TRANSFORMER SIZING & TENTATIVE LOAD LIST


Sl. Installed Power Power Consumption
Description
No. Qty KW/ Unit Rpm Total KW Working Demand kW D.Factor U. Factor Running kW

1a Mobile conveyor -Belt Feeder MBC1 1 132.00 1440 132.00 1 132 0.60 0.85 67.32
1b Mobile conveyor -Belt Feeder MBC2 1 132.00 1440 132.00 1 132 0.60 0.85 67.32
2a BC01A 1 37.00 1440 37.00 1 37 0.80 0.85 25.16
2b BC01B 1 30.00 1440 30.00 1 30 0.80 0.85 20.40
3a BC02A 1 55.00 1440 55.00 1 55 0.80 0.85 37.40
3b BC02B 1 45.00 1440 45.00 1 45 0.80 0.85 30.60
4a BC03A 1 75.00 1440 75.00 1 75 0.80 0.85 51.00
4b Actuator for Plough 6 1.50 730 9.00 1 1.5 0.80 0.85 1.02
5 BC3 A1-A6 6 18.50 1440 111.00 1 37 0.80 0.85 12.58
6 Motorized Gate-(chute) 2 1.50 1440 3.00 1 3 0.80 0.85 1.02
7 BC3B 1 22.00 1440 22.00 1 22 0.80 0.85 14.96
8a BC4B 1 37.00 1440 37.00 1 37 0.80 0.85 25.16
8b Actuator for Plough 2 1.50 730 3.00 1 1.5 0.40 0.85 0.51
9 Hoist 3 5.50 1440 16.50 0 0 0.30 0.85 0.00
10 Dust Suppression System 2 75.00 1440 150.00 1 150 0.50 0.70 26.25
11 Unit Dust collector 3 45.00 1440 135.00 1 45 0.50 0.70 15.75
12 Motorized plough 2 1.50 1440 3.00 1 1.50 0.40 0.85 0.51
13 Fire Fighting system 1 7.50 1440 7.50 0 0 0.80 0.85 0.00
14 Lighting and Utility Power 1 35.00 1440 35.00 1 35 0.80 0.60 16.80
15 Control Supply & UPS Power 1 25.00 1440 25.00 1 25 0.80 0.60 12.00
Total Installed 1063.00 864.5
Total Running 425.76 12.10 15.00
Maximum Demand (kVA) 1017.059
Installed (kW) 1063.00
Running (kW) 425.76
Future Margin (25%) 1328.75
Transformer Loading (80%) 1660.94
Transformer Efficiency (95%) 1748.36
Transformer Size in KVA 2056.89
Nearby Transformer Size (kVA) 2000.00

1 of 2
Date:
TRANSFORMER SIZING & TENTATIVE LOAD LIST
Sl. Installed Power Power Consumption
Description
No. Qty KW/ Unit Rpm Total KW Working Demand kW D.Factor U. Factor Running kW

Note: The above are indiactive only. Actual kw rating c/w e&I related changes will be submitted upon finalize design.