You are on page 1of 8

IL 01301034E IL 01301034E

Installation Instructions for Series NRX Modbus Communications Adapter


Module (MCAM)
TABLE OF CONTENTS
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY DESCRIPTION PAGE
SECTION 1: General Information 1
The information, recommendations, descriptions and safety notations in this
document are based on Eaton Electrical Inc. and/or Eaton Corporations SECTION 2: Installation of Modbus Communications Adapter Module 2
(Eaton) experience and judgment and may not cover all contingencies. If SECTION 3: Basic Modbus RS485 Network Wiring 4
further information is required, an Eaton sales office should be consulted. SECTION 4: Modbus Communications Adapter Module Connections 4
SECTION 5: Jumpers and Indicator LEDS 4
Sale of the product shown in this literature is subject to the terms and condi-
tions outlined in appropriate Eaton selling policies or other contractual agree- SECTION 6: Viewing/Setting Modbus Address 7
ment between Eaton and the purchaser. SECTION 7: Network Communications Protocol 7
SECTION 8: Troubleshooting 15
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES,
EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PAR- FIGURES
TICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICAL- FIGURE 1: Series NRX Modbus Communications Adapter Module 1
LY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY FIGURE 2: Modbus Communications Adapter Module in a Modbus Network 2
SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CON- FIGURE 3: Series NRX Communication with Digitrip 520M 5
TENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY
FIGURE 4: Communications Control (SR and ST Wiring) 6
CONTRACT BETWEEN THE PARTIES.
FIGURE 5: Modbus Communications Adapter Module (front view closeup) 4
In no event will Eaton be responsible to the purchaser or user in contract, in FIGURE 6: Setting Sequence Programming Flow Chart for Series NRX 520M Trip Unit 7
tort (including negligence), strict liability or otherwise for any special, indirect, FIGURE 7: Control of Product Data Format 8
incidental or consequential damage or loss whatsoever, including but not limit-
FIGURE 8: 4-Register Energy Data Format 9
ed to damage or loss of use of equipment, plant or power system, cost of capi-
tal, loss of power, additional expenses in the use of existing power facilities, or TABLES
claims against the purchaser or user by its customers resulting from the use of TABLE 1: Power Connector Pin Outs 4
the information, recommendations and descriptions contained herein. TABLE 2: Modbus Connector Pin Outs 4
The information contained in this manual is subject to change without notice. TABLE 3: MCAM Communication Setting Ranges 7
TABLE 4: Modbus Register Map In Register Number Order 10
TABLE 5: Modbus Register Map In Functional Order 12
TABLE 6: MCAM Configuration Registers 14
TABLE 7: Control Slave Action Number Definitions 14
TABLE 8: Date and Time Register Definitions 14
TABLE 9: Diagnostic Sub Function Numbers 14
TABLE 10: Primary Status Code Definitions 15
TABLE 11: Secondary Status Code Defintions 15
TABLE 12: Cause-of-Status Defintions 15
network using the Modbus RTU (Remote Terminal Unit)
protocol. Information is exchanged through the MCAM
between the Modbus master and the Series NRX trip
(1) Only qualified electrical personnel should be unit using assigned registers.
permitted to work on the equipment. Figure 1 Series NRX Modbus Communications
(2) Always de-energize primary and secondary Adapter Module
circuits.
(3) Drawout circuit breakers should be removed
from their drawout cassette.
(4) All circuit breakers should be switched to the
off position and mechanism springs discharged.
Eaton Corporation
Electrical Group Failure to follow these steps for all procedures
1000 Cherrington Parkway described in this instruction leaflet could result
Moon Township, PA 15108 in death, bodily injury, or property damage.
United States
877-ETN CARE (877-386-2273) PowerChain Management Section 1: General Information
Eaton.com is a trademark of Eaton
Corporation. All other The Series NRX Modbus Communications Adapter
trademarks are property
of their respective owners. Module (Figure 1) is an accessory that will operate as a
communicating device in conjunction with a compatible
Series NRX trip unit/breaker in a master communica-
tions network (Figure 2). The catalog number of this
2009 Eaton Corporation
All Rights Reserved product is MCAM.
Printed in USA
Publication No. IL01301034E The MCAM communicates to a master on a Modbus
March 2009
Effective 03/09 For more information visit: www.eaton.com 1
IL 01301034E IL 01301034E

Figure 2 Modbus Communications Adapter For drawout circuit breakers, secondary terminal blocks Table 10 Primary Status Table 11 Secondary Status
Modules in a Modbus Network as well as the Modbus Communications Adapter Code Definitions Code Definitions
Module are DIN rail mounted on the top front portion of
the drawout cassette. The module is designed to install Code Definition Code Definition
or replace the four terminal blocks (eight contacts in 0 Unknown 0 Unknown
total) at secondary contacts 19 through 26. Refer to the 1 Open 3 Test Mode
master connection diagram which can be found in the 2 Closed 7 Powered up
Master
Device
Communications breaker instruction manual MN01301001E. For addi- 3 Tripped 8 Alarm
Network tional information relative to secondary terminal block 4 Alarmed
installation and/or removal beyond that which is pre-
sented in this section, refer to IL01301037E. Table 12 Cause-of-Status Code Definitions
Proceed with the following 7 steps: Code Defintion Code Defintion

Step 1: Using a T-15 Torx, remove the four mounting 0 Unknown 66 Fixed Instantaneous Phase Overcurrent #2
screws holding the Terminal Block Alignment Bracket in 1 Normal operating mode 67 Reverse Phase
place. 3 Instantaneous Phase Overcurrent 68 Reverse Sequence
MCAM MCAM MCAM Over Voltage Phase Current Loss
11 69
Module Module Module
Steps 1 12 Under Voltage 71 Alarm Active
1 2 3
15 Under Frequency 72 Bad Frame
16 Over Frequency 73 Phase Currents Near Pickup
17 Current Unbalance 75 Making Current Release
18 Voltage Unbalance 76 Fixed Instantaneous Phase Overcurrent #3
Series Series Series 19 Apparent Power Factor 77 Setpoints Error
NRX NRX NRX 26 Power Demand 78 Over-temperature
Breaker Breaker Breaker VA Demand 79 Accessory Bus
27
30 Total Harmonic Distortion 80 Long Delay Neutral Overcurrent
31 Operations Count 82 Historical Data
The Modbus Communications Adapter Module is a 33 Control via Communications 84 Ground Fault (Instantaneous or Delay)
slave device and as such requires a master device for 37 Coil Supervision 85 Earth Fault (Instantaneous or Delay)
control command initiation. Each Modbus 39 RAM Error 146 Frequency Out Of Range
Communications Adapter Module provides: 43 EEROM Error 148 Check Aux Switch
Circuit Breaker Open/Close/Reset Control 46 Watchdog 149 Overcurrent
61 Long Delay Phase Overcurrent 153 Maintenance Mode
NRX Trip Unit Source/Residual Ground Selection (if 62 Short Delay Phase Overcurrent 154 Breaker Mech Fault
applicable) 63 Fixed Instantaneous Phase Overcurrent #1 156 Disconnect Position
Flashing Status LED indicating module has power 64 Bad / Missing Rating Plug 157 Shunt Trip Problem
65 Reverse Power
Modbus Communication Enable/Disable selection Step 2: Carefully slide the Alignment Bracket out from
jumper for Remote Open/Close Control between any mounted terminal blocks, and put it aside Section 8: Troubleshooting
DIN rail mounting (11mm H, 28mm W DIN rail mini- with its mounting hardware for re-installment after the
mum requirement) Communications Adapter Module is connected to the The most common issues experienced with the installa-
DIN rail. tion of a Series NRX Modbus Communications Adapter
Input power for module from 24 Vdc Module are addressed below. If you have additional
Steps 2
The Modbus Communications Adapter Module is questions or need further information and/or instruc-
designed to be installed, operated, and maintained by tions, please contact your local representative or the
adequately trained people. These instructions do not Customer Support Center at 1-800-356-1234.
cover all details or variations of the equipment for its
storage, delivery, installation, checkout, safe operation Observation 1: Status LED not flashing
or maintenance. Action - Verify proper input power to module
If you have any questions or need additional informa- connectors
tion or instructions, please contact your local represen-
tative or the Customer Support Center at 1-800-356- Observation 2: Status LED flashing, but module
1243. does not change state in response to master
command requests
Section 2: Installation of Modbus Action - Verify correct module address
Communications Adapter Module
Action - Verify communication cable is con-
The following steps outline the installation procedure nected correctly from master to module
for a Series NRX Modbus Communications Adapter
Module in a drawout circuit breaker configuration only.
For fixed mounted circuit breakers, a separate DIN rail
mounting configuration is preferred. Consult the
Customer Support Center for additional information.
The following tools should be available:
#T-15 Torx
Small flat blade screwdriver

2 For more information visit: www.eaton.com Effective 03/09 Effective 03/09 For more information visit: www.eaton.com 15
IL 01301034E IL 01301034E

Table 6 MCAM Configuration Registers Step 3: Remove the terminal block in location 19/20 by
Steps 5
Modbus Modbus inserting a small screwdriver in the recessed area in the
Register Definition R/W Register10 Register # of top front of the terminal block as shown, and gently pry
Number Address16 Regs10 down to release and remove the block from the DIN rail.
Low High Low High
Steps 3
Mapped Block of Registers Configuration R/W 41001 420481 03E8 5000 100
Mapped Block of Registers Data R 41201 420737 04B0 5100 4 * 100
Invalid Object Access Configuration R/W 42001 425345 07D0 6300 1
Floating Pt Data Word Order Configuration R/W 42002 425346 07D1 6301 1
Fixed Pt Data Word Order Configuration R/W 42003 425347 07D2 6302 1
Supervisory Control Query R/W 42901 425089 0B54 6200 3
Date and Time Registers R/W 42921 0B68 8

Table 7 Control Slave Action Number Definitions


Control Group Definition Byte2 Byte1 Byte0
Reset Reset trip 0 0 2
Reset (peak) demand-watts 0 0 4
Reset (synchronize) demand watts window 0 0 64 (4016)
Step 6: Carefully slide the Terminal Block Alignment
Snapshot command 0 0 128 (8016) Bracket back into position. Before securing the
Reset (peak) demand-currents 0 1 1 bracket in place, inspect it from the bottom to
Reset all min/max values 0 1 4 ensure that the teeth on the bracket separate
Unlock waveform buffer (clear upload-in-progress) 0 1 5 each individual terminal block. One installed ter-
Reset min/max currents 0 1 13 Step 4: Repeat the same procedure performed in Step minal block only should be visible between two
Reset min/max PF-apparent 0 1 16 3 to remove terminal blocks at locations 21/22, 23/24 teeth when the alignment bracket is properly
Circuit Breaker Open request 1 0 8 and 25/26. Note: The extra DIN rail mounting positioned. Secure the Terminal Block Alignment
Open-Close Close request 1 0 9 screw located in the space where the four termi- bracket using the four screws previously removed.
nal blocks were mounted may need to be Hand tighten the four mounting screws.
removed to allow the units pogo pin ground to
Table 8 Date and Time Register Definitions
properly hit the metal DIN rail. Steps 6
Definition Register Number Register Address Data Range
(decimal) (hexadecimal) (decimal) Steps 4

Month 402921 0B68 1 -12


Day 402922 0B69 1 - 31
Year 402923 0B6A
Day of Week 402924 0B6B 1=Sunday...7=Saturday
Hour 402925 0B6C 0 - 23
Minute 402926 0B6D 0 - 59
Second 402927 0B6E 0 - 59
1/100th Second 402928 0B6F 0 - 99 Mounting
Screw

Table 9 Diagnostic Sub Function Numbers


Sub-function Name
No. # (decimal) Step 7: A mounted communications module appears
0 echo query as shown, and the installation procedure is complete.
1 restart communications The module can now be wired in keeping with the infor-
4 force listen mation presented in Section 3.
10 clear MCAM / slave product counters
Steps 7
11 Modbus UART bus message count Step 5: Tilt the communications module forward to
12 Modbus UART communication error count engage the upper part of the DIN rail, and then snap it
13 MCAM exception error count back into the DIN rail for complete engagement.
14 MCAM message count
15 MCAM no response count
16 MCAM NAK count
17 MCAM busy count
18 Modbus UART over run error count
20 clear Modbus UART counters
21 slave product checksum error count
22 slave product over run count
23 Modbus UART framing error count
24 Modbus UART noise error count
25 Modbus UART parity error count
26 MCAM firmware version & rev
27 MCAM firmware month & day
28 MCAM firmware year
29 reset MCAM Block0Of-Registers

14 For more information visit: www.eaton.com Effective 03/09 Effective 03/09 For more information visit: www.eaton.com 3
IL 01301034E IL 01301034E

Section 3: Basic Modbus RS485 Network Figure 5 Modbus Communications Adapter Table 5 Modbus Register Map In Functional Order (continued from previous page)
Wiring Module (front view closeup) Objects (complete list) Modbus Register Number Modbus Register Address Modbus Products
The following simplified rules apply to a given system
consisting of a cable link between master and slave Name Numeric Units IEEE Fixed IEEE Fixed FP NRX NRX
float point float point Scale 520M 1150
devices (Figure 2). For more complex considerations, (FP) (FP) Factor
please refer to standard Modbus RTU wiring specifica-
tion rules for the RS485 network. (hex) (hex)

1) The recommended Modbus cable has twisted-pair freq Hz 404661 406197 1234 1834 10 x
Frequency x
freq Hz 404721 406257 1270 1870 100
wires (24 AWG stranded 7x32 conductors with PVC x
real 3 ph (power) W 404715 406251 126A 186A 1
insulation) having an aluminum/mylar foil shield with peak demand W 404697 406233 1258 1858 1 x
drain wire. real 3 ph (power) W 404651 406187 122A 182A 1 x
reactive 3 ph VAR 404653 406189 122C 182C 1 x
2) The maximum system capacity is 4,000 feet of com- apparent 3 ph VA 404655 406191 122E 182E 1 x
munications cable and 247 devices on the Modbus RTU A ph W 404667 406203 123A 183A 1
network.. LEDs Power
B ph W 404669 406205 123C 183C 1
C ph W 404671 406207 123E 183E 1
3) Make sure there is twisted-pair wire that is recom- reactive A ph VAR 404673 406209 1240 1840 1
mended for Modbus RTU network use. Use shielded reactive B ph VAR 404675 406211 1242 1842 1
Jumper Plugs reactive C ph VAR 404677 406213 1244 1844 1
twisted-pair wire to connect each slave to the Modbus apparent A ph VA 404679 406215 1246 1846 1
for
RTU network, daisy-chain style. The polarity of the Communication apparent B ph VA 404681 406217 1248 1848 1
twisted pair is CRITICALLY important. Control apparent C ph VA 404683 406219 124A 184A 1
pf pf 404717 406253 126C 186C 100 x
displacement 3 ph pf 404657 406193 1230 1830 100
Section 4: Modbus Communications Adapter displacement A ph pf 404685 406221 124C 184C 100
Module Connections displacement B ph pf 404687 406223 124E 184E 100
Power Factor displacement C ph pf 404689 406225 1250 1850 100
Jumper Plug apparent A ph pf 404691 406227 1252 1852 100
for Source apparent B ph pf 404693 406229 1254 1854 100
All applicable safety codes, safety standards, and Sensing apparent C ph pf 404695 406231 1256 1856 100
apparent pf 404659 406195 1232 1832 100 x
safety regulations must be strictly adhered to
K-Factor K-factor 404663 406199 1236 1836 1
when installing, operating, or maintaining this THD Factor THD factor 404665 406201 1238 1
1838
equipment. Failure to comply could result in forward KWh N/A 406259 N/A 1872 1 x
MicroController LED (Status)
death, bodily injury, or property damage. reverse KWh N/A 406261 N/A 1874 1 x
This indicator will be flashing green whenever the mod- (K) Energy total KWh N/A 406263 N/A 1876 1 x
For installation specifics, refer to Figures 3 and 4 on ule is powered up and when the microprocessor is exe- apparent KVAh N/A 406271 N/A 187E 1 x
pages 5 and 6 respectively for wiring diagrams, as well cuting instructions. When the Series NRX Modbus forward Wh N/A 406305 N/A 18A0 1 x
as pin out Table 1 (power connections) and Table 2 Communications Adapter Module is connected to a
Energy reverse Wh N/A 406309 N/A 18A4 1 x
(4 reg objects) total Wh N/A 406313 N/A 18A8 1 x
(Modbus connections) on this page. Series NRX trip unit for the first time, this LED will apparent VAh N/A 406329 N/A 18B8 1 x
Table 1 Power Connector Pin Outs alternately flash red and green to signal a learning lead KVARh N/A 406267 N/A 1878 1
Reactive
process between both units. This automatic process (K) Energy
lag KVARh N/A 406269 N/A 187A 1
Pin # Input Signal net
will take approximately 15 seconds and occurs only KVARh N/A 206271 N/A 187C 1
1 24 Vdc + lead VARh N/A 406317 N/A 18AC 1
once during the initial startup. The LED will also flash Reactive Energy
2 24 Vdc - lag VARh N/A 406321 N/A 18B0 1
red if the module is not connected to, or unable to com- (4 reg objects)
N/A
3 Control Signal Common net VARh N/A 406325 18B4 1
municate with a Series NRX trip unit. Motor phase unbalance % 404737 406273 1280 1880 100
4 Control Open Signal thermal capacity %
Modbus RS485 Network Tx LED (Transmit) 404739 406275 1282 1882 100
5 Control Close Signal motor winding 1 C 404741 406277 1284 1884 1
This LED will be lit whenever the module is transmit- motor winding 2 C 404743 406279 1286 1886 1
Module power uses a 5-pin input connector.
ting on the Modbus RTU network. motor winding 3 C 404745 406281 1288 1
Power requirement is 24 Vdc, 10 watts. 1888
motor winding 4 C 404747 406283 128A 188A 1
Modbus RS485 Network Rx LED (Receive) motor winding 5 C 404749 406285 128C 188C 1
Table 2 Modbus Connector Pin Outs motor winding 6 1
Temperature C 404751 406287 128E 188E
Pin # Signal
This LED will be lit whenever the module is receiving motor bearing 1 1290
C 404753 406289 1890 1
from the Modbus RTU network. motor bearing 2 C 404755 406291 1292 1892 1
1 RS485 Network-B (non-inverting)
load bearing 1 C 404757 406293 1294 1894 1
2 RS485 Network-A (inverting) Modbus Control Jumper load bearing 2 1296
C 404759 406295 1896 1
3 Common This jumper provides the user with a means of enabling auxiliary C 404761 406297 1298 1898 1
device temperature C 404763 406299 129A 189A 1
4 Shield or disabling remote communication control commands
to the Series NRX trip unit. With jumper placed in the Note: All objects are two (2) registers in length unless specified otherwise.
This 4-Pin connector provides the interface
to the Modbus network. Enable position, remote Open and Close Breaker The primary and secondary codes are mapped to the high and low bytes, respectively, of registers 404609 (120016) and 406145 (180016).
commands can be acted upon. With the jumper in the The primary status codes are shown in Table 10. The secondary status codes are shown in Table 11. The cause-of-status codes are mapped
Connect shield wire to ground at master device end only. to registers 404610 (120116) and 406146 (180116). The cause-of-status codes are shown in Table 12. The primary/secondary and cause-of-status
Interconnect shielding where devices are daisy-chained. Disable position, these commands will not be accept- must be read as a single two (2) register object.
ed.
Section 5: Jumpers and Indicator LEDS These numeric entries have specific definitions dependent on the the particular Eaton product.
Source/Residual Ground Selection Jumper
Refer to Figure 5 to become familiar with specific This jumper selects the protection configuration for
jumper and LED locations on the Modbus Series NRX trip units with ground fault protection or
Communications Adapter Module. ground fault alarm functionality. Consult Series NRX
trip unit instructions (IL 70C1619) for further informa-
tion on ground sensing. This jumper is not applicable
and does not function for non-ground fault style trip
units.

4 For more information visit: www.eaton.com Effective 03/09 Effective 03/09 For more information visit: www.eaton.com 13
IL 01301034E IL 01301034E

Table 5 Modbus Register Map In Functional Order (continued on next page) Figure 3 Series NRX Modbus Communication with Digitrip 520M
Objects (complete list) Modbus Register Number Modbus Register Address Modbus Products

Name Numeric Units IEEE Fixed IEEE Fixed FP NRX NRX


float point float point Scale 520M 1150
(FP) (FP) Factor

(hex) (hex)
Product ID prod ID 404719 or 406255 126E or 186E x x
primary 404609 or 406145 hi byte 1200 or 1800 hi byte x x
Status secondary 404609 or 406145 lo byte 1200 or 1800 lo byte x x
Cause x x
cause 404610 or 406146 1201 or 1801
IA A 404611 406147 1202 1802 10 x x
IB A 404613 406149 1204 1804 10 x x
IC A 404615 406151 1206 1806 10 x x
IG A 404617 406153 1208 1808 10 x x
IN A 404619 406155 120A 180A 10 x x
Current IAvg A avg 404621 406157 120C 180C 10
peak IA demand A 404641 406177 1220 1820 10 x
peak IB demand A 404643 406179 1222 1822 10 x
peak IC demand A 404645 406181 1224 1824 10 x
peak IG demand A 404647 406183 1226 1826 10
peak IN demand A 404649 406185 1228 1828 10
VAB V 404623 406159 120E 180E 10 x
VBC V 404625 406161 1210 1810 10 x
L-L Voltage
VCA V 404627 406163 1212 1812 10 x
VLLavg V avg 404629 406165 1214 1814 10
VAN V 404631 406167 1216 1816 10 x
VBN V 404633 406169 1218 1818 10 x
L-N Voltage VCN V 404635 406171 121A x
181A 10
VLN V avg 404637 406173 121C 181C 10
N-G Voltage VNG V 404639 406175 121E 181E 10
Communications
VAB V 404699 406235 125A 185A 10
VBC V 404701 406237 125C 185C 10 Module
Source 1 VCA V 404703 406239 125E 185E 10
freq Hz 404705 406241 1260 1860 10
VAB V 404707 406243 1262 1862 10
VBC V 404709 406245 1264 1864 10
Source 2 VCA V 404711 406247 1266 1866 10
freq Hz 404713 406249 1268 1868 10
404801 406337 12C0 18C0 10

Network A ph V
B ph V 404803 406339 12C2 18C2 10
Voltage
C ph V 404805 406341 12C4 18C4 10
A ph V 404807 406343 12C6 18C6 10
Transformer
B ph V 404809 406345 12C8 18C8 10
Voltage
C ph V 404811 406347 12CA 18CA 10
A ph V 404813 406349 12CC 18CC 10
B ph V 404815 406351 12CE 18CE 10
C ph V 404817 406353 12D0 18D0 10
A ph direct V 404819 406355 12D2 18D2 10
A ph quadrature V 404821 406357 12D4 18D4 10
Phasing
B ph direct V 404823 406359 12D6 18D6 10 Series NRX
Voltage
B ph quadrature V 404825 406361 12D8 18D8 10 Circuit Digitrip 520M
C ph direct V 404827 406363 12DA 18DA 10
C ph quadrature V 404829 406365 12DC 18DC 10 Breaker
pos seq direct V 404831 406367 12DE 18DE 10
pos seq quadrature V 404833 406369 12E0 18E0 10
Note: All objects are two (2) registers in length unless specified otherwise.
The primary and secondary codes are mapped to the high and low bytes, respectively, of registers 404609 (120016) and 406145 (180016).
The primary status codes are shown in Table 10. The secondary status codes are shown in Table 11. The cause-of-status codes are mapped
to registers 404610 (120116) and 406146 (180116). The cause-of-status codes are shown in Table 12. The primary/secondary and cause-of-status
must be read as a single two (2) register object. Notes

These numeric entries have specific definitions dependent on the the particular Eaton product. 1. The Series NRX Communication Module is a separate device that snaps into the DIN Rail starting at location 19 through 26. (Removal of the four con-
tact blocks is required.)
2. The Trip Unit AUX Voltage is 24VDC 10% and should be sourced from a reliable service.
3. Ground the shield at the master device, and refer to Section 3 on page 4.
4. Set the jumper on the module to enable or disable the communications control as desired.
5. When the Communications Module is employed and Source Ground or Zero Sequence Ground Sensing method is required, the Ground Fault function
is enabled by this jumper.
6. Connectors are UL/CSA rated 300V, VDE rated 250V. Recommended: Weidmuller (BL 3.5/90/5BK) Orientation: 90 lead exit, but other lead orientations
are possible. Wire guage: # 18 AWG/0.82mm.
7. The final device in the daisy-chain configuration must have a 121 ! termination resistor installed across terminals #1 and #2 on TB #2.

12 For more information visit: www.eaton.com Effective 03/09 Effective 03/09 For more information visit: www.eaton.com 5
IL 01301034E IL 01301034E

Figure 4 Communications Control (SR and ST Wiring) Table 4 Modbus Register Map In Register Number Order (continued from previous page)
Objects (complete list) Modbus Register Number Modbus Register Address Modbus Products

Name Numeric Units IEEE Fixed IEEE Fixed FP NRX NRX


float point float point Scale 520M 1150
(FP) (FP) Factor

(hex) (hex)
Frequency freq Hz 404721 406257 1270 1870 100 x
forward KWh N/A 406259 N/A 1872 1 x
(K) Energy reverse KWh N/A 406261 N/A 1874 1 x
total KWh N/A 406263 N/A 1876 1 x
lead KVARh N/A 406265 N/A 1878 1
Reactive
lag KVARh N/A 406267 N/A 187A 1
(K) Energy
net KVARh N/A 406269 N/A 187C 1
(K) Energy apparent KVAh N/A 406271 N/A 187E 1 x
phase unbalance % 404737 406273 1280 1880 100
Motor
thermal capacity % 404739 406275 1282 1882 100
motor winding 1 C 404741 406277 1284 1884 1
motor winding 2 C 404743 406279 1286 1886 1
motor winding 3 C 404745 406281 1288 1888 1
motor winding 4 C 404747 406283 128A 188A 1
motor winding 5 C 404749 406285 128C 188C 1
motor winding 6 C 404751 406287 128E 188E 1
Temperature
motor bearing 1 C 404753 406289 1290 1890 1
motor bearing 2 C 404755 406291 1292 1892 1
load bearing 1 C 404757 406293 1294 1894 1
load bearing 2 C 404759 406295 1296 1896 1
auxiliary C 404761 406297 1298 1898 1
device temperature C 404763 406299 129A 189A 1
404765 406301 129C 189C
404767 406303 129E 189E
forward Wh N/A 406305 N/A 18A0 1 x
Energy
reverse Wh N/A 406309 N/A 18A4 1 x
(4 reg objects)
total Wh N/A 406313 N/A 18A8 1 x
lead VARh N/A 406317 N/A 18AC 1
Reactive Energy N/A 18B0 1
lag VARh N/A 406321
(4 reg objects) N/A 18B4 1
net VARh N/A 406325
Energy (4 reg) apparent VAh N/A 406329 N/A 18B8 1 x
(4 reg) N/A 406333 N/A 18BC
A ph V 404801 406337 12C0 18C0 10
Network
B ph V 404803 406339 12C2 18C2 10
Voltage
C ph V 404805 406341 12C4 18C4 10
A ph V 404807 406343 12C6 18C6 10
Transformer 12C8 18C8 10
Communications B ph V 404809 406345
Voltage 12CA 18CA 10
Module Series NRX Circuit Breaker C ph V 404811 406347
A ph V 404813 406349 12CC 18CC 10
B ph V 404815 406351 12CE 18CE 10
C ph V 404817 406353 12D0 18D0 10
A ph direct V 404819 406355 12D2 18D2 10
A ph quadrature V 404821 406357 12D4 18D4 10
Phasing
B ph direct V 404823 406359 12D6 18D6 10
Voltage
B ph quadrature V 404825 406361 12D8 18D8 10
C ph direct V 404827 406363 12DA 18DA 10
Notes
C ph quadrature V 404829 406365 12DC 18DC 10
1. Spring Release and Shunt Trip wiring as shown for optional communication close or open capability. pos seq direct V 404831 406367 12DE 18DE 10
2. Choose Spring Release coil voltage rating as desired if communications is required. pos seq quadrature V 404833 406369 12E0 18E0 10
3. Choose Shunt Trip voltage rating to be the same as Spring Release voltage rating if communication is required. Note: All objects are two (2) registers in length unless specified otherwise.
4. Control Power voltage rating must match ST and SR coil voltage rating.
The primary and secondary codes are mapped to the high and low bytes, respectively, of registers 404609 (120016) and 406145 (180016).
5. Close duration is two seconds on communication activation when comm control is enabled. The primary status codes are shown in Table 10. The secondary status codes are shown in Table 11. The cause-of-status codes are mapped
to registers 404610 (120116) and 406146 (180116). The cause-of-status codes are shown in Table 12. The primary/secondary and cause-of-status
must be read as a single two (2) register object.

These numeric entries have specific definitions dependent on the the particular Eaton product.

6 For more information visit: www.eaton.com Effective 03/09 Effective 03/09 For more information visit: www.eaton.com 11
IL 01301034E IL 01301034E

Table 4 Modbus Register Map In Register Number Order (continued on next page) Section 6: Viewing/Setting Modbus Address Table 3 MCAM Communication Setting Ranges
Objects (complete list) Modbus Register Number Modbus Register Address Modbus Products The Series NRX trip unit is used as the means to display Setting Number Allowable Range
and modify the programmed Modbus Address setting Communication
Address SP00 001 to 247
Name Numeric Units IEEE Fixed IEEE Fixed FP NRX NRX of the MCAM Module. All modules are shipped with a
float point float point Scale 520M 1150 00 = 1200
(FP) (FP) Factor
factory set default address of 220. The allowable 01 = 4800
Baud Rate SP01
address range is 001 through 247. 02 = 9600
03 = 19200
(hex) (hex)
A trip unit containing a Full Display, such as the Series 00 = None
Status primary 404609 or 406145 hi byte 1200 or 1800 hi byte x x NRX 1150, will provide the MCAM settings in menu Parity SP02 01 = Odd
secondary 404609 or 406145 lo byte 1200 or 1800 lo byte x x 02 = Even
Cause
cause 404610 or 406146 1201 or 1801 x x form. To set or view MCAM settings on a Series NRX
IA A 404611 406147 1202 1802 10 x x
520M limited display, the following sequence is used. Stop Bit SP03
00 = 1 bit
01 = 2 bits
IB A 404613 406149 1204 1804 10 x x To set or view the address, depress and hold the
IC A 404615 406151 1206 1806 10 x x
Current Reset/Battery Test Button located on the front of the
IG A 404617 406153 1208 1808 10 x x Section 7: Network Communications
IN A 404619 406155 120A 180A 10 x x Series NRX trip unit for approximately five seconds
Protocol
IAvg A avg 404621 406157 120C 180C 10 until the address information is displayed. This button
VAB V 404623 406159 120E 180E 10 x must be held in continuously during the process. In order to satisfy the MCAM communications needs,
VBC V 404625 406161 1210 1810 10 x The Series NRX trip unit display will then alternate please refer to the following reference material:
L-L Voltage VCA V 406163 1212 10 x
404627 1812 between SP00 (denoting the address display mode)
VLLavg V avg 404629 406165 1214 1814 10 Modicon Modbus Protocol
and the programmed Modbus address value. http://www.modicon.com/techpubs/toc7.html
VAN V 404631 406167 1216 1816 10 x
VBN V 404633 406169 1218 1818 10 x To select a new address, depress the trip unit Scroll The contents of Modbus registers are product objects
L-N Voltage
VCN V 404635 406171 121A 181A 10 x Display to increment the address value shown. Users (e.g. IA - phase A current). The MCAM ensures that
VLN V avg 404637 406173 121C 181C 10 may simultaneously depress and hold in the Scroll and unique objects reside in identical registers independent
N-G Voltage VNG V 404639 406175 121E 181E 10 Reset/Battery Test Buttons for fast advance. The of Eaton products. Consequently, Eaton products use a
peak IA demand A 404641 406177 1220 1820 10 x next setting will be displayed when the Reset/Battery single register map of objects (Tables 4 or 5).
peak IB demand A 404643 406179 1222 1822 10 x Test Button is released and then once again
Peak Current peak IC demand A 404645 406181 1224 1824 10 x depressed. Objects occupy two (2) registers except for certain ener-
peak IG demand A 404647 406183 1226 1826 10 gy (real and reactive) objects. These energy objects
peak IN demand A 404649 406185 1228 1828 10 Once the last setting (SP03) has been viewed and the occupy four (4) registers. The MCAM can support a
real 3 ph (power) W 404651 406187 122A 182A 1 x Reset/Battery Test Button has been released, the maximum of 122 registers within a single Modbus
Power reactive 3 ph (power) VAR 404653 406189 122C 182C 1 x new Modbus settings will be saved.
apparent 3 ph (power) VA 404655 406191 122E 182E 1 x transaction.
Power Factor displacement 3 ph pf 404657 406193 1230 1830 100 A block diagram of the setting sequence and program- To accommodate Modbus masters which can only
apparent pf 404659 406195 1232 1832 100 x ming options is shown in Figure 6. For the Series NRX access to register 9999, some Eaton registers initially
Frequency freq Hz 404661 406197 1234 1834 10 x Modbus Communications Adapter Module, four com- assigned above 9999 have been assigned dual access,
K-Factor K-factor 404663 406199 1236 1836 1 munication settings are available and can be viewed as both at the original register (to provide compatibility)
THD Factor THD factor 404665 406201 1238 1838 1 shown in Table 3. and at a new register assignment below 9999. The for-
A ph W 404667 406203 123A 183A 1
B ph W 404669 406205 123C 183C 1 Figure 6 Setting Sequence Programming mat is given as low/high register numbers followed by
C ph W 404671 406207 123E 183E 1 Flow Chart for Series NRX 520M Trip Unit (low16/high16 Modbus register addresses). An example
reactive A ph VAR 404673 406209 1240 1840 1 is: 4xxxx/5yyyyy (XXXX+116/YYYY+116). Refer to
Power reactive B ph VAR 404675 406211 1242 1842 1
reactive C ph VAR 404677 406213 1244 1844 1 Address Table 6.
apparent A ph VA 404679 406215 1246 1846 1 Range Only the RTU communications mode is recognized by
apparent B ph VA 404681 406217 1248 1848 1 SP00 001
apparent C ph VA 404683 406219 124A 184A 1 to the MCAM.
displacement A ph pf 404685 406221 124C 184C 100 247 Function Codes
displacement B ph pf 404687 406223 124E 184E 100
displacement C ph pf 404689 406225 1250 1850 100 The MCAM responds to a limited number of Modbus
Power Factor apparent A ph pf 404691 406227 1252 1852 100 function codes. These are function codes 03, 04, 06, 08
apparent B ph pf 404693 406229 1254 1854 100
apparent C ph pf 404695 406231 1256 1856 100 Baud and 16 (1016). Function codes 03 and 04 are used inter-
peak demand W 404697 406233 1258 1858 1 x Rate changeably to obtain register data. Function code 06
Power
SP01 00 can only be used to set the few single configuration
VAB V 404699 406235 125A 185A 10 to
125C registers (Section <Register Access Configuration>).
Source 1
VBC V 404701 406237 185C 10 03
VCA V 404703 406239 125E 185E 10
freq Hz 404705 406241 1260 1860 10
Block of Registers
VAB V 404707 406243 1262 1862 10 A block of registers (from the register column of Tables
VBC V 404709 406245 1264 1864 10
Source 2 VCA V 404711 406247 1266 1866 10
4 or 5) can be established in the MCAM to remap the
freq Hz 404713 406249 1268 1868 10 Parity object registers of an Eaton product. The block of regis-
Power power (real 3 ph) W 404715 406251 126A 186A 1 x 00 ters list is stored in non-volatile memory.
SP02 to
Power Factor pf pf 404717 406253 126C 186C 100 x 02 Function code 16 (1016) is used to load the object
Product ID prod ID 404719 or 406255 126E or 186E x x assignments for the block of registers. The block
Note: All objects are two (2) registers in length unless specified otherwise. assignments are stored beginning at register
41001/420481 (03E816/500016). Only the first object reg-
The primary and secondary codes are mapped to the high and low bytes, respectively, of registers 404609 (120016) and 406145 (180016). ister address is assigned within the block of registers.
The primary status codes are shown in Table 10. The secondary status codes are shown in Table 11. The cause-of-status codes are mapped
to registers 404610 (120116) and 406146 (180116). The cause-of-status codes are shown in Table 12. The primary/secondary and cause-of-status Stop For example, although object IA occupies registers
must be read as a single two (2) register object. Bit
00 404611 (120216) and 404612 (120316), only register
SP03 address (120216) is loaded into the block of assignment
These numeric entries have specific definitions dependent on the the particular Eaton product. to
01 registers. Verification of this block of assignment regis-
ters can be read from the MCAM by a read function

10 For more information visit: www.eaton.com Effective 03/09 Effective 03/09 For more information visit: www.eaton.com 7
IL 01301034E IL 01301034E

code 03 or 04 from these 41001/420481 (03E816/500016) They begin at register 42901/425089 (0B5416/620016) and The 2-register format is presented in units of Supported Diagnostic Sub-Functions
registers. extend through 42903/425091 (0B5616/620216). These Kwatthours and is valid for products reporting energy in
three registers are written with a slave action number It is possible to obtain diagnostics from the MCAM or
Data pertaining to the objects configured in the block of watthours or Kwatthours only. Products reporting in
and its 1s complement using function code 16 (1016). an attached product using function code 08. Refer to
assignment registers is mapped into registers starting units greater than Kwatthours (e.g. Mwatthours) could
The current slave action numbers, their support being Table 9. A single register is used for each UART/slave
at 41201/420737 (04B016/510016) and continuing in suc- not guarantee consistent Kwatthour resolution up to
product dependent, are listed in Table 7. The format of counter within the MCAM. Each product and the
cessive order for each object assigned. The number of and through their rollover values.
the data is shown in Figure 7. These three registers, MCAM contain a unique slave counter.
objects and their placement order in this data block of All products reporting energy (independent of energy
and only these three registers, must be written in one Exception Codes
registers is dependent on the configuration of the block units) support the energy objects occupying four (4)
Modbus transaction.
of assignment registers. The total number of data block registers register 3 through register 0. Register 3 is Under certain circumstances, the MCAM will return an
of registers is limited to 100. Note that an object can Figure 7 Control of Product Data Format the high order register and register 0 is the low order exception code.
occupy two or four registers. register.
Register 42901/425089 (0B5416/620016) If the function in the query is not supported by the
The data can be obtained from the data block of regis- Register 3 high byte contains a value corresponding to MCAM, exception code 01 is returned in the response.
ters by a read function code 03 or 04. The address of 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Engineering Units (power of 10 signed exponent).
the starting object must be aligned with a starting If the data (object) register is illegal, exception code 02
Register 3 low byte contains a Mantissa Multiplier value
address of an object within the data block of registers. is returned in the response.
(power of 2 signed exponent).
The number of registers to obtain must align with an Slave Action Byte1 Slave Action Byte0 If the data in the query is illegal, exception code 03 is
ending address of an object within the data block of Register 2 through register 0 contains a 48-bit energy
returned.
registers. mantissa in units of watthours. Net and total energy
objects are signed values. All other energy objects are If the attached product falls (usually a timeout), excep-
Register Access Configurations Register 42902/425090 (0B5516/620116) unsigned values. tion code 04 is returned.
Non-volatile register 42001/425345 (07D016/630016) is 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 The data format of these 4 registers is given in Figure 8. In certain circumstances, an exception code 05 (NAK)
used to configure the MCAM to respond to a group of is returned.
Energy = 2Mantissa Multiplier x (48-bit energy value) x 10 Engineering Units
data objects, of which some objects are invalid within
that group. When non-zero (factory default value), any If the MCAM cannot perform the requested function,
1s Complement of Slave Action Byte2 Figure 8 4-Register Energy Data Format exception code 07 (NAK) is returned.
attempt to access a group of data objects which contain Slave Action Byte0
an invalid object will result in an illegal data object If only a partial register is used in the query, exception
exception code 02. Refer to a later Section entitled Energy Register 0 code 84 is returned.
Exception Codes. Register 42903/425091 (0B5616/620216)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
When register 42001/425345 (07D016/630016) is set to 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
zero, however, the MCAM will respond to a group of
objects with data contained in the valid objects of the
Byte1 of Mantissa Byte0 of Mantissa
group along with an illegal value, if available else
1s Complement of 1s Complement of
000016 data contained in the invalid objects. Slave Action Byte2 Slave Action Byte1
Non-volatile register 42002/425346 (07D116/630116) is
Energy Register 1
used to configure 32-bit IEEE floating point word order.
If the slave action number and it 1s complement are
When non-zero (factory default), the floating point low 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
valid, the MCAM issues the slave action control com-
order word is first in the Modbus register space.
mand to the product. If the slave action request is suc-
When register 42002/425346 (07D116/630116) is set to cessfully acknowledged by the product, the MCAM
zero, however, the floating point high order word is first returns a normal function code 16 (1016) response to the Byte3 of Mantissa Byte2 of Mantissa
in the Modbus register space Modbus master. The Modbus master may further
determine if the product completed the slave action
Non-volatile register 42002/425347 (07D116/630216) is
function successfully by interrogating the product, for
used to configure 32-bit fixed point and 64-bit energy Energy Register 2
example, by reading its status.
word order. When non-zero (factory default), the fixed
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
point and energy low order word is first in the Modbus If the product does not acknowledge the slave action
register space. request, the MCAM returns an exception code 04. If the
slave action number and its 1s complement are
When register 42003/425347 (07D216/630216) is set to
invalid, the MCAM responds to the Modbus master Byte5 of Mantissa Byte4 of Mantissa
zero, however, the fixed point and energy high order
with a data value illegal exception code 03. Refer to a
word is first in the Modbus register space.
later Section entitled Exception Codes.
Registers not containing a 32-bit or 64-bit format such
Date and Time Registers
as Status and Product ID binary encoded objects, and Energy Register 3
MCAM control of product registers are not affected by Access to date and time registers provide the opportu- 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
the word order configuration registers. nity for a Modbus master to setup and/or read real time
clock information within an Eaton product. Eight regis-
Configuring any or all registers 42001/425345 through
ters, beginning at register number 402921 (i.e. holding
42003/425347 (07D016/630016 through 07D216/630216) is Engineering Units Mantissa Multiplier
register address 0B6816), are reserved for this informa-
accomplished using a write function codes 06 or 16
tion, as defined in Table 8. Registers are read using
(1016).
function code 03 or 04 and written using function code
Energy = 2Mantissa Multiplier x (48-bit energy value) x 10 Engineering Units
Control of Product 16 (1016).
Since a control error could result in unwanted actions Energy Format
initiated by a device, the MCAM requires a specific pro- Energy objects in the MCAM are supported in 2-register
tocol by the Modbus master in order to perform control fixed point object format and a 4-register power/mantis-
related functions within the product. sa format. These objects do not support IEEE floating
point format.
A set of registers is reserved for the control protocol.

8 For more information visit: www.eaton.com Effective 03/09 Effective 03/09 For more information visit: www.eaton.com 9

You might also like