FIRE DAMPERS
STANDARD CONSTRUCTION
FRAME.
4-1/4 " Maximum X 22 gauge Galvanized steel channel. (D
AM
PE
BLADES. RS
UP
22 gauge Galvanized steel curtain type in the air stream. PL
IED OR
1/4 DE
RW
FINISH. "L
ES
ST
IDT
H
Mill. HA
NO
RD
CLOSURE SPRINGS. ER
WI
DT
301 Stainless Steel Spring. H)
(For Horizontal mount only, optional on vertical mount)
4-1/4"
FUSIBLE LINK. VARIATION.
Standard 165 F. Other available. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MOUNTING. procedures. Approved variations available at
ORDER HEIGHT
FIRE DAMPERS
STANDARD CONSTRUCTION
FRAME.
4-3/8 " Maximum X 20 gauge Galvanized steel channel. (D
AM
PE
BLADES. RS
UP
22 gauge Galvanized steel curtain type in the air stream. PL
IED OR
1/4 DE
RW
FINISH. "L
ES
ST
IDT
H
Mill. HA
NO
RD
CLOSURE SPRINGS. ER
WI
DT
301 Stainless Steel Spring. H)
(For Horizontal mount only, optional on vertical mount)
4-3/8"
FUSIBLE LINK. VARIATION.
Standard 165 F. Other available. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MOUNTING. procedures. Approved variations available at
ORDER HEIGHT
FIRE DAMPERS
MODEL K75 TYPE B
UL CLASSIFIED 1-1/2 HOURS RATING
ORDER HEIGHT
FEATURES.
APPLICATION
MODEL K75 IS APPROVED FOR USE
IN WALLS, FLOORS AND PARTITIONS ORDER HEIGHT
DAMPER SUPPLIED 1/4"
WITH FIRE RESISTANCE RATINGS LESS THAN ORDER HEIGHT
LESS THAN 3 HOURS.
STANDARD CONSTRUCTION
FRAME. OVERALL HEIGHT
4-1/4 " Maximum X 22 gauge Galvanized steel channel. IS ORDER HEIGHT
PLUS "B" PAN TABLE
HEIGHT LESS 1/4".
BLADES.
22 gauge Galvanized steel curtain type out of the air stream. (D
AM OR
TH PER D
FINISH. AN SU ER
OR PP W
DE LIE IDTH
Mill. R D1
WI /4
DT " L
CLOSURE SPRINGS. H) ES
S
301 Stainless Steel Spring.
(For Horizontal mount only, optional on vertical mount)
FUSIBLE LINK. 4-1/4" VARIATION.
Standard 165 F. Other available. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MOUNTING. procedures. Approved variations available at
OVERALL DAMPER HEIGHT
FIRE DAMPERS
MODEL K75-T TYPE B
UL CLASSIFIED 1-1/2 HOURS RATING
ORDER HEIGHT
FEATURES.
APPLICATION
MODEL K75 IS APPROVED FOR USE
IN WALLS, FLOORS AND PARTITIONS ORDER HEIGHT
WITH FIRE RESISTANCE RATINGS DAMPER SUPPLIED 1/4"
LESS THAN ORDER HEIGHT
LESS THAN 3 HOURS.
STANDARD CONSTRUCTION
FRAME. OVERALL HEIGHT
4-3/8 " Maximum X 20 gauge Galvanized steel channel. IS ORDER HEIGHT
PLUS "B" PAN TABLE
BLADES. HEIGHT LESS 1/4".
FIRE DAMPERS
MODEL K75 TYPE C, CR & CO
UL CLASSIFIED 1-1/2 HOURS RATING
Overall Damper Height
Order Height
Damper Supplied 1/4" Less
FEATURES.
Than Order Height
MINIMUM SIZE.
Overall Damper Height
1"
C
FIRE DAMPERS
MODEL K75-T TYPE C, CR & CO
UL CLASSIFIED 1-1/2 HOURS RATING
Overall Damper Height
Order Height
Damper Supplied 1/4" Less
FEATURES.
Than Order Height
MAXIMUM SIZE.
K75-T COV NOTE.
* Dampers furnished approximately 1/4" smaller
Model K75-T C Single Section: than given duct dimension
Vertical Installation ---- 58"Wx 52"H. * Refer to the KBE Installation Instruction and
Typical
Horizontal Installation ---- 58"Wx 52"H. 2-1/2" supplements for complete installation details.
Model K75-T CR & CO Single Section L
AS
S I F I
E UNDERWRITERS LABORATORIES (UL 555)
D
1"
C
FIRE DAMPERS
MODEL K75 SC TYPE A or B
(304 STAINLESS STEEL CONSTRUCTION)
UL CLASSIFIED 1-1/2 HOURS RATING
NO
CLOSURE SPRINGS. RD
ER
301 Stainless Steel Spring. WI
DT
H)
(For Horizontal mount only, optional on vertical mount)
FUSIBLE LINK. 4-3/8" 4-3/8"
VARIATION.
Standard 165 F. Other available. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MOUNTING. procedures. Approved variations available at
Vertical or Horizontal .
ORDER HEIGHT
ORDER HEIGHT
NOTE.
MAXIMUM SIZE. * Dampers furnished approximately 1/4" smaller
Single Section than given duct dimension
Vertical Installation ---- 60"Wx 60"H. * Refer to the KBE Installation Instruction and
Horizontal Installation ---- 60"Wx 60"H. (V) VERTICAL MOUNT (V) VERTICAL MOUNT supplements for complete installation details.
Multiple Section
Vertical Installation ---- 120"Wx 120"H. L
AS
S I F I
E UNDERWRITERS LABORATORIES (UL 555)
D
C
FIRE DAMPERS
MODEL K75 SB TYPE A or B
(304 STAINLESS STEEL BLADES)
UL CLASSIFIED 1-1/2 HOURS RATING
STANDARD CONSTRUCTION
FRAME.
4-1/4 " Maximum X 22 gauge galvanized steel channel.
(D
AM
BLADES. PE
RS
22 gauge 304 stainless steel curtain type in the air stream. UP
PL
IED OR
DE
FINISH. 1/4
"L
ES
RW
IDT
H
Mill. ST
HA
NO
CLOSURE SPRINGS. RD
ER
301 Stainless Steel Spring. WI
DT
H)
(For Horizontal mount only, optional on vertical mount)
4-1/4" 4-1/4"
FUSIBLE LINK. VARIATION.
Standard 165 F. Other available. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MOUNTING. procedures. Approved variations available at
ORDER HEIGHT
Vertical or Horizontal .
ORDER HEIGHT
MODEL K75
CURTAIN TYPE FIRE DAMPER PERFORMANCE DATA
Free Area and Static Friction Loss at various velocities.
DAMPER FREE AREA (SQ FT)
HEIGHT WIDTH (INCHES) HEIGHT WIDTH (INCHES)
(INCHES) (INCHES)
6" 12" 18 " 24 " 30" 36 " 42 " 48" 54" 60 " 6" 12" 18 " 24 " 30 " 36 " 42 " 48" 54" 60 "
6" .14 .33 .52 .70 .89 1.1 1.3 1.5 1.7 1.8 6" .16 .38 .60 .81 1.0 1.3 1.5 1.7 1.9 2.1
12" .31 .72 1.1 1.5 1.9 2.4 2.8 3.2 3.5 4.0 12" .34 .81 1.3 1.8 2.2 2.7 3.2 3.6 4.1 4.6
18 " .48 1.1 1.7 2.4 3.0 3.7 4.3 4.9 5.6 6.2 18 " .53 1.3 2.0 2.7 3.4 4.1 4.8 5.6 5.6 7.0
24 " .65 1.5 2.4 3.2 4.1 5.0 5.8 6.7 7.5 8.4 24 " .72 1.7 2.7 3.6 4.6 5.6 6.5 7.5 7.5 9.4
30 " .82 1.9 3.0 4.1 5.2 6.3 7.3 8.4 9.5 10.6 30 " .91 2.1 3.3 4.6 5.8 7.0 8.2 9.4 10.7 11.9
36 " .99 2.3 3.6 4.9 6.3 7.6 8.9 10.2 11.5 12.8 36 " 1.1 2.6 4.0 5.5 7.0 8.4 9.9 11.4 12.8 14.3
42 " 1.2 2.7 4.2 5.8 7.3 8.8 10.4 11.9 13.4 15.0 42 " 1.3 3.0 4.7 6.4 8.2 9.9 11.6 13.3 15.0 16.8
48 " 1.3 3.1 4.9 6.6 8.4 10.2 11.9 13.7 15.5 17.2 48 " 1.5 3.4 5.4 7.4 9.3 11.3 13.3 15.3 17.2 19.2
54 " 1.5 3.5 5.5 7.5 9.5 11.5 13.5 15.5 17.5 19.4 54 " 1.7 3.9 6.1 8.3 10.5 12.8 15.0 17.2 19.4 21.6
60 " 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.4 21.7
TYPE B
TYPE A
0.2
0.3
0.4
INSPECTION INSTALLATION
Inspect for shipping damage. The basic intent of a proper installation is to secure
Inspect for proper size and model. the fire damper in, not to, the opening in such a
Inspect installed damper for proper orientation, as stated manner as to prevent distortion and disruption of the
on damper label. damper operation by allowing the fire damper in
Inspect for obstructions which could interfere with free openings to expand and the connecting duct to
operation and complete closure. separate in the event of the collapse of the hanging
Manually cycle the damper to verify proper operation. system. The fire damper must be positioned within
the masonry, block or gypsum wallboard fire barrier.
SLEEVE THICKNESS
Sleeves shall be the same gauge or heavier as the
SEE NOTE ON duct to which it is attached. Gauges shall conform to
DAMPER TO SLEEVE SMACNA or ASHRAE duct standards. Damper sleeve
ATTACHMENT AND
SLEEVE GAUGE can be no thicker than 10 GA steel. On type
REQUIREMENTS C dampers, the sleeve must be 18 GA. or heavier.
EXPANSION CLEARANCE
The opening in the wall or floor for the fire damper
shall be sized so as to provide expansion clearance
SEE NOTE between the sleeve and opening. Clearances do not
ON DUCT
CONNECTION vary with walls constructed of different materials. A
minimum of 1/8" per foot of overall damper/sleeve
width and height is required. The maximum opening
3" MIN. FOR DUCT
CONNECTION AND
size shall not exceed 1/8" per foot plus 1", minimum
MTG. ANGLES total clearance shall be at least 1/4" larger than the
overall assembly.
6" MAX.
S I F I
AS E
L
16" MAX. WHEN INSTALLATION INSTRUCTIONS
D
C
FACTORY INSTALLED
FIRE DAMPERS
APPLICATION FEATURES.
MODEL K75 L IS APPROVED FOR USE *Each damper is marked with a 3 hours
IN WALLS, FLOORS AND PARTITIONS UL 555 Classified fire damper label.
WITH FIRE RESISTANCE RATINGS *Meets all UL and NFPA criteria for primary fire
FOR 4 HOURS AND LESS. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
STANDARD CONSTRUCTION
FRAME.
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES. Order Height
22 gauge Galvanized steel curtain type in the air stream. (Damper supplied 1/4"
less than order height)
FINISH.
Mill.
CLOSURE SPRINGS (Optional) .
301 Stainless Steel Spring .
(D
AM
PE
RS
UP
PL
FUSIBLE LINK. IED OR
DE
1/4 RW
Standard 165 F. Other available. "L
ES IDT
ST H
HA
NO
RD
ER
MOUNTING. WI
DT
H)
Vertical .
4-1/4"
MINIMUM SIZE. VARIATION.
Vertical Installation ---- 4"Wx 4"H. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MAXIMUM SIZE. procedures. Approved variations available at
ORDER HEIGHT
NOTE.
AS
S I F I
E
* Dampers furnished approximately 1/4" smaller
L UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C
UL R
FIRE RESISTANCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
* Refer to the KBE Installation Instruction and
(V) VERTICAL MOUNT supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
FEATURES.
APPLICATION
*Each damper is marked with a 3 hours
MODEL K75-T L IS APPROVED FOR USE UL 555 Classified fire damper label.
IN WALLS, FLOORS AND PARTITIONS *Meets all UL and NFPA criteria for primary fire
WITH FIRE RESISTANCE RATINGS dampers in walls and floors with fire resistance
4 HOURS AND LESS. ratings of 4 hours and less.
STANDARD CONSTRUCTION
FRAME.
4-3/8 " Maximum X 20 gauge Galvanized steel channel. Order Height
BLADES. (Damper supplied 1/4"
less than order height)
22 gauge Galvanized steel curtain type in the air stream.
FINISH.
Mill.
CLOSURE SPRINGS. (Optional)
(D
301 Stainless Steel Spring. AM
PE
RS
UP
PL
IED OR
1/4 DE
FUSIBLE LINK. "L
ES
RW
IDT
ST H
Standard 165 F. Other available. HA
NO
RD
ER
WI
DT
H)
MOUNTING.
Vertical .
4-3/8"
VARIATION.
MINIMUM SIZE. All UL Classified fire dampers must be fabricated in
Vertical Installation ---- 4"Wx 4"H. accordance with UL procedures. Available variation
are limited to those incorporated in the approved
procedures. Approved variations available at
MAXIMUM SIZE.
ORDER HEIGHT
L
AS
S I F I
E UNDERWRITERS LABORATORIES (UL 555) NOTE.
D
C
FIRE DAMPERS
APPLICATION FEATURES.
MODEL K75 L IS APPROVED FOR USE *Each damper is marked with a 3 hours
IN WALLS, FLOORS AND PARTITIONS UL 555 Classified fire damper label.
WITH FIRE RESISTANCE RATINGS *Meets all UL and NFPA criteria for primary fire
OF 4 HOURS AND LESS. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
STANDARD CONSTRUCTION
FRAME.
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type out of the air stream.
ORDER HEIGHT
FINISH. DAMPER SUPPLIED 1/4"
LESS THAN ORDER HEIGHT
Mill.
CLOSURE SPRINGS. (Optional)
301 Stainless Steel Spring.
(D
AM OR
TH PER
MOUNTING. AN SU ER
OR PP
D
W
Vertical . DE LIE IDTH
R D1
WI /4
DT " L
H) ES
S
MINIMUM SIZE.
Vertical Installation ---- 4"Wx 4"H.
4-1/4"
MAXIMUM SIZE. VARIATION.
Single Section All UL Classified fire dampers must be fabricated in
Vertical Installation ---- 60"Wx 53"H. accordance with UL procedures. Available variation
are limited to those incorporated in the approved
OVERALL DAMPER HEIGHT
UL R
FIRE RESISTANCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
K75 LBV and in lengths required for the specific application.
NOTE.
* Dampers furnished approximately 1/4" smaller
than given duct dimension
(V) VERTICAL MOUNT * Refer to the KBE Installation Instruction and
supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
MODEL K75-T TYPE LB
UL CLASSIFIED 3 HOURS RATING
APPLICATION FEATURES.
MODEL K75-T L IS APPROVED FOR USE *Each damper is marked with a 3 hours
IN WALLS, FLOORS AND PARTITIONS UL 555 Classified fire damper label.
WITH FIRE RESISTANCE RATINGS *Meets all UL and NFPA criteria for primary fire
OF 4 HOURS AND LESS. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
STANDARD CONSTRUCTION
FRAME.
4-3/8 " Maximum X 20 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type out of the air stream. ORDER HEIGHT
DAMPER SUPPLIED 1/4"
FINISH. LESS THAN ORDER HEIGHT
Mill.
CLOSURE SPRINGS. (Optional)
301 Stainless Steel Spring
OVERALL HEIGHT
FUSIBLE LINK. IS ORDER HEIGHT
PLUS "B" PAN TABLE
Standard 165 F. Other available. HEIGHT LESS 1/4".
(D
AM OR
TH PER D
AN SU ER
MOUNTING. OR PP W
DE LIE IDTH
R D1
Vertical . WI /4
DT " L
H) ES
S
MINIMUM SIZE.
Vertical Installation ---- 4"Wx 4"H. VARIATION.
4-3/8"
All UL Classified fire dampers must be fabricated in
MAXIMUM SIZE. accordance with UL procedures. Available variation
are limited to those incorporated in the approved
Vertical Installation ---- 60"Wx 53"H. procedures. Approved variations available at
additional cost are :
OVERALL DAMPER HEIGHT
UL R
FIRE RESISTANCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
* Refer to the KBE Installation Instruction and
supplements for complete installation details.
(V) VERTICAL MOUNT
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
MODEL K75 TYPE LC, LCR & LCO
UL CLASSIFIED 3 HOURS RATING
APPLICATION FEATURES.
MODEL K75 L IS APPROVED FOR USE IN *Each damper is marked with a 3 hours
WALLS, FLOORS AND PARTITIONS WITH UL 555 Classified fire damper label.
FIRE RESISTANCE RATINGS OF 4 HOURS *Meets all UL and NFPA criteria for primary fire
AND LESS. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
STANDARD CONSTRUCTION OR
DE "C
R O"
HE
FRAME. IG
HT OV
AL
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type out of the air stream.
OR "
FINISH. DE CO"
R
WI
Mill. DT
H
CLOSURE SPRINGS. (Optional) RE
OR
301 Stainless Steel Spring. DE "C CT
AN RO
R " GL UN
HE E
IG D
HT
FUSIBLE LINK.
Standard 165 F. Other available.
OR
DE "C"
MOUNTING. R
WI
DT
Vertical . H "
OR CR"
DE
R
DI
MINIMUM SIZE. A.
4-1/4"
Model K75L C ---- 4"Wx 4"H.
VARIATION.
Model K75L CR ---- diameter 3".
All UL Classified fire dampers must be fabricated in
Model K75L CO ---- diameter 3".
accordance with UL procedures. Available variation
MAXIMUM SIZE. are limited to those incorporated in the approved
procedures. Approved variations available at
Model K75LC Single Section:
Damper Supplied 1/4" Less
1"
(V) VERTICAL MOUNT
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
MODEL K75-T TYPE LC, LCR & LCO
UL CLASSIFIED 3 HOURS RATING
FEATURES.
APPLICATION
*Each damper is marked with a 3 hours
MODEL K75-T L IS APPROVED FOR USE IN UL 555 Classified fire damper label.
WALLS, FLOORS AND PARTITIONS WITH *Meets all UL and NFPA criteria for primary fire
FIRE RESISTANCE RATINGS OF 4 HOURS dampers in walls and floors with fire resistance
AND LESS. ratings of 4 hours and less.
STANDARD CONSTRUCTION
OR
FRAME. DE "C
R O"
HE
4-3/8 " Maximum X 20 gauge Galvanized steel channel. IG OV
HT AL
BLADES.
22 gauge Galvanized steel curtain type out of the air stream.
FINISH.
OR "
Mill. DE CO"
R
WI
CLOSURE SPRINGS. (Optional) DT
H
301 Stainless Steel Spring.
OR RE
DE "C CT
R " AN RO
GL
FUSIBLE LINK. HE
IG E UN
D
HT
Standard 165 F. Other available.
MOUNTING.
OR
Vertical . DE "C"
R
WI
DT
H
MINIMUM SIZE. "
OR CR"
DE
Model K75-T LC ---- 4"Wx 4"H. R
DI
A.
Model K75-T LCR ---- diameter 3".
Model K75-T LCO ---- diameter 3".
4-3/8" VARIATION.
MAXIMUM SIZE. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
Model K75-T LC Single Section:
are limited to those incorporated in the approved
Vertical Installation ---- 58"Wx 52"H.
procedures. Approved variations available at
Model K75-T LCR & LCO Single Section additional cost are :
Damper Supplied 1/4" Less
MATERIALS RATED 4 HOURS OR LESS. * Refer to the KBE Installation Instruction and
Typical
supplements for complete installation details.
2-1/2"
1"
(V) VERTICAL MOUNT
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
APPLICATION FEATURES.
MODEL K75 L IS APPROVED FOR USE *Each damper is marked with a 3 hours
IN WALLS, FLOORS AND PARTITIONS UL 555 Classified fire damper label.
WITH FIRE RESISTANCE RATINGS *Meets all UL and NFPA criteria for primary fire
FOR 4 HOURS AND LESS. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
STANDARD CONSTRUCTION
FRAME.
4-3/8 " Maximum X 22 gauge stainless steel channel. Order Height
BLADES. (Damper supplied 1/4"
less than order height)
22 gauge stainless steel curtain type in the air stream.
FINISH.
Mill.
CLOSURE SPRINGS. (Optional) (D
301 Stainless Steel Spring . AM
PE
RS
UP
PL
IED OR
FUSIBLE LINK. 1/4
"L
DE
RW
ES IDT
Standard 165 F. Other available. ST H
HA
NO
RD
ER
WI
MOUNTING. DT
H)
Vertical .
4-3/8" 4-3/8"
VARIATION.
MINIMUM SIZE. All UL Classified fire dampers must be fabricated in
Vertical Installation ---- 4"Wx 4"H. accordance with UL procedures. Available variation
are limited to those incorporated in the approved
procedures. Approved variations available at
MAXIMUM SIZE.
ORDER HEIGHT
ORDER HEIGHT
NOTE.
AS
S I F I
E
* Dampers furnished approximately 1/4" smaller
L UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C
UL R
FIRE RESISTANCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
* Refer to the KBE Installation Instruction and
(V) VERTICAL MOUNT (V) VERTICAL MOUNT supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
APPLICATION FEATURES.
MODEL K75 L IS APPROVED FOR USE *Each damper is marked with a 3 hours
IN WALLS, FLOORS AND PARTITIONS UL 555 Classified fire damper label.
WITH FIRE RESISTANCE RATINGS *Meets all UL and NFPA criteria for primary fire
FOR 4 HOURS AND LESS. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
STANDARD CONSTRUCTION
FRAME.
4-1/4 " Maximum X 22 gauge galvanized steel channel.
BLADES. Order Height
22 gauge stainless steel curtain type in the air stream. (Damper supplied 1/4"
less than order height)
FINISH.
Mill.
CLOSURE SPRINGS. (Optional)
301 Stainless Steel Spring .
(D
AM
PE
RS
FUSIBLE LINK. UP
PL
IED OR
Standard 165 F. Other available. 1/4
"L
DE
RW
ES IDT
ST H
HA
NO
RD
MOUNTING. ER
WI
DT
Vertical . H)
4-1/4" 4-1/4"
MINIMUM SIZE. VARIATION.
Vertical Installation ---- 4"Wx 4"H. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available variation
are limited to those incorporated in the approved
MAXIMUM SIZE.
procedures. Approved variations available at
Single Section
ORDER HEIGHT
ORDER HEIGHT
NOTE.
AS
S I F I
E
* Dampers furnished approximately 1/4" smaller
L UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C
UL R
FIRE RESISTANCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
* Refer to the KBE Installation Instruction and
(V) VERTICAL MOUNT (V) VERTICAL MOUNT supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
MODEL K75
CURTAIN TYPE FIRE DAMPER PERFORMANCE DATA
Free Area and Static Friction Loss at various velocities.
DAMPER FREE AREA (SQ FT)
HEIGHT WIDTH (INCHES) HEIGHT WIDTH (INCHES)
(INCHES) (INCHES)
6" 12" 18 " 24 " 30" 36 " 42 " 48" 54" 60 " 6" 12" 18 " 24 " 30 " 36 " 42 " 48" 54" 60 "
6" .14 .33 .52 .70 .89 1.1 1.3 1.5 1.7 1.8 6" .16 .38 .60 .81 1.0 1.3 1.5 1.7 1.9 2.1
12" .31 .72 1.1 1.5 1.9 2.4 2.8 3.2 3.5 4.0 12" .34 .81 1.3 1.8 2.2 2.7 3.2 3.6 4.1 4.6
18 " .48 1.1 1.7 2.4 3.0 3.7 4.3 4.9 5.6 6.2 18 " .53 1.3 2.0 2.7 3.4 4.1 4.8 5.6 5.6 7.0
24 " .65 1.5 2.4 3.2 4.1 5.0 5.8 6.7 7.5 8.4 24 " .72 1.7 2.7 3.6 4.6 5.6 6.5 7.5 7.5 9.4
30 " .82 1.9 3.0 4.1 5.2 6.3 7.3 8.4 9.5 10.6 30 " .91 2.1 3.3 4.6 5.8 7.0 8.2 9.4 10.7 11.9
36 " .99 2.3 3.6 4.9 6.3 7.6 8.9 10.2 11.5 12.8 36 " 1.1 2.6 4.0 5.5 7.0 8.4 9.9 11.4 12.8 14.3
42 " 1.2 2.7 4.2 5.8 7.3 8.8 10.4 11.9 13.4 15.0 42 " 1.3 3.0 4.7 6.4 8.2 9.9 11.6 13.3 15.0 16.8
48 " 1.3 3.1 4.9 6.6 8.4 10.2 11.9 13.7 15.5 17.2 48 " 1.5 3.4 5.4 7.4 9.3 11.3 13.3 15.3 17.2 19.2
54 " 1.5 3.5 5.5 7.5 9.5 11.5 13.5 15.5 17.5 19.4 54 " 1.7 3.9 6.1 8.3 10.5 12.8 15.0 17.2 19.4 21.6
60 " 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.4 21.7
TYPE LB
TYPE L
2.0
3.0
4.0
INSPECTION INSTALLATION
Inspect for shipping damage. The basic intent of a proper installation is to secure
Inspect for proper size and model. the fire damper in, not to, the opening in such a
Inspect installed damper for proper orientation, as stated manner as to prevent distortion and disruption of the
on damper label. damper operation by allowing the fire damper in
Inspect for obstructions which could interfere with free openings to expand and the connecting duct to
operation and complete closure. separate in the event of the collapse of the hanging
Manually cycle the damper to verify proper operation. system. The fire damper must be positioned within
the masonry, block or gypsum wallboard fire barrier.
SLEEVE THICKNESS
Sleeves shall be the same gauge or heavier as the
SEE NOTE ON
DAMPER TO SLEEVE duct to which it is attached. Gauges shall conform to
ATTACHMENT AND SMACNA or ASHRAE duct standards. Damper sleeve
SLEEVE GAUGE
REQUIREMENTS can be no thicker than 10 GA steel. On type C dampers,
the sleeve must be 18 GA. or heavier.
EXPANSION CLEARANCE
The opening in the wall or floor for the fire damper shall be sized
SEE NOTE so as to provide expansion clearance between the sleeve and
ON DUCT
CONNECTION
opening. Clearances do not vary with walls constructed of
different materials. A minimum of 1/8" per foot of overall
damper/sleeve width and height is required. The maximum
3" MIN. FOR DUCT opening size shall not exceed 1/8" per foot plus 1", minimum
CONNECTION AND
MTG. ANGLES total clearance shall be at least 1/4" larger than the overall
assembly.
6" MAX.
S I F I
16" MAX. WHEN AS E
L
INSTALLATION INSTRUCTIONS
D
C
FACTORY INSTALLED
ACCESS DOOR
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
WALL MOUNT SHOWN (VERTICAL INSTALLATION)
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
APPLICATION FEATURES.
MODEL K75-Dy IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 1-1/2 hours
LESS THAN 3 HOURS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of less than 3 hours.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM
MOUNTING. 4-1/4"
Vertical .
VARIATION.
All UL Classified fire dampers must be fabricated in
MINIMUM SIZE. accordance with UL procedures. Available variation
Vertical Installation ---- 4"Wx 4"H. are limited to those incorporated in the approved
ORDER HEIGHT
NOTE.
S I F I
* Dampers furnished approximately 1/4" smaller
AS
L E UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C
UL R
DYNAMIC SYSTEM.
FIRE RESISTANCE RATED 1-1/2 HOUR.
(V) VERTICAL MOUNT
* Refer to the KBE Installation Instruction and
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
APPLICATION FEATURES.
MODEL K75-Dy IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 1-1/2 hours
LESS THAN 3 HOURS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of less than 3 hours.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM
STANDARD CONSTRUCTION
ORDER HEIGHT
FRAME. DAMPER SUPPLIED 1/4"
LESS THAN ORDER HEIGHT
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type out of the air stream.
FINISH.
Mill. OVERALL HEIGHT
IS ORDER HEIGHT
CLOSURE SPRINGS. PLUS "B" PAN TABLE
HEIGHT LESS 1/4".
301 Stainless Steel Spring.
(D
AM OR
FUSIBLE LINK. TH PER
AN SU ER
D
Standard 165 F. Other available. OR PP W
DE LIE IDTH
R D1
WI /4
DT " L
H) ES
MOUNTING. S
4-1/4"
Vertical .
VARIATION.
All UL Classified fire dampers must be fabricated in
MINIMUM SIZE. accordance with UL procedures. Available variation
Vertical Installation ---- 4"Wx 4"H. are limited to those incorporated in the approved
OVERALL DAMPER HEIGHT
NOTE.
S I F I
* Dampers furnished approximately 1/4" smaller
AS
L E UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C
UL R
DYNAMIC SYSTEM.
FIRE RESISTANCE RATED 1-1/2 HOUR. (V) VERTICAL MOUNT
* Refer to the KBE Installation Instruction and
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
APPLICATION FEATURES.
MODEL K75-Dy IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 1-1/2 hours
LESS THAN 3 HOURS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of less than 3 hours.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM OR
DE "C
R O"
HE
IG OV
HT AL
STANDARD CONSTRUCTION
FRAME. OR "
DE CO"
4-1/4 " Maximum X 22 gauge Galvanized steel channel. R
WI
DT
BLADES. H
22 gauge Galvanized steel curtain type out of the air stream. O RE
RD " CT
ERC" AN
FINISH. HE GL
E
RO
UN
IG D
Mill. HT
CLOSURE SPRINGS.
301 Stainless Steel Spring.
OR
FUSIBLE LINK. DE "C"
R
Standard 165 F. Other available. WI
DT
H "
OR CR"
4-1/4" DE
MOUNTING. R
DI
A.
Vertical
VARIATION.
MINIMUM SIZE. All UL Classified fire dampers must be fabricated in
Model K75 C ---- 4"Wx 4"H. accordance with UL procedures. Available variation
Model K75 CR ---- diameter 3". are limited to those incorporated in the approved
Damper Supplied 1/4" Less
UL R
DYNAMIC SYSTEM.
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
supplements for complete installation details.
MATERIALS RATED 2 HOURS OR LESS. 1"
(V) VERTICAL MOUNT
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
MODEL K75-Dy- SB TYPE A or B
(304 STAINLESS STEEL BLADES)
UL CLASSIFIED 1-1/2 HOURS RATING
APPLICATION FEATURES.
MODEL K75-Dy IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 1-1/2 hours
LESS THAN 3 HOURS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of less than 3 hours.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM
VARIATION.
MOUNTING. All UL Classified fire dampers must be fabricated in
Vertical .
accordance with UL procedures. Available variation
ORDER HEIGHT
ORDER HEIGHT
UL R
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
MODEL K75
CURTAIN TYPE FIRE DAMPER PERFORMANCE DATA
Free Area and Static Friction Loss at various velocities.
DAMPER FREE AREA (SQ FT)
HEIGHT WIDTH (INCHES) HEIGHT WIDTH (INCHES)
(INCHES) (INCHES)
6" 12" 18 " 24 " 30" 36 " 42 " 48" 54" 60 " 6" 12" 18 " 24 " 30 " 36 " 42 " 48" 54" 60 "
6" .14 .33 .52 .70 .89 1.1 1.3 1.5 1.7 1.8 6" .16 .38 .60 .81 1.0 1.3 1.5 1.7 1.9 2.1
12" .31 .72 1.1 1.5 1.9 2.4 2.8 3.2 3.5 4.0 12" .34 .81 1.3 1.8 2.2 2.7 3.2 3.6 4.1 4.6
18 " .48 1.1 1.7 2.4 3.0 3.7 4.3 4.9 5.6 6.2 18 " .53 1.3 2.0 2.7 3.4 4.1 4.8 5.6 5.6 7.0
24 " .65 1.5 2.4 3.2 4.1 5.0 5.8 6.7 7.5 8.4 24 " .72 1.7 2.7 3.6 4.6 5.6 6.5 7.5 7.5 9.4
30 " .82 1.9 3.0 4.1 5.2 6.3 7.3 8.4 9.5 10.6 30 " .91 2.1 3.3 4.6 5.8 7.0 8.2 9.4 10.7 11.9
36 " .99 2.3 3.6 4.9 6.3 7.6 8.9 10.2 11.5 12.8 36 " 1.1 2.6 4.0 5.5 7.0 8.4 9.9 11.4 12.8 14.3
42 " 1.2 2.7 4.2 5.8 7.3 8.8 10.4 11.9 13.4 15.0 42 " 1.3 3.0 4.7 6.4 8.2 9.9 11.6 13.3 15.0 16.8
48 " 1.3 3.1 4.9 6.6 8.4 10.2 11.9 13.7 15.5 17.2 48 " 1.5 3.4 5.4 7.4 9.3 11.3 13.3 15.3 17.2 19.2
54 " 1.5 3.5 5.5 7.5 9.5 11.5 13.5 15.5 17.5 19.4 54 " 1.7 3.9 6.1 8.3 10.5 12.8 15.0 17.2 19.4 21.6
60 " 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.4 21.7
TYPE B
TYPE A
2.0
3.0
4.0
INSPECTION INSTALLATION
Inspect for shipping damage. The basic intent of a proper installation is to secure
Inspect for proper size and model. the fire damper in, not to, the opening in such a
Inspect installed damper for proper orientation, as stated manner as to prevent distortion and disruption of the
on damper label. damper operation by allowing the fire damper in
Inspect for obstructions which could interfere with free openings to expand and the connecting duct to
operation and complete closure. separate in the event of the collapse of the hanging
Manually cycle the damper to verify proper operation. system. The fire damper must be positioned within
the masonry, block or gypsum wallboard fire barrier.
SLEEVE THICKNESS
Sleeves shall be the same gauge or heavier as the
SEE NOTE ON duct to which it is attached. Gauges shall conform to
DAMPER TO SLEEVE SMACNA or ASHRAE duct standards. Damper sleeve
ATTACHMENT AND
SLEEVE GAUGE can be no thicker than 10 GA steel. On type
REQUIREMENTS C dampers, the sleeve must be 18 GA. or heavier.
EXPANSION CLEARANCE
The opening in the wall or floor for the fire damper
shall be sized so as to provide expansion clearance
SEE NOTE between the sleeve and opening. Clearances do not
ON DUCT
CONNECTION vary with walls constructed of different materials. A
minimum of 1/8" per foot of overall damper/sleeve
width and height is required. The maximum opening
3" MIN. FOR DUCT
CONNECTION AND
size shall not exceed 1/8" per foot plus 1", minimum
MTG. ANGLES total clearance shall be at least 1/4" larger than the
overall assembly.
6" MAX.
S I F I
AS E
L
16" MAX. WHEN INSTALLATION INSTRUCTIONS
D
C
FACTORY INSTALLED
FIRE DAMPERS
APPLICATION FEATURES.
MODEL K75-Dy-L IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 3 hours
FOR 4 HOURS OR LESS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM
MOUNTING. 4-1/4"
Vertical .
VARIATION.
All UL Classified fire dampers must be fabricated in
MINIMUM SIZE. accordance with UL procedures. Available variation
Vertical Installation ---- 4"Wx 4"H. are limited to those incorporated in the approved
ORDER HEIGHT
NOTE.
S I F I
* Dampers furnished approximately 1/4" smaller
AS
L E UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C
UL R
DYNAMIC SYSTEM.
FIRE RESISTANCE RATED 1-1/2 HOUR.
(V) VERTICAL MOUNT
* Refer to the KBE Installation Instruction and
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
APPLICATION FEATURES.
MODEL K75-Dy- L IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 3 hours
FOR 4 HOURS OR LESS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM
STANDARD CONSTRUCTION
ORDER HEIGHT
FRAME. DAMPER SUPPLIED 1/4"
LESS THAN ORDER HEIGHT
4-1/4 " Maximum X 22 gauge Galvanized steel channel.
BLADES.
22 gauge Galvanized steel curtain type out of the air stream.
FINISH.
Mill. OVERALL HEIGHT
IS ORDER HEIGHT
CLOSURE SPRINGS. PLUS "B" PAN TABLE
HEIGHT LESS 1/4".
301 Stainless Steel Spring.
(D
AM OR
FUSIBLE LINK. TH PER
AN SU ER
D
Standard 165 F. Other available. OR PP W
DE LIE IDTH
R D1
WI /4
DT " L
H) ES
MOUNTING. S
4-1/4"
Vertical .
VARIATION.
All UL Classified fire dampers must be fabricated in
MINIMUM SIZE. accordance with UL procedures. Available variation
Vertical Installation ---- 4"Wx 4"H. are limited to those incorporated in the approved
OVERALL DAMPER HEIGHT
NOTE.
S I F I
* Dampers furnished approximately 1/4" smaller
AS
L E UNDERWRITERS LABORATORIES (UL 555)
than given duct dimension
D
C
UL R
DYNAMIC SYSTEM.
FIRE RESISTANCE RATED 1-1/2 HOUR. (V) VERTICAL MOUNT
* Refer to the KBE Installation Instruction and
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
APPLICATION FEATURES.
MODEL K75-Dy-L IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 3 hours
FOR 4 HOURS OR LESS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM OR
DE "C
R O"
HE
IG OV
HT AL
STANDARD CONSTRUCTION
FRAME. OR "
DE CO"
4-1/4 " Maximum X 22 gauge Galvanized steel channel. R
WI
DT
BLADES. H
22 gauge Galvanized steel curtain type out of the air stream. O RE
RD " CT
ERC" AN
FINISH. HE GL
E
RO
UN
IG D
Mill. HT
CLOSURE SPRINGS.
301 Stainless Steel Spring.
OR
FUSIBLE LINK. DE "C"
R
Standard 165 F. Other available. WI
DT
H "
OR CR"
4-1/4" DE
MOUNTING. R
DI
A.
Vertical
VARIATION.
MINIMUM SIZE. All UL Classified fire dampers must be fabricated in
Model K75 C ---- 4"Wx 4"H. accordance with UL procedures. Available variation
Model K75 CR ---- diameter 3". are limited to those incorporated in the approved
Damper Supplied 1/4" Less
UL R
DYNAMIC SYSTEM.
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
supplements for complete installation details.
MATERIALS RATED 2 HOURS OR LESS. 1"
(V) VERTICAL MOUNT
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIRE DAMPERS
MODEL K75-Dy- SB TYPE L or LB
(304 STAINLESS STEEL BLADES)
UL CLASSIFIED 3 HOURS RATING
APPLICATION FEATURES.
MODEL K75-Dy-L IS APPROVED FOR USE *Closure spring operation for assured closure under
IN WALLS, FLOORS AND PARTITIONS air flow (fans on) in HVAC System.
WITH FIRE RESISTANCE RATINGS *Each damper is marked with a 3 hours
FOR 4 HOURS OR LESS. UL 555 Classified fire damper label for use in
UL 555 CLASSIFIED DYNAMIC RATED FIRE dynamic system.
DAMPER FOR USE IN HVAC SYSTEMS THAT *Meets all UL and NFPA criteria for primary fire
ARE OPERATIONAL IN THE EVENT OF FIRE. dampers in walls and floors with fire resistance
ratings of 4 hours and less.
DYNAMIC CLOSURE WITH AIRFLOW ON
BOTH SIDES RATED:
- MAXIMUM PRESSURE: TO 4" W.G
- MAXIMUM VELOCITY: TO 2400 FPM
VARIATION.
MOUNTING. All UL Classified fire dampers must be fabricated in
Vertical .
accordance with UL procedures. Available variation
ORDER HEIGHT
ORDER HEIGHT
UL R
FIRE RESISTANCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
MODEL K75
CURTAIN TYPE FIRE DAMPER PERFORMANCE DATA
Free Area and Static Friction Loss at various velocities.
DAMPER FREE AREA (SQ FT)
HEIGHT WIDTH (INCHES) HEIGHT WIDTH (INCHES)
(INCHES) (INCHES)
6" 12" 18 " 24 " 30" 36 " 42 " 48" 54" 60 " 6" 12" 18 " 24 " 30 " 36 " 42 " 48" 54" 60 "
6" .14 .33 .52 .70 .89 1.1 1.3 1.5 1.7 1.8 6" .16 .38 .60 .81 1.0 1.3 1.5 1.7 1.9 2.1
12" .31 .72 1.1 1.5 1.9 2.4 2.8 3.2 3.5 4.0 12" .34 .81 1.3 1.8 2.2 2.7 3.2 3.6 4.1 4.6
18 " .48 1.1 1.7 2.4 3.0 3.7 4.3 4.9 5.6 6.2 18 " .53 1.3 2.0 2.7 3.4 4.1 4.8 5.6 5.6 7.0
24 " .65 1.5 2.4 3.2 4.1 5.0 5.8 6.7 7.5 8.4 24 " .72 1.7 2.7 3.6 4.6 5.6 6.5 7.5 7.5 9.4
30 " .82 1.9 3.0 4.1 5.2 6.3 7.3 8.4 9.5 10.6 30 " .91 2.1 3.3 4.6 5.8 7.0 8.2 9.4 10.7 11.9
36 " .99 2.3 3.6 4.9 6.3 7.6 8.9 10.2 11.5 12.8 36 " 1.1 2.6 4.0 5.5 7.0 8.4 9.9 11.4 12.8 14.3
42 " 1.2 2.7 4.2 5.8 7.3 8.8 10.4 11.9 13.4 15.0 42 " 1.3 3.0 4.7 6.4 8.2 9.9 11.6 13.3 15.0 16.8
48 " 1.3 3.1 4.9 6.6 8.4 10.2 11.9 13.7 15.5 17.2 48 " 1.5 3.4 5.4 7.4 9.3 11.3 13.3 15.3 17.2 19.2
54 " 1.5 3.5 5.5 7.5 9.5 11.5 13.5 15.5 17.5 19.4 54 " 1.7 3.9 6.1 8.3 10.5 12.8 15.0 17.2 19.4 21.6
60 " 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.4 21.7
TYPE LB
TYPE L
2.0
3.0
4.0
INSPECTION INSTALLATION
Inspect for shipping damage. The basic intent of a proper installation is to secure
Inspect for proper size and model. the fire damper in, not to, the opening in such a
Inspect installed damper for proper orientation, as stated manner as to prevent distortion and disruption of the
on damper label. damper operation by allowing the fire damper in
Inspect for obstructions which could interfere with free openings to expand and the connecting duct to
operation and complete closure. separate in the event of the collapse of the hanging
Manually cycle the damper to verify proper operation. system. The fire damper must be positioned within
the masonry, block or gypsum wallboard fire barrier.
SLEEVE THICKNESS
Sleeves shall be the same gauge or heavier as the
SEE NOTE ON
DAMPER TO SLEEVE duct to which it is attached. Gauges shall conform to
ATTACHMENT AND SMACNA or ASHRAE duct standards. Damper sleeve
SLEEVE GAUGE
REQUIREMENTS can be no thicker than 10 GA steel. On type C dampers,
the sleeve must be 18 GA. or heavier.
EXPANSION CLEARANCE
The opening in the wall or floor for the fire damper shall be sized
SEE NOTE so as to provide expansion clearance between the sleeve and
ON DUCT
CONNECTION
opening. Clearances do not vary with walls constructed of
different materials. A minimum of 1/8" per foot of overall
damper/sleeve width and height is required. The maximum
3" MIN. FOR DUCT opening size shall not exceed 1/8" per foot plus 1", minimum
CONNECTION AND
MTG. ANGLES total clearance shall be at least 1/4" larger than the overall
assembly.
6" MAX.
S I F I
16" MAX. WHEN AS E
L
INSTALLATION INSTRUCTIONS
D
C
FACTORY INSTALLED
ACCESS DOOR
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
WALL MOUNT SHOWN (VERTICAL INSTALLATION)
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
"K"
STANDARD "K"
SLEEVE EDGE SLEEVE EDGE
TO DAMPER WHEN ORDERING SPECIFY: TO DAMPER
CENTER LINE CENTER LINE
WIDTH X HEIGHT X LENGTH X
GAUGE + ("K" DIMENSION)
WHEN NOT SPECIFIED, DAMPERS
WILL BE PROVIDED CENTERED
"H" SLEEVE IN SLEEVE LENGTH. (L/2) "H" SLEEVE
1-1/2
FLANGES
HEIGHT HEIGHT (4 SIDES)
(1 END)
SLEEVE TYPE "AF"
FLANGED
WHEN ORDERING SPECIFY:
WIDTH X HEIGHT X LENGTH X
"W" SLEEVE "W" SLEEVE
WIDTH
GAUGE + ("K" DIMENSION) WIDTH
WHEN NOT SPECIFIED, DAMPERS
SLEEVE GAUGE
WILL BE PROVIDED CENTERED
IN SLEEVE LENGTH. (L/2)
"L" SLEEVE
LENGTH OVERALL
"L" SLEEVE
LENGTH OVERALL "K"
SLEEVE EDGE
TO DAMPER
"K" CENTER LINE
SLEEVE EDGE
TO DAMPER SLEEVE
CENTER LINE OVERALL
HEIGHT
"H"
SLEEVE
SLEEVE HEIGHT
OVERALL
HEIGHT "H"
SLEEVE
DISTANCE IS BASED ON
HEIGHT
"B" PAN SIZING CHART.
DISTANCE IS BASED ON
1-3/4" "B" PAN SIZING CHART.
"W"
SLEEVE
WIDTH
"W"
SLEEVE
WIDTH SLEEVE TYPE "B"
SLEEVE TYPE "B-1"
WHEN ORDERING SPECIFY: WHEN ORDERING SPECIFY:
WIDTH X HEIGHT X LENGTH X WIDTH X HEIGHT X LENGTH X
GAUGE + ("K" DIMENSION) GAUGE + ("K" DIMENSION)
WHEN NOT SPECIFIED, DAMPERS WHEN NOT SPECIFIED, DAMPERS
WILL BE PROVIDED CENTERED WILL BE PROVIDED CENTERED
IN SLEEVE LENGTH. (L/2) IN SLEEVE LENGTH. (L/2)
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
"K"
SLEEVE EDGE
TO DAMPER
TYPE "CR" ROUND SLEEVE CENTER LINE
DISTANCE IS BASED ON
MODEL K75 CR ROUND
DIA.+2" SIZING CHART.
OVERALL 1" ON THREE
SLEEVE SIDES
WIDTH
"L" SLEEVE
LENGTH OVERALL "L"
SLEEVE
LENGTH
"K" OVERALL
SLEEVE EDGE
TO DAMPER
"K"
CENTER LINE
SLEEVE EDGE
TO DAMPER
CENTER LINE
"H" 2.25
OVAL STD.
HEIGHT
2.25
OVERALL
STD.
SLEEVE
HEIGHT
OVERALL
SLEEVE
HEIGHT
"H"
RECTANGLE
HEIGHT
DISTANCE IS BASED ON
"W" "C" RECTANGLE
1" ON DISTANCE IS BASED ON SIZING CHART.
OVAL THREE OVAL SIZING CHART.
WIDTH SIDES
OVERALL MINIMUM. 1.00" MINIMUM
SLEEVE "W" TYP (4) SIDES
WIDTH RECTANGLE
WIDTH
OVERALL TYPE "C"
TYPE "CO" OVAL SLEEVE SLEEVE
WIDTH RECTANGLE SLEEVE
WHEN ORDERING SPECIFY:
WHEN ORDERING SPECIFY:
OVAL WIDTH X OVAL HEIGHT
RECTANGLE WIDTH X RECTANGLE HEIGHT
X LENGTH X GAUGE
X LENGTH X GAUGE
+ ("K" DIMENSION)
+ ("K" DIMENSION)
WHEN NOT SPECIFIED, DAMPERS
WHEN NOT SPECIFIED, DAMPERS
WILL BE PROVIDED CENTERED
WILL BE PROVIDED CENTERED
IN SLEEVE LENGTH. (L/2)
IN SLEEVE LENGTH. (L/2)
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FEATURES.
APPLICATION
STANDARD CONSTRUCTION
FRAME.
2" Maximum X 22 gauge Galvanized steel channel.
BLADES. DA
MP
22 gauge Galvanized steel curtain type in the air streeam. E
TH R SU
OR
DE
AN PP R
FINISH. OR LIE
D
WI
DT 2"
DE 1 H
Mill. R / 4
WI
DT
"L
ES "THINLINE"
H S
CLOSURE SPRINGS.
301 Stainless Steel Spring.
2"
(For Horizontal mount only, optional on vertical mount) VARIATION.
All UL Classified fire dampers must be fabricated in
FUSIBLE LINK.
accordance with UL procedures. Available variation
Standard 165 F. Other available.
are limited to those incorporated in the approved
procedures. Approved variations available at
MOUNTING.
ORDER HEIGHT
UL R
FIRE RESISTENCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FEATURES.
MODEL K75 DBH * Slim profile design for minimum clearance applications.
*Each damper is marked with a 1-1/2 hours
UL 555 Classified fire damper label.
ORDER HEIGHT
*Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
(H) HORIZONTAL MOUNT ratings of less than 3 hours.
STANDARD CONSTRUCTION
FRAME. OVERALL HEIGHT
IS ORDER HEIGHT
2" Maximum X 22 gauge Galvanized steel channel. PLUS "B" PAN
BLADES. TABLE HEIGHT
(D LESS 1/4"
22 gauge Galvanized steel curtain type out of the air stream. AM O
PE RDE
TH R S R
FINISH. AN UP WID
OR PLIE TH
Mill. DE D
R 1/4
WI " L
CLOSURE SPRINGS. DT ES
H) S
2"
301 Stainless Steel Spring. "THINLINE"
2"
(For Horizontal mount only, optional on vertical mount) VARIATION.
All UL Classified fire dampers must be fabricated in
FUSIBLE LINK.
accordance with UL procedures. Available variation
Standard 165 F. Other available.
are limited to those incorporated in the approved
procedures. Approved variations available at
MOUNTING.
ORDER HEIGHT
UL R
FIRE RESISTENCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
APPLICATION FEATURES.
MODEL K75 IS APPROVED FOR USE * Slim profile design for minimum clearance applications.
IN WALLS, FLOORS AND PARTITIONS *Each damper is marked with a 3 hours
WITH FIRE RESISTANCE RATINGS OF UL 555 Classified fire damper label.
4 HOURS AND LESS. *Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
ratings of 4 hours and less.
STANDARD CONSTRUCTION
FRAME.
ORDER HEIGHT
2" Maximum X 22 gauge Galvanized steel channel. DAMPER SUPPLIED
BLADES. 1/4" LESS
THAN ORDER HEIGHT
22 gauge Galvanized steel curtain type in the air streeam.
FINISH.
Mill.
CLOSURE SPRINGS.
301 Stainless Steel Spring.
FUSIBLE LINK.
Standard 165 F. Other available. DA
MP
E OR
TH R SU DE
AN PP R
MOUNTING. OR LIE
DE D
WI
DT 2"
1 H
Vertical . R
WI / 4 "L "THINLINE"
DT ES
H S
MINIMUM SIZE.
2"
Vertical Installation ---- 4"Wx 4"H. VARIATION.
All UL Classified fire dampers must be fabricated in
MAXIMUM SIZE. accordance with UL procedures. Available variation
Single Section are limited to those incorporated in the approved
Vertical Installation ---- 48"Wx 49"H. procedures. Approved variations available at
ORDER HEIGHT
UL R
FIRE RESISTENCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
* Dampers furnished approximately 1/4" smaller
than given duct dimension
* Refer to the KBE Installation Instruction and
(V) VERTICAL MOUNT supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
APPLICATION FEATURES.
MODEL K75 IS APPROVED FOR USE * Slim profile design for minimum clearance applications.
IN WALLS, FLOORS AND PARTITIONS *Each damper is marked with a 3 hours
WITH FIRE RESISTANCE RATINGS OF UL 555 Classified fire damper label.
4 HOURS AND LESS. *Meets all UL and NFPA criteria for primary fire
dampers in walls and floors with fire resistance
ratings of 4 hours and less.
STANDARD CONSTRUCTION "B" PAN
FRAME.
2" Maximum X 22 gauge Galvanized steel channel.
BLADES.
ORDER HEIGHT
22 gauge Galvanized steel curtain type out of the air
(DAMPER SUPPLIED
stream. 1/4" LESS THAN
FINISH. ORDER HEIGHT
Mill.
CLOSURE SPRINGS.
Optional Stainless Steel Negator Spring. OVERALL HEIGHT
IS ORDER HEIGHT
PLUS "B" PAN
TABLE HEIGHT
FUSIBLE LINK. (D LESS 1/4"
AM O
Standard 165 F. Other available. PE RDE
TH R S R
AN UP WID
OR PLIE TH
MOUNTING. DE D
R 1/4
WI " L
Vertical . DT ES
H) S
2"
"THINLINE"
2"
MINIMUM SIZE. VARIATION.
Vertical Installation ---- 4"Wx 4"H. All UL Classified fire dampers must be fabricated in
accordance with UL procedures. Available varaition
MAXIMUM SIZE. are limited to those incorporated in the approved
Single Section procedures. Approved variations available at
Vertical Installation ---- 48"Wx 44"H. additional cost are :
ORDER HEIGHT
UL R
FIRE RESISTENCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 4 HOURS OR LESS.
* Dampers furnished approximately 1/4" smaller
than given duct dimension
* Refer to the KBE Installation Instruction and
(V) VERTICAL MOUNT supplements for complete installation details.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
DA DA
MP MP
E OR
TH R SU DE E
TH R SU
OR
DE
AN P R AN R
OR PLIE WI
DT 2" P
OR PLIE WI 2"
DE D H DE D DT
R 1 H
WI /4" L "THINLINE" R 1/4
DT
H SS
E WI "
DT LES "THINLINE"
H S
ORDER
HEIGHT
(-1/4")
ORDER
MODEL FLOOR HEIGHT
MODEL
2"
K75DH PARTITION (-1/4")
HORIZONTAL K75DV
MOUNT VERTICAL
MOUNT
2"
WALL
PARTITION
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
one leg inserted into the wall / floor opening providing 6" M
AX
the required clearance is maintained between angle leg
fasteners and the wall / opening. 6" M
AX
CONNECTING DUCTS TO FIRE DAMPER
2" M
SLEEVE AX
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS Duct
Neoprene Gasket
between all angles
7" 7"
48" DUCT
TDC and TDF systems are approved as
3 REQD
breakaway connections when installed
5" 5"
as described in the TDC or TDF SLEEVE DUCT 36" DUCT
addendum to the SMACNA Duct
3 REQD
construction Standards except the
5" 5"
corners may not be bolted. Standard 6"
24" DUCT
metal clip may be used with spacing as TYPICAL TDC/TDF JOINT
shown in diagram. 2 REQD
18" DUCT
& SMALLER CL
1 REQD
DUCT
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
S I F I
AS E
L
INSTALLATION INSTRUCTIONS
D
C
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
SEE NOTES
1&3
6" MAX.
1" MIN.
1" MIN.
TYPE "B"
2" MAX.
DUCT
TYPE "B-1"
FIRE SLEEVE MOUNTING
DAMPER
GRILLE TO BE A
MINIMUM 26 GAUGE
MOUNTING ANGLE
STEEL OR .025" THICK
ALUMINUM
MOUNTING ANGLE
DAMPER BEHIND A GRILLE
SLEEVE
FIRE DAMPERS
PAN SIZING CHART MODEL K75 TYPE B
Vertical & Horizontal Mount.
Maximum Overall Sizes
Type Installation Single Section Multiple Section
Width X Height Width X Height
Vertical 60" X 60" 120" X 120"
Horizontal 60" X 60" 120" X 120"
"P"
"P" BLADE STACK
PAN SIZE OUT OF AIRSTREAM
"O" "H"
"O" Over-all Duct
"H" MODEL K75 TYPE (B)
Height Conection
(Order
Height)
4 5 1 27 31 4
5 6 1 28 32 4
6 7 1 29 33 4
7 8 1 30 34 4
8 10 2 31 35 4
9 11 2 32 36 4
10 12 2 33 37 4
11 13 2 34 38 4
12 14 2 35 39 4
13 15 2 36 41 5
14 16 2 37 42 5
15 17 2 38 43 5
16 18 2 39 44 5
17 20 3 40 45 5
18 21 3 41 46 5
19 22 3 42 47 5
20 23 3 43 48 5
21 24 3 44 49 5
22 25 3 45 51 6
23 26 3 46 52 6
24 27 3 47 53 6
25 28 3 48 54 6
26 29 3 49 55 6
50 56 6
51 57 6
Note : All Sizing in Inches
52 58 6
53 59 6
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
5.75
ACTUAL
WIDTH
6.0"
1.0" "C" SIZE
"C" SIZE BLADE STACK
BLADE STACK
58.75
ACTUAL
51.75
1" 1"
5.75 O.D
ACTUAL ACTUAL
3.75
1" 1"
O.D HEIGHT
ACTUAL
1"
1" MIN.
1" MIN.
TRANSFER GRILLE
BOTH SIDES
4-1/4"
4-1/4"
MODEL
K75 MODEL
Type A or L TRANSFER GRILLE K75
SINGLE SIDE Type A or L
TO BREAKAWAY JOINT
PARTITION
PARTITION
1" MIN.
1" MIN.
TRANSFER GRILLE
BOTH SIDES
4-3/8"
4-3/8"
MODEL
K75-T MODEL
Type A or L TRANSFER GRILLE K75-T
SINGLE SIDE Type A or L
TO BREAKAWAY JOINT
PARTITION
PARTITION
1" MIN.
1" MIN.
TO BREAKAWAY JOINT
TRANSFER GRILLE
BOTH SIDES 2.00
2.00
MODEL
MODEL K75D
K75D
TRANSFER GRILLE
SINGLE SIDE
TO BREAKAWAY JOINT
PARTITION
PARTITION
3. Secure angles to sleeve only, so as to frame the wall opening.
Fasten to the sleeve only using the same means as required for
fastening the damper to the sleeve.
1. Perimeter mounting angles to be a minimum 4. Grille to flange attachment by means of 1/4" dia. pop rivets, #8
of 1-1/2 x 1-1/2 x 16 GA on dampers sheet metal screws or #8 bolts and nuts. Fasteners to be plated
36 x 50 and smaller. For dampers greater steel or stainless steel, minimum two fasteners per side.
than 36 x 50, angles to be a minimum of
1-1/2 x 1-1/2 x 14 GA.
FIRE DAMPER
CLOSURE INDICATION SWITCHS
MODEL K75 AV
MODEL K75 AV
ORDER HEIGHT
Negator Stainless Steel
ORDER HEIGHT
Blade Lock
Blade Lock
TYPE 1 TYPE 2
MODEL: SWITCH VM5 MODEL: SWITCH VM6
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
A DETAILS C, D, AND E
2" 2"
3/4"
DETAILS A AND B
B 3/16"
BLIND 3-1/2"
HORIZONTAL
MULLION RIVET
OR 3/4"
LONG WELDS
12" OC
120" 6" MAX
MAX HEIGHT FROM
DETAIL F
ENDS
VERTICAL WALL THICKNESS
MULLION
MULLION CROSS SECTION
16 GA. GALVANIZED STEEL
1"
MIN.
CONDITIONS & RESTRICTIONS
Fabricated from galvanized steel with a normal yield
strength of 42,000 psi.
Intended for use in concrete block or poured walls only
with a minimum wall thickness of 7" and a maximum wall
thickness of 12"
To permit proper embedding of anchors, hollow con-
crete block walls are to be filled at the opening by
minimum 3,500 psi concrete. FIRE
Steel mullions are not to be inside the ductwork. For DAMPER
ducted systems, each sub-divided opening must be
individually ducted.
MULLION
TUBE
EXPANSION CLEARANCE
DAMPER
SLEEVE
RETAINING
AS
S I F I
E
ANGLE DETAIL B
L
INSTALLATION INSTRUCTIONS Reference the damper's installation instructions
D
C
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
regarding the approved method of attaching the
damper to the sleeve, attaching the retaining
angles to the sleeve, required expansion clear-
ances, sleeve gauge, ect.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
6-1
3/1
6"
COUNTERSUNK HOLES
FOR 1/4" DIA. FLAT HEAD
MACHINE SCREWS
OR 1" LONG WELDS
SEE DETAIL C
DETAIL D
Top, bottom or side end caps
12 GA galvanized steel
DETAIL C
The end caps are attached by means of X= WALL THICKNESS MADE UP OF
1" long x 3/8" dia. steel expansion
anchors embedded into the opening 3-1 TWO WELDED
/4"
with 1/4" dia. flat head machine screws, /4" ZEE SECTIONS
eight per end cap. If a steel lintel is X- 1 ALL 1-1
3/1
6"
ER
used, four 1" long welds per end cap OV
(two per leg) may be used.
COUNTERSUNK HOLES
FOR 1/4" DIA. FLAT
HEAD MACHINE SCREWS
3" P
LUS
1
FO /8" PE
OT
OF R
WID SPAN
TH
X 1/4" 1-1
/2 X
3X
AN 6-1
GL /4 L 1/4" FULL LENGTH
ES G
WELD ALL AROUND
6"
X/4 1/1 GS
X+ E LE
S ID
IN
X/8
(2) FASTENERS 4. When wooden studs are used, filler pieces must be
2" installed around the entire opening. Filler pieces are
optional when metal studs are used (consult local codes
to determine if filler pieces are required). Filler pieces are
(2) FASTENERS 2" to be double screwed (or nailed to wooden studs) on 12"
max. centers to the web of runners and studs.
5. The Office of the California State Fire Marshal and other
FLOOR FLANGE
local jurisdictions require filler pieces around both wood
and metal framed openings (no filler pieces around
MIN. 2-1/2" STUD MIN. 1-1/2" MINERAL FIBER concrete or masonry openings). These codes also
OR RUNNER GYPSUM WALLBOARD require a double header for wood framed openings,
consult local code authorities.
MIN. 1/2" THICK 6. Double jamb studding shown and required when opening
GYPSUM WALLBOARD width or height exceeds 36". Single jamb studding
MIN. 1" acceptable for openings 36" x 36" and smaller.
OVERLAP DRYWALL SCREWS (METAL STUDS)
NAILS (WOOD STUDS)
S I F I
AS E
L
INSTALLATION INSTRUCTIONS
D
C
SEE NOTE 2
UL R
IN CONFORMANCE TO
UNDERWRITERS LABORATORIES
REQUIREMENTS
MIN. 1/2" THICK FILLER FIRE DAMPER SLEEVE
PIECE, SEE NOTES 4 & 6
1 HOUR RATED PARTITION WALL
SECTION "B-B" 2-1/2" MIN.
MIN. 1-1/2" MINERAL FIBER RUNNER 2-1/2" MIN.
MIN. 2-1/2" STUD STUD
OR RUNNER GYPSUM WALLBOARD
PANHEAD SCREWS
MIN. 1" (METAL STUDS)
DRYWALL SCREWS (METAL STUDS) NAILS (WOODEN STUDS)
OVERLAP
NAILS (WOOD STUDS) (4) PER 90 DEG BEND
RETAINING ANGLE
ONE SIDE MAY BE REVERSED
PROVIDING THAT ADEQUATE
CLEARANCE IS MAINTAINED
SECTION "A-A"
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
FIBER GLASS
DUCT BOARD
FASTENER
NOTE: Sealing of fibrous glass duct
board to sheet metal sleeve must be
made with glass fabric and mastic, TAPE
except where operation pressure is
less than 1" wg and sheet metal FIRE DAMPER
surfaces are carefully cleaned, in which
case pressure sensitive aluminum foil
tape may be used ACCESS DOOR #10 SHEET METAL SCREWS
& 2-1/2 " SQUARE WASHER
CLOSURE
FIRE DAMPER
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
ETL
ELECTRO - THERMAL LINK
ORDER HEIGHT
Damper Supplied 1/4" Less Than Order Height.
4"
1
UL R
FIRE RESISTENCE RATED 3 HOURS.
FOR USE IN UL CLASSIFIED BUILDING
Detailed Description of Electro Thermal Link
(ETL) , Suggested Usage, and Specifications.
MATERIALS RATED 4 HOURS OR LESS.
S I F I
AS E UNDERWRITERS LABORATORIES (UL 555)
L
D
C
UL R
FIRE RESISTENCE RATED 1-1/2 HOUR.
FOR USE IN UL CLASSIFIED BUILDING
MATERIALS RATED 2 HOURS OR LESS.
S I F I
AS E
L
D
C
UNDERWRITERS LABORATORIES
UL R
CLASSIFIED FUSIBLE LINK
USED WITH FIRE DAMPERS.
kbe
AIR MOVEMENT PRODUCTS
TEL: 961-1-898268, FAX: 961-1-887113, Email: kbe@kbelebanon.com
ORDER
QTY DAMPER
FUSIBLE
WIDTH
X LINK F
Dy : Dynamic 135, 165, SLEEVE
HEIGHT SPECIFY
-- : Static 212, 285,
O.A.LENGTH
VERTICAL OR ETL.
T: FOR 20GA FRAME HORIZONTAL SLEEVE
--: FOR 22GA FRAME MOUNT TYPE OF EDGE TO
FOR TYPE SLEEVE:
DAMPER C, CR, CO FIRE
MODEL A, AF,B,B-1, C, DAMPER
NECK TO BE CR, CO AND
K75 A SEALED OR CENTER
B SIZES.
UNSEALED LINE K.
C
--- : NORMAL CR
CO
SB: STAINLESS D SLEEVE SPECIFY
STEEL BLADES DB GAUGE: 22/20, 18,
L 16, 14, 12, 10.
SC: STAINLESS LB
STEEL LC
CONSTRUCTION LCR
LCO
N
NB