SOUTHWEST TYPE

5GP

Selection & Specification Data Substrates & Surface Preparation


Generic Type A gypsum based, Spray-applied Fire Resistive required that Southwest Type DK3 (spatter coat) is
Material (SFRM) designed for the fire protection of used. Also be sure that all roof work is completed
interior structural steel. Formulated and applied to and water tight before commencing installation
meet the minimum bond strength requirements of the of fire protection. Roof traffic shall be limited to
IBC Code listed in the High Rise Building Section" for maintenance after fire protection is applied and cured.
buildings up to 75' (22.9 m). No fireproofing shall be applied prior to completion of
Description A 15 lb./ft (240 kg/m) SFRM intended for the fire concrete work on steel floor decking.
protection of interior structural columns, beams, Painted/Primed Apply to painted/primed steel decking only if permitted
joists, decks, walls, roofs, girders, floors and pre- Steel Decks by the UL design. If the painted/primed deck is not an
cast concrete units. It is tested and certified for fire approved substrate, metal lath must first be secured
resistance ratings up to 4 hours. Southwest Type 5GP to the deck surfaces in accordance with the UL
is a trademark of the Southwest Fireproofing Products requirements.
Company. Painted/Primed Painted steel joists do not require adhesive, lath or
Features Durable cementitious formulation Steel Joists fastening devices. It is acceptable to apply directly to
Noncombustible steel joists.
Can be injected with Accelerator A-20 for fast set Painted/Primed Painted/primed structural steel is generally not
and increased yield (optional) Structural Steel approved by UL as an acceptable substrate for
Asbestos-free compliant with EPA and OSHA SFRMs unless the paint or primer was included in
Mineral Wool free no airborne fibers. the fire test and/or UL listed for SFRM applications
Styrene free no toxic decomposition gases to structural steel. UL has established conditions that
Economical Maintains project on budget must be satisfied for application to primed or painted
Design flexibility with over 100 UL designs structural steel, including: minimum bond strength
Color Non-Uniform Tan criteria; dimensional limitations for the structural
Finish Textured members; use of a bonding agent or adhesive such as
A/D Type TC-55 Sealer; use of metal lath to provide
Primer Primers are not required or recommended. If a a mechanical bond; or, use of mechanical breaks of
primer is specified, or steel is primed, bond strength metal lath strips or steel pins and disks. Refer to the
must meet minimum UL criteria. A/D Type TC-55 UL Fire Resistance Directory-Volume 1 for details or
Sealer is used as a primer/bonding agent to meet contact Carboline Technical Service before applying to
this requirement where specified. Southwest Type any painted/primed steel beams or columns.
DK3 (spatter coat) must be used as a primer/bonding
agent on cellular decks and roof decks per UL design
requirements. Contact Carboline Technical Service for Performance Data
further information. Southwest Fireproofing materials
Test Method Results
neither promote nor prevent corrosion. Fireproofing
ASTM 1042 DOD Classification Type 1, NCR 50,
should not be considered part of the corrosion
Class (a), Category A
protection system.
ASTM C384 Acoustics 0.37 @ 0.30" (7.6 mm)
Fireproofing Generally not required. In severely corrosive Noise Reduction Coefficient (NRC) 0.51 @ 0.45 (11.4 mm)
Topcoats atmospheres, consult Carboline Technical Service for ASTM E136 Combustibility Passed (non-combustible)
selection of coating most suitable for the operating 1
ASTM E605 Density 15 pcf (240 kg/m)
environment.
minimum average
Application 1/2" - 5/8" (12.7 - 15.9 mm) on initial pass ASTM E736 Cohesion/Adhesion >200 psf
Thickness ASTM E759 Deflection Passed
Limitations Not intended for permanent direct exposure to ASTM E760 Impact Passed
weather or excessive physical abuse beyond normal ASTM E761 Compresive Strength 3,700 psf (177 kPa)
construction cycles. Not recommended for use as ASTM E84 Surface Burning Flame Spread: 0
refractory cement or where operating temperatures Smoke Development: 0
exceed 200F (93C). ASTM E859 Air Erosion 0.00 g/ft (0.00 g/m)
ASTM E937 Corrosion Passed
Substrates & Surface Preparation ASTM G21 Fungi Resistance Passed (no growth)
1
General Prior to application, all substrates must be clean and Air dry at ambient conditions to constant weight. Do not force cure. Use ASTM E605 Positive Bead
Displacement method utilizing #8 lead shot. Test density in accordance with AWCI Technical Manual
free of loose scale, dirt, oil, grease, condensation, 12-A (Standard Practice for the Testing and Inspection of Field Applied Sprayed Fire-Resistive
or any other substance that would impair adhesion. Materials, an Annotated Guide).
Contact Carboline Technical Service for further All values derived under controlled laboratory conditions.
Test reports and additional data available upon written request.
information. Fireproofing shall be applied to the
underside of roof deck assemblies only after all roofing
work has been completed, and all roof traffic has
ceased. When applying to flexible roof systems it is

August 2015 24AD


To the best of our knowledge the technical data contained herein is true and accurate on the date of publication and is subject to change without prior notice. User must contact Carboline Company
to verify correctness before specifying or ordering. No guarantee of accuracy is given or implied. We guarantee our products to conform to Carboline quality control. We assume no responsibility for
coverage, performance or injuries resulting from use. Liability, if any, is limited to replacement of products. NO OTHER WARRANTY OR GUARANTEE OF ANY KIND IS MADE BY CARBOLINE,
EXPRESS OR IMPLIED, STATUTORY, BY OPERATION OF LAW, OR OTHERWISE, INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Carboline and Carboguard
are registered trademarks of Carboline Company.
Page 1 of 3

SOUTHWEST TYPE 5GP
Mixing & Thinning Application Procedures
Mixer 1. Use a minimum 12-16 cubic foot (340-453 liter) General Thicknesses of 1/2" - 5/8" (12.7 mm - 15.9 mm) or
heavy-duty mortar mixer capable of rotating at 40 rpm less can be applied in one pass. When additional
with rubber tipped blades that wipe the sides. coats are required to reach specified thickness, apply
2. Use continuous feed mixer. Contact Carboline subsequent coats after prior coat has set. If preceding
Technical Service for recommendation. Densities may coat has dried, dampen the surface with water prior
vary when using this type of mixing equipment. to application of additional coats. Material can be
Mixing Always mix with clean potable water. The mixer injected with Accelerator A-20 solution to increase
shall be kept clean and free of any previously mixed set time and yield. Refer to Southwest Fireproofing
materials which may cause premature setting of Injection Procedures For High Production for detailed
product. A 2 bag mix is recommended for paddle type instructions. Type DK3 (spatter coat) shall be applied
mixers. Mix time should be approximately 2 minutes to all cellular floor units and to all roof deck systems
minutes at 40 rpm. Do not over mix. The material where indicated by the UL design. For complete
volume should not go over center bar of mixer. Use application instructions, refer to the Southwest
10 to 11 gallons (37.8 to 41.6 liters) of water per 50 lb. Fireproofing Products Field Application Manual.
(22.7 kg) bag. Add water to the mixer first with blades Field Tests Test for thickness and density in accordance with the
stopped. With mixer turned on, add material to the applicable building code, AWCI Technical Manual 12-
water and begin mixing. A (Standard Practice for the Testing and Inspection
Density For information and recommendations obtaining the of Field Applied Sprayed Fire-Resistive Materials, an
proper density and yield, contact the local Carboline Annotated Guide), and ASTM E605 (Standard Test
representative or Carboline Fireproofing Technical Methods for Thickness and Density of Sprayed Fire-
Service. Resistive Materials Applied to Structural Members).
Finishing Normally left as a sprayed texture finish.
Application Equipment Guidelines
Listed below are general equipment guidelines for the application of this product. Job site conditions
Application Conditions
may require modifications to these guidelines to achieve the desired results.
Condition Material Surface Ambient Humidity
Pump This material can be pumped with a wide range of Minimum 40 F (4 C) 40 F (4 C) 40 F (4 C) 0%
piston, rotor stator and squeeze pumps designed to Maximum 100 F (38 C) 125 F (52 C) 110 F (43 C) 95%
pump cement & plaster materials including: Air and substrate temperatures shall be maintained 24 hours before, during and 24 hours after
Essick - model# FM9/FM5E (Rotor Stator/2L4) application. Gypsum based products are susceptible to water and must be protected accordingly.
Putzmeister - model# S5EV(Rotor Stator/2L6) Contact Carboline Fireproofing Technical Service for recommendations.
Hy-Flex - model# HZ-30E(Rotor Stator/2L6)
Hy-Flex - model# H320E (Piston)
Strong Mfg. - model# Spraymate 60 (Rotor Stator/2L6)
Curing Schedule
Airtech - model# Swinger (Piston) Surface Temp. & 50% Dry to Recoat
Mayco - model# PF30 (Dual Piston) Relative Humidity
Thomsen - model# PTV 700 (Dual Piston) 77 F (25 C) 4 Hours
Marvel kit must be removed from piston pumps.
Recoat times will vary based upon ambient conditions and air movement. Material can be injected
with Accelerator A-20 for fast set time and increased yield.
Ball Valves Ball valves should be located at the manifold and at
the end of the surge hose to facilitate cleaning of the
pump and/or hoses. Cleanup & Safety
Material Hose Use 15 to 25 feet (4.5 m to 7.6 m) of 3 (76 mm) I.D.
Cleanup Pump, mixer and hoses should be cleaned with
or larger surge hose from the manifold. Follow with a
potable water. Sponges should be run through the
16 (406 mm) tapered fitting to a 2 (50 mm) I.D. hose
hoses to remove any material remaining in the hoses.
to the spray area. Taper to 15 to 20 feet (4.5 m to 6 m)
Wet overspray must be cleaned up with clean, potable
of minimum 1-1/4 or 1 (25 mm) whip hose.
water. Cured overspray material may be difficult to
Standpipe Use 3 (76 mm) I.D. aluminum tubing with quick remove and may require chipping or scraping to
external disconnections. Elbows should be 3 (76 mm) remove.
I.D. with minimum 36 (0.9 m).
Safety Follow all safety precautions on the Material Safety
Nozzle/Gun Use a minimum 1 (25 mm) I.D. plaster type nozzle Data Sheet. It is recommended that personal
with shut off valve, swivel and air shut off valve. protective equipment be worn, including spray suits,
Orifice Size and 9/16 to 5/8 (9.5 mm - 15.9 mm) I.D. blow-off tips gloves, eye protection and respirators.
Shields (mini shields optional) Overspray Adjacent surfaces shall be protected from damage
Compressor Compressor on pump must be capable of maintaining and overspray. Sprayed fireproofing materials may
minimum 30 psi (206 kPa) and 9 to 11 cfm at the be difficult to remove from surfaces and may cause
nozzle. damage to architectural finishes.
Air Line Use 5/8 (15.9 mm) I.D. hose with a minimum bursting Ventilation In enclosed areas, ventilation shall not be less than 4
pressure of 100 psi (689 kPa). complete air exchanges per hour until the material is
dry.

August 2015 24AD


To the best of our knowledge the technical data contained herein is true and accurate on the date of publication and is subject to change without prior notice. User must contact Carboline Company
to verify correctness before specifying or ordering. No guarantee of accuracy is given or implied. We guarantee our products to conform to Carboline quality control. We assume no responsibility for
coverage, performance or injuries resulting from use. Liability, if any, is limited to replacement of products. NO OTHER WARRANTY OR GUARANTEE OF ANY KIND IS MADE BY CARBOLINE,
EXPRESS OR IMPLIED, STATUTORY, BY OPERATION OF LAW, OR OTHERWISE, INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Carboline and Carboguard
are registered trademarks of Carboline Company.
Page 2 of 3

SOUTHWEST TYPE 5GP
Testing / Certification / Listing
Underwriters Tested in accordance with ASTM E119/UL 263 at
Laboratories, Inc. Underwriters Laboratories, Inc. and listed by UL in the
following designs (most commonly used in bold):
Protected Floor/Ceiling:
D739, D788 (Restrained/Unrestrained)
Additional designs: A702, D701, D703, D704, D705,
D706, D708, D709, D710, D711, D712, D715, D716,
D722, D723, D725, D726, D727, D728, D729, D730,
D740, D742, D743, D744, D745, D746, D747, D748,
D750, D751, D752, D753, D754, D756, D758, F817,
F818
Unprotected Floor/Ceiling:
D949 (Restrained/Unrestrained)
Additional designs: D905, D907, D909, D910, D916,
D917, D920, F906
Concrete Floor/Roof:
J718 (Restrained/Unrestrained)
Additional designs: G701, G702, G703, J701, J704,
J705, J706, J709, J919, J957, J966
Beam/Joist:
N791, S740 (Restrained/Unrestrained)
Additional designs: N401, N404, N706, N708, N732,
N736, N754, N756, N791, S701, S702, S715, S739
Protected Roof/Ceiling:
P741 (Restrained/Unrestrained)
Additional designs: P675, P676, P701, P708, P709,
P710, P711, P714, P717, R705
Unprotected Roof/Ceiling:
P921 (Restrained)
Additional designs: P901, P902, P907, P919, P920,
P923, P937
Metal Wall Assembly:
U703 (Restrained/Unrestrained)
Columns:
X771, Y725
Additional designs: X527, X701, X704, X722, X723,
X772, X751, X752, X808, X813, X819, X820, X821,
X822, Z805, Z806, Z807, Z810
City of New York MEA No. 55-04-M Vol. II (Wall)
MEA No. 56-04-M Vol. II (Beam and Floor/Ceiling)
MEA No. 409-02-M Vol. III (Columns and Roof/Ceiling

Packaging, Handling & Storage


Shelf Life 12 months
Shipping Weight 50 lb. (22.7 kg)
(Approximate)
Storage Store indoors in a dry environment between
32F - 125F (0C - 52C)
Material must be kept dry or clumping of material may occur.

Packaging 50 lb. (22.7 kg) bags

August 2015 24AD


To the best of our knowledge the technical data contained herein is true and accurate on the date of publication and is subject to change without prior notice. User must contact Carboline Company
to verify correctness before specifying or ordering. No guarantee of accuracy is given or implied. We guarantee our products to conform to Carboline quality control. We assume no responsibility for
coverage, performance or injuries resulting from use. Liability, if any, is limited to replacement of products. NO OTHER WARRANTY OR GUARANTEE OF ANY KIND IS MADE BY CARBOLINE,
EXPRESS OR IMPLIED, STATUTORY, BY OPERATION OF LAW, OR OTHERWISE, INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Carboline and Carboguard
are registered trademarks of Carboline Company.
Page 3 of 3