES.

MODEL K75 L IS APPROVED FOR USE *Each damper is marked with a 3 hours
IN WALLS, FLOORS AND PARTITIONS UL 555 Classified fire damper label.
WITH FIRE RESISTANCE RATINGS *Meets all UL and NFPA criteria for primary fire
FOR 4 HOURS AND LESS. dampers in walls and floors with fire resistance
ratings of 4 hours and less.

STANDARD CONSTRUCTION
FRAME.
4-3/8 " Maximum X 22 gauge stainless steel channel. Order Height
BLADES. (Damper supplied 1/4"
less than order height)
22 gauge stainless steel curtain type in the air stream.
FINISH.
Mill.
CLOSURE SPRINGS. (Optional) (D
301 Stainless Steel Spring . AM
PE
RS
UP
PL
IED OR
FUSIBLE LINK. 1/4
"L
DE
RW
ES IDT
Standard 165 F. Other available. ST H
HA
NO
RD
ER
WI
MOUNTING. DT
H)
Vertical .
4-3/8" 4-3/8"
VARIATION.
MINIMUM SIZE. All UL Classified fire dampers must be fabricated in
Vertical Installation ---- 4"Wx 4"H. accordance with UL procedures. Available variation
are limited to those incorporated in the approved
procedures. Approved variations available at
MAXIMUM SIZE.
ORDER HEIGHT
ORDER HEIGHT

additional cost are :


Single Section *Factory furnished sleeves.
Vertical Installation ---- 60"Wx 60"H. Sleeves are available in 10 through 20 gauge steel
MODEL MODEL and in lengths required for the specific application.
K75 SC LV K75 SC LBV

NOTE.
AS
S I F I
E
* Dampers furnished approximately 1/4" smaller
L UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTANCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
* Refer to the KBE Installation Instruction and
(V) VERTICAL MOUNT (V) VERTICAL MOUNT supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS

MODEL K75 SB TYPE L & LB


(304 STAINLESS STEEL BLADES)
UL CLASSIFIED 3 HOURS RATING

APPLICATION FEATURES.

MODEL K75 L IS APPROVED FOR USE *Each damper is marked with a 3 hours
IN WALLS, FLOORS AND PARTITIONS UL 555 Classified fire damper label.
WITH FIRE RESISTANCE RATINGS *Meets all UL and NFPA criteria for primary fire
FOR 4 HOURS AND LESS. dampers in walls and floors with fire resistance
ratings of 4 hours and less.

STANDARD CONSTRUCTION
FRAME.
4-1/4 " Maximum X 22 gauge galvanized steel channel.
BLADES. Order Height
22 gauge stainless steel curtain type in the air stream. (Damper supplied 1/4"
less than order height)
FINISH.
Mill.
CLOSURE SPRINGS. (Optional)
301 Stainless Steel Spring .
(D
AM
PE
RS
FUSIBLE LINK. UP
PL
IED OR
Standard 165 F. Other available. 1/4
"L
DE
RW
ES IDT
ST H
HA
NO
RD
MOUNTING. ER
WI
DT
Vertical . H)

4-1/4" 4-1/4"
MINIMUM SIZE. VARIATION.
Vertical Installation ---- 4"Wx 4"H. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MAXIMUM SIZE.
procedures. Approved variations available at
Single Section
ORDER HEIGHT
ORDER HEIGHT

additional cost are :


Vertical Installation ---- 60"Wx 60"H.
*Factory furnished sleeves.
Sleeves are available in 10 through 20 gauge steel
MODEL MODEL and in lengths required for the specific application.
K75 SB LV K75 SB LBV

NOTE.
AS
S I F I
E
* Dampers furnished approximately 1/4" smaller
L UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTANCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
* Refer to the KBE Installation Instruction and
(V) VERTICAL MOUNT (V) VERTICAL MOUNT supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

MODEL K75
CURTAIN TYPE FIRE DAMPER PERFORMANCE DATA
Free Area and Static Friction Loss at various velocities.
DAMPER FREE AREA (SQ FT)
HEIGHT WIDTH (INCHES) HEIGHT WIDTH (INCHES)
(INCHES) (INCHES)
6" 12" 18 " 24 " 30" 36 " 42 " 48" 54" 60 " 6" 12" 18 " 24 " 30 " 36 " 42 " 48" 54" 60 "
6" .14 .33 .52 .70 .89 1.1 1.3 1.5 1.7 1.8 6" .16 .38 .60 .81 1.0 1.3 1.5 1.7 1.9 2.1
12" .31 .72 1.1 1.5 1.9 2.4 2.8 3.2 3.5 4.0 12" .34 .81 1.3 1.8 2.2 2.7 3.2 3.6 4.1 4.6

18 " .48 1.1 1.7 2.4 3.0 3.7 4.3 4.9 5.6 6.2 18 " .53 1.3 2.0 2.7 3.4 4.1 4.8 5.6 5.6 7.0

24 " .65 1.5 2.4 3.2 4.1 5.0 5.8 6.7 7.5 8.4 24 " .72 1.7 2.7 3.6 4.6 5.6 6.5 7.5 7.5 9.4
30 " .82 1.9 3.0 4.1 5.2 6.3 7.3 8.4 9.5 10.6 30 " .91 2.1 3.3 4.6 5.8 7.0 8.2 9.4 10.7 11.9

36 " .99 2.3 3.6 4.9 6.3 7.6 8.9 10.2 11.5 12.8 36 " 1.1 2.6 4.0 5.5 7.0 8.4 9.9 11.4 12.8 14.3
42 " 1.2 2.7 4.2 5.8 7.3 8.8 10.4 11.9 13.4 15.0 42 " 1.3 3.0 4.7 6.4 8.2 9.9 11.6 13.3 15.0 16.8
48 " 1.3 3.1 4.9 6.6 8.4 10.2 11.9 13.7 15.5 17.2 48 " 1.5 3.4 5.4 7.4 9.3 11.3 13.3 15.3 17.2 19.2

54 " 1.5 3.5 5.5 7.5 9.5 11.5 13.5 15.5 17.5 19.4 54 " 1.7 3.9 6.1 8.3 10.5 12.8 15.0 17.2 19.4 21.6

60 " 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.4 21.7
TYPE LB
TYPE L

Free Area is Equal to Nominal Duct Area for Type-LC dampers.


To find pressure drop compute FREE AREA VELOCITY
intersect desired damper type curve and extend line
perpendicular to velocity lines down to Static Pressure Drop (in.wg.)

cfm = Free Area Velocity (FAV)


PRESSURE DROP CURVE free area
4000 in feet per min
EXAMPLE:
TYPE "LC" A 24" x 24" type-L damper is required for a
TYPE "LB" 3,000 cfm application:

FAV= 3,000 = 937 fpm


3.2 Square Feet
3000 TYPE "L"
by locating 937 fpm on the
FREE AREA VELOCITY

"A" damper curve and following


the vertical intersection point
down to the bottom of the
graph, read .041 in.wg. static pressure drop.

2000 cfm= cubic feet per minute


fpm= feet per minute
FAV= free area velocity
SP= Static Pressure
1500 P= Pressure difference or pressure drop
FA= Free Area
1000
Metric system conversions:
800
Multiply cfm by .4719 to obtain liters per second
600 fpm by .00508 for meters per second
in. wg. by .2486 to obtain kilopascals
400 sq.ft. by .0929 for square meters
200 Test data in accordance with AMCA Std 500
.01
.02
.03
.04
.05
.06
.07
.08
.09
1.0

2.0

3.0

4.0

Static Pressure Drop (in. wg.)


kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS


INSTALLATION AND MAINTENANCE INSTRUCTIONS
3 HOURS RATED, UL CLASSIFIED FIRE DAMPER
FOR USE IN FIRE BARRIERS WITH RATINGS OF 4 HOURS AND LESS

INSPECTION INSTALLATION
Inspect for shipping damage. The basic intent of a proper installation is to secure
Inspect for proper size and model. the fire damper in, not to, the opening in such a
Inspect installed damper for proper orientation, as stated manner as to prevent distortion and disruption of the
on damper label. damper operation by allowing the fire damper in
Inspect for obstructions which could interfere with free openings to expand and the connecting duct to
operation and complete closure. separate in the event of the collapse of the hanging
Manually cycle the damper to verify proper operation. system. The fire damper must be positioned within
the masonry, block or gypsum wallboard fire barrier.

TYPICAL WALL INSTALLATION


DAMPER TO SLEEVE ATTACHMENT
MIN. 1" OVERLAP A Sleeve shall be used of sufficient length to permit direct
ON ALL SIDES AND attachment of perimeter mounting angles.
CORNERS
This damper can be supplied with factory mounted sleeve.
SEE NOTE ON
CLEARANCE If the sleeve is not factory supplied, it must be attached on both
SEE NOTE ON sides of the damper by one of the following methods:
REVERSE ANGLE
Secure with 1/4" dia. bolts and nuts or by welding with
beads 1/2" in length, or with No. 10 steel sheet metal
screws, or 3/16" steel rivets. Fasteners shall be 8"maximum
on centers. Fasteners cannot be placed where they will interfere
with damper operation.
Gaps at corners between the damper and its sleeve must be small
enough to prohibit the passage of an 1/8" diameter rod through the
entire depth of the gap between two damper panels and its sleeve.

SLEEVE THICKNESS
Sleeves shall be the same gauge or heavier as the
SEE NOTE ON
DAMPER TO SLEEVE duct to which it is attached. Gauges shall conform to
ATTACHMENT AND SMACNA or ASHRAE duct standards. Damper sleeve
SLEEVE GAUGE
REQUIREMENTS can be no thicker than 10 GA steel. On type C dampers,
the sleeve must be 18 GA. or heavier.
EXPANSION CLEARANCE
The opening in the wall or floor for the fire damper shall be sized
SEE NOTE so as to provide expansion clearance between the sleeve and
ON DUCT
CONNECTION
opening. Clearances do not vary with walls constructed of
different materials. A minimum of 1/8" per foot of overall
damper/sleeve width and height is required. The maximum
3" MIN. FOR DUCT opening size shall not exceed 1/8" per foot plus 1", minimum
CONNECTION AND
MTG. ANGLES total clearance shall be at least 1/4" larger than the overall
assembly.
6" MAX.
S I F I
16" MAX. WHEN AS E
L
INSTALLATION INSTRUCTIONS
D
C

FACTORY INSTALLED
ACCESS DOOR
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
WALL MOUNT SHOWN (VERTICAL INSTALLATION)
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS

MODEL K75-Dy TYPE A


UL CLASSIFIED 1-1/2 HOURS RATING
FOR USE IN DYNAMIC SYSTEM

APPLICATION FEATURES.

MODEL K75-Dy IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 1-1/2 hours
LESS THAN 3 HOURS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of less than 3 hours.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM

STANDARD CONSTRUCTION Order Height


(Damper supplied 1/4"
FRAME. less than order height)
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type in the air stream.
FINISH. (D
AM
PE
Mill. RS
UP
PL
CLOSURE SPRINGS. IED
1/4
OR
DE
RW
301 Stainless Steel Spring. "L IDT
ES H
ST
HA
FUSIBLE LINK. NO
RD
Standard 165 F. Other available. ER
WI
DT
H)

MOUNTING. 4-1/4"
Vertical .
VARIATION.
All UL Classified fire dampers must be fabricated in
MINIMUM SIZE. accordance with UL procedures. Available variation
Vertical Installation ---- 4"Wx 4"H. are limited to those incorporated in the approved
ORDER HEIGHT

procedures. Approved variations available at


MAXIMUM SIZE. additional cost are :
Vertical Installation ---- 24"Wx 24"H. *Factory furnished sleeves.
MODEL Sleeves are available in 10 through 20 gauge steel
K75-Dy-A
and in lengths required for the specific application.

NOTE.
S I F I
* Dampers furnished approximately 1/4" smaller
AS
L E UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C

CLASSIFIED FIRE DAMPERS FOR USE IN

UL R
DYNAMIC SYSTEM.
FIRE RESISTANCE RATED 1-1/2 HOUR.
(V) VERTICAL MOUNT
* Refer to the KBE Installation Instruction and
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS

MODEL K75-Dy TYPE B


UL CLASSIFIED 1-1/2 HOURS RATING
FOR USE IN DYNAMIC SYSTEM

APPLICATION FEATURES.

MODEL K75-Dy IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 1-1/2 hours
LESS THAN 3 HOURS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of less than 3 hours.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM

STANDARD CONSTRUCTION
ORDER HEIGHT
FRAME. DAMPER SUPPLIED 1/4"
LESS THAN ORDER HEIGHT
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type out of the air stream.
FINISH.
Mill. OVERALL HEIGHT
IS ORDER HEIGHT
CLOSURE SPRINGS. PLUS "B" PAN TABLE
HEIGHT LESS 1/4".
301 Stainless Steel Spring.
(D
AM OR
FUSIBLE LINK. TH PER
AN SU ER
D
Standard 165 F. Other available. OR PP W
DE LIE IDTH
R D1
WI /4
DT " L
H) ES
MOUNTING. S
4-1/4"
Vertical .
VARIATION.
All UL Classified fire dampers must be fabricated in
MINIMUM SIZE. accordance with UL procedures. Available variation
Vertical Installation ---- 4"Wx 4"H. are limited to those incorporated in the approved
OVERALL DAMPER HEIGHT

procedures. Approved variations available at


MAXIMUM SIZE. additional cost are :
ORDER HEIGHT

Vertical Installation ---- 24"Wx 24"H. *Factory furnished sleeves.


Sleeves are available in 10 through 20 gauge steel
MODEL
K75-Dy-B and in lengths required for the specific application.

NOTE.
S I F I
* Dampers furnished approximately 1/4" smaller
AS
L E UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C

CLASSIFIED FIRE DAMPERS FOR USE IN

UL R
DYNAMIC SYSTEM.
FIRE RESISTANCE RATED 1-1/2 HOUR. (V) VERTICAL MOUNT
* Refer to the KBE Installation Instruction and
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS

MODEL K75-Dy TYPE C, CR & CO


UL CLASSIFIED 1-1/2 HOURS RATING
FOR USE IN DYNAMIC SYSTEM

APPLICATION FEATURES.
MODEL K75-Dy IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 1-1/2 hours
LESS THAN 3 HOURS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of less than 3 hours.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM OR
DE "C
R O"
HE
IG OV
HT AL

STANDARD CONSTRUCTION
FRAME. OR "
DE CO"
4-1/4 " Maximum X 22 gauge Galvanized steel channel. R
WI
DT
BLADES. H
22 gauge Galvanized steel curtain type out of the air stream. O RE
RD " CT
ERC" AN
FINISH. HE GL
E
RO
UN
IG D
Mill. HT

CLOSURE SPRINGS.
301 Stainless Steel Spring.
OR
FUSIBLE LINK. DE "C"
R
Standard 165 F. Other available. WI
DT
H "
OR CR"
4-1/4" DE
MOUNTING. R
DI
A.
Vertical
VARIATION.
MINIMUM SIZE. All UL Classified fire dampers must be fabricated in
Model K75 C ---- 4"Wx 4"H. accordance with UL procedures. Available variation
Model K75 CR ---- diameter 3". are limited to those incorporated in the approved
Damper Supplied 1/4" Less

Model K75 CO ---- diameter 3".


Overall Damper Height

procedures. Approved variations available at


Than Order Height
Order Height

additional cost are :


MAXIMUM SIZE. Models *Factory furnished sleeves.
K75-Dy C Sleeves are available in 10 through 20 gauge steel
Model K75C Single Section:
K75-Dy CR
Vertical Installation ---- 24"Wx 24"H. K75-Dy CO and in lengths required for the specific application.
Model K75CR & CO Single Section NOTE.
Vertical Installation ---- Diameter 24" * Dampers furnished approximately 1/4" smaller
AS
S I F I Typical than given duct dimension
E UNDERWRITERS LABORATORIES (UL 555)
L 2-1/2" * Refer to the KBE Installation Instruction and
D
C

CLASSIFIED FIRE DAMPERS FOR USE IN

UL R
DYNAMIC SYSTEM.
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
supplements for complete installation details.
MATERIALS RATED 2 HOURS OR LESS. 1"
(V) VERTICAL MOUNT
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS
MODEL K75-Dy- SB TYPE A or B
(304 STAINLESS STEEL BLADES)
UL CLASSIFIED 1-1/2 HOURS RATING

APPLICATION FEATURES.

MODEL K75-Dy IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 1-1/2 hours
LESS THAN 3 HOURS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of less than 3 hours.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM

STANDARD CONSTRUCTION Order Height


(Damper supplied 1/4"
less than order height)
FRAME.
4-1/4 " Maximum X 22 gauge galvanized steel channel.
BLADES.
22 gauge 304 stainless steel curtain type in the air stream.
(D
FINISH. AM
PE
Mill. RS
UP
PL
IED
CLOSURE SPRINGS. 1/4
OR
DE
RW
"L IDT
301 Stainless Steel Spring. ES
ST H
HA
NO
FUSIBLE LINK. RD
4-1/4" ER
Standard 165 F. Other available. 4-1/4" WI
DT
H)

VARIATION.
MOUNTING. All UL Classified fire dampers must be fabricated in
Vertical .
accordance with UL procedures. Available variation
ORDER HEIGHT
ORDER HEIGHT

are limited to those incorporated in the approved


MINIMUM SIZE. procedures. Approved variations available at
Vertical Installation ---- 4"Wx 4"H. additional cost are :
MODEL MODEL *Factory furnished sleeves.
MAXIMUM SIZE. K75-Dy-SB-A K75-Dy-SB-B
Sleeves are available in 10 through 20 gauge steel
For Type A and in lengths required for the specific application.
Vertical Installation ---- 24"Wx 24"H.
For Type B NOTE.
Vertical Installation ---- 24"Wx 24"H. * Dampers furnished approximately 1/4" smaller
(V) VERTICAL MOUNT (V) VERTICAL MOUNT than given duct dimension
* Refer to the KBE Installation Instruction and
S I F I
AS
L E UNDERWRITERS LABORATORIES (UL 555) supplements for complete installation details.
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

MODEL K75
CURTAIN TYPE FIRE DAMPER PERFORMANCE DATA
Free Area and Static Friction Loss at various velocities.
DAMPER FREE AREA (SQ FT)
HEIGHT WIDTH (INCHES) HEIGHT WIDTH (INCHES)
(INCHES) (INCHES)
6" 12" 18 " 24 " 30" 36 " 42 " 48" 54" 60 " 6" 12" 18 " 24 " 30 " 36 " 42 " 48" 54" 60 "
6" .14 .33 .52 .70 .89 1.1 1.3 1.5 1.7 1.8 6" .16 .38 .60 .81 1.0 1.3 1.5 1.7 1.9 2.1
12" .31 .72 1.1 1.5 1.9 2.4 2.8 3.2 3.5 4.0 12" .34 .81 1.3 1.8 2.2 2.7 3.2 3.6 4.1 4.6

18 " .48 1.1 1.7 2.4 3.0 3.7 4.3 4.9 5.6 6.2 18 " .53 1.3 2.0 2.7 3.4 4.1 4.8 5.6 5.6 7.0

24 " .65 1.5 2.4 3.2 4.1 5.0 5.8 6.7 7.5 8.4 24 " .72 1.7 2.7 3.6 4.6 5.6 6.5 7.5 7.5 9.4
30 " .82 1.9 3.0 4.1 5.2 6.3 7.3 8.4 9.5 10.6 30 " .91 2.1 3.3 4.6 5.8 7.0 8.2 9.4 10.7 11.9

36 " .99 2.3 3.6 4.9 6.3 7.6 8.9 10.2 11.5 12.8 36 " 1.1 2.6 4.0 5.5 7.0 8.4 9.9 11.4 12.8 14.3
42 " 1.2 2.7 4.2 5.8 7.3 8.8 10.4 11.9 13.4 15.0 42 " 1.3 3.0 4.7 6.4 8.2 9.9 11.6 13.3 15.0 16.8
48 " 1.3 3.1 4.9 6.6 8.4 10.2 11.9 13.7 15.5 17.2 48 " 1.5 3.4 5.4 7.4 9.3 11.3 13.3 15.3 17.2 19.2

54 " 1.5 3.5 5.5 7.5 9.5 11.5 13.5 15.5 17.5 19.4 54 " 1.7 3.9 6.1 8.3 10.5 12.8 15.0 17.2 19.4 21.6

60 " 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.4 21.7
TYPE B
TYPE A

Free Area is Equal to Nominal Duct Area for Type-C dampers.


To find pressure drop compute FREE AREA VELOCITY
intersect desired damper type curve and extend line
perpendicular to velocity lines down to Static Pressure Drop (in.wg.)

cfm = Free Area Velocity (FAV)


PRESSURE DROP CURVE free area
4000 in feet per min
EXAMPLE:
TYPE "C" A 24" x 24" type-A damper is required for a
TYPE "B" 3,000 cfm application:

FAV= 3,000 = 937 fpm


3.2 Square Feet
3000
TYPE "A"
by locating 937 fpm on the
FREE AREA VELOCITY

"A" damper curve and following


the vertical intersection point
down to the bottom of the
graph, read .041 in.wg. static pressure drop.

2000 cfm= cubic feet per minute


fpm= feet per minute
FAV= free area velocity
SP= Static Pressure
1500 P= Pressure difference or pressure drop
FA= Free Area
1000
Metric system conversions:
800
Multiply cfm by .4719 to obtain liters per second
600 fpm by .00508 for meters per second
in. wg. by .2486 to obtain kilopascals
400 sq.ft. by .0929 for square meters
200 Test data in accordance with AMCA Std 500
.01
.02
.03
.04
.05
.06
.07
.08
.09
1.0

2.0

3.0

4.0

Static Pressure Drop (in. wg.)


kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS


INSTALLATION AND MAINTENANCE INSTRUCTIONS
1-1/2 HOUR RATED, UL CLASSIFIED FIRE DAMPER
FOR USE IN FIRE BARRIERS WITH RATINGS OF LESS THAN 3 HOURS

INSPECTION INSTALLATION
Inspect for shipping damage. The basic intent of a proper installation is to secure
Inspect for proper size and model. the fire damper in, not to, the opening in such a
Inspect installed damper for proper orientation, as stated manner as to prevent distortion and disruption of the
on damper label. damper operation by allowing the fire damper in
Inspect for obstructions which could interfere with free openings to expand and the connecting duct to
operation and complete closure. separate in the event of the collapse of the hanging
Manually cycle the damper to verify proper operation. system. The fire damper must be positioned within
the masonry, block or gypsum wallboard fire barrier.

TYPICAL WALL INSTALLATION


DAMPER TO SLEEVE ATTACHMENT
A Sleeve shall be used of sufficient length to
MIN. 1" OVERLAP
permit direct attachment of perimeter mounting angles.
ON ALL SIDES AND This damper can be supplied with factory mounted
CORNERS
sleeve. If the sleeve is not factory supplied, it
SEE NOTE ON
CLEARANCE
must be attached on both sides of the damper by one
SEE NOTE ON
of the following methods:
REVERSE ANGLE Secure with 1/4" dia. bolts and nuts or by welding with
beads 1/2" in length, or with No. 10 steel sheet metal
screws, or 3/16" steel rivets. Fasteners shall be 8"
maximum on centers. Fasteners cannot be placed
where they will interfere with damper operation.
Gaps at corners between the damper and its sleeve
must be small enough to prohibit the passage of an
1/8" diameter rod through the entire depth of the
gap between two damper panels and its sleeve.

SLEEVE THICKNESS
Sleeves shall be the same gauge or heavier as the
SEE NOTE ON duct to which it is attached. Gauges shall conform to
DAMPER TO SLEEVE SMACNA or ASHRAE duct standards. Damper sleeve
ATTACHMENT AND
SLEEVE GAUGE can be no thicker than 10 GA steel. On type
REQUIREMENTS C dampers, the sleeve must be 18 GA. or heavier.

EXPANSION CLEARANCE
The opening in the wall or floor for the fire damper
shall be sized so as to provide expansion clearance
SEE NOTE between the sleeve and opening. Clearances do not
ON DUCT
CONNECTION vary with walls constructed of different materials. A
minimum of 1/8" per foot of overall damper/sleeve
width and height is required. The maximum opening
3" MIN. FOR DUCT
CONNECTION AND
size shall not exceed 1/8" per foot plus 1", minimum
MTG. ANGLES total clearance shall be at least 1/4" larger than the
overall assembly.
6" MAX.
S I F I
AS E
L
16" MAX. WHEN INSTALLATION INSTRUCTIONS
D
C

FACTORY INSTALLED

WALL MOUNT SHOWN


ACCESS DOOR
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
FLOOR MOUNT SIMILAR
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS

MODEL K75-Dy TYPE L


UL CLASSIFIED 3 HOURS RATING
FOR USE IN DYNAMIC SYSTEM

APPLICATION FEATURES.

MODEL K75-Dy-L IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 3 hours
FOR 4 HOURS OR LESS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM

STANDARD CONSTRUCTION Order Height


(Damper supplied 1/4"
FRAME. less than order height)
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type in the air stream.
FINISH. (D
AM
PE
Mill. RS
UP
PL
CLOSURE SPRINGS. IED
1/4
OR
DE
RW
301 Stainless Steel Spring. "L IDT
ES H
ST
HA
FUSIBLE LINK. NO
RD
Standard 165 F. Other available. ER
WI
DT
H)

MOUNTING. 4-1/4"
Vertical .
VARIATION.
All UL Classified fire dampers must be fabricated in
MINIMUM SIZE. accordance with UL procedures. Available variation
Vertical Installation ---- 4"Wx 4"H. are limited to those incorporated in the approved
ORDER HEIGHT

procedures. Approved variations available at


MAXIMUM SIZE. additional cost are :
Vertical Installation ---- 24"Wx 24"H. *Factory furnished sleeves.
MODEL Sleeves are available in 10 through 20 gauge steel
K75-Dy-L
and in lengths required for the specific application.

NOTE.
S I F I
* Dampers furnished approximately 1/4" smaller
AS
L E UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C

CLASSIFIED FIRE DAMPERS FOR USE IN

UL R
DYNAMIC SYSTEM.
FIRE RESISTANCE RATED 1-1/2 HOUR.
(V) VERTICAL MOUNT
* Refer to the KBE Installation Instruction and
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS

MODEL K75-Dy TYPE LB


UL CLASSIFIED 3 HOURS RATING
FOR USE IN DYNAMIC SYSTEM

APPLICATION FEATURES.

MODEL K75-Dy- L IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 3 hours
FOR 4 HOURS OR LESS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM

STANDARD CONSTRUCTION
ORDER HEIGHT
FRAME. DAMPER SUPPLIED 1/4"
LESS THAN ORDER HEIGHT
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type out of the air stream.
FINISH.
Mill. OVERALL HEIGHT
IS ORDER HEIGHT
CLOSURE SPRINGS. PLUS "B" PAN TABLE
HEIGHT LESS 1/4".
301 Stainless Steel Spring.
(D
AM OR
FUSIBLE LINK. TH PER
AN SU ER
D
Standard 165 F. Other available. OR PP W
DE LIE IDTH
R D1
WI /4
DT " L
H) ES
MOUNTING. S
4-1/4"
Vertical .
VARIATION.
All UL Classified fire dampers must be fabricated in
MINIMUM SIZE. accordance with UL procedures. Available variation
Vertical Installation ---- 4"Wx 4"H. are limited to those incorporated in the approved
OVERALL DAMPER HEIGHT

procedures. Approved variations available at


MAXIMUM SIZE. additional cost are :
ORDER HEIGHT

Vertical Installation ---- 24"Wx 24"H. *Factory furnished sleeves.


Sleeves are available in 10 through 20 gauge steel
MODEL
K75-Dy-LB and in lengths required for the specific application.

NOTE.
S I F I
* Dampers furnished approximately 1/4" smaller
AS
L E UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C

CLASSIFIED FIRE DAMPERS FOR USE IN

UL R
DYNAMIC SYSTEM.
FIRE RESISTANCE RATED 1-1/2 HOUR. (V) VERTICAL MOUNT
* Refer to the KBE Installation Instruction and
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS

MODEL K75-Dy TYPE LC, LCR & LCO


UL CLASSIFIED 3 HOURS RATING
FOR USE IN DYNAMIC SYSTEM

APPLICATION FEATURES.
MODEL K75-Dy-L IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 3 hours
FOR 4 HOURS OR LESS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM OR
DE "C
R O"
HE
IG OV
HT AL

STANDARD CONSTRUCTION
FRAME. OR "
DE CO"
4-1/4 " Maximum X 22 gauge Galvanized steel channel. R
WI
DT
BLADES. H
22 gauge Galvanized steel curtain type out of the air stream. O RE
RD " CT
ERC" AN
FINISH. HE GL
E
RO
UN
IG D
Mill. HT

CLOSURE SPRINGS.
301 Stainless Steel Spring.
OR
FUSIBLE LINK. DE "C"
R
Standard 165 F. Other available. WI
DT
H "
OR CR"
4-1/4" DE
MOUNTING. R
DI
A.
Vertical
VARIATION.
MINIMUM SIZE. All UL Classified fire dampers must be fabricated in
Model K75 C ---- 4"Wx 4"H. accordance with UL procedures. Available variation
Model K75 CR ---- diameter 3". are limited to those incorporated in the approved
Damper Supplied 1/4" Less

Model K75 CO ---- diameter 3".


Overall Damper Height

procedures. Approved variations available at


Than Order Height
Order Height

additional cost are :


MAXIMUM SIZE. Models *Factory furnished sleeves.
K75-Dy C Sleeves are available in 10 through 20 gauge steel
Model K75C Single Section:
K75-Dy CR
Vertical Installation ---- 24"Wx 24"H. K75-Dy CO and in lengths required for the specific application.
Model K75CR & CO Single Section NOTE.
Vertical Installation ---- Diameter 24" * Dampers furnished approximately 1/4" smaller
AS
S I F I Typical than given duct dimension
E UNDERWRITERS LABORATORIES (UL 555)
L 2-1/2" * Refer to the KBE Installation Instruction and
D
C

CLASSIFIED FIRE DAMPERS FOR USE IN

UL R
DYNAMIC SYSTEM.
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
supplements for complete installation details.
MATERIALS RATED 2 HOURS OR LESS. 1"
(V) VERTICAL MOUNT
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS
MODEL K75-Dy- SB TYPE L or LB
(304 STAINLESS STEEL BLADES)
UL CLASSIFIED 3 HOURS RATING

APPLICATION FEATURES.

MODEL K75-Dy-L IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 3 hours
FOR 4 HOURS OR LESS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM

STANDARD CONSTRUCTION Order Height


(Damper supplied 1/4"
less than order height)
FRAME.
4-1/4 " Maximum X 22 gauge galvanized steel channel.
BLADES.
22 gauge 304 stainless steel curtain type in the air stream.
(D
FINISH. AM
PE
Mill. RS
UP
PL
IED
CLOSURE SPRINGS. 1/4
OR
DE
RW
"L IDT
301 Stainless Steel Spring. ES
ST H
HA
NO
FUSIBLE LINK. RD
4-1/4" ER
Standard 165 F. Other available. 4-1/4" WI
DT
H)

VARIATION.
MOUNTING. All UL Classified fire dampers must be fabricated in
Vertical .
accordance with UL procedures. Available variation
ORDER HEIGHT
ORDER HEIGHT

are limited to those incorporated in the approved


MINIMUM SIZE. procedures. Approved variations available at
Vertical Installation ---- 4"Wx 4"H. additional cost are :
MODEL MODEL *Factory furnished sleeves.
MAXIMUM SIZE. K75-Dy-SB-A K75-Dy-SB-B
Sleeves are available in 10 through 20 gauge steel
For Type A and in lengths required for the specific application.
Vertical Installation ---- 24"Wx 24"H.
For Type B NOTE.
Vertical Installation ---- 24"Wx 24"H. * Dampers furnished approximately 1/4" smaller
(V) VERTICAL MOUNT (V) VERTICAL MOUNT than given duct dimension
* Refer to the KBE Installation Instruction and
S I F I
AS
L E UNDERWRITERS LABORATORIES (UL 555) supplements for complete installation details.
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

MODEL K75
CURTAIN TYPE FIRE DAMPER PERFORMANCE DATA
Free Area and Static Friction Loss at various velocities.
DAMPER FREE AREA (SQ FT)
HEIGHT WIDTH (INCHES) HEIGHT WIDTH (INCHES)
(INCHES) (INCHES)
6" 12" 18 " 24 " 30" 36 " 42 " 48" 54" 60 " 6" 12" 18 " 24 " 30 " 36 " 42 " 48" 54" 60 "
6" .14 .33 .52 .70 .89 1.1 1.3 1.5 1.7 1.8 6" .16 .38 .60 .81 1.0 1.3 1.5 1.7 1.9 2.1
12" .31 .72 1.1 1.5 1.9 2.4 2.8 3.2 3.5 4.0 12" .34 .81 1.3 1.8 2.2 2.7 3.2 3.6 4.1 4.6

18 " .48 1.1 1.7 2.4 3.0 3.7 4.3 4.9 5.6 6.2 18 " .53 1.3 2.0 2.7 3.4 4.1 4.8 5.6 5.6 7.0

24 " .65 1.5 2.4 3.2 4.1 5.0 5.8 6.7 7.5 8.4 24 " .72 1.7 2.7 3.6 4.6 5.6 6.5 7.5 7.5 9.4
30 " .82 1.9 3.0 4.1 5.2 6.3 7.3 8.4 9.5 10.6 30 " .91 2.1 3.3 4.6 5.8 7.0 8.2 9.4 10.7 11.9

36 " .99 2.3 3.6 4.9 6.3 7.6 8.9 10.2 11.5 12.8 36 " 1.1 2.6 4.0 5.5 7.0 8.4 9.9 11.4 12.8 14.3
42 " 1.2 2.7 4.2 5.8 7.3 8.8 10.4 11.9 13.4 15.0 42 " 1.3 3.0 4.7 6.4 8.2 9.9 11.6 13.3 15.0 16.8
48 " 1.3 3.1 4.9 6.6 8.4 10.2 11.9 13.7 15.5 17.2 48 " 1.5 3.4 5.4 7.4 9.3 11.3 13.3 15.3 17.2 19.2

54 " 1.5 3.5 5.5 7.5 9.5 11.5 13.5 15.5 17.5 19.4 54 " 1.7 3.9 6.1 8.3 10.5 12.8 15.0 17.2 19.4 21.6

60 " 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.4 21.7
TYPE LB
TYPE L

Free Area is Equal to Nominal Duct Area for Type-C dampers.


To find pressure drop compute FREE AREA VELOCITY
intersect desired damper type curve and extend line
perpendicular to velocity lines down to Static Pressure Drop (in.wg.)

cfm = Free Area Velocity (FAV)


PRESSURE DROP CURVE free area
4000 in feet per min
EXAMPLE:
TYPE "LC" A 24" x 24" type-A damper is required for a
TYPE "LB" 3,000 cfm application:

FAV= 3,000 = 937 fpm


3.2 Square Feet
3000
TYPE "L"
by locating 937 fpm on the
FREE AREA VELOCITY

"A" damper curve and following


the vertical intersection point
down to the bottom of the
graph, read .041 in.wg. static pressure drop.

2000 cfm= cubic feet per minute


fpm= feet per minute
FAV= free area velocity
SP= Static Pressure
1500 P= Pressure difference or pressure drop
FA= Free Area
1000
Metric system conversions:
800
Multiply cfm by .4719 to obtain liters per second
600 fpm by .00508 for meters per second
in. wg. by .2486 to obtain kilopascals
400 sq.ft. by .0929 for square meters
200 Test data in accordance with AMCA Std 500
.01
.02
.03
.04
.05
.06
.07
.08
.09
1.0

2.0

3.0

4.0

Static Pressure Drop (in. wg.)


kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS


INSTALLATION AND MAINTENANCE INSTRUCTIONS
3 HOURS RATED, UL CLASSIFIED FIRE DAMPER
FOR USE IN FIRE BARRIERS WITH RATINGS OF 4 HOURS AND LESS

INSPECTION INSTALLATION
Inspect for shipping damage. The basic intent of a proper installation is to secure
Inspect for proper size and model. the fire damper in, not to, the opening in such a
Inspect installed damper for proper orientation, as stated manner as to prevent distortion and disruption of the
on damper label. damper operation by allowing the fire damper in
Inspect for obstructions which could interfere with free openings to expand and the connecting duct to
operation and complete closure. separate in the event of the collapse of the hanging
Manually cycle the damper to verify proper operation. system. The fire damper must be positioned within
the masonry, block or gypsum wallboard fire barrier.

TYPICAL WALL INSTALLATION


DAMPER TO SLEEVE ATTACHMENT
MIN. 1" OVERLAP A Sleeve shall be used of sufficient length to permit direct
ON ALL SIDES AND attachment of perimeter mounting angles.
CORNERS
This damper can be supplied with factory mounted sleeve.
SEE NOTE ON
CLEARANCE If the sleeve is not factory supplied, it must be attached on both
SEE NOTE ON sides of the damper by one of the following methods:
REVERSE ANGLE
Secure with 1/4" dia. bolts and nuts or by welding with
beads 1/2" in length, or with No. 10 steel sheet metal
screws, or 3/16" steel rivets. Fasteners shall be 8"maximum
on centers. Fasteners cannot be placed where they will interfere
with damper operation.
Gaps at corners between the damper and its sleeve must be small
enough to prohibit the passage of an 1/8" diameter rod through the
entire depth of the gap between two damper panels and its sleeve.

SLEEVE THICKNESS
Sleeves shall be the same gauge or heavier as the
SEE NOTE ON
DAMPER TO SLEEVE duct to which it is attached. Gauges shall conform to
ATTACHMENT AND SMACNA or ASHRAE duct standards. Damper sleeve
SLEEVE GAUGE
REQUIREMENTS can be no thicker than 10 GA steel. On type C dampers,
the sleeve must be 18 GA. or heavier.
EXPANSION CLEARANCE
The opening in the wall or floor for the fire damper shall be sized
SEE NOTE so as to provide expansion clearance between the sleeve and
ON DUCT
CONNECTION
opening. Clearances do not vary with walls constructed of
different materials. A minimum of 1/8" per foot of overall
damper/sleeve width and height is required. The maximum
3" MIN. FOR DUCT opening size shall not exceed 1/8" per foot plus 1", minimum
CONNECTION AND
MTG. ANGLES total clearance shall be at least 1/4" larger than the overall
assembly.
6" MAX.
S I F I
16" MAX. WHEN AS E
L
INSTALLATION INSTRUCTIONS
D
C

FACTORY INSTALLED
ACCESS DOOR
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
WALL MOUNT SHOWN (VERTICAL INSTALLATION)
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

SLEEVE DIMENSIONAL INFORMATION


SLEEVES
FOR CURTAIN FIRE DAMPERS AND DOORS For CURTAIN FIRE DAMPERS
1. Dampers and sleeves are always priced and ordered by
W x H or dimensions as shown. TYPE A (K75 B STANDARD)
The types B, and B-1 both require the damper to be oversized.
Actual overall dimensions can be determined by adding sleeve material
TYPE AF (K75 FLANGED STD)
thickness to the basic damper dimensions (after allowing for the TYPE B (K75 B STANDARD)
standard 1/4" damper under sizing.
2. "K" distance may be ordered at any dimension up to the sleeve TYPE B-1 (K75 B MIN. DUCTING)
length less one half the damper frame width. If "K" dimension is not
specified, "K" dimension will be provided as sleeve length (L)/2.
(Damper On Centerline)

"L" SLEEVE "L" SLEEVE


LENGTH OVERALL
SLEEVE TYPE "A" LENGTH OVERALL

"K"
STANDARD "K"
SLEEVE EDGE SLEEVE EDGE
TO DAMPER WHEN ORDERING SPECIFY: TO DAMPER
CENTER LINE CENTER LINE
WIDTH X HEIGHT X LENGTH X
GAUGE + ("K" DIMENSION)
WHEN NOT SPECIFIED, DAMPERS
WILL BE PROVIDED CENTERED
"H" SLEEVE IN SLEEVE LENGTH. (L/2) "H" SLEEVE
1-1/2
FLANGES
HEIGHT HEIGHT (4 SIDES)
(1 END)
SLEEVE TYPE "AF"
FLANGED
WHEN ORDERING SPECIFY:
WIDTH X HEIGHT X LENGTH X
"W" SLEEVE "W" SLEEVE
WIDTH
GAUGE + ("K" DIMENSION) WIDTH
WHEN NOT SPECIFIED, DAMPERS
SLEEVE GAUGE
WILL BE PROVIDED CENTERED
IN SLEEVE LENGTH. (L/2)

"L" SLEEVE
LENGTH OVERALL
"L" SLEEVE
LENGTH OVERALL "K"
SLEEVE EDGE
TO DAMPER
"K" CENTER LINE
SLEEVE EDGE
TO DAMPER SLEEVE
CENTER LINE OVERALL
HEIGHT

"H"
SLEEVE
SLEEVE HEIGHT
OVERALL
HEIGHT "H"
SLEEVE
DISTANCE IS BASED ON
HEIGHT
"B" PAN SIZING CHART.

DISTANCE IS BASED ON
1-3/4" "B" PAN SIZING CHART.

"W"
SLEEVE
WIDTH
"W"
SLEEVE
WIDTH SLEEVE TYPE "B"
SLEEVE TYPE "B-1"
WHEN ORDERING SPECIFY: WHEN ORDERING SPECIFY:
WIDTH X HEIGHT X LENGTH X WIDTH X HEIGHT X LENGTH X
GAUGE + ("K" DIMENSION) GAUGE + ("K" DIMENSION)
WHEN NOT SPECIFIED, DAMPERS WHEN NOT SPECIFIED, DAMPERS
WILL BE PROVIDED CENTERED WILL BE PROVIDED CENTERED
IN SLEEVE LENGTH. (L/2) IN SLEEVE LENGTH. (L/2)
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

SLEEVE DIMENSIONAL INFORMATION


FOR CURTAIN FIRE DAMPERS AND DOORS SLEEVES
For CURTAIN FIRE DAMPERS
1. Dampers and sleeves are always priced and ordered by
W x H or dimensions as shown. TYPE C (K75 C RECTANGLE)
The types C, CR, and CO all require the damper to be oversized. TYPE CR (K75 CR ROUND)
Actual overall dimensions can be determined by adding sleeve material
thickness to the basic damper dimensions (after allowing for the TYPE CO (K75 CO OVAL)
standard 1/4" damper under sizing.
2. "K" distance may be ordered at any dimension up to the sleeve
length less one half the damper frame width. If "K" dimension is not
specified, "K" dimension will be provided as sleeve length (L)/2.
(Damper On Centerline)
"L"
SLEEVE
LENGTH
OVERALL

"K"
SLEEVE EDGE
TO DAMPER
TYPE "CR" ROUND SLEEVE CENTER LINE

WHEN ORDERING SPECIFY:


COLLAR DIAMETER X LENGTH 2.25 STD.
X GAUGE + ("K" DIMENSION)
WHEN NOT SPECIFIED, DAMPERS
OVERALL SLEEVE
WILL BE PROVIDED CENTERED "D" HEIGHT
DIAMETER
IN SLEEVE LENGTH. (L/2)

DISTANCE IS BASED ON
MODEL K75 CR ROUND
DIA.+2" SIZING CHART.
OVERALL 1" ON THREE
SLEEVE SIDES
WIDTH
"L" SLEEVE
LENGTH OVERALL "L"
SLEEVE
LENGTH
"K" OVERALL
SLEEVE EDGE
TO DAMPER
"K"
CENTER LINE
SLEEVE EDGE
TO DAMPER
CENTER LINE
"H" 2.25
OVAL STD.
HEIGHT
2.25
OVERALL
STD.
SLEEVE
HEIGHT
OVERALL
SLEEVE
HEIGHT
"H"
RECTANGLE
HEIGHT
DISTANCE IS BASED ON
"W" "C" RECTANGLE
1" ON DISTANCE IS BASED ON SIZING CHART.
OVAL THREE OVAL SIZING CHART.
WIDTH SIDES
OVERALL MINIMUM. 1.00" MINIMUM
SLEEVE "W" TYP (4) SIDES
WIDTH RECTANGLE
WIDTH
OVERALL TYPE "C"
TYPE "CO" OVAL SLEEVE SLEEVE
WIDTH RECTANGLE SLEEVE
WHEN ORDERING SPECIFY:
WHEN ORDERING SPECIFY:
OVAL WIDTH X OVAL HEIGHT
RECTANGLE WIDTH X RECTANGLE HEIGHT
X LENGTH X GAUGE
X LENGTH X GAUGE
+ ("K" DIMENSION)
+ ("K" DIMENSION)
WHEN NOT SPECIFIED, DAMPERS
WHEN NOT SPECIFIED, DAMPERS
WILL BE PROVIDED CENTERED
WILL BE PROVIDED CENTERED
IN SLEEVE LENGTH. (L/2)
IN SLEEVE LENGTH. (L/2)
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS - THINLINE


MODEL K75 TYPE D
UL CLASSIFIED 1-1/2 HOURS RATING

FEATURES.

MODEL K75 DH * Slim profile design for minimum clearance applications.


*Each damper is marked with a 1-1/2 hours
UL 555 Classified fire damper label.
ORDER HEIGHT *Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
(H) HORIZONTAL MOUNT ratings of less than 3 hours.

APPLICATION

MODEL K75 IS APPROVED FOR USE ORDER HEIGHT


DAMPER SUPPLIED
IN WALLS, FLOORS AND PARTITIONS 1/4" LESS
WITH FIRE RESISTANCE RATINGS THAN ORDER HEIGHT

LESS THAN 3 HOURS.

STANDARD CONSTRUCTION
FRAME.
2" Maximum X 22 gauge Galvanized steel channel.
BLADES. DA
MP
22 gauge Galvanized steel curtain type in the air streeam. E
TH R SU
OR
DE
AN PP R
FINISH. OR LIE
D
WI
DT 2"
DE 1 H
Mill. R / 4
WI
DT
"L
ES "THINLINE"
H S
CLOSURE SPRINGS.
301 Stainless Steel Spring.
2"
(For Horizontal mount only, optional on vertical mount) VARIATION.
All UL Classified fire dampers must be fabricated in
FUSIBLE LINK.
accordance with UL procedures. Available variation
Standard 165 F. Other available.
are limited to those incorporated in the approved
procedures. Approved variations available at
MOUNTING.
ORDER HEIGHT

additional cost are :


Vertical or Horizontal .
*Factory furnished sleeves.
Sleeves are available in 10 through 20 gauge steel
MINIMUM SIZE. MODEL and in lengths required for the specific application.
Vertical Installation ---- 4"Wx 4"H. K75 DV

Horizontal Installation ---- 4"Wx 4"H. NOTE.


* Dampers furnished approximately 1/4" smaller
MAXIMUM SIZE. than given duct dimension
Single Section * Refer to the KBE Installation Instruction and
Vertical Installation ---- 48"Wx 49"H. (V) VERTICAL MOUNT supplements for complete installation details.
Horizontal Installation ---- 41"Wx 36"H.
S I F I
AS E UNDERWRITERS LABORATORIES (UL 555)
L
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTENCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS - THINLINE


MODEL K75 TYPE DB
UL CLASSIFIED 1-1/2 HOURS RATING

FEATURES.

MODEL K75 DBH * Slim profile design for minimum clearance applications.
*Each damper is marked with a 1-1/2 hours
UL 555 Classified fire damper label.
ORDER HEIGHT
*Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
(H) HORIZONTAL MOUNT ratings of less than 3 hours.

APPLICATION "B" PAN

MODEL K75 IS APPROVED FOR USE


IN WALLS, FLOORS AND PARTITIONS
WITH FIRE RESISTANCE RATINGS ORDER HEIGHT
LESS THAN 3 HOURS. (DAMPER SUPPLIED
1/4" LESS THAN
ORDER HEIGHT)

STANDARD CONSTRUCTION
FRAME. OVERALL HEIGHT
IS ORDER HEIGHT
2" Maximum X 22 gauge Galvanized steel channel. PLUS "B" PAN
BLADES. TABLE HEIGHT
(D LESS 1/4"
22 gauge Galvanized steel curtain type out of the air stream. AM O
PE RDE
TH R S R
FINISH. AN UP WID
OR PLIE TH
Mill. DE D
R 1/4
WI " L
CLOSURE SPRINGS. DT ES
H) S
2"
301 Stainless Steel Spring. "THINLINE"
2"
(For Horizontal mount only, optional on vertical mount) VARIATION.
All UL Classified fire dampers must be fabricated in
FUSIBLE LINK.
accordance with UL procedures. Available variation
Standard 165 F. Other available.
are limited to those incorporated in the approved
procedures. Approved variations available at
MOUNTING.
ORDER HEIGHT

additional cost are :


Vertical or Horizontal .
*Factory furnished sleeves.
Sleeves are available in 10 through 20 gauge steel
MINIMUM SIZE. MODEL and in lengths required for the specific application.
Vertical Installation ---- 4"Wx 4"H. K75 DBV

Horizontal Installation ---- 4"Wx 4"H. NOTE.


* Dampers furnished approximately 1/4" smaller
MAXIMUM SIZE. than given duct dimension
Single Section * Refer to the KBE Installation Instruction and
Vertical Installation ---- 48"Wx 44"H. (V) VERTICAL MOUNT supplements for complete installation details.
Horizontal Installation ---- 41"Wx 32"H.
S I F I
AS E UNDERWRITERS LABORATORIES (UL 555)
L
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTENCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS - THINLINE


MODEL K75 TYPE N
UL CLASSIFIED 3 HOURS RATING

APPLICATION FEATURES.

MODEL K75 IS APPROVED FOR USE * Slim profile design for minimum clearance applications.
IN WALLS, FLOORS AND PARTITIONS *Each damper is marked with a 3 hours
WITH FIRE RESISTANCE RATINGS OF UL 555 Classified fire damper label.
4 HOURS AND LESS. *Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
ratings of 4 hours and less.
STANDARD CONSTRUCTION
FRAME.
ORDER HEIGHT
2" Maximum X 22 gauge Galvanized steel channel. DAMPER SUPPLIED
BLADES. 1/4" LESS
THAN ORDER HEIGHT
22 gauge Galvanized steel curtain type in the air streeam.
FINISH.
Mill.
CLOSURE SPRINGS.
301 Stainless Steel Spring.

FUSIBLE LINK.
Standard 165 F. Other available. DA
MP
E OR
TH R SU DE
AN PP R
MOUNTING. OR LIE
DE D
WI
DT 2"
1 H
Vertical . R
WI / 4 "L "THINLINE"
DT ES
H S

MINIMUM SIZE.
2"
Vertical Installation ---- 4"Wx 4"H. VARIATION.
All UL Classified fire dampers must be fabricated in
MAXIMUM SIZE. accordance with UL procedures. Available variation
Single Section are limited to those incorporated in the approved
Vertical Installation ---- 48"Wx 49"H. procedures. Approved variations available at
ORDER HEIGHT

additional cost are :


*Factory furnished sleeves.
Sleeves are available in 10 through 20 gauge steel
MODEL and in lengths required for the specific application.
K75 NV
S I F I
AS E UNDERWRITERS LABORATORIES (UL 555)
L
NOTE.
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTENCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
* Dampers furnished approximately 1/4" smaller
than given duct dimension
* Refer to the KBE Installation Instruction and
(V) VERTICAL MOUNT supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS - THINLINE


MODEL K75 TYPE NB
UL CLASSIFIED 3 HOURS RATING

APPLICATION FEATURES.

MODEL K75 IS APPROVED FOR USE * Slim profile design for minimum clearance applications.
IN WALLS, FLOORS AND PARTITIONS *Each damper is marked with a 3 hours
WITH FIRE RESISTANCE RATINGS OF UL 555 Classified fire damper label.
4 HOURS AND LESS. *Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
ratings of 4 hours and less.
STANDARD CONSTRUCTION "B" PAN

FRAME.
2" Maximum X 22 gauge Galvanized steel channel.
BLADES.
ORDER HEIGHT
22 gauge Galvanized steel curtain type out of the air
(DAMPER SUPPLIED
stream. 1/4" LESS THAN
FINISH. ORDER HEIGHT

Mill.
CLOSURE SPRINGS.
Optional Stainless Steel Negator Spring. OVERALL HEIGHT
IS ORDER HEIGHT
PLUS "B" PAN
TABLE HEIGHT
FUSIBLE LINK. (D LESS 1/4"
AM O
Standard 165 F. Other available. PE RDE
TH R S R
AN UP WID
OR PLIE TH
MOUNTING. DE D
R 1/4
WI " L
Vertical . DT ES
H) S
2"
"THINLINE"
2"
MINIMUM SIZE. VARIATION.
Vertical Installation ---- 4"Wx 4"H. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available varaition
MAXIMUM SIZE. are limited to those incorporated in the approved
Single Section procedures. Approved variations available at
Vertical Installation ---- 48"Wx 44"H. additional cost are :
ORDER HEIGHT

*Factory firnished sleeves.


Sleeves are available in 10 through 20 gauge steel
MODEL and in lengths required for the specific application.
K75 NBV
S I F I
AS E UNDERWRITERS LABORATORIES (UL 555)
L
NOTE.
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTENCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
* Dampers furnished approximately 1/4" smaller
than given duct dimension
* Refer to the KBE Installation Instruction and
(V) VERTICAL MOUNT supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

MODEL K75 D (THINLINE)


OPTIONAL MOUNTING TABS

MOUNTING TABS (4) PCS MOUNTING TABS (4) PLCS


22 GAUGE X 1/2 X 3" LONG 22 GAUGE X 1/2 X 3" LONG
0.19 DIAMETER RIVETS ON CENTER 0.19 DIAMETER RIVETS ON CENTER
(SHOWN IN INSTALLATION POSITION) (SHOWN IN SHIPPING POSITION)

ORDER HEIGHT ORDER HEIGHT


DAMPER SUPPLIED DAMPER SUPPLIED
1/4" LESS 1/4" LESS
THAN ORDER HEIGHT THAN ORDER HEIGHT

DA DA
MP MP
E OR
TH R SU DE E
TH R SU
OR
DE
AN P R AN R
OR PLIE WI
DT 2" P
OR PLIE WI 2"
DE D H DE D DT
R 1 H
WI /4" L "THINLINE" R 1/4
DT
H SS
E WI "
DT LES "THINLINE"
H S

MODEL K75 D (THINLINE)


OPTIONAL MOUNTING TAB
INSTALLATION

ORDER
HEIGHT
(-1/4")

ORDER
MODEL FLOOR HEIGHT
MODEL
2"
K75DH PARTITION (-1/4")
HORIZONTAL K75DV
MOUNT VERTICAL
MOUNT

2"

WALL
PARTITION
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

SLEEVE INSTALLATION INSTRUCTION


ATTACHING FIRE DAMPERS TO SLEEVES
ATTACHMENTS
Fire dampers must be attached to sleeves as shown in fig. 1.
All four sides of the damper frame must be attached to the NOTE: ATTACHMENTS MUST NOT
ENTER BLADE CHANNEL OR THEY MAY CAUSE
sleeve with one row of attachments on each side of the blade
INTERFERENCE WITH BLADE CLOSURE. NARROW LINE
channel. Attachments must be spaced a maximum of 6" on BLADE
AND ULTRA THIN DAMPERS DO NOT HAVE FLANGE
CHANNEL
centers and a maximum of 2" from corners. A minimum of FOR ATTACHMENTS AND MUST BE WELDED TO
4 attachments (2 on each side of the blade channel) per side SLEEVE.
(16 per damper) are required. One of the methods of attachment
shown below must be used. 2" M
AX
- tack or spot welds
- No.10 sheet metal screws
- 1/4" bolts and nuts
6" M
AX
- 3/16" steel pop rivets

SECURING FIRE DAMPER AND SLEEVES TO


WALL AND FLOOR OPENINGS
Fire damper and sleeve assemblies must be installed in wall
and floor openings using retaining angles on each side of the wall ATT
AC
EV HM
or floor as described below: FIG EN ENT
LY S
.1 SP CAN
- Retaining angles must be a minimum of AC
ED BE S
TAG
16 gauge steel and have a minimum of 1-1/2" x 1-1/2" legs. GE
RE
DO
- Retaining angles must be attached to the sleeve using R

the procedures and methods described hereunder.


The angles must be attached to all 4 sides of the sleeve
with butt joints at each corner. A minimum of two WALL OR FLOOR
attachments are required on each side, top and bottom.
The angles need not be attached to each other at the 1"
corners. MIN LAP
ER
- Retaining angles must completely cover the clearance G OV
NIN
space between the sleeve and the wall / floor opening, E TAI E
R GL
AN
plus overlap the wall / floor a minimum of 1". This
E
coverage includes all corners (fig. 2). EV
SLE
- Retaining angles should not be fastened CT
to the wall / floor material. The angles should only DU
sandwich the wall / floor and allow for damper / sleeve
expansion during periods of intense heat.
2" M
- For grille installation, angle legs may be reversed and AX

one leg inserted into the wall / floor opening providing 6" M
AX
the required clearance is maintained between angle leg
fasteners and the wall / opening. 6" M
AX
CONNECTING DUCTS TO FIRE DAMPER
2" M
SLEEVE AX

Any duct connection other than breakaway is considered


rigid. The connections shown on next pages are considered
breakaway. Factory furnished duct collars on type R and FIG. 2
CR fire dampers are also considered breakaway.

MULTIPLE SECTION FIRE DAMPERS L


AS
S I F I
E
INSTALLATION INSTRUCTIONS
D
C

When multiple sections are shipped unassembled, installer


shall fasten dampers together.
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS


BREAKAWAY CONNECTIONS

Breakaway Style Transverse Joints


Transverse joints illustrated at right have always been
approved as breakaway connections . SMACNA testing
has also approved the following variations as breakaway
connections. PLAIN "S" SLIP HEMMED "S" SLIP DOUBLE "S" SLIP

Standing "S" joints can be applied with no. 10


sheetmetal screws (through joint and duct) subject to
the following limitations: Maximum 2 screws in each
side and in bottom joint. INSIDE SLIP JOINT PLAIN "S" SLIP STANDING "S" (ALT.)

Transverse joints illustrated can


be applied as top and bottom
joints with Drive Slip - side joints
in duct heights up to 20 inches.
DRIVE SLIP JOINT STANDING "S" (ALT.) STANDING "S" STANDING "S"
(BAR REINFORCED) (BAR REINFORCED)
Round and Oval Duct Breakaway Connections
Round or flat oval ducts connected to type R, CR or CO damper collars may use no. 10 sheetmetal screws as follows:
Ducts to 22" wide (or dia.) and smaller may use 3 screws.
Ducts larger than 22" wide (or dia.) may use 5 screws.
NOTE: All breakaway connections described may have duct sealant applied in accordance with SMACNA reccomendations.

6" long 1/16" max. Fire Damper


thickness plastic
Manufactured Flanged System Sleeve
cleats 12" c-c
Breakaway Connections (min. 1 per side)

Flanged system angles


Flanged connection systems manufactured
by Ductmate, Ward, and Nexus are
approved as breakaway connections (Attach per
when installed as illustrated. manufacturers
instructions)
S I F I
AS E
L Do not bolt corners
INSTALLATION INSTRUCTIONS
D
C

UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS Duct
Neoprene Gasket
between all angles

PROPRIETARY FLANGE SYSTEM STD. CLIP


CLIP SPACING
LENGTH
BREAKAWAY CONNECTIONS
6" 6" 9" 6"
(TDC by Lockformer, TDF by Engle)
60" DUCT
3 REQD

7" 7"
48" DUCT
TDC and TDF systems are approved as
3 REQD
breakaway connections when installed
5" 5"
as described in the TDC or TDF SLEEVE DUCT 36" DUCT
addendum to the SMACNA Duct
3 REQD
construction Standards except the
5" 5"
corners may not be bolted. Standard 6"
24" DUCT
metal clip may be used with spacing as TYPICAL TDC/TDF JOINT
shown in diagram. 2 REQD

18" DUCT
& SMALLER CL
1 REQD
DUCT
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS

MOUNTING ANGLES DUCT CONNECTION


The installation of the damper and all duct connections
Secure mounting angles to the sleeve and not to the wall or floor.
to the damper sleeve shall conform to NFPA-90A and the SMACNA Fire,
Mounting angles to frame the four sides of the sleeve on both faces.
Smoke and Radiation Damper Installation Guide. All duct connections shall
When reverse mounting angles are used the size of the opening must
also conform to UL555. Connecting ducts shall not be continuous but shall
be increased to maintain the specified expansion clearance between
terminate at the damper sleeve. Duct connections to the sleeve will be
the angle / fasteners and the opening.
either of the breakaway or rigid types, breakaway types are listed below.
Angles shall be a minimum of 1-1/2" x 1-1/2" x 16 ga.
The following determines if the connections are to be rigid or breakaway.
on dampers 36 x 50 and smaller. For dampers greater than 36 x 50,
For rigid type duct connections, sleeve shall be a minimum of 16 GA
angles to be a minimum of 1-1/2 x 1-1/2 x14 ga. Fasten angles to
on dampers not exceeding 36" wide or 24" high or 24" diameter and
the sleeve using 1/4" dia. bolts and nuts or by welding with beads
14 ga on larger units. Dampers supplied with thinner sleeves will
1/2" in length, or with No. 10 steel sheet metal screws, or with 3/16"
require a breakaway connection of the following type. Plain "S" slip,
steel rivets. Fasteners or weld beads shall be 8" maximum on centers.
double "S" slip shown below. All connections not listed as breakaway
shall be considered as rigid. Breakaway joints of the types shown below
ACCESS shall have no more than two No.10 (4.8 mm) diameter sheet metal screws
Suitable access must be provided for damper inspection and on each side and on the top and bottom located in the center of the slip
servicing. Where it is not possible to achieve sufficient size pocket and shall penetrate both sides of the slip pocket.
access, it will be necessary to install a removable section of duct. Breakaway joints of the type shown below are permitted on the top
and bottom of horizontal ducts (vertical dampers)
with flat slips not exceeding 20 inches (508 mm) in length on the sides.
CAULKING
Caulking is allowed between the mounting angles and the
damper sleeve, and between the mounting angles and the
MAINTENANCE
floor or wall construction. Caulking is not allowed between Dampers shall be maintained in intervals as stated in NFPA-90A,
the damper sleeve and the wall or floor inside the opening. Appendix B, unless local codes require more frequent inspections.
Caulk shall be one of the following: Check the fuse link, check the stainless steel closure springs
Dow Corning RTV 732, or a UL approved substitute. where furnished, cycle damper and check for free operation and
complete closure, clean with mild detergent or solvent, secure damper
open with fusible link.

DOUBLE "S" SLIP INSIDE SLIP JOINT HEMMED "S" SLIP


PLAIN "S" SLIP

STANDING "S" SLIP STANDING "S" SLIP STANDING "S"


STANDING "S" (ALT.)
(BAR REINFORCED) (ANGLE REINFORCED)

S I F I
AS E
L
INSTALLATION INSTRUCTIONS
D
C

UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS


MOUNTING
ANGLE
SLEEVE

SEE NOTES
1&3
6" MAX.

1" MIN.
1" MIN.

TYPE "B"

MOUNTING ANGLE (MIN. 10 GA.)

2" MAX.

DUCT

TYPE "B-1"
FIRE SLEEVE MOUNTING
DAMPER
GRILLE TO BE A
MINIMUM 26 GAUGE
MOUNTING ANGLE
STEEL OR .025" THICK
ALUMINUM

MOUNTING ANGLE
DAMPER BEHIND A GRILLE
SLEEVE

1. Perimeter mounting angles to be a mini-


mum of 1-1/2 x 1-1/2 x 16 GA on dampers
36 x 50 and smaller. For dampers greater
than 36 x 50, angles to be a minimum of
1-1/2 x 1-1/2 x 14 GA.
2. Grille to flange fasteners cannot pen-
etrate fire wall (see note 4).
SEE NOTE 1
3. Secure angles to sleeve only, so as to
frame the wall opening. Fasten to the
TYPE "CR" sleeve only using the same means as
required for fastening the damper to the
TYPE "CR" sleeve.
The factory supplied 22 GA. collar to 18 GA cap
connection on type "C" dampers is a breakaway 4. Grille to flange attachment by means of
connection under the following conditions: 1/4" dia. pop rivets, #8 sheet metal screws
1. Round unit duct diameters are no larger than 52" or #8 bolts and nuts. Fasteners to be
2. Oval duct sizes are no larger than 58" W x 29"H. plated steel or stainless steel, minimum
3. Duct gauges shall conform to the SMACNA two fasteners per side.
or ASHRAE duct standard.
4. Duct diameters of 22 inches (559 mm) and smaller
shall have three (3) No. 10 (4.8 mm) diameter sheet metal
screws evenly spaced around the circumference of the duct. S I F I
AS E
5. Duct diameters greater than 22 inches and up shall have L
INSTALLATION INSTRUCTIONS
D
C

five (5) sheet metal screws evenly spaced around the


circumference of the duct.
6. Dampers outside of these restrictions (ie) multiple dampers
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
and special size and application dampers must use a 4"
wide drawband connection as shown in the SMACNA Fire,
Smoke, and Radiation Damper Installation Guide.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPERS
PAN SIZING CHART MODEL K75 TYPE B
Vertical & Horizontal Mount.
Maximum Overall Sizes
Type Installation Single Section Multiple Section
Width X Height Width X Height
Vertical 60" X 60" 120" X 120"
Horizontal 60" X 60" 120" X 120"

"P"
"P" BLADE STACK
PAN SIZE OUT OF AIRSTREAM

"O" "H"
"O" Over-all Duct
"H" MODEL K75 TYPE (B)
Height Conection
(Order
Height)

"H" "O" "P" "H" "O" "P"


Duct Opening Over-all Pan Size Duct Opening Over-all Pan Size
Order Size Height Order Size Height

4 5 1 27 31 4
5 6 1 28 32 4
6 7 1 29 33 4
7 8 1 30 34 4
8 10 2 31 35 4
9 11 2 32 36 4
10 12 2 33 37 4
11 13 2 34 38 4
12 14 2 35 39 4
13 15 2 36 41 5
14 16 2 37 42 5
15 17 2 38 43 5
16 18 2 39 44 5
17 20 3 40 45 5
18 21 3 41 46 5
19 22 3 42 47 5
20 23 3 43 48 5
21 24 3 44 49 5
22 25 3 45 51 6
23 26 3 46 52 6
24 27 3 47 53 6
25 28 3 48 54 6
26 29 3 49 55 6
50 56 6
51 57 6
Note : All Sizing in Inches
52 58 6
53 59 6
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPER AND DOORS


Rounds Sizing Chart
MODEL K75 CR AND MODEL K75-T CR
MODEL K75 LCR AND MODEL K75-T LCR
ORDER DAMPER FRAME ORDER DAMPER FRAME
DIAMETER WIDTH X HEIGHT DIAMETER WIDTH X HEIGHT

4" 6X6 29" 31 X 34


5" 7X7 30" 32 X 35
6" 8X8 31" 33 X 36
7 9X9 32" 34 X 37
8" 10 X 11 33" 35 X 38
9" 11 X 12 34" 36 X 39
10" 12 X 13 35" 37 X 40
11" 13 X 14 36" 38 X 42
12" 14 X 15 37" 39 X 43
13" 15 X 16 38" 40 X 44
14" 16 X 17 39" 41 X 45
15" 17 X 18 40" 42 X 46
16" 18 X 19 41" 43 X 47
17" 19 X 21 42" 44 X 48
18" 20 X 22 43" 45 X 49
19" 21 X 23 44" 46 X 50
20" 22 X 24 45" 47 X 52
21" 23 X 25 46" 48 X 53
22" 24 X 26 47" 49 X 54
23" 25 X 27 48" 50 X 55
24" 26 X 28 49" 51 X 56
25" 27 X 29 50" 52 X 57
26" 28 X 30 51" 53 X 58
27" 29 X 32 52" 54 X 59
28" 30 X 33
53.75
ACTUAL

5.75
ACTUAL
WIDTH
6.0"
1.0" "C" SIZE
"C" SIZE BLADE STACK
BLADE STACK

58.75
ACTUAL
51.75
1" 1"
5.75 O.D
ACTUAL ACTUAL
3.75
1" 1"
O.D HEIGHT
ACTUAL

1"

52" ORDER DIAMETER


1"

4" ORDER DIAMETER


NOTE : ALL SIZING IN INCHES
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS


TRANSFER OPENINGS AND DUCT TERMINALS
FOR 1-1/2 HOUR AND 3 HOURS CURTAIN FIRE DAMPERS
K75 Type A or L
6" MAX.
PARTITION
PARTITION

1" MIN.
1" MIN.

TRANSFER GRILLE
BOTH SIDES
4-1/4"
4-1/4"
MODEL
K75 MODEL
Type A or L TRANSFER GRILLE K75
SINGLE SIDE Type A or L

TO BREAKAWAY JOINT

PARTITION
PARTITION

1. Perimeter mounting angles to be a minimum


of 1-1/2 x 1-1/2 x 16 GA on dampers
36 x 50 and smaller. For dampers greater
than 36 x 50, angles to be a minimum of 3. Secure angles to sleeve only, so as to frame the wall
1-1/2 x 1-1/2 x 14 GA. opening. Fasten to the sleeve only using the same means
2. Grille to flange fasteners cannot penetrate as required for fastening the damper to the sleeve.
the fire wall.
4. Grille to flange attachment by means of 1/4" dia. pop
rivets, #8 sheet metal screws or #8 bolts and nuts.

U SEE DETAILS ON UNDERWRITERS LABORATORY


CLASSIFICATIONS ON THE ENCLOSED KBE
Fasteners to be plated steel or stainless steel, minimum
two fasteners per side.
RL INDUSTRIES PRODUCT AND THE PRODUCT
INSTALLATION SHEETS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS


TRANSFER OPENINGS AND DUCT TERMINALS
FOR 1-1/2 HOUR AND 3 HOURS CURTAIN FIRE DAMPERS
K75-T Type A or L
6" MAX.
PARTITION
PARTITION

1" MIN.
1" MIN.

TRANSFER GRILLE
BOTH SIDES
4-3/8"
4-3/8"
MODEL
K75-T MODEL
Type A or L TRANSFER GRILLE K75-T
SINGLE SIDE Type A or L

TO BREAKAWAY JOINT

PARTITION
PARTITION

1. Perimeter mounting angles to be a minimum


of 1-1/2 x 1-1/2 x 16 GA on dampers
36 x 50 and smaller. For dampers greater
than 36 x 50, angles to be a minimum of 3. Secure angles to sleeve only, so as to frame the wall
1-1/2 x 1-1/2 x 14 GA. opening. Fasten to the sleeve only using the same means
2. Grille to flange fasteners cannot penetrate as required for fastening the damper to the sleeve.
the fire wall.
4. Grille to flange attachment by means of 1/4" dia. pop
rivets, #8 sheet metal screws or #8 bolts and nuts.

U SEE DETAILS ON UNDERWRITERS LABORATORY


CLASSIFICATIONS ON THE ENCLOSED KBE
Fasteners to be plated steel or stainless steel, minimum
two fasteners per side.
RL INDUSTRIES PRODUCT AND THE PRODUCT
INSTALLATION SHEETS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTION


TRANSFER OPENINGS AND DUCT TERMINALS
FOR 1-1/2 HOUR AND 3 HOUR CURTAIN FIRE DAMPERS
K75 Type D OR N
PARTITION
6" MAX.
PARTITION

1" MIN.

1" MIN.

TO BREAKAWAY JOINT

TRANSFER GRILLE
BOTH SIDES 2.00
2.00

MODEL
MODEL K75D
K75D

TRANSFER GRILLE
SINGLE SIDE

TO BREAKAWAY JOINT

PARTITION

PARTITION
3. Secure angles to sleeve only, so as to frame the wall opening.
Fasten to the sleeve only using the same means as required for
fastening the damper to the sleeve.
1. Perimeter mounting angles to be a minimum 4. Grille to flange attachment by means of 1/4" dia. pop rivets, #8
of 1-1/2 x 1-1/2 x 16 GA on dampers sheet metal screws or #8 bolts and nuts. Fasteners to be plated
36 x 50 and smaller. For dampers greater steel or stainless steel, minimum two fasteners per side.
than 36 x 50, angles to be a minimum of
1-1/2 x 1-1/2 x 14 GA.

2. Grille to flange fasteners cannot penetrate U SEE DETAILS ON UNDERWRITERS LABORATORY


CLASSIFICATIONS ON THE ENCLOSED KBE
the fire wall.
R L INDUSTRIES PRODUCT AND THE PRODUCT
INSTALLATION SHEETS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

FIRE DAMPER
CLOSURE INDICATION SWITCHS

Fusible link Fusible link

MODEL K75 AV
MODEL K75 AV

Negator Stainless Steel

ORDER HEIGHT
Negator Stainless Steel
ORDER HEIGHT

Closure Spring Closure Spring

LIMIT SWITCH MICROSWITCH

Blade Lock
Blade Lock

SWITCH PROBE MOUNITNG


BRACKET

TYPE 1 TYPE 2
MODEL: SWITCH VM5 MODEL: SWITCH VM6
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS


MULLION INSTALLATION INSTRUCTIONS
FOR FIRE DAMPERS INSTALLED OVERSIZED
WALL OPENINGS
These fabricated galvanized steel mullions are intended to subdivide a large vertical wall opening into smaller openings.
These smaller openings are not to exceed the maximum size restrictions of the UL Classified 1-1/2 hour
galvanized steel fire damper assembly.

A DETAILS C, D, AND E
2" 2"

3/4"
DETAILS A AND B
B 3/16"
BLIND 3-1/2"
HORIZONTAL
MULLION RIVET
OR 3/4"
LONG WELDS
12" OC
120" 6" MAX
MAX HEIGHT FROM
DETAIL F
ENDS
VERTICAL WALL THICKNESS
MULLION
MULLION CROSS SECTION
16 GA. GALVANIZED STEEL

"A" and "B" opening sizes are not to exceed


the damper's approved maximum-multiple DETAIL A
assembly size. Vertical, horizontal, or vertical
and horizontal mullions can be used,
depending on the opening size. RETAINING ANGLES ARE NOT
FASTENED TO MULLION TUBE

1"
MIN.
CONDITIONS & RESTRICTIONS
Fabricated from galvanized steel with a normal yield
strength of 42,000 psi.
Intended for use in concrete block or poured walls only
with a minimum wall thickness of 7" and a maximum wall
thickness of 12"
To permit proper embedding of anchors, hollow con-
crete block walls are to be filled at the opening by
minimum 3,500 psi concrete. FIRE
Steel mullions are not to be inside the ductwork. For DAMPER
ducted systems, each sub-divided opening must be
individually ducted.
MULLION
TUBE
EXPANSION CLEARANCE

DAMPER
SLEEVE

RETAINING
AS
S I F I
E
ANGLE DETAIL B
L
INSTALLATION INSTRUCTIONS Reference the damper's installation instructions
D
C

UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
regarding the approved method of attaching the
damper to the sleeve, attaching the retaining
angles to the sleeve, required expansion clear-
ances, sleeve gauge, ect.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS


MULLION INSTALLATION INSTRUCTIONS
FOR FIRE DAMPERS INSTALLED OVERSIZED
WALL OPENINGS
MADE UP OF
3-1 TWO WELDED
/4"
/4" ZEE SECTIONS
1/4" MIN X- 1 ALL 1-1
3/1
6"
END CAPS ER
1-1/4" MAX OV
(SEE DETAIL B)
1/4" FULL LENGTH
WELD ALL AROUND
OPENING
SPAN
3" P
LUS
1
MULLION TUBE FO /8" PE
OT
LENGTH = OPENING OF R
1/8" PER FOOT WID SPAN
TH

6-1
3/1
6"
COUNTERSUNK HOLES
FOR 1/4" DIA. FLAT HEAD
MACHINE SCREWS
OR 1" LONG WELDS
SEE DETAIL C

DETAIL D
Top, bottom or side end caps
12 GA galvanized steel

DETAIL C
The end caps are attached by means of X= WALL THICKNESS MADE UP OF
1" long x 3/8" dia. steel expansion
anchors embedded into the opening 3-1 TWO WELDED
/4"
with 1/4" dia. flat head machine screws, /4" ZEE SECTIONS
eight per end cap. If a steel lintel is X- 1 ALL 1-1
3/1
6"
ER
used, four 1" long welds per end cap OV
(two per leg) may be used.
COUNTERSUNK HOLES
FOR 1/4" DIA. FLAT
HEAD MACHINE SCREWS

3" P
LUS
1
FO /8" PE
OT
OF R
WID SPAN
TH

X 1/4" 1-1
/2 X
3X
AN 6-1
GL /4 L 1/4" FULL LENGTH
ES G
WELD ALL AROUND
6"
X/4 1/1 GS
X+ E LE
S ID
IN
X/8

SEE DETAIL D FOR END


DETAIL F
1/2" CAP DETAILS, CAP Horizontal to vertical end cap 12 ga. galvanized steel
MUST SLIP FIT INTO
MULLION Attach the horizontal mullion end caps to the
vertical mullion tube by means of (12) 3/16" dia.
DETAIL E L
AS
S I F I
E
INSTALLATION INSTRUCTIONS
blind rivets or by 1/8" full length weld.
D
C

END CAP INSERTED INTO MULLION


All horizontal and vertical mullion tubes must be
terminated with an end cap. These end caps
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
may not be fastened to the mullion tube and
must slide freely inside the mullion tube.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS


INSTALLATION INSTRUCTIONS FOR 1-1/2 HOUR
UL CLASSIFIED FIRE DAMPERS INSTALLED INTO
METAL OR WOOD FRAMED 1 HOUR AND 2 HOURS RATED DRYWALL PARTITIONS
NOTES:
CEILING RUNNER 1. These illustrated partition designs have successfully been
tested in conjunction with 1-1/2 hour classified fire
dampers, for additional designs, reference Underwriters
18" Laboratories, Inc. Fire Resistance Directory. Specific
24" O.C. MAX framing requirements of openings may vary with the local
MAX. "B authority that has jurisdiction. Specific framing require-
ments should be provided in the architectural and
structural drawings.

B" 2. Reference the damper's installation instructions regarding


"A A" the approved method of attaching the damper to the
RUNNER sleeve, attaching the retaining angles to the sleeve,
90 DEGREE LOCAL CODES MAY
required expansion clearances, sleeve gauge, ect. Type
BEND REQUIRE DOUBLE
HEADER
of framing does not effect the stated required expansion
clearance.

3. Gypsum panels surrounding the opening are to be


fastened to all stud and runner flanges, 12" O.C.
maximum.

(2) FASTENERS 4. When wooden studs are used, filler pieces must be
2" installed around the entire opening. Filler pieces are
optional when metal studs are used (consult local codes
to determine if filler pieces are required). Filler pieces are
(2) FASTENERS 2" to be double screwed (or nailed to wooden studs) on 12"
max. centers to the web of runners and studs.
5. The Office of the California State Fire Marshal and other
FLOOR FLANGE
local jurisdictions require filler pieces around both wood
and metal framed openings (no filler pieces around
MIN. 2-1/2" STUD MIN. 1-1/2" MINERAL FIBER concrete or masonry openings). These codes also
OR RUNNER GYPSUM WALLBOARD require a double header for wood framed openings,
consult local code authorities.
MIN. 1/2" THICK 6. Double jamb studding shown and required when opening
GYPSUM WALLBOARD width or height exceeds 36". Single jamb studding
MIN. 1" acceptable for openings 36" x 36" and smaller.
OVERLAP DRYWALL SCREWS (METAL STUDS)
NAILS (WOOD STUDS)

S I F I
AS E
L
INSTALLATION INSTRUCTIONS
D
C

SEE NOTE 2
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
MIN. 1/2" THICK FILLER FIRE DAMPER SLEEVE
PIECE, SEE NOTES 4 & 6
1 HOUR RATED PARTITION WALL
SECTION "B-B" 2-1/2" MIN.
MIN. 1-1/2" MINERAL FIBER RUNNER 2-1/2" MIN.
MIN. 2-1/2" STUD STUD
OR RUNNER GYPSUM WALLBOARD

PANHEAD SCREWS
MIN. 1" (METAL STUDS)
DRYWALL SCREWS (METAL STUDS) NAILS (WOODEN STUDS)
OVERLAP
NAILS (WOOD STUDS) (4) PER 90 DEG BEND

RETAINING ANGLE
ONE SIDE MAY BE REVERSED
PROVIDING THAT ADEQUATE
CLEARANCE IS MAINTAINED
SECTION "A-A"
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

DAMPER INSTALLATION INSTRUCTIONS


FIRE DAMPER INSTALLATION IN FIBROUS DUCT

FIRE DAMPER INSTALLATION


Sheet metal sleeve must be installed
through rated fire wall. Check local
codes for proper sheet metal gauge
and attachment angle RATED FIRE WALL

SHEET METAL FIXING ANGLES


SLEEVE

FIBER GLASS
DUCT BOARD
FASTENER
NOTE: Sealing of fibrous glass duct
board to sheet metal sleeve must be
made with glass fabric and mastic, TAPE
except where operation pressure is
less than 1" wg and sheet metal FIRE DAMPER
surfaces are carefully cleaned, in which
case pressure sensitive aluminum foil
tape may be used ACCESS DOOR #10 SHEET METAL SCREWS
& 2-1/2 " SQUARE WASHER

#10 SHEET METAL SCREWS AND


2-1/2 " SQUARE WASHERS, 12" (MAX)
O.C TO ATTACH DUCT BOARD TO
SHEET MEATL SLEEVE
SHEET METAL SLEEVE
THROUGH FIRE WALL AS
SPECIFIED IN FIRE DAMPER
MANUFACTURER INSTRUCTION

CLOSURE

FIRE DAMPER
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

ETL
ELECTRO - THERMAL LINK

What it is - What it does?


The Electro Thermal Link ( ETL ) is a multipurpose
dual - responsive fusible link which reacts (melts)
when subjected to :
1- Local heat (165 F) exactly the same as on ordinary
The ETL,s thermal response is identical to that of
link.
ordinary fusible links of identical temperature ( 165 F )
2- External electrical impulse of low power and a short
and strength ( 40 # ) rating.
duration.
In its capacity of converting a FIRE safety device into a
It is specifically designed to substitute for ordinary links
FIRE / SMOKE safety device, the ETL can be
and / or other actuators in existing and new installations of :
substituted for both an ordinary link and motor, or link
Fire Dampers, Fire & Smoke Roof Hatches, Fire
and electro - magnetic operator with advantages of
Extinguishers, Sprinklers, Smoke Towers, and Gas or
simplicity, operational reliability, wide acceptability and
Chemical Automatic Release Systems.
economy.
The substitution should be made in every installation
of the above devices where it is desirable for those
With its dual responsiveness, the ETL can be
devices to respond to :
substituted for two other devices at a savings in first
cost as well as operating cost and maintenance.
SMOKE, in the early form of invisible products of
The ETL is built to zero defect standards and to last at
combustion through ionization detectors, or
least fifty years and then still react properly - only on
FIRE, at the earlier stage than ordinary links thru the
fire or smoke emergency.
use of rate of rise or maximum temperature devices.
The ETL's electro - response is the unique feature. It
It is independent of power failures since it draws
is not smoke responsive of itself, but its power
power from the detector standby source if needed
requirement is so low that it can be released with an
The ETL is listed by Underwriters Laboratories Inc. As
electrical impulse from any smoke detector's power
a Fusible Link, and also has become the basis of a
source. It is compatible with every smoke detector on
new UL test procedure for electro - chemical servo
the market in the Middle East today.
mechanisms.
The operating range is 6 to 30 VAC or DC, less than S I F I
AS E
0.2 ampere of trip current required, and 1/2 millisecond L
UNDERWRITERS LABORATORIES
D
C

(.0005 sec.) response at 24 V. The electrical response


Is a trigger for the chemical heating of the center UL R
CLASSIFIED FUSIBLE LINK
USED WITH FIRE DAMPERS.
element which is self-contained exo-thermic reactor,
yielding no noise, smoke or gas... just quick heat to
open the link in 7 seconds.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

CONTROLED FIRE DAMPERS


HORIZONTAL & VERTICAL MOUNT
MODEL K75
Interlocking Steel
4-1/4" Blades 22ga. UL CLASSIFIED 1-1/2 & 3 HOURS RATING

Blade Lock Electro Thermal Link


Negator Stainless Steel 165 F
Closure Spring
Less Than Order Height.

Electro Thermal Link MODEL K75 AH


165 F
ORDER HEIGHT

ORDER HEIGHT
Damper Supplied 1/4" Less Than Order Height.
4"
1

MODEL (H) HORIZONTAL MOUNT


Damper Supplied

K75 AV Horizontal Mount Model Includes


Rollformed Steel Frame
Stainless Steel Negator Springs & Blade Locks.
22 ga.
HORIZONTAL MOUNTING SHOWN. VERTICAL MOUNTING SAME AS
HORIZONTAL LESS STAINLESS STEEL. NEGATOR SPRING AND BLADE LOCK

Model K75 Fire Dampers (1-1/2 & 3 Hours) are


( V) VERTICAL MOUNT available with Electro Thermal Link ( ETL ) in
all normally available sizes for any Particular
type damper. For horizontal and / or vertical
mountings.
S I F I
AS E UNDERWRITERS LABORATORIES (UL 555)
L
Refer to the ETL Information Sheet for a
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTENCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
Detailed Description of Electro Thermal Link
(ETL) , Suggested Usage, and Specifications.
MATERIALS RATED 4 HOURS OR LESS.

S I F I
AS E UNDERWRITERS LABORATORIES (UL 555)
L
D
C

CLASSIFIED FIRE DAMPERS.

UL R
FIRE RESISTENCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.

S I F I
AS E
L
D
C

UNDERWRITERS LABORATORIES

UL R
CLASSIFIED FUSIBLE LINK
USED WITH FIRE DAMPERS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com

CUSTOMER ORDERING INFORMATION


FIRE DAMPER CURTAIN TYPE
1- Standard dampers will be provided for use in static system and with type A model
for vertical mount.
2- Standard damper will be provided without sleeve.
3- Standard damper will be provided with galvanizedframe and blades.
4- Standard damper will be provided as UL classified 1-1/2 hours rated.
5- Standard damper will be provided with 165F fusible links.

Ordering standard dampers.

Order Qty Damper Model Width X Height

12 K75 24W X 24H

Ordering Non-Standard dampers

6 K75 Dy T SB C V 26W X 24H SEALED 285 AF 20 14 6

ORDER
QTY DAMPER
FUSIBLE
WIDTH
X LINK F
Dy : Dynamic 135, 165, SLEEVE
HEIGHT SPECIFY
-- : Static 212, 285,
O.A.LENGTH
VERTICAL OR ETL.
T: FOR 20GA FRAME HORIZONTAL SLEEVE
--: FOR 22GA FRAME MOUNT TYPE OF EDGE TO
FOR TYPE SLEEVE:
DAMPER C, CR, CO FIRE
MODEL A, AF,B,B-1, C, DAMPER
NECK TO BE CR, CO AND
K75 A SEALED OR CENTER
B SIZES.
UNSEALED LINE K.
C
--- : NORMAL CR
CO
SB: STAINLESS D SLEEVE SPECIFY
STEEL BLADES DB GAUGE: 22/20, 18,
L 16, 14, 12, 10.
SC: STAINLESS LB
STEEL LC
CONSTRUCTION LCR
LCO
N
NB