Bulletin HY11-5715-577/UK

Installation Manual
VS111 Series

Plug-In Amplier for


Proportional Valves

Parker Hannin GmbH


Hydraulic Controls Division
Gutenbergstr. 38
41564 Kaarst, Germany
Tel.: +49-181 99 44 43 0
Fax: +49-2131-513-230
E-mail: infohcd@parker.com
Copyright 2002, Parker Hannin GmbH
Plug-In Amplier
Installation Manual VS111 Series

Note
This document and other information from Parker Hannin GmbH,
its subsidiaries, sales ofces and authorized distributors provide
product or system options for further investigation by users having
technical expertise. Before you select or use any product or system
it is important that you analyse all aspects of your application and
review the information concerning the product or system in the cur-
rent product catalogue. Due to the variety of operating conditions
and applications for these products or systems, the user, through
his own analysis and testing, is solely responsible for making the
nal selection of the products and systems and assuring that all
performance and safety requirements of the application are met.
The products are subject to change by Parker Hannin GmbH at
any time without notice.

IA UK VS111.INDD 19.06.06 RH

2 Parker Hannin GmbH


Hydraulic Controls Division
Plug-In Amplier
Installation Manual VS111 Series
The plug-in amplier VS111 is used to control
proportional pressure, directional control, and
ow valves.
The amplier is mounted directly on the propor-
tional solenoid and secured by a central screw.

It supplies a drive current for one proportional so-


lenoid. This current is proportional to the command
signal at the amplier input. In conjunction with a
proportional valve this allows an innite adjustment
of a pressure or ow rate.

Features

Solenoid drive
Simple mounting direct to the valve
Standard voltage or current signal inputs
Control from PLC also possible
Temperature-independent solenoid current
Solenoid connection acc. EN 175301-803 (2+E)
Installation connection acc. EN 175201-804 (6+E)
Conformity to the European EMC standards (CE)

Block diagram

IA UK VS111.INDD 19.06.06 RH

3 Parker Hannin GmbH


Hydraulic Controls Division
Plug-In Amplier
Installation Manual VS111 Series
Ordering Code

VS 1 1 1 0 0 20

Valve Valve type Design


amplier Series

Code Valve type


0 without*
1 Proportional ow valve
2 Proportional DC valve *The versions acc. codes 1...8 will be shipped factory set.
8 Proportional pressure valve The version Code 0 needs to be set to the connected valve's
characteristics.
Attention: Installation connector has to be ordered separately (order no. HR 2150 2072).

EMC

EN 50081-2 EN 55011
EN 50082-2 EN 61000-4-2 EN 61000-4-4
EN 61000-4-3 EN 61000-4-5

Characteristics
Supply voltage range [V] 18...32, ripple < 5%
Current consumption [A] 0.8
Power consumption (at 24V) [VA] 20
Input signal ranges
input voltage [V] 0...+10 / 0...+15, 100kOhm
input current [mA] 0...20 / 4...20, 500Ohm
Diagnostic output [V] 0.1 =
^ 0.2A
Reference output [V] 15 5% / max. 5mA
Solenoid output current max. [A] 0.8
Temperature drift of output current [%] < 2%
Adjustment ranges
Min [%] 0...50
Max [%] 0...100
Ramp time range [s] 0.1...8
Dither amplitude range [%] 0...90
Dither frequency [Hz] 40 / 80
Protection class IP65 mounted condition
Ambient temperature range [C] -20...60
Connection
Installation connector 6 + E, EN 175201-804
Solenoid connector 2 + E, EN 175301-803
Installation cross sections min. AWG 17
Cable outer dimension [mm] max. 11
Cable length [m] max. 50
Pre-fuse [A] 2.0 lag, DIN 41571

IA UK VS111.INDD 19.06.06 RH

4 Parker Hannin GmbH


Hydraulic Controls Division
Plug-In Amplier
Installation Manual VS111 Series
Connection Examples
Command value given by external signal Command value given by potentiometer

Selection and Adjustment Options


Com. signal B1 B3 B4 B5
0...10V x - 2-3 x
0...15V - - 2-3 x
0...20mA x x 2-3 x
4...20mA x x 1-2 -

Dither frequency B2
40 Hz -
80 Hz x

Connection Arrangement Installation Connector

IA UK VS111.INDD 19.06.06 RH

5 Parker Hannin GmbH


Hydraulic Controls Division
Plug-In Amplier
Installation Manual VS111 Series
Dimensions

Adjustment Instruction
Note:
For all following adjustments the potentiometer
"Dither signal" has to set fully counterclockwise
rst. The solenoid current measured at the diag-
nostic output should be observed (plug-in amplier
connected to the solenoid). Please take notice of
the adjustment sequence!

1. MIN current setting 3. Ramp time setting


-Command signal zero (0V/0mA) - Adjust the response time by variation
-Turn the potentiometer "MIN current" of the potentiometers "Ramp up" and
clockwise, until the required valve "Ramp down", until the required transi-
adjustment is reached. tion behaviour is
reached.
2. MAX current setting
-Command signal maximum 4. Dither adjustment
(10V/15V/20mA) - Select dither frequency aac. solenoid/
-Turn the potentiometer "MAX valve type,
current", until the required valve with jumper B2 = 80 Hz
adjustment is reached. without jumper B2 = 40 Hz
- Feed in approx. 40% command signal.
- Turn the potentiometer "Dither signal"
max. clockwise, until an oscillating is
audible within the hydraulic system.

Direction to trouble shooting


The required max. current can just keep constant until the condition
Supply voltage (V) 2V
Max current (A) =
actual solenoid spool resistance (Ohms)*
will be keeped. This means for example, that if a solenoid spool of 24V/0.8A will be connected to the
amplier, the supply voltage should reach approx. 30V.
*the resistance of the spool increases by warming for up to 40%.

IA UK VS111.INDD 19.06.06 RH

6 Parker Hannin GmbH


Hydraulic Controls Division
Plug-In Amplier
Installation Manual VS111 Series

Installation Guide
to Provision of Electromagnetic Compatibility

Power Supply

The utilized power supply has to comply with the EMC-standards (CE-sign, certicate of conformity).
Relays and solenoids operating from the same supply circuit has to be tted by surge protection ele-
ments.

Wiring Cable

The wiring cable between the control cabinet and the valve has to be shielded. The wiring has to be
installed from a 7wire cable that utilizes a common shielding and a cross section of min. AWG17. The
capacity should not exceed a value of approx. 130pF/m (wire/wire). The maximum cable length is 50 m.
No power current lines may be placed in parallel to the valve's wiring cables. The cable shield has to be
connected to the connector pin 2. The earth pin of the connector has to be installed as separate wire
within the cable to the cabinet and should there be connected to the Earth Ground potential.

Example

IA UK VS111.INDD 19.06.06 RH

7 Parker Hannin GmbH


Hydraulic Controls Division