Input & output Signals Philosophy

DI DO AI AO Communications
# Equipment
Signal No. Signal No. Signal No. Signal No. Signal No.
pump bearing Temp.,
motor winding Temp.,
1 Pump Run/Stop, fult, remote 3 Run/Stop command 1 6 - - - -
motor bearing temp.,
motor current
open, close, in operation, fault, remote,
2 Motorized Vlave 7 open, close commend 2 - - - - - -
torque fult open, torque fult close
open, close, in operation, fault, remote,
3 Needle valve 7 open, close commend 2 position indication 1 position command 1 - -
torque fult open, torque fult close
4 Solenoid valve open, close, fault, remot 4 open, close commend 2 - - - - - -
5 Switche (level, pressure..) Limit level (High\ Low) 2 - - - - - - - -
6 Switche (Multi Levels ) Limit levels (High High,High,Low, Low Low) 4 - - - - - - - -
7 Transmitter Alarm (High\ Low, Low water Flow, fault 4 - - Measurd value 1 - - - -
8 Eletrical Panels
Voltage,Amp (if C.B not
Voltage, Amp, Power
8.1 Incoming C.B On/Off, Trip 2 - - iclouding 2 - - 1
and Available Data
Communications Port)
8.2 Outgoing C.B On/Off, Trip 2 - - - - - - - -
8.3 Power consumed Measurement - - - - - - - - KWH - KVARH 2
8.4 Soft Start or VSD - - - - - - - - Available Data 1
ToTAL Used 35 7 10 1 4

ToTAL Installation 39 8 11 2 5