Installation Manual
VS111 Series
Note
This document and other information from Parker Hannin GmbH,
its subsidiaries, sales ofces and authorized distributors provide
product or system options for further investigation by users having
technical expertise. Before you select or use any product or system
it is important that you analyse all aspects of your application and
review the information concerning the product or system in the cur-
rent product catalogue. Due to the variety of operating conditions
and applications for these products or systems, the user, through
his own analysis and testing, is solely responsible for making the
nal selection of the products and systems and assuring that all
performance and safety requirements of the application are met.
The products are subject to change by Parker Hannin GmbH at
any time without notice.
IA UK VS111.INDD 19.06.06 RH
Features
Solenoid drive
Simple mounting direct to the valve
Standard voltage or current signal inputs
Control from PLC also possible
Temperature-independent solenoid current
Solenoid connection acc. EN 175301-803 (2+E)
Installation connection acc. EN 175201-804 (6+E)
Conformity to the European EMC standards (CE)
Block diagram
IA UK VS111.INDD 19.06.06 RH
VS 1 1 1 0 0 20
EMC
EN 50081-2 EN 55011
EN 50082-2 EN 61000-4-2 EN 61000-4-4
EN 61000-4-3 EN 61000-4-5
Characteristics
Supply voltage range [V] 18...32, ripple < 5%
Current consumption [A] 0.8
Power consumption (at 24V) [VA] 20
Input signal ranges
input voltage [V] 0...+10 / 0...+15, 100kOhm
input current [mA] 0...20 / 4...20, 500Ohm
Diagnostic output [V] 0.1 =
^ 0.2A
Reference output [V] 15 5% / max. 5mA
Solenoid output current max. [A] 0.8
Temperature drift of output current [%] < 2%
Adjustment ranges
Min [%] 0...50
Max [%] 0...100
Ramp time range [s] 0.1...8
Dither amplitude range [%] 0...90
Dither frequency [Hz] 40 / 80
Protection class IP65 mounted condition
Ambient temperature range [C] -20...60
Connection
Installation connector 6 + E, EN 175201-804
Solenoid connector 2 + E, EN 175301-803
Installation cross sections min. AWG 17
Cable outer dimension [mm] max. 11
Cable length [m] max. 50
Pre-fuse [A] 2.0 lag, DIN 41571
IA UK VS111.INDD 19.06.06 RH
Dither frequency B2
40 Hz -
80 Hz x
IA UK VS111.INDD 19.06.06 RH
Adjustment Instruction
Note:
For all following adjustments the potentiometer
"Dither signal" has to set fully counterclockwise
rst. The solenoid current measured at the diag-
nostic output should be observed (plug-in amplier
connected to the solenoid). Please take notice of
the adjustment sequence!
IA UK VS111.INDD 19.06.06 RH
Installation Guide
to Provision of Electromagnetic Compatibility
Power Supply
The utilized power supply has to comply with the EMC-standards (CE-sign, certicate of conformity).
Relays and solenoids operating from the same supply circuit has to be tted by surge protection ele-
ments.
Wiring Cable
The wiring cable between the control cabinet and the valve has to be shielded. The wiring has to be
installed from a 7wire cable that utilizes a common shielding and a cross section of min. AWG17. The
capacity should not exceed a value of approx. 130pF/m (wire/wire). The maximum cable length is 50 m.
No power current lines may be placed in parallel to the valve's wiring cables. The cable shield has to be
connected to the connector pin 2. The earth pin of the connector has to be installed as separate wire
within the cable to the cabinet and should there be connected to the Earth Ground potential.
Example
IA UK VS111.INDD 19.06.06 RH