Space Design Load Summary for AROMA RE MUZN

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:55AM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' AROMA REST MUZN '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 C / 30.0 C HEATING OA DB / WB 12.0 C / 10.0 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 20.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 110 m 9636 - 110 m - -
Wall Transmission 82 m 0 - 82 m 282 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 110 m 6627 - 110 m 2464 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 240 m 2679 - 240 m 0 -
Partitions 53 m 895 - 53 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 5280 W 3696 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 14000 W 13999 - 0 0 -
People 55 3707 1936 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 2% / 2% 825 39 0% 0 0
>> Total Zone Loads - 42064 1975 - 2746 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' AROMA REST MUZN '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 32 0.431 - 0 - 110
WINDOW 1 40 2.800 0.410 2410 3015 896
NW EXPOSURE
WALL 50 0.431 - 0 - 172
WINDOW 1 70 2.800 0.410 4217 6620 1568

Hourly Analysis Program v4.50 Page 1 of 1