You are on page 1of 72

CENTUM CS3000

Tr aining Manual Pr oblem Repor t

YOUR NAME

DATE PHONE

PAGE NUMBER

TYPE OF PROBLEM:
Typographical Error

Content Error

Content Unclear

Missing Information

Other

DESCRIPTION:

2
CENTUM CS3000

Cour se Evaluation
YOUR NAME (please print)

YOUR COMPANY NAME

COURSE NAME COURSE DATE INSTRUCTOR

To assist us in planning and improving our future classes, we are asking for your
frank and honest evaluation of this course.

Please comment constructively on the following categories.


Also, rate each category on a 5 (high) to 1 (low) scale:
Quality of Instructors Presentations: Circle One
5 4 3 2 1

Adequacy of Course Materials:


5 4 3 2 1

Adequacy of Course Content:


5 4 3 2 1

Manner in which the Course was Conducted:


5 4 3 2 1

Adequacy of Training Facilities:


5 4 3 2 1

Please rate the overall effectiveness of this training course:


5 4 3 2 1

We encourage you to use the back side of this form for any additional comments.
Thank You.

3
CENTUM CS3000

TABLE OF CONTENTS

1 System Overview .................................................................................................................................................6


1.1 Hardware terminology .................................................................................................................................8
1.2 Human Interface Station (HIS) ..................................................................................................................12
1.3 CS3000 Field Control Station....................................................................................................................14
1.4 I/O Modules and Nodes .............................................................................................................................15
1.5 Used I/O Modules......................................................................................................................................18
2 System Operations .............................................................................................................................................21
2.1 Operator Keyboard ....................................................................................................................................22
2.2 System Message area .................................................................................................................................26
2.3 HIS Operation Displays .............................................................................................................................27
2.4 Control Window ........................................................................................................................................31
2.5 Overview Window.....................................................................................................................................34
2.6 Tuning Window .........................................................................................................................................36
2.7 Trend Window...........................................................................................................................................38
2.8 Graphic Window........................................................................................................................................41
2.9 Process Alarm Window .............................................................................................................................43
2.10 Operator Guide Message Window.............................................................................................................45
2.11 Navigation..................................................................................................................................................47
3 System Maintenance Windows ..........................................................................................................................48
3.1 System Overview Window.........................................................................................................................50
3.2 System Alarm Window ..............................................................................................................................52
3.3 CS3000 Control Station Status Display Window.......................................................................................54
3.4 HIS Setup Display .....................................................................................................................................56
4 Process and Historical Reports ..........................................................................................................................57
4.1 Process Report Window.............................................................................................................................59
4.2 I/O Searches...............................................................................................................................................61
4.3 Historical Report Window .........................................................................................................................63
5 Control System Design ......................................................................................................................................64
5.1 Architecture ...............................................................................................................................................64
5.2 I/O Module Arrangement...........................................................................................................................65
6 Control Concept.................................................................................................................................................66
6.1 Tag naming standards ................................................................................................................................66
6.2 Tag alarms standards .................................................................................................................................67
7 Process screens standards ..................................................................................................................................68
7.1 Colors of medium ......................................................................................................................................68
7.2 Colors of device states ...............................................................................................................................68
7.3 Colors of electrical failures........................................................................................................................68
7.4 Basic types of equipment (shapes).............................................................................................................69
7.4.1 Pump, fan ...........................................................................................................................................69
7.4.2 Solenoid Valve (ON/OFF) .................................................................................................................70
7.4.3 Regulation valve ................................................................................................................................71
7.4.4 Analog measurement..........................................................................................................................72
7.4.5 Regulator............................................................................................................................................72
7.4.6 Faceplates ..........................................................................................................................................72
8 Operator displays ...............................................................................................................................................73
9 Pro-Safe .............................................................................................................................................................74
9.1 SCS System................................................................................................................................................74
9.2 Communication..........................................................................................................................................74
9.3 Used I/O Modules......................................................................................................................................75

4
CENTUM CS3000

5
CENTUM CS3000

1 System Overview
OBJ ECTIVES OF THIS CHAPTER

1. Learn the overall layout concept of CENTUM 3000.

2. Learn the terminology of the CENTUM 3000 system.

3. Show how to setup unit addressing.

4. Learn the Field Control Station hardware.

5. Identify the different types of I/O modules and how software addresses each point.

6
CENTUM CS3000

Ethernet

HIS HIS

Vnet

FCS FCS

7
CENTUM CS3000

1.1 Hardware terminology


The CS3000 is a distributed control system, which means that the intelligence to run the process resides in the
control hardware in the process area.
The CS3000 system has a maximum of 64 stations per domain, (16 Domains and 256 stations maximum) and
100,000 tags (expandable to 1 000 000 tags).

Human Inter face Station (HIS)


This station is used mainly for operating and monitoring plant functions. With optional engineering software, system
builder functions can be defined.

Field Contr ol Station (FCS)


The FCS provides control of the plant functions through instruments in its database. Process information is placed on
the Vnet and Vnet/IP for monitoring or control by an HIS.

Processing speeds of 1 second (Standard), 500 ms, 200 ms, 100ms and 50ms are selectable for the function blocks.

Vnet (Vnet/IP)
This is the communication highway that links the system components together for control and monitoring functions.
New instruments are downloaded to the FCS from the HIS via the Vnet (Vnet/IP). Vnet (Vnet/IP) runs at a 10
Mbits/1Gbits rate.

Ethernet
Ethernet communication link between HIS units used to download files from the PC with builder if Vnet is used.
Vnet/IP is using Bus 2 for inter HIS communication (open communication)

Vnet - process communication highway

Type of Bus 10BASE-5=10- speed 10Mbps;BASE data transmission in the


BASEBAND;5-500 distance between station(PC)[YELLOW CABLE THICK]1cm
10BASE-2=THIN=5mm
type of communication BUS 1 "Control communication"
BUS 2 "Open communication"
Redundant it means BUS 1 + BUS 2.Both busses are divided to several layers
BUS

Ethernet communication link for loading soft and transmission data from printers,
amount of PC station

8
CENTUM CS3000

FCS
HIS

Ethernet
Domain 1 Vnet

BCV

FCS

HIS

Vnet
Domain 2

9
CENTUM CS3000

Bus conver ter (BCV)


The ABC bus converter is used to connect CENTUM 3000 to existing CENTUM-XL or Micro XL systems. The
ABC is also used for splitting the CENTUM CS3000 into what are called Domains.

Domain
A Domain is a grouping of stations on a Vnet segment. CS3000 Domains can have up to 64 stations; the domain
address range on the V net is 1-16. A maximum of 256 stations are allowed per CS3000 system.
CS1000 is fixed as Domain 1 with a maximum of 24 station.
When CS1000 is connected to a uXL, the uXL is assigned Domain 17.

10
CENTUM CS3000

11
CENTUM CS3000

1.2 Human Interface Station (HIS)


The HIS is used mainly used for plant operation and monitoring, but can have system engineering and test function
software installed. The test function allows the engineer to create and test control function without the use of an
FCS. The HIS can also have an optional spill resistant operator keyboard.

Since the HIS runs Windows XP, this allows the user to run standard Windows XP based applications, like MS
Word , or Excel for spreadsheets.

Minimum Requir ements:

CPU
Pentium 800MHz or higher.

Memory
128 MB for operations and monitoring.
256 MB for operations and builder.

Hard Disk Drive


1 GB (2 GB recommended for using builder functions).

CRT
17 inch or larger; 1024 x 768 (16 bit color depth colors).

Station Addr essing


There is a card in the HIS that defines its station number on the Vnet by the physical switch settings.

Vnet STATION
ADDRESS Switches ODD PARITY ODD PARITY

DOMAIN NO. STATION NO.


0 0 16 8 4 2 1 0 0 16 8 4 2 1

1 1
Domain 1 0 Station 24 0
12345678 12345678

*NOTE: Active switch positions are white

12
CENTUM CS3000

FCS Application Capacity


Process I/O
Analog I/O: 8x16x14+6*16=1888
Contact I/O: 4096
Internal Status Switch
Common: 4000 (shared within that FCS)
Number of Control Drawings
CS3000 200
Number of Function Blocks
Depends upon database type

Addressing for both types of units is carried out through setting dip-switches on the unit.

Vnet STATION
ADDRESS Switches ODD PARITY ODD PARITY

DOMAIN NO. STATION NO.


0 0 16 8 4 2 1 0 0 16 8 4 2 1

1 1
Domain 1 0 Station 1 0
12345678 12345678

*NOTE: Active switches are white

13
CENTUM CS3000

1.3 CS3000 Field Control Station


The Field Contr ol Station, if purchased as redundant, has dual processor cards; each processor running dual RISC
processors. Depending on the FCS purchased, memory will be 16/32MB. Data is transferred to and from the FCS
via the Vnet. Data is transferred to and from the Field Control Unit and the Node Interface Unit via the ESB bus.
The ESB bus can connect up to 10 Nodes to the FCS; each Node can have up to 8 I/O modules. ESB bus can be
extended by ER bus (10 Mbs Ethernet network, 10BASE2, 10BASETP), connecting max. 15 nodes.

FCS Application Capacity Max.


Process I/O
Analog I/O: 640
Contact I/O: 4096
Internal Status Switch
Global (future): 256 (shared with other FCSs)
Common: 4000 (shared within that FCS)
Function Blocks
Control Drawings: 200
Function blocks: Depends upon FCS type.

The Node Inter face Unit houses the I/O modules that are wired directly to the process.

14
CENTUM CS3000

1.4 I/O Modules and Nodes

15
CENTUM CS3000

I/O connection:

16
CENTUM CS3000

CONTROL DRAWING SOFTWARE MODULE ADDRESSING

When a user creates an instrument (called a function block), it must be told which input point it will be using for
reference or output point for control. This is accomplished in an engineering screen called a Control Drawing.

Using FIC100 (on the previous page) as an example, this is how the function blocks running in the processor know
which I/O module to use.

%Z 0 1 1 1 0 1
CS3000 NIU #
(1-15)
1 Slot #
(1-8) Terminal #

%Z011107 %Z011108 %Z011109

17
CENTUM CS3000

1.5 Used I/O Modules

AAI143-H Cur r ent Input Module


This module inputs 4 to 20 mA.
Number of input channels 16, isolated
Input signal 4 to 20 mA
Accuracy 16 A
Data update period 10 ms
Transmitter power supply 24.0 to 25.5 V (output current limit: 25 mA)
Setting of 2-wire or 4-wire transmitter for each channel by setting pin
Maximum current consumption 230 mA (5 V DC), 540 mA (24 V DC)
Weight 0.3 kg
External communication Pressure clamp terminal, MIL connector cable, Dedicated cable (KS1)
HART communication

AAI543-H Cur r ent Output Module


This module outputs 4 to 20 mA.
Number of output channels 16, isolated
Output signal 4 to 20 mA
Between output and system: 1500 V AC, For 1 minute
Allowable load resistance 0 to 750
Accuracy 48 A
Data update period 10 ms
Maximum current consumption 230 mA (5 V DC), 540 mA (24 V DC)
Weight 0.4 kg
External communication Pressure clamp terminal, MIL connector cable, Dedicated cable (KS1)
Circuit-open detection Less than 0.65 mA
HART communication

18
CENTUM CS3000

AAT141-S TC Input Module


These modules receive signals from mV and thermocouple (TC).
Number of input channels 16, isolated
Input signal
TC: JIS C1602:1995, IEC584:1995, Type J, K, E, B(*1), R, S, T, N
mV: -100 to 150 mV, -20 to 80 mV
Switching input signals TC/mV can be set individually for CH1 to CH16.
Withstanding voltage Between input and system: 1500 V AC, For 1 minute
Data update period 1sec
Weight 0.2 kg
Maximum current consumption 450 mA (5 V DC)
External connection Pressure clamp terminal

ADV157-S Digital Input Module


The Digital Input Modules receive 32-channel 24 V DC ON/OFF signals.
Number of input channels 32
Rated input voltage 24 V DC (sink/source)
Input ON voltage 18 to 26.4
Input OFF voltage 5.0 V or less
Input current (at rated input voltage) 4.1 mA_20 % / channel
Maximum allowable input voltage 30.0 V DC
Maximum current consumption 350 mA (5 V DC)
Weight 0.4 kg
Pressure clamp terminal,

19
CENTUM CS3000

ALR121 Ser ial Communication Module


This Module exchanges data with a subsystem such as a programmable controller via a serial communication line
using the
Interface RS-422/RS-485 (2 ports)
How connected Point-to-point Point-to-point (RS-422), Multipoint (RS-485)
How communicates Half-duplex
How synchronizes Start-stop synchronization
Communication speed 1200/2400/4800/9600/19200/38400/57600/76800/115200 bps
Transmission code ASCII/binary
Character length 7/8 bits
Stop bit length 1/2 bits
Parity check None/even/odd
When a signal is received
after data transmission 1 ms
Transmission distance Maximum 1200 m (total extended length)
Cable with 3-pair shield
Wiring connection Clamped with terminal blocks M4 screws (5 poles x 2)
Current consumption 0.5 A
Weight 0.3 kg

20
CENTUM CS3000

2 System Operations
OBJ ECTIVES OF THIS CHAPTER

Upon completion of this chapter you should be able to:

1. Identify the standard display windows of the CENTUM CS3000.


2. Operate the Overview, Control Group, Operator Guide, and Process Alarm window.
3. Explain the function of the above windows.

21
CENTUM CS3000

2.1 Operator Keyboard

22
CENTUM CS3000

OFF
ON
EN

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

SYSTE COPY AUX HELP ?

_
! @ # $ % ^ & * ( ) + ~ | .
ES 1 2 3 4 5 6 7 8 9 0 BS
- = ` \

TA Q W E R T Y U I O P { } DE
[ ]
: "
CAPS LOCK A S D F G H J K L ; RETUR ITE
'
SHIF Z X C V B M N < > ? SHIF NAM
, . /

CTR AL SPAC AL CTR EX C

23
CENTUM CS3000

OPERATOR KEYS

Programmable function key


1
Page forward and backward

SYSTEM Display SYSTEM overview Fast ramp

COPY Screen hard copy Ramp UP

AUX AUX key Ramp DOWN

HELP Help message for the window Target key

Circulate

Clear screen Manual

Process alarm display Auto

?
Operator guide message Cascade

Control group

Tuning panel
Move cursor
Trend panel

Graphic panel Select cursor item

Process report ITEM Define Item

Navigator window call key NAME Panel Name

Upper window CL Clear line

Left Brother window

Right Brother window Acknowledge alarm

Process overview panel Buzzer silence

Scroll keys

Cancel
.
Confirm

24
Process Alarm
System Alarm
Tool Box

OperationGuide messages
Message monitor
Display Always
User In
System Ststus Display
Window Call Menu
HELP Message Window
Operation Menu
Process Alarm Window Preset Window Menu
Operator Guide Window
Tool Box
Control Window Navigator
Tuning Window Name Input
Trend Window Circulate

Graphic Window Clear All


Buzzer Reset
25

Process Report

Historical Report Hard Copy


Navigate Left
Input Window Name

Next Level Up
Navigate right
Overview Window

Save Window Set

Release Window Set


Save Image
Rotate Windows
Larger Size CENTUM CS3000
Middle Size
CENTUM CS3000

2.2 System Message area


At the top of the HIS screen is the System Message Area. Shown here are:

The last pr ocess alar m OR last system alar m that occurred.


The date and time are shown in the upper right-hand side.

Icons in the System Message Ar ea:


Process alar m: Lights when an alarm condition occurs in an instrument.
System Alar m: Lights when a system level occurrence happens, such as hardware failure or software file load.
Oper ator Guide message: Lights when a message is generated by the system for the operator.
Change user : Used to change security levels on the HIS, based upon the user who logs on.
Window call menu: Allows access to display window without the use of the Tool box or the operator
keyboard.
Oper ation menu: Allows the user to manipulate windows related with the currently displayed operation
window.
Preset Window menu: Windows that the operator uses often can be shown here. They are defined under the
HIS Setup icon on the System display.
Tool Box: Gives access to different categories of displays.
Navigator : Is used to display the plant window configuration. Icons under the Navigator can be selected to
display their specific windows.
Name: Used to enter the name of the window or function block to be displayed.
Cir culate: Used to switch between an NT package and a HIS display.
Clear all: Erases operation display screens
Buzzer r eset: Silences alarm tones.
Copy: Makes a screen copy of the current display.

Tool Box Icons:


These icons represent another way of accessing the operation displays without the use of the operator keyboard. The
purpose of these icons is discussed in this chapter.

26
CENTUM CS3000

2.3 HIS Operation Displays


The HIS can be defined as Full-scr een mode" or Windows mode
Full-screen mode has a window displayed as full screen, this is the primary window. In full-screen mode there
can be up to 4 secondary windows displayed.
Windows mode does not have a primary and secondary window. As displayed windows are called up, they
move to the front. There is a maximum of 5 windows displayed, when a 6th window is displayed the secondary
window at the back is closed.

27
CENTUM CS3000

Feedback Control Instrument Switch Instrument

Tag Number
Tag Comment
Tag mark
Mode Cascade Mark
Alarm status
Engineering Units

Index Mark

Scale

Manipulated Variable High High alarm setting


Limits
Process
High alarm setting Variable

Manipulated Variable

Setpoint

Index Mark
Process Variable
Manipulated
Scale Variable

Drain
(On/Off)

Answerback

Puts the loop into MANUAL

Puts the loop into AUTO

and Puts the loop into CASCADE

.
After the new mode has been selected, push the to confirm the change.

28
CENTUM CS3000

INSTRUMENT FACEPLATE

Instr ument mode examples:


AUT: Control computation (PID) determines the instruments output.
MAN: No control computation and the instruments output is manually adjusted.
IMAN: Displayed on the primary instrument of a cascade loop when the secondary instrument
isnt in CAS. Shows there is no control computation or output on this instrument.
CAS: Setpoint control of this instrument comes from another (primary) instrument.
O/S: Out of Service. All functions are non-operational.
The color of the pointers (SV and MV) on the tag faceplate also show the tags mode. The r ed pointer is in
contr ol.
If a tag is in AUT, the MV pointer will be yellow, and the SV pointer will be r ed.
If a tag is in MAN, the MV pointer will be r ed, and the SV pointer will be yellow.
If a tag is in CAS, the MV pointer and the SV pointer will be yellow.

MODE Changes
Clicking on the text of the current mode makes the mode selection box appears. Click on the appropriate icon, then
Confir m.

If a tag is a cascade, then will be shown on the faceplate.

Setpoint (SV) or MV Changes


Click the box under the tag.
A box will appear under the selected tag; type in the new value. MV appears in the box if the loop is in MAN,
SV appears if the loop is in AUT. Clicking on the data item on the faceplate also displays this box.
Use the mouse and select the SV or MV pointer (depending on the mode of the instrument) and a ramping
window appears. The item can be adjusted by selecting the up or down arrows.
On the operator keyboard, the SV or MV can be changed with the ramping keys after the loop has
been selected. To ramp quickly, select a tag, press the button and then hold the ramping arrow.

Switch Instr uments


Switch instruments are used to control ON/OFF devices like valves, motors, or pumps. A switch instrument has to be
in MAN for the operator to make any changes in the output.

To open or close a switch instrument, press the up or down ramping arrow for the selected tag or
click on the faceplate position you want.
The left-hand box on the faceplate shows the current output.
The right-hand box on the faceplate shows the answer back (digital confir mation) from the field instrument.

29
CENTUM CS3000

CG0007

30
CENTUM CS3000

2.4 Control Window


The control window is an operation window using instrument faceplates to display the control status of each tag.

Push the key (or icon) to bring up the Control window.


Each control group window can show up to 16 tags.
To bring up a specific window, select the NAME icon and type in the window name. The Faceplate window
for that tag appears. Next, select the Contr ol window icon from the Tool Bar or on the Window Call
Menu.
Operation Marks used as flags for the operator.
Click on the X in the upper corner of any window to close it.

Alar m color s:
Gr een: Normal operations
Red: Process alarm (IOP, HH, LL, OOP)
Yellow: Alarm has occurred (Deviation, Velocity, or Output limits)
Blue: Alarm output disabled
White: Tag without alarms (i.e.: internal switch)

Security Levels:
Eight different access levels can be selected to specify the instruments operation, the mode selection key affects
the security level assigned to an instrument. The chart shown below contains a simplified version of the
different security levels. Specific security information can be found in the Instruction Manuals.

Monitoring Operation
Level
S1 S2 S3 S1 S2 S3
1
2 **1
3 **2
4 x
5 x x x
6 x x x
7 x x x x x
8 x x x x x x

Can be executed x Cannot be executed


**1 Only the alarm settings, SV, MV, and block mode can be changed.
**2 Only the SV, MV, and block mode can be changed.

Tag Impor tance Mar ks


One of the four different tag importance marks can be assigned to a function block.
Important: The users must acknowledge SV and MV changes, and tag marks remains flashing after alarm
recovers.
General: No acknowledge SV and MV changes, but tag marks remains flashing after alarm recovers.
Auxiliary 1: No acknowledge SV and MV changes, and tag marks stops flashing after alarm
recovers.
Auxiliary 2: No acknowledge SV and MV changes, and tag mark doesnt flash before or after
alarm.

31
CENTUM CS3000

HELP WINDOWS

Help messages can be assigned to any operation window, with specific text created to aid the operator.

32
CENTUM CS3000

OV0001

Reactor Boiler Furnace Sample Displays

CG0007 CG0002 CG0005 Logo

CG0008 CG0003 CG0006 Bit map

CG0004 3D type

TG0007 TG0001 TG0005 CUSTOM

01FRC-103 01LIC-601 01TIC-101 16 Loops


0.0L/M 5% 234DEGC
AUT NR AUT NR CAS HI

01FIC-101 01PIC-101 01TIC-201 Trend Group


0.0L/M 100TNE/H 479DEGC
MAN NR AUT NR CAS NR

Help SEQ Table Status Face Plate System status

33
CENTUM CS3000

2.5 Overview Window


The Overview window can be used for monitor ing the oper ation of a plant.

Specifications:
Number of display blocks: 32 per page

Items that can be assigned to the overview blocks are:


Function blocks (instruments),
Windows (overview, control group, graphic),
Comments
Annunciators messages.

Overview block selection:


Mouse
Cursor keys (on the keyboard).

When a instrument is assigned to one of the 32 overview blocks, the alarm status of the assigned that tag or window
is reflected as the color of the block. The display block changes color and flashes according to the alarm status.

Alar m color s: (Same as on the Control Window)


Gr een: Normal operations
Red: Process alarm (IOP, HH, LL, OOP)
Yellow: Alarm has occurred (Deviation, Velocity, or Output limits)
Blue: Alarm output disabled
White: Tag without alarms (i.e.: internal switch)

Pressing the key (or icon) will acknowledge (stops flashing status) all of the alarms on the displayed window.

{xe "**Empty**"}
Scr een Hier ar chy Layout:
The alarm statuses can be read from the lowest level window to the Overview window.

Overview Overview
Plant-A Plant-B

Overview Overview
Area-A Area-B Area-A Area-D

Graphic

Reactor-1 Reactor-2 Reactor-3 Reactor-4

34
CENTUM CS3000

35
CENTUM CS3000

2.6 Tuning Window


This window is used to display the parameters and tuning trend data for an instrument. The different types of
function blocks will have items unique to their function.
The Tuning Window can be displayed by typing in the tag name (to bring up the faceplate window) and selecting the
icon on the Tool Box or Window Call Menu, or selecting this key on the optional keyboard.

Oper ation mar k assignment menu window


Touching the Operation mar k icon displays the menu window, then select the desired text.

To select items on this window:


1. Only items with a = mark next to them can be changed.

Tr end data that can be displayed:


Process variables (PV, CPV, or FV).
Setpoint values (SV).
Manipulated output values (MV).
Switch positions (SW)

Tr end display.
The Tuning Trend starts displaying when the window is displayed. 48 minutes of data maximum.
Selecting the Reduce or Enlarge time or data axis icon allows the modified for optimum viewing.
Moving the scroll bar under the tuning trend allows viewing of past trend data.
Selecting the Reduce or Enlarge data axis changes the vertical scale. Move the up or down arrow at the
right- hand side of the trend to see the expanded data. (1, 2, 5, 10x)
Selecting the Stop/Resume icon will pause the updating of the trend data. Selecting it again releases the
pause.
Touching the Reser ve icon allows the trend data to be recorded even when the Tuning Window isnt being
displayed. Up to 16 points can be reserved.

PG-L13 TUNING PANEL


The PG-L13 is a 13 zone program set block. The user sets the time base in Zones, and the ramping to occur in
during that time. Can be used to heat, cool, or cook products at a pre-defined rate.
AUT allows the PG-L13 to run one time and then goes to MAN.
CAS allows the PG-L13 to run continuously.
MAN holds the output at the point it was put into that mode.

36
Pen assignment
Stop/Resume display
Enlarge time axis
Reduce time axis
Reduce data axis
Enlarge data axis
Pen numbers
Display/delete reference
Display initialize
Save data
Read data
Stop/resume collection
Start collection
37

TG0006

CENTUM CS3000
CENTUM CS3000

2.7 Trend Window


There are 128 trend group windows (8 blocks with 16 trend group windows in each) on each HIS, each window can
record up to 8 pens. Numeric data (like PV, SV, MV, and CPV) can be trended, including totalization.
Blocks Groups Pens

1 1 1

2 2 2

3 3 3

4 4 4

5 5 5

6 6 6

7 7 7

8 8 8

10

11

12

13

14

15

16

Trend blocks can have different sampling periods. (2880 samples each):
1 second, (48 minutes)
10 seconds (8 hours)
1 minute (2 day)
2 minutes (4 days)
5 minutes (10 days)
10 minutes (20 days)
There is a maximum of 1024 trend pens, with 256 pens for 1 and 10 second sampling.

Tr end display. Trends are displayed by typing in TGbbgg (bb=block #, gg=group # i.e. TG0101)
Selecting the Reduce or Enlar ge time axis icon changes the displayed time scale.
Moving the scroll bar under the tuning trend allows viewing of past trend data.
Selecting the Reduce or Enlar ge data axis changes the vertical scale. Move the up or down arrow at the
right- hand side of the trend to see the expanded data. (1, 2, 5, 10x).
Selecting the Stop/Resume icon pauses the updating of the trend data. Selecting it again releases the pause.

There is a blue (cyan) pointer at the top of the trend, the data shown at the right-hand side of the screen
is the result of where the pointer is on the trend. To move the pointer, click where you want it to be.
Trend data can be saved (maximum of 100) and read from a Windows file. Trend data can also be read from
other HIS.

38
CENTUM CS3000

TREND POINT WINDOW


Double clicking on the desired trend item displays a window that shows only that single items pen.

39
CENTUM CS3000

40
CENTUM CS3000

2.8 Graphic Window

Each window can have:


Up to 200 process data items
16 bit colors
Up to 400 condition modifiers per graphic

Graphic items can be modified, depending upon the process state, to change color or blink.
Each primitive (graphic item) can have up to 8 condition modifiers.

A graphic window can be a representation of a plant or a control system. Displaying the plant status graphically for
intuitive operation and monitoring. The Over view and Contr ol windows ar e gr aphic windows also.
The window can be built with:
Process data displayed
Touch targets assigned (so a loop can be controlled from this window)
Links to other windows.
Bit maps can be imported.
Faceplate windows
Overview primitives.

41
CENTUM CS3000

42
CENTUM CS3000

2.9 Process Alarm Window


When a process alarm occurs in the FCS the notification is sent to the HIS and is shown in the System Message
Ar ea.
When the process alarm window is displayed, selecting the acknowledge key stops the alarm icon from
flashing.
The operator can select either all or just important alarms to be displayed.
The process alarm window also has a filter icon which allows custom alarm searches.
18 alarms per window, 200 maximum displayed.

Re-alar m:
If the process doesnt return to a normal state on a loop with a pr ior ity alar m, the HIS will re-generate the alarm at
a specified time interval.

43
CENTUM CS3000

44
CENTUM CS3000

2.10 Operator Guide Message Window


The operator guide message window (up to 70 characters) displays messages that are generated by a response to a
specific condition.
The messages are date and time stamped.
The operator guide window has a filter for custom message source searching.
40 messages will be displayed.

45
CENTUM CS3000

Save window set


Release window set

Rotate windows
M ake larger
M ake smaller

Recall saved image

46
CENTUM CS3000

2.11 Navigation
The Navigator window displays a list of HIS window like Windows Explorer. Clicking on the panel name will
display that panel.
USER displays all of the operation windows in the HIS.
Clicking on a graphic panel with a + in front displays the assigned panel hierarchy.
SYSTEM displays all of the message and system level windows in the HIS.

SAVE / RELEASE WINDOW SET


When multiple windows are displayed on the HIS, they can be saved and displayed again by calling up the window
they were overlaying when the save was made. Up to 30 window sets can be defined.

MAKE LARGER / SMALLER


A windows size can be changed by using these icons.

HELP WINDOWS
Help windows can be created for special help situations. A help window (up to 70 characters and 21 lines) can be
attached to any of the graphic operations windows and is displayed when the "HELP" button is pressed.

47
CENTUM CS3000

3 System Maintenance Windows


OBJ ECTIVES OF THIS CHAPTER

Explain and view the following system maintenance items:

1. System overview window.


2. System alarm message window.
3. Control station display window.
4. Define HIS setup items.

48
CENTUM CS3000

49
CENTUM CS3000

3.1 System Overview Window


The System Overview window shows the hardware statuses of the stations.
Up to 32 stations are shown on this window.
The HIS that this panel is displayed on is back-lit.

Alar m conditions:
Green: Normal.
Red: Failure (Duplex stations will also show processor failures).

50
CENTUM CS3000

51
CENTUM CS3000

SYSTEM ALARM MESSAGES

The system alarm message window is used to display the system alarms in order of occurrence, beginning with the
most recent.

System alarms can be acknowledged by selecting the button.


The message marks will stop blinking when the alarms have been acknowledged.

3.2 System Alarm Window


System alarms can be displayed, as a smaller window, on any operations screen by selecting the System Alar m
icon in the System Message Area.

HELP icon displays an on-line help message for the system message with the cursor positioned in front.
Filter icon allows for custom system alarm searching either by FCS, HIS (current) or All stations.

52
CENTUM CS3000

53
CENTUM CS3000

3.3 CS3000 Control Station Status Display Window


Clicking on the FCS block on the SYSTEM window displays this status window.

The control station status display shows:


The module configuration of the FCS. The status of the card is shown by the color.
CPU loading.
Clicking on the box beneath the FCS will display the Node Interface Unit and I/O module statuses.

IOM Load reloads a selected I/O modules database.


Save Tuning Parameter s icon saves the contents of the FCS setup file for control parameters like P, I and D.

54
CENTUM CS3000

HIS Setting

55
CENTUM CS3000

3.4 HIS Setup Display


This window is used to show the status information for the operator station.

Selecting HIS Setting icon on the System Overview window will bring up this display.
Station displays the setup information when the HIS was defined.
Printer defines the Windows printer to use for specific message types.
Buzzer allows the changing of alarm tones and volumes.
Display defines the screen mode (full screen or window) and the length of the tag name to be displayed.
Window switching allows the changing of the size or type of display when the process alarm window, system
alarm window, Operator Guide, or process alarms are selected.
Vnet shows the status of the Vnet.
Alar m allows definition of the alarm types to be displayed on the HIS.
Preset Menu is used to configure the Preset Window Menu which allows quick access to important or often
used operation windows.
Equalize used to equalize the database files. A message will appear when this is necessary.
Function key shows the current definition of the programmable function keys on the operator keyboard. The
keys can be re-assigned on this display by using drop down menus.
Example
Display pre-defined operation screens. O CG0001
Start and stop trends. T TG0001 STOP
Execute system function K HDCP Most of these are existing Keyboard, Tool
Box, or System Message Window functions.
Light LED (FLASH, ON, or OFF) E 10 F
Run programs F C:\file\program
Run multimedia files X PLAY1 filename.avi
NOTE: The multimedia files must be in file: C:\CS1000/3000\his\Media\User

A function keys LED can be defined to show the alarm status of an operation window.

Oper ation Mar k allows the creation and customization of the operation marks text and color.

56
CENTUM CS3000

4 Process and Historical Reports


OBJ ECTIVES OF THIS CHAPTER

Learn the functions of the Pr ocess report and Histor ical report pages:

1. Search for specific tags.


2. Display past alarm occurrences.
3. Define a search for specific date and time.

57
CENTUM CS3000

Tag Search

Tag Search Dialog

58
CENTUM CS3000

4.1 Process Report Window


Selecting the Pr ocess Repor t icon displays this window.

Tag Sear ch Dialog icon allows the user to conduct custom searches for:
A range of FCS or control drawings.
Specific tags
Specific elements with tag names assigned.
Specific alarm states.
Arbitrary Character can be used to search for a Tag Comment

Tag Sear ch icon searches for the parameters defined on the selected Sheet.

59
CENTUM CS3000

I/O Search
I/O Search Dialog

60
CENTUM CS3000

4.2 I/O Searches


Under the Pr ocess Repor t a user can search for digital elements.

I/O Sear ch Dialog icon allows the user to display screens showing:
Which annunciator messages are active.
The state of Common switches.
Which digital inputs and outputs are active.
The status of communication bits to subsystems (PLC).

I/O Sear ch icon searches for the parameters defined on the I/O Search Dialog icon..

61
CENTUM CS3000

62
CENTUM CS3000

4.3 Historical Report Window


Select the HISTORY icon to display this window.

The historical message window is used to search the operation records and process alarms that are stored on the HIS
hard drive, and displays up to 3500 previously generated messages.

Date allows searching for a specific date and time.

Message type displays:


Process Alarm: Displays the process alarm messages.
Status Changed: Shows mode changes (AUT, MAN CAS, O/S).
Operation Guide Messages.
Sequence Messages.
Maintenance: Displays the system operation and file loading messages.
Operation Message: Shows operation messages like setpoint and mode changes.
System Alarm: Shows the system alarm messages.
Specific Number: Allows the user to look for up to four (4) specific alarm numbers.

Occur r ence Sour ce:


Station: Select the station name by using the down arrow.
Hierarchy Name: Search for a specific drawing.
TAG: Allows for a search to be conducted for a specific tag. An * can be used as a search wildcard.
Batch ID: When batches are run (using the batch software), a specific ID is assigned. Searches can be made
from this number.

User search conditions:


This allows searching of system activities when a specific user was logged on.

MESSAGE MONITOR WINDOW


This icon displays up to 100 items that are also found in the "Historical Search" such as:
Process Alarms
System Alarms
Operation messages
Sequence messages

63
CENTUM CS3000

5 Control System Design

5.1 Architecture

64
CENTUM CS3000

5.2 I/O Module Arrangement

65
CENTUM CS3000

6 Control Concept

6.1 Tag naming standards

In all system is created one tag standard and programming standard. This standard will include PCS and also SCS
controllers.

I/O tag name should consist of the following figures and characters:
XXX-YYZZZS
Description of tag creation:
Position Description

XXX Unit number 102, 107

YY Type of signal TI, TO, etc.

First letter Y means A - Analysis


F - Flow
L - Level
P - Pressure
Q - Gas detector
T - Temperature
X - Motor/driver, push button
Z - Valve

Second letter Y means I - Input signal


O - Output signal
X - Signal from panel controller
T - Temperature transmitter
C - PID regulator
Y - SW element
A - Alarm

ZZZ Number of loop 001, 002, etc.

S (suffix) A, B, C
O - Open
C - Close
R - Run
F - Failure

66
CENTUM CS3000

6.2 Tag alarms standards

Alarm functions shall be implemented using the data acquisition and shared processing equipment of the control
system. All alarms shall be visually and audibly indicated and shall be connected to event logging facilities.

Standar ds

Each tag in control system can have alarm detection option.


For analog tag signals we can use L alarm, LL alarm, H alrm, HH alarm and Open loop alarm. Optionally we can use
also deviation alarm.
For digital tag signals we can use Status alarm and Change of state alarm.
Tag alarming will be applied according process design requirements.

We will use three levels of alarms:


High Alarm (Critical alarms)
Low alarm
Log alarm

Each alarm level gives its importance. High alarm is most critical alarm for the technology and in control system will
have separate critical alarm display. Low alarm has lowest priority. Log alarm will not be represented on alarm
screen, but will be written to alarm history file. By these alarm levels we can optimally manage our alarm strategy.
Also each alarm will have audible and graphical representation.
Each alarm will have graphical representation on the process screen and on alarm summary screen.

Alarm Representation for analog signals:


Bad Measure High Alarm
HH High Alarm
H Low Alarm
L Low Alarm
LL High Alarm

Bad Measure include open loop, out of the measure range and other, according the control system capabilities.
On the alarm summary screen we can clearly distinguish importance of the incoming alarms:
Not acknowledge alarm Blinking
Acknowledge alarm remaining Remain current alarm colour without blinking

67
CENTUM CS3000

7 Process screens standards


7.1 Colors of medium

7.2 Colors of device states


Run / Open state - Green
Stop / Close state - White

Uncertain state (Failure) - Red

Starting / Opening - Green blinking


Stopping / Closing - White blinking

7.3 Colors of electrical failures


Failure - Red

68
CENTUM CS3000

7.4 Basic types of equipment (shapes)

7.4.1 Pump, fan

Stop - White

Run - Green

Failure - Red

69
CENTUM CS3000

7.4.2 Solenoid Valve (ON/OFF)

Close - White

Open - Green

Failure - Red

70
CENTUM CS3000

7.4.3 Regulation valve

Manual

Close - White

Auto

Feedback of the
setpoint

Cascade

Open - Green

71
CENTUM CS3000

7.4.4 Analog measurement

Alarm

- Number of decimal places shall be designed by technological requirements.


- Engineering units shall be always visible.

7.4.5 Regulator

Set point value

Measurement value

Output value

Alarm

Measurement value:
Green if measurement value is in operational limits.
Red if measurement value reaches LO or HI limits or LL or HH limits.

7.4.6 Faceplates

- Faceplates shall be designed according technological requirements and possibilities of selected control system.

72