You are on page 1of 19

PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

Advanced Insulation System


The Advanced Insulation System (AIS) is an optional 3. Turn on the MCE tester and the AIS unit.
accessory unit that is connected to the MCE for
enhanced insulation testing. The AIS allows greater 4. Turn the main center switch on the AIS unit to the
voltage selection, from 250V to 5000V DC, and offers var. position.
the ability to perform a step voltage test at any of the
selectable voltage levels. 5. In the Plant Layout, highlight the motor to be
tested.
You may choose to perform the Step Voltage test
initially or any of the other MCE tests and change to the 6. Select Test from the menu.
AIS unit as needed.
7. On the Select Software Option window, highlight
Testing using either the MCE unit or the AIS unit may MCE and click OK, or double click MCE.
be suspended for several reasons and an appropriate
er ror message will be disp layed. S ome of these 8. On the MCE Test Selection window select Step
messages are: Voltage from the Test List.

Test Suspended Due to Excessive Leakage Note: If the AIS unit is not turned on, Step Voltage
Current will not appear in the Test List. Click Exit to return
to the Plant Layout, turn the AIS unit on, select Test
Test Suspended! Disconnect MCE Standard Test from the menu, and MCE from the Select Software
Leads and Connect AIS High Voltage Test Leads. Option window.
Following Lead Change, Press <OK> to Continue
Testing. The only selection to be made from Test Setup is
While performing a standard test if the AIS is Resistance to Ground.
connected and turned on, this message informs
you to use the Advanced Insulation System for To activate the Resistance to Ground Low
the test. Limit, click the checkbox beside Low Limit in
the Test Setup area. A default value has been
Testing was halted due to exceeding the insulation entered in the kohm text box. To change the
resistance low limit setpoint value, click in the kohm text box and enter a
This message may appear if the Low Limit value between 50 and 9999.
Resistance to Ground check box in the Test
Setup section has been activated. All other Test Setup selections will be made on the
Step Voltage - xyz window, where xyz is the plant
Unable to receive Data from AIS location. Click OK.
When communication between the MCE and
AIS is interrupted, the AIS Is Not Responding 9. In the Test Setup area of the Step Voltage window,
window opens with this message. The AIS select the desired starting volts value from the
con tinues to send voltage. Before available test volts in the drop-down list. The
disconnecting the test leads, either turn the AIS minimum value is 0V and the maximum value is
off or click OK, the AIS unit will discharge, 2500V. The default value is the same as the
and the test can be restarted or ended. recommended value.

PROCEDURE FOR STEP Note: Occasionally the Voltage and Time graphs
will appear without the numerical identifiers along
VOLTAGE TESTING the bottom and side axis. This is an Access software
problem and is out of the con trol of PdMA.
1. Attach the AIS unit to the MCE unit. However, as soon as testing begins the numbers
will appear.
2. Connect the AIS test leads to the motor.

REV. 0-8/01 1999, 2001 PdMA Corporation 4-87


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

10. Select the final volts value from the available test step in the testing interval, an audible sound is
volts in the drop-down list. The minimum value is emitted, the final value is displayed on the graph,
500V and the maxim um value is 5000V. The the testing pauses for approximately 10 seconds,
default value is the same as the recommended testing begins again at the next voltage interval, and
value. The final voltage may not be lower than the graph again begins to change with each one second
start voltage. If the final voltage is entered with a test value.
value less than the start voltage, the start voltage
adjusts automatically to a lower value. During testing the voltage and time graphs refresh
each second. This may cause your display screen to
11. Select the voltage interval value from the available flicker.
volts in the drop-down list. The value changes
depending upon the values chosen for the start and Note: With certain test results there is a possibility
final volts. The default value is the same as the that the scale on the A axis will try to adjust to
recommended value. The voltage interval is the accommodate them. When this happens the entire
amount that the voltage is increased at each step length of the graph line appears to be jumping up
interval. and down from the beginning point. As the test
progresses and the results change this situation will
12. No change can be made to the time interval. Each stop.
interval is set at 60 seconds.
The total/accumulated test time is displayed in the
13. When all of the test setup selections have been Elapsed box in the upper right corner of the
made, click Test. window.

14. The AIS Supply Voltage window opens with the 16. At the end of testing a pop-up window displays the
message You are about to apply up to xyz volts to message End of Test. Click OK.
AIS test leads. Do you want to continue? XYZ
denotes the value selected for the final voltage. 17. On the Step Voltage - xzy window, where xyz is the
Click Cancel to return to the Step Voltage location of the motor, select Exit.
window or OK to continue with the test.
18. The Step Voltage Test window opens with the
15. As the test is proceeding, the values are inserted message Do you want to save data. Click Cancel
into the Current table. The value from each one to return to the Step Voltage - xyz window. Click
second test is briefly displayed, however the value No to exit without saving data. Click Yes to save
at the end of 5 seconds is permanently displayed. test data and exit.

The graphs on the right side of the window display 19. If test data is saved, the Assign Condition Code Y/
the time and voltage values in graphical form. In N window opens with the message Do you wish to
the Time graph the values are displayed at one assign condition Code? Click No to exit without
second intervals. The values clear at the end of each assigning a condition code. Click Cancel to exit
minute, a new blank graph appears with the without assigning a condition code. Click Yes to
numbers along the bottom axis reflecting the total open the Motor Condition window.
test time in seconds.
20. Click on the radio button to select the condition
On the voltage graph, no test values are displayed code you wish to assign this motor and then click
for the first interval. However, after the first one OK. If a condition code was assigned the Add New
minute the values are displayed. The voltage graph Note Y/N window opens. Click Yes to go to the
changes with each one second value, so that the notes area or No to exit without entering a note.
graph is constantly changing to reflect the readings.
At the end of one minute, which is the end of each

REV. 0-8/01 1999, 2001 PdMA Corporation 4-88


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

Step Voltage Window

Figure 4-142: Step Voltage

Across the top of the Step Voltage window are the displays the test value for each second, but retains only
Motor ID,Voltage, and Elapsed time boxes. the final value of each five second interval.

Motor ID displays the ID of the motor selected from the Below the data table is the Voltage Setup text boxes,
Plant Layout. which display the Recommended and Actual Start and
F i n al v o l ta ge . N o c ha n ge s ca n b e mad e t o t he
Voltage displays the voltage being used for the current recommended values. The Actual values can be changed
testing phase. It initially displays the starting voltage as previously discussed in the procedure section.
value. After each one minute of testing the value
increases by the voltage interval selected. The Interval Setup text boxes, located below theVoltage
Setup text boxes, display the Recommended and Actual
Elapsed time displays the cumulative time of the test in volt and time interval. No changes can be made to the
minutes and seconds. The value increases by one second recommended values or the actual time interval. The
until the end of the test. Actual volt interval value can be changed as previously
discussed in the procedure section. The Actual voltage
On the upper left side of the box is a data table which interval is the amount the voltage is increased by at the
displays the Time, Volts, and Current test values. The end of each one minute testing period. The time interval,
Time table displays the test tim e in five second which cannot be changed, reflects the interval in
increments. The Volts table displays the voltage being seconds for the testing period.
used at that point in the testing. The Current table briefly

REV. 0-8/01 1999, 2001 PdMA Corporation 4-89


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

On the right side of the window is the Voltage graph. The Voltage graph, on the left of the window,
The test data results are displayed here beginning with represents the values taken at one minute intervals.
the end of the first interval selected in the Voltage Setup The bottom axis represents the voltage value at
section, not the 0,0 point on the graph. During testing each step. The side axis represents the test voltage
the graph refreshes every second. This may cause the value.
display screen to flicker.
The Time graph, on the right of the window, plots
Below the Voltage graph is the Time graph. The test data the values taken at five second intervals. The
results are displayed here every second. The graph bottom axis represents the cumulative test time in
begins at 0 seconds and the grid is in 10 second seconds. The side axis represents the test voltage
intervals. Every 60 seconds (one minute) a new graph is value.
displayed and the grid markers increment accordingly.
The Time graph may be expanded for greater detail
History Chart by using the Zoom In button. Click on the Zoom
In button until the desired level of detail is
A tab identifying Step Voltage has been added to the displayed. When the graph is displayed in expanded
Test Summary window. The Test Summary window detail, a slide bar is available for use in scrolling. To
contains the date the test was performed, voltage compress the graph click the Zoom Out button.
interval used for testing, MCE tester number, User name
if entered, starting voltage, and ending voltage. The There are two menu items found on the menu bar,
MCE# will have HV to indicate that the test was File and Notes. The File menu contains, Print,
performed using the AIS. Printer Setup, Save as Bitmap, and Exit. The Notes
menu opens the Notes window. All of these menu
Viewing Step Voltage test data. items have been discussed earlier in this manual.

1. Highlight the motor in the Plant Layout. 9. Click the Cancel button or select File, Exit to close
the Step Voltage Test window and return to the
2. Select Data from the menu. History Chart window.

3. On the Select Software Option window select MCE 10. Select File, Exit to return to the main Plant Layout
and click OK. window.

4. Click the Step Voltage tab on the Test Summary for


(xyz) window, where xyz is the motor ID. STAND ALONE
5. Highlight the test to be viewed. OPERATING
6. Select View Data to see the actual test values. Go to
step 7. Or select View Graph to see the complete
INSTRUCTIONS FOR
test results in a graphical display. Go to step 9. THE AIS:
7. The History Chart for (xyz) window, where xyz is The Stand Alone Operating Instructions for the AIS are
the motor ID, displays the time point of the test in reproduced with permission from LEM Instruments,
five second increments, voltage used at that testing Inc.
point, and Current Amps value at that testing
point. Use the scroll bar to view the entire test data.
To return to the main Plant Layout window, select
ABOUT THIS SECTION
File and Exit. Or you may select View Graph from In this section Ip = PI, RISO = RTG, Rad = DA, and V ISO
this window. Go to step 8. = voltage.

8. The Step Voltage Test window opens.

This symbol means please read with particular


care.

REV. 0-8/01 1999, 2001 PdMA Corporation 4-90


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

* This symbol is followed by a list. * use only the safety test leads supplied. The test
leads may only be used with the AIS in CAT III
This symbol requires an action. networks with a maximum 600V to earth
ground and a maximum current that does not
SAFETY exceed 0.1A.

This unit may only be used by qualified staff having the Qualified Staff
technical specifications set out below and using
the following safety instructions. During use Qualified staff are persons familiar with the installation,
any additional legal or safety requirements assembly, setting up, and operation of this product and
applicable to the type of application must also have the following qualifications
be met. This also applies to any accessories.
* training or instruction/authorization to switch
When operating electrical devices some of their parts on/off, earth ground and mark circuits and
necessarily carry dangerous voltages. Ignoring devices/system s according to the safety
the safety instructions may therefore result in engineering standard
serious health hazards or damage to the
equipment. * training or instruction according to the safety
e nginee ring s ta nda rds with re gard to
The accurate and safe operation of this device depends maintenance and use of appropriate safety
on appropriate transportation and storage, professional equipment
installation and assembly, and careful operation and
maintenance. * first aid training

If it becomes apparent that the device cannot be START UP


operated safely, it must be immediately taken out of
service and protected against accidental activation. Although the unit is very easy to operate, please read the
following operating instructions carefully for safety
Safe operation is not guaranteed when the device reasons and to make optimum use of the unit.

* displays visible damages Power Supply


The imprint on the battery cover is not applicable. This
* has been exposed to unfavorable conditions version is only supplied with built-in storage batteries.
(e.g. s torage outside the adm is sible The batteries must be charged prior to starting the unit
temperature limits, in dew, or similar) for some for at least eight hours using the battery charger
time supplied. The unit is then ready for operation.

* has sustained heavy stress during transport


(e.g. falling from great height even if no
external damage is visible)

* the display reads -E 1-

WARNING! Testing should not be done on unprotected


test circuits. Make sure prior to measurement
that the measuring object is potential-free.

For safe operation

* avoid contact with the testing probes

* do not use in an explosive atmosphere

* do not disconnect the test leads until the


external capacitors have been discharged

REV. 0-8/01 1999, 2001 PdMA Corporation 4-91


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

Opening the unit There are four buttons on the left side of the front panel
to start measurement, call supplementary measured
Press in the two snap-in locks as shown above at the values and select the special functions.
positions indicated (D) and open the unit top as
indicated by (E). Put the top into the required position This construction provides for quick and easy single-
and let the snap-in locks catch. To close the unit first handed operation.
press in the snap-in locks, then fold the top down.
The measured values are displayed on the liquid crystal
CAUTION: Do not use force to open or close the unit. display with correct decimal point and unit. Various
additional special characters are used to display the
General function, operating state or error messages.
Measurement and test functions:
The auxiliary voltage is supplied by 10 1.2V storage
* Voltage measurement batteries in a rechargeable block which is firmly
integrated in the casing.
* Insulation resistance measurement to IEC
61557 Part 2 (EN61557-2) with GUARD The test instrument meets protection category IP 40.
feature. This enables the polarization index and
the dielectric absorption coefficient to be The air gaps and leakage distances are dimensioned to
displayed directly IEC61010-1 (EN 61010-1).

Step Voltage for insulation resistance The device corresponds to safety class II.
measurements and for surge voltage protector Operating voltage 600V, overvoltage category III,
tests contamination level 2.

All device settings can be permanently programmed by The measuring voltage of 5750V DC generated in the
means of a user code so they remain set even after unit is current limited to <2mA.
switching the instrument On and Off. This enables the
instrument to be completely customized. In order to T he unit has been developed, designed, and
prevent measurements with undesirably high insulation manufactured in compliance with the DIN ISO 9001
measuring voltages, e.g. because of misoperation, every quality assurance system.
fixed measuring voltage (500V, 1000V, 2500V, and
50 0 0V ) c an be lo c k e d separa t e ly . A ma ximum Operation
admissible measuring voltage can be programmed at the
Voltage Measurement. The applied voltage is
var. position. This setting can only be changed after
analyzed automatically for its direct (DC) and alternate
entering a personal code.
(AC) current fraction. The larger value, alternate or
direct voltage is then displayed. During voltage
Design measurement the source is loaded with approximately
The test instrument consists of two parts: 500 .

The base part which integrates the protective cover, set- Insulation resistance measurement.
up bracket and compartment for the quick reference After pressing the START button, a test for applied
manual. It also contains the power supply (storage voltage is carried out prior to measurement. If 50V are
batteries and battery charger). exceeded the measurement is blocked and an audible
warning is sounded.
The measuring part which can be unfolded from the
base part in six lock-on positions (five when using the The measuring voltage for insulation measurement can
DOCU-PACK). It contains the entire measuring be selected via a central switch.
electronics and operating ele ments, display and
connecting sockets. Four fixed voltages are available; 0.5kV, 1kV, 2.5kV,and
5kV.
The functions and measuring voltage ranges are selected
with the central switch.

REV. 0-8/01 1999, 2001 PdMA Corporation 4-92


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

There is also a variable range with 10V increments from


50V to 250V or with 50V increments from 250V to
5000V.

The measuring voltage is generated by a


microprocessor-controlled DC/DC converter. The rated
values and voltage/current characteristics are pre-
defined by the software.

The insulation resistance RTG = is determined

from the measuring voltage and the test current


I M . The measurement continues as long as
START is pressed. Upon completion of the
measurement the last measured insulation Operation: Central switch and function buttons
resistance is stored and displayed in digitized
form at. Any residu al voltage of the test Working temperature range: -10 C ...+50 C
specimen is represented on the analog scale,
automatically discharging the test specimens. Operating Temperature range: 0 C ... +35 C

Buzzer.
Reference temperature range: 23 C ... 2 C
The integrated buzzer, which is microprocessor-
controlled, fulfills two functions: Storage Temperature range: -30 C ... +60 C

* signaling any upper or lower deviation of the Temperature Coefficient: 0.2% or m.r./K
limit values set (LIMITS)
Operating error: refers to the operating temperature
* signaling dangerous states or misoperation.
range
LO-BAT. Intrinsic error: refers to the reference temperature
range
The supply voltage is monitored by comparator circuit.
The microprocessor detects a lowering of the voltage to Climatic class: JWG as per DIN 40040 (3/73) relative
9V even during a measurement operation and signals
this with LO-BAT on the display. In this case, the humidity 65% annual mean, 85% maximum, no
integrated storage batteries must be recharged with the damp for measuring values >30 G climatic class KWJ
battery charger. A flashing LED indicates a switch to according to DIN40040.
float charging and the battery charger can be removed.
Maximum operating altitude: 2000 m
Technical Specifications
Clearance and Creepage Distance: according to IEC
General Technical Specifications. 61010-1 (EN 61010-1)

Gen eral: Micro processor -contro lled insu lation Safety Class: safety class II, operating voltage 600V,
measuring instrument with additional functions. overvoltage category III, pollution level 2

Measurement functions: Voltage, insulation resistance Working voltage: 5750V DC maximum, current -
with GUARD limited to < 2 mA

Display: 4-digit, (2999) - 7-segment liquid crystal Test voltage: 10kV as per IEC 1010-1 (EN 61010 - 1)
display, 16mm high, 56-div. analog scale, additional
symbols and fluorescent display lighting. Electro-magnetic compatibility: emission values IEC
61326-1 (ENC 50081-1) /Class B immission values IEC
61326 - 1 (ENC 50082-1)

REV. 0-8/01 1999, 2001 PdMA Corporation 4-93


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

Q u a l i t y s t a n d a r d s: d e v e l o p e d , d e si g n e d a n d Weight: < 3kg without accessories, < 4kg including


manufactured in compliance with DIN ISO 9001 accessories and carrying case

Auxiliary power: 1 NiMH storage battery, 12V, Casing material: NORYL, shock and scratch-proof
integrated thermoplast

Numb er of measu rements: typically 3,000 Voltage measurements (AC/DC).


measurements (Voltage = 500V, 1mA), typically 1,000 Measuring method: Mean value rectification for AC,
measurements (Voltage = 5000V, 1mA), 5 seconds calibrated for RMS display for sine-shaped signals. The
measuring time, 25 seconds pause as per IEC 61557-2. larger value (AC or DC) is displayed.

Dimensions: 265 mm (L) x 265mm (W) x 90mm (H)

Table 4-24: Digital display

Measuring Display Resolu- Frequency


Intrinsic error
range range tion range
1 ... 600V 1 ... 1000V 1V DC (2% of m.v. +1d)
1 ... 100V 1 ... 1000V 1V 45 ...65 Hz* (2% of m.v. +2d)
100 ... 400V 1 ... 1000V 1V 45 ...65 Hz* (2% of m.v. +1d)
400 ... 600V 1 ... 1000V 1V 45 ...65 Hz* (2% of m.v. +2d)

at 400 Hz typically -5% * calibrated for RMS display of sine-shaped signals

Table 4-25: Analog display

Measuring Display Resolu- Intrinsic


range range tion error
20 ... 600V 0 ... 1000V 20V 1 scale
div.

Measu rin g sequ ence: app roxim ately two Nominal voltage: UN=500V, 1000V, 2500V, 5000V DC
measurements for digital display and approximately five or adjustable from 250V to 5000V DC with 50V
measurements for analog display increments.

Internal resistance: approximately 4 0 0 k I d l e Vo l t a g e : Uo


x U 1.5 N ( 2 5 0 V . . . 4 5 0 V:
Uo 1, 25 x UN )
Maximum admissible overload: Ueff = 1000V
Nominal current: 1mA (505V ... 5000V) DC
Insulation resistance measurement
(RTG) . Short-circuit current: <2mA DC

Measuring method: Current, voltage measurement to


IEC 61557-2 and EN 61557-2 for distribution systems
up to 600V to earth ground.

REV. 0-8/01 1999, 2001 PdMA Corporation 4-94


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

Table 4-26: Digital display

Measuring
Measuring range Resolution Operating error
voltage
10 k ...299,9 G 1 k ... 0,1 G 250 ...5000V (3% v. MW + 3 Dig)

0,30o T ...2,99 T 10 G 1000 ... 5000V (3% v. MW + 1o Dig + 1 %/T )

3,0o T ...9,9 T 0,1 T


10.oo k ...29 T 1 T 5000V (3% v. MW + 1oo Dig + 1%/T )

Digit o ... always 0

Table 4-27: Analog display

Display Operating
Measuring range Resolution error
range
10 k ... 1T 5 k ... 1T 5 k ... 200 G 1 scale div.

Preset limit values:


RTG LIMIT: <500 k
Adjustable 100 ... 9.99 T />LIMIT or < LIMIT Measuring time: Measurement continues as long as
Voltage LIMIT: 5000V; adjustable 250 ... 5000V START button is pressed, 1 minute for DA, 10
only with CODE entry in the 0.25 ... 5kV var. minutes for PI or freely adjustable with TIMER
range. FUNCTION in the range: 1.00 ... 59.00 minutes.

Capacitor influence:100 nF parallel to insulation Response time:


resistance in the range 100 ... 100M typically no For RTG < 3M approximately 3 seconds
influence. In the 100M ...300G range influence For 3 M < RTG < 2.9 G approximately 5
<10% is met by the measured value. As per IEC (EN) seconds
For 3 G < RTG < 29.9 G approximately 10
61557-2 the shunt capacitor influence of 5 F at U N .
seconds
1000 <10% is met.
For 30 G <RTG <299 G approximately 15
seconds
Measu rin g s eq uence: Approx im ately two
measurements for digital display, approximately five
NOTE: The response time can be prolonged with
measurements for analog display.
external capacitors depending on the time constant.

REV. 0-8/01 1999, 2001 PdMA Corporation 4-95


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

Diagram of measurement voltage during load

Supplementary functions: Display of the measurement voltage.


Table 4-28: Digital Display

Display Resolu
DC measuring range Operating error
range tion
20 ... 5000V 0 ... 550V 1V (1% of m.v. + 3 Dig)

Table 4-29: Analog display

Display Resolu
DC measuring range Operating error
range tion
100V ... 5000V 0 ... 5500V 100V 1 scale div.

Internal resistance: approximately 600 k

Description of operating elements: 1. Central switch to select measuring functions and


ON/OFF.

2. START button to trigger the selected measuring


function.

3. DISPLAY button to call the respective


supplementary values.

4. CHANGE button to change preset values.

5. SELECT button to select the position to be


changed.

6. Display unit, liquid crystal display digits (LCD),


16mm high with automatic decimal point and
analog scale with 56 divisions and fluorescent
lighting.

REV. 0-8/01 1999, 2001 PdMA Corporation 4-96


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

16. Socket for battery charger, located on back of the


unit.

17. Control light for charging status, located on back of


the unit next to the charger socket.

Description of display elements:

7. Connecting socket GUARD for screen


connection (suitable for supplied test leads only).

WARNING! Maximum admissible voltage to earth


ground: Ueff = 600V

8. Connecting socket +Rx (suitable for supplied test


leads only). Positive pole for voltage and insulation
measurements.
The display is divided into display elements
WARNING! Maximum admissible voltage to earth
ground: Ueff = 600V
1. Analog representation of measured values for
9. Connecting socket -Rx (suitable for supplied test
voltage and resistance. Range 100V...550V, 1 k...
lea ds on ly ) . N eg at iv e p o le fo r v ol tag e and 1T
insulation measurements.
2. Digital representation of measured values with
WARNING! Maximum admissible voltage to earth additional information
ground: Ueff = 600V.
3. Measuring function field to display the selected
10. Snap-in locks to lock the instrument in seven function
positions. In order to tilt the instrument press the
snap-in locks on the right and left simultaneously 4. Units field: V, , k ,M ,G , T , minimum
and rotate it.
5. Special characters for user guidance
CAUTION: Do not use force to open or close the
instrument. Explanation of display symbols

11. Carrying strap attachments, can also be removed by U~ AC voltage


pressing them towards the instrument and lifting
them. U DC voltage

12. Technical specifications printed to the bottom side. U ISO Insulation measuring voltage

13. Compartment for accessories. U ISO LIMITMeasuring voltage limit in position


0.25 ... 5 kV var.
14. Type plate with serial number.
U ISO OFF Fixed measuring voltage off
15. Port for serial interface (RS232C, option) located
on back of the unit.
RISO Insulation resistance

REV. 0-8/01 1999, 2001 PdMA Corporation 4-97


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

LIMIT Limit value The special test leads supplied may only be used in CAT
III networks with maximum 600V to earth
< Lower limit violation ground. Maximum current may not exceed
0.1A.
> Upper limit violation
The best possible use is made of the instrument if you
Rad Dielectric absorption coefficient observe the following points:

General.
Power On functions. While switching on the unit with
the central switch it is possible to obtain special
Ip Polarization index
operating states by pressing a combination of buttons.
The buttons must be pressed for at least four seconds.

* Normal operation - If the unit is turned on without


pressing any other buttons it will switch to energy-
s av in g m o d e ( S t an d B y - d is pl a y: - - - )
I Interval (timer) function, measuring time approximately four minutes after completion of a
freely selectable measurement, the last pressing of a button or
turning of the switch. Pressing a button or turning
GUARD Guard screen connected the central switch will reactivate the unit. The
previous measured values can still be called with
DISPLAY. A new measurement is triggered by
Buzzer is activated (signalling a LIMIT pressing the START button.
violation)
* Preventing Stand By - Simultaneous pressing of
LO-BAT Battery voltage too low, recharge the DISPLAY and CHANGE buttons during
switch-on will prevent automatic switch-over to the
REMOTE Remote control via interface (option) energy-saving mode (Stand By). The energy-
activated - operation via buttons saving mode is reactivated via On/Off with the
blocked, interval printing activated central switch.

WARNING! A dangerous state may occur. Read text in * Prolonging the display test - Holding down the
operating manual very carefully. DISPLAY button during switch-over enables the
Display Test to be prolonged at will. Return to
Effecting Measurements normal operation by pressing any button or turning
the central switch.
Manual operation is very simple
* Software version number - Holding down the
1. Set required measuring voltage with the central SELECT button during the switch-on displays
switch. the software version number. Pressing DISPLAY
switches to the last recalibration date. The display
2. Turn unit on and connect. is stopped by turning the central switch or pressing
START.
3. Trigger measurement with START button.
Display format: SOFTWARE version: x.xx
4. Read measured value.
Recalibration date: MM.YY
CAUTION: During measurement (until results are
displayed) you must not change the position of MM...two - digit indication of month, YY two - digit
the central switch or any connections of the indication of the year. Note: At the time of delivery the
unit. calibration date is indicated with 0.00. A date will only
be displayed once the instrument has been recalibrated
for the first time.

REV. 0-8/01 1999, 2001 PdMA Corporation 4-98


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

Safety Measures. Prior to any measurement the unit Insulation resistance measurement (RTG) This
auto m atica lly ch ecks th e pr eva ilin g m easur ing measuring function is used to measure insulation
conditions and prevents the start of the measurement resistances up to maximum 30 T with the measuring
while displaying the error if any of the following range being selected automatically. The measuring
conditions occur: voltage used is a DC voltage between 250V and 5000V
with a rated current of 1mA to IEC61557-2 generated
* inadmissible voltage at the measuring sockets by the integrated storage batteries.
(>50V for RTG) Voltages >50V are also
signalled acoustically when the unit is switched NOTE: When measuring in installations with connected
off consumers it is important to make sure that consumers
are separated from the network by at least one pole by
* instrument faulty (display -E 1-) switching off the mains switch or removing the
integrated fuse. If the required insulation resistance
Voltage measurement U. This measuring function is values are still not reached the devices must be
activated automatically for every central switch position separated from the network with all poles.
prior to pressing START. DC and AC voltages from 0
... 600V can be measured. The unit alternately measures WARNING! During measurement voltages up to 5750V
the AC and DC values, automatically displaying the w il l o c cu r. I n co n j u n c ti o n w it h h ig h l y
larger value. AC voltage measurement is effected on the capacitive installations these can be mortally
principle of mean value rectification and displays the dangerous! Overvoltage-sensitive devices like
RMS value for sine-shaped voltages. automatic controls, microprocessor-controlled
devices and similar should be separated with
WARNING! Voltage m easurements may only be all poles from the network to be measured prior
effected on equipment or distribution networks with to measurement.
circuit breakers connected in series and Common Mode
v o l ta g e s ( t o e a r t h g r o u n d ) o f ma x i m u m 6 0 0 V Measuring procedure:
(installation category III).

1. Connect unit as shown, the regulations require all


connectors to be measured against each other and/
or together against earth ground.

Measuring procedure: 2. Select required measuring voltage with central


switch. By pressing DISPLAY all settings and
1. Connect unit as shown. limits available can be called. In the var. switch
position any measuring voltage between 250V and
2. Set central switch to the required measuring 1000V can be adjusted in 50V increments. To do so
function. SELECT and CHANGE buttons.

3. Read measured value. CAUTION: The installation/test specimen must be set


potential-free prior to measurement! In case of

REV. 0-8/01 1999, 2001 PdMA Corporation 4-99


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

external voltages above 50V measurement is With the Code programming any fixed measuring
blocked. voltage can be blocked (UISO Off). In the var position
a U ISO LIMIT can be set. This LIMIT prevents
3. Press START and hold the button until the measuring voltages above the set LIMIT from being
measured value is stable.The measurement will entered in the var position. Note: Higher fixed
continue until the button is released. measuring voltages are not blocked by UISO LIMIT.

4. Read measured value. Depending on the


Error messages. Flashing symbols in the display
programing, the analog scale is set to insulation
indicate basic inadmissible conditions or errors. For
resistance or voltage display during measurement.
more details see the section on Display Elements.
After completion of the measurement the analog
scale always displays the residual voltage in the test
Measured value evaluation: The minimum display
specimen.
value, which must at least be displayed taking into
consideration the maximum operation error in order not
5. Read residual voltage on the analog scale, in case of
to fall below the required insulation resistance, can be
voltages above 50V the display flashes
determined from the diagrams below.
automatically.
299.0 G measuring range
WARNING! The test specimen must remain connected
until the residual voltage falls below 50V.
R e si d u a l v o l t a g e s a b o v e 5 0 V p r e v e n t
measurement to be restarted.

By using the DISPLAY button it is possible to display


the measuring voltage, which occurred during insulation
measurement.

NOTE: If, after starting a measurement, an acoustic


signal is output together with the display of U ISO LIMIT
this means that a measuring voltage was selected which
is abo ve th e vo ltage l im it set w ith Cod e an d
measurement is not started.
29.99 G measuring range
Parameter Programming:
Briefly turn the central switch to call the setting loop.
Call the required display with DISPLAY and change
CHANGE or SELECT .

Possible settings:
RTG: 0 ... 9.99 T ; > LIMIT exceeded; < LIMIT not
reached

Buzzer: (N) On/Off in casae of LIMIT violation

Analog display: resistance value or measuring voltage


Measurement with GUARD up to maximum 30 T .
Measuring voltage: 250V...5000V only with switch The function insulation resistance measurement with
position RTG var. GUARD (screen) is used for accurate measurements of
resistance without the influence of leakage or parallel
In the lp (polarization index) function SELECT/ resistances.
CHA NG E can be used to change the 10 min ute
measuring time displayed. For measuring times other It is indispensable for measurements in the 100 G or
than 10 minutes this is displayed by the I (interval/ T range as the insulation resistances of the test leads
timer) function. Setting range 01 ... 59 minutes. Abort alone (they are parallel to the test specimen) may cause
the Timer function by pressing START.

REV. 0-8/01 1999, 2001 PdMA Corporation 4-100


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

significant measuring errors. When using GUARD any the voltage measured is smaller the current load was too
leakage currents are diverted via the GUARD conductor large, the measured value is invalid.
direct to mass. Thus, they are not measured and cannot
influence the measuring result. Step Test
Condition: The sum of the flowing currents may not With this measuring function an increasing step voltage
exceed the maximum measuring current (1-2.5 mA). can be programmed, which makes it possible to perform
This condition can be met by checking the measuring automatically insulation resistance measurements with
voltage after measurement. increasing measuring voltage or surge voltage protector
tests (spark gaps, gaseous discharge tubes or metal
Measurement without GUARD: oxide varistors, etc.).

The leakage resistances, R A 1 and R A 2 , falsify the


measured value. The displayed value R ISO is smaller
than the required RX.

Measurement with GUARD:

U ad Nominal voltage for the test


(entry in the setting loop;
range: 50...5250V DC; default 250V)

U start Programmable starting voltage


(entry in Code-programming in % of Uad
range: 1...099%, default: 50%)

U stop Programmable stop voltage


(entry in Code-programming in % of Uad
range: 100...255%; default:125%)

N Programmable number of voltage steps


1. Connect the instrument as shown. between Ustart and Ustop
(entry in Code-programming
2. Select required measuring voltage. range: 1...255; default 15)

3. Press Start and hold until the measured value is Td Duration of each voltage step
stable. (entry in Code-programming in seconds
range: 10...2550, default: 10 seconds
Note: Any present shunt capacitors may cause the
measurement to take longer. NOTE: When measuring in installations with connected
consumers it is important to make sure that consumers
4. Read the measured value. are separated from the network by at least one pole by
switching off the mains switch or removing the
In order to check GUARD for correct functioning press integrated fuse. If the required insulation resistance
DISPLAY and read the insulation measuring voltage. values are still not reached the devices must be
If the value displayed corresponds to the voltage separated from the network with all poles.
selected prior to measurement, the measurement is ok. If

REV. 0-8/01 1999, 2001 PdMA Corporation 4-101


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

WARNING! During measurement voltages up to 5750V Surge Voltage protector test


will occur. In conjunction with highly capacitive
in sta ll ati on s th ese can be m or t a ll y d an ge rous. At this test the measuring voltage also increases stair-
Overvoltage-sensitive devices like automatic controls, step, but with a defined duration of 3 steps/seconds.
microprocessor-controlled devices and similar should be This function serves for checking the correct function of
separated with all poles from the network to be sure voltage protectors (e.g. spark gaps, gaseous
measured prior to measurement. discharge tubes or metal oxide varistors).

1. Connect instrument to the installation or test


specimen with the supplied connecting leads.
Measuring procedure:
2. Before measuring define the nominal voltage (Uad).
Choose between two main functions; voltage stair-step Do this by pressing DISPLAY the nominal
method for insulation resistance measurements or surge voltage Uad can be called and set to any voltage
voltage protector test. between 50V and 5250V. Use the SELECT and
CHANGE button for this.
Insulation resistance measurements
3. Select function cont with the central switch.
In this function the measuring voltage for the insulation
resistance measurement increases stair-step.XXX CAUTION: The installation/test specimen must be set
potential free prior to measurement. In case of external
1. Connect instrument to the installation or test voltages above 50V measurement is blocked.
specimen with the supplied connecting leads.
4. After pressing the START button, a test for
2. Before measuring define the nominal voltage (U ad). applied voltage is carried out prior to measurement.
Do this by pressing DISPLAY the nominal If 50V are exceeded the measurement is blocked
voltage U ad can be called and set to any voltage and an acoustic warning is sounded.
between 50V and 5250V. Use the SELECT and
CHANGE button for this. 5. The measuring voltage rises from Ustart (= % of
U ad ; default 50%) to U stop (= %of U ad ; default:
3. Select function cont with the central switch. 125%) in the steps (N, Td).

CAUTION: The installation/test specimen must be set


6. An insulation current of 1mA interrupts the test
potential free prior to measurement. In case of external
prematurely and the latest applied measuring
voltages above 50V measurement is blocked.
voltage Uad (breakdown voltage) and by pressing
DISPLAY the insulation current IISO at U start is
4. Press the START button.
shown in the display.
5. The measuring voltage rises from Ustart (= % of
7. If the measurement ends without reaching an
U ad ; default 50%) to U stop (= %of U ad ; default:
insulation current of 1mA (e.g. because of too low
125%) in the steps (N,Td). adjusting Uad) or if the insulation current is higher
than 1mA already after the first step (e.g. because
6. An insulation current of 1mA (spurious of too high adjusting U ad ) an appropriate error
response) interrupts the test immediately and the message will be displayed because no breakdown
latest applied voltage Uad (breakdown voltage) and voltage could be determined.
by pressing DISPLAY the actual insulation
resistance RSIO is shown in the display. Modifying all settings with
7. If the measurement ends without reaching an personal code
insulation current of 1mA (normal case) the latest This function is used to permanently program all limits
applied measuring voltage U ad (=U stop ) and by and settings so they remain stored even after turning the
pressing DISPLAY the latest measured insulation instrument On/Off. This enables the instrument to be
resistance RISO is displayed. entirely customized.

REV. 0-8/01 1999, 2001 PdMA Corporation 4-102


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

The setting is only possible in the respective function 3. Entry is effected via the CHANGE or
(central switch position). SELECT buttons. Pressing DISPLAY


confirms the entry. The Code is now stored and C
The following settings can be modified: On appears on the display.

Default values: When confirming the display C On with DISPLAY


the first parameter of the selected measuring function is
RTG Measurement:USIO (with var only) displayed and can be changed with the CHANGE
or SELECT buttons.


U ISO LIMIT (with var only)500V
The modified value is stored with DISPLAY. Pressing
UISO 500, 1000, 2500, 5000VOn the START button quits the setting program.

RTG LIMIT<500 k The new parameters are now always used for the
measurements when turning on the unit in the future.
BuzzerOn
CAUTION: When changing the limits conforming to
Analog scaleresistance display specification wrong test results may be displayed.

Storing the code. Deleting the Code and settings

1. Press all four buttons simultaneously and turn 1. Press all four buttons simultaneously.
central switch from Off position to required
measuring function. 2. Turn central switch from Off position to any
measuring function.
C --- appears on the display.
C --- appears on the display.
2. Enter the desired Code number with Change and
Select. Any three-digit number may be entered. 3. Enter the Code number.

Caution: Once a Code has been stored any programmed 4. Entry is effected via the CHANGE or
values can only be changed after entering the SELECT buttons.

Code number. A Code once entered can only


be deleted or modified if it is known. An 5. Pressing DISPLAY confirms the entry.
unknown Code can only be read or deleted
by the manufacturer or user of the WinlSO C On appears on the display.
computer software.
During C On the C ode function can be
Therefore, please write your personal Code deactivated by pressing CHANGE. C Off is
in the space provided below: displayed.

Code ________ When this display is confirmed with DISPLAY the


user code and all stored limits are deleted and the
original default values are used once again.

After that a new Code number can be programmed and


used to set new parameters.

REV. 0-8/01 1999, 2001 PdMA Corporation 4-103


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

Symbols in the Display

Upkeep and Maintenance


If used and treated properly the unit is maintenance-free.
To clean the unit only use a wet cloth with a little soap
and water, do not use aggressive domestic flushing
agents or alcohol. Avoid strong detergents and solvents
(tri-chlorothene, etc.).

M ai n ten an ce w or k m a y on ly be c a rrie d o u t b y
appropriately instructed staff.

When carrying out repairs take particular care not to


change the construction features of the unit so as to
reduce safety, that spare parts are equivalent to original
parts in quality and that they are fitted professionally
(state of delivery).

WA R N I N G ! P r i o r t o ma i n t e n a n c e , r e p a i r, o r
replacement of parts or fuses the unit must be
disconnected from all voltage sources.

Power Supply. The instrument is equipped with a block


of storage batteries. If LO-BAT is displayed during a
measurement the batteries must be recharged.

Recalibration. Upon delivery this unit exceeds the


required specifications, in order to maintain this
condition we recommend having the instrum ent

REV. 0-8/01 1999, 2001 PdMA Corporation 4-104


PdMA PRODUCT SUPPORT MANUAL ADVANCED INSULATION SYSTEM

checked once a year. Please contact PdMA Technical Rad 1.00 min. appears.
Support at 813-621-6463.
3. Initiate the test by pressing the START button.
Calibration. The technical specifications can be tested
with a multimeter and reference resistances. The output The test can be terminated anytime by pressing the
voltage is to be calibrated at U N = 1000 /V. The START button again.
measuring range calibration can be effected at the final
value of the measuring range. Test duration is one minute. (ATTENTION: the
testing voltage is applied all of the time.) At the end
of the test the DA value is displayed. While the test
Service is in progress the remaining time can be seen from
This high-performance unit has been developed, the analog bar of the display and an audible signal
designed and manufactured by experts according to is issued as a warning.
state-of-the-art aspects and the DIN ISO 9000 quality
assurance system. 4. Pressing DISPLAY acts as a toggle between DA,
the latest measured value of RTG and the actual
If used to specification we guarantee proper functioning measuring voltage.
and calibration for one year from the day of purchase.
We will not be responsible for damages resulting from Procedure for Measuring the Polarization Index
improper use, inexpert treatment and operation or
overstressing. 1. Select measuring voltage using the rotary switch.
(0.5kV - 1 kV - 2.5 kV - 5 kV - var.)
If your unit is in need of repairs call PdMA Technical
Support at 813-621-6463 for a Returned Materials 2. Press the DISPLAY button twice.
Authorization (RMA) number before returning unit to
PdMA. The unit must be prepaid and packaged to Ip 10.00 min appears.
prevent damage while in transit to PdMAs facility.
Damage during shipment is the responsibility of the Use the SELECT and CHANGE buttons to
customer. change the test length if desired. If the measuring
time is different from 10 minutes, the display
NOTE: This section doesnt contain all of the detailed changes from IP (PI) to I (interval), because IP(PI)
information for all of the product types for clarity is only defined for a duration of 10 minutes by the
reasons and is therefore not able to present every regulations.
possible case concerning the setting up, operation or
maintenance. 3. Initiate the test by pressing the START button.

Should you require additional information or encounter The test can be terminated anytime by pressing the
particular problems which are not dealt with in enough START button again. The test lasts for ten
detail please contact PdMA Technical Support at 813- minutes (ATTENTION: The testing voltage is
621-6463. applied all of the time.) At the end of the test the
value IP (PI) is displayed. While the test is in
Appendix progress the remaining time can be seen from the
analog bar of the display and an audible signal is
Procedure for measuring the Dielectric Absorption
issued as a warning.
Ratio
4. The DISPLAY button acts a a toggle between PI,
1. Select the measuring voltage with rotary switch
the latest measured value of RTG, and the actual
(0.5kV - 1 kV - 2.5 kV - 5 kV - var.)
measuring voltage.
2. Press the DISPLAY button once.

REV. 0-8/01 1999, 2001 PdMA Corporation 4-105

You might also like