You are on page 1of 18

SUBSTATION AUTOMATION SOLUTIONS

END CUSTOMER : JSPL, ANGUL


PROJECT : 220kV GIS CRP & SAS MSDS-1 & MSDS-2
DIRECT CUSTOMER : ALSTOM SOLUTIONS

TECHNICAL OFFER

GRID
Ref: OP1209387545
Date:16/09/2014

CONTACT DETAILS

Author: Ram Sofia Tel:044-22648479


Fax:044-2264 1131 Email:ram.sofia@alstom.com
Address :ALSTOM T&D India Ltd, 19/1, GST Road, Pallavaram, Chennai-43

Reference : SASTEC- 2 OP1209387545


Version : C
Date 16/09/2014

Distribution : Limited to JSPL


Confidentiality level : Confidential
Reproduction : Unauthorised externally to distribution list above

TABLE OF CONTENT

1.PROTECTION & CONTROL EQUIPMENT LIST 3

2.PANEL SETS/ DESCRIPTION 4

3. COMMENTS AND CLARIFICATIONS 15

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 2/18
Ref: OP1209387545
Date:16/09/2014

1.PROTECTION & CONTROL EQUIPMENT LIST

SL CIRCUIT TOTAL QTY


CIRCUIT NAME
NO

A 220KV GIS MSDS-1 MSDS-2


1A 220KV LINE BAY PROTECTION PANEL 2 SETS -

1B 220KV LINE BAY PROTECTION PANEL - 2 SETS

2 220KV 160MVA TRANSFORMER BAY PROTECTION PANEL 8 SETS 7 SETS

3 220KV BUS COUPLER PROTECTION PANEL 1 SET 1 SET

4A 220KV BUSBAR PROTECTION SYSTEM (DUPLICATED) 1 SET -

4B 220KV BUSBAR PROTECTION SYSTEM (DUPLICATED) - 1 SET


220KV INCOMING FEEDER (AS PART OF BUS EXTN FROM
5 2 SETS -
EXISITNG SYTEM) PROTECTION PANEL
B SAS
1 SCADA EQUIPMENT LIST (MSDS-1) 1 SET -

2 SCADA EQUIPMENT LIST (MSDS-2) - 1 SET

C TRAINING 1 LOT
D SPARES 1 SET
1 MANDATORY SPARES 1 SET 1 SET

2 RECOMMENDED SPARES 1 SET 1 SET

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 3/18
Ref: OP1209387545
Date:16/09/2014

2.PANELS/SETS DESCRIPTION

A. 220KV GIS

QTY/
ITEM TYPE DESIGNATION
CKT

1A 220KV LINE BAY PROTECTION PANEL (MSDS-1)

SIMPLEX PANEL 1 SET

MICOM C264 BAY CONTROL UNIT 1

MICOM P543 NUMERICAL MAIN-1 LINE DIFFERENTIAL PROTECTION RELAY WITH FO PORT (ST
CONNECTORS) SUITABLE FOR DISTANCE UPTO 10 KMs 1
(MSDS-1 END) 87L1
ABB / EQVT NUMERICAL MAIN-2 LINE DIFFERENTIAL PROTECTION RELAY WITH FO PORT
SUITABLE FOR DISTANCE UPTO 10 KMs 1
(MSDS-1 END) 87L2
RA 331 / NUMERICAL DISTURBANCE RECORDER WITH 8 ANALOG CHANNELS & 16 DIGITAL
1
RPV311 CHANNELS
50LBB CB FAILURE PROTECTION INBUILT IN MICOM P74x BUSBAR PERIPHERAL RELAY -

MVAXM31 TRIP CIRCUIT SUPERVISION RELAY (95) 6

MVAJM HIGH SPEED TRIPPING RELAY (86) 2

MVAJM HIGH SPEED TRIPPING RELAY FOR A/R LOCKOUT 1

MVAJM14 VOLTAGE SELECTION RELAY 2

MVAAM21 AUXILIARY RELAY FOR SCHEME REQUIREMENT 1 SET

MVAAM AUXILIARY RELAY FOR CB TROUBLES 1 SET

ODS CIRCUIT BREAKER SELECTOR SWITCH 1

MVAAM11 AUXILIARY RELAY FOR DC SUPERVISION 2

MPG TEST BLOCK 4

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 4/18
Ref: OP1209387545
Date:16/09/2014

QTY/
ITEM TYPE DESIGNATION
CKT

1B 220KV LINE BAY PROTECTION PANEL (MSDS-2)

SIMPLEX PANEL 1 SET

MICOM C264 BAY CONTROL UNIT 1

MICOM P543 NUMERICAL MAIN-1 LINE DIFFERENTIAL PROTECTION RELAY WITH FO PORT (ST
CONNECTORS) SUITABLE FOR DISTANCE UPTO 10 KMs 1
(MSDS-2 END) 87L1
ABB / EQVT NUMERICAL MAIN-2 LINE DIFFERENTIAL PROTECTION RELAY WITH FO PORT
SUITABLE FOR DISTANCE UPTO 10 KMs 1
(MSDS-2 END) 87L2
RA 331 / NUMERICAL DISTURBANCE RECORDER WITH 8 ANALOG CHANNELS & 16 DIGITAL
1
RPV311 CHANNELS
50LBB CB FAILURE PROTECTION INBUILT IN MICOM P74x BUSBAR PERIPHERAL RELAY -

MVAXM31 TRIP CIRCUIT SUPERVISION RELAY (95) 6

MVAJM HIGH SPEED TRIPPING RELAY (86) 2

MVAJM HIGH SPEED TRIPPING RELAY FOR A/R LOCKOUT 1

MVAJM14 VOLTAGE SELECTION RELAY 2

MVAAM21 AUXILIARY RELAY FOR SCHEME REQUIREMENT 1 SET

MVAAM AUXILIARY RELAY FOR CB TROUBLES 1 SET

ODS CIRCUIT BREAKER SELECTOR SWITCH 1

MVAAM11 AUXILIARY RELAY FOR DC SUPERVISION 2

MPG TEST BLOCK 4

QTY/
ITEM TYPE DESIGNATION
CKT

2 220KV 160MVA TRANSFORMER (220/34.5/33KV) BAY PROTECTION PANEL

SIMPLEX PANEL 1 SET

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 5/18
Ref: OP1209387545
Date:16/09/2014

QTY/
ITEM TYPE DESIGNATION
CKT

MICOM C264 BAY CONTROL UNIT 1

MICOM P643 DIFFERENTIAL RELAY WITH FOLLOWING INBUILT PROTECTIONS:


1) OVERFLUXING PROTECTION 99 1
2) THERMAL OVERLOAD 49
3) STANDBY EARTH FAULT 51G HV
MICOMP14x NUMERICAL OVERCURRENT & EARTH FAULT PROTECTION RELAY FOR HV SIDE
1
50/51, 50N/51N, 64R
MICOMP14x NUMERICAL OVERCURRENT & EARTH FAULT PROTECTION RELAY FOR LV 33KV
1
SIDE - 50/51, 50N/51N
IN SCOPE OF
1) NUMERICAL OVERCURRENT & EARTH FAULT PROTECTION RELAY FOR
33KV
33KV SIDE 51G, 64R -
SWITCHGEAR
2) MFM
SUPPLIER
MICOMP14x NUMERICAL EARTH FAULT & OVERLOAD PROTECTION RELAY FOR UNLOADED
TERTIARY (TV) SIDE 1
50N/51N, 49
50LBB CB FAILURE PROTECTION INBUILT IN MICOM P74x BUSBAR PERIPHERAL RELAY -

MVAJM HIGH SPEED TRIPPING RELAY (86) 2

MVAXM31 TRIP CIRCUIT SUPERVISION (95) 6

MVAAM AUXILIARY RELAY FOR CB TROUBLES 1 SET

MVAAM23 AUXILIARY RELAYS FOR TRANSFORMER TROUBLE 5

MVAAM11 AUXILIARY RELAY FOR DC SUPERVISION 2

MVAJM14 VOLTAGE SELECTION RELAY 2

ODS CB CONTROL SWITCH 1

MPG TEST BLOCK 2

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 6/18
Ref: OP1209387545
Date:16/09/2014

QTY/
ITEM TYPE DESIGNATION
CKT

3 220KV BUS COUPLER BAY PROTECTION PANEL

SIMPLEX PANEL 1 SET

MICOM C264 BAY CONTROL UNIT 1

MICOMP14x NUMERICAL OVERCURRENT & EARTH FAULT PROTECTION RELAY


1
50/51, 50N/51N
50LBB CB FAILURE PROTECTION INBUILT IN MICOM P74x BUSBAR PERIPHERAL RELAY -

MVAJM HIGH SPEED TRIPPING RELAY (86) 2

MVAXM31 TRIP CIRCUIT SUPERVISION (95) 6

MVAAM AUXILIARY RELAY FOR CB TROUBLES 1 SET

MVAJM14 VOLTAGE SELECTION RELAY 2

MVAAM11 AUXILIARY RELAY FOR DC SUPERVISION 2

ODS CB CONTROL SWITCH 1

MPG TEST BLOCK 1

ITEM DESIGNATION QTY

4A 220KV BUSBAR PROTECTION SYSTEM (MSDS-1)

SIMPLEX PANEL 1

MICOMP746 NUMERICAL CENTRALISED LOW IMPEDANCE BUSBAR PROTECTION RELAY WITH


(3 BOX) MAIN & CHECK ZONE (MAIN-I 87BB1) SUITABLE FOR 18 BAYS (14 BAYS UNDER 1 SET
PRESENT SCOPE + PROVISION TO ACCEPT UPTO 4 ADDLN FUTURE BAYS)
MICOMP746 NUMERICAL CENTRALISED LOW IMPEDANCE BUSBAR PROTECTION RELAY WITH
(3 BOX) MAIN & CHECK ZONE (MAIN-II 87BB1) SUITABLE FOR 18 BAYS (14 BAYS UNDER 1 SET
PRESENT SCOPE + PROVISION TO ACCEPT UPTO 4 ADDLN FUTURE BAYS)
MICOMP743 NUMERICAL PERIPHERAL UNIT FOR INTEGRATION WITH EXISTING MSDS-I AIS
2
MAIN-1 SIDE
MICOMP743 NUMERICAL PERIPHERAL UNIT FOR INTEGRATION WITH EXISTING MSDS-I AIS
2
MAIN-2 SIDE

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 7/18
Ref: OP1209387545
Date:16/09/2014

ITEM DESIGNATION QTY

MVAJM BUSBAR TRIPPING RELAY 14

ODS CONTROL SWITCH IN/OUT 2

MVAAM11 AUXILIARY RELAY FOR DC SUPERVISION 2

MPG TEST BLOCK 14

ITEM DESIGNATION QTY

4B 220KV BUSBAR PROTECTION SYSTEM (MSDS-2)

SIMPLEX PANEL 1

MICOMP746 NUMERICAL CENTRALISED LOW IMPEDANCE BUSBAR PROTECTION RELAY WITH


(3 BOX) MAIN & CHECK ZONE (MAIN-I 87BB1) SUITABLE FOR 18 BAYS (11 BAYS UNDER 1 SET
PRESENT SCOPE + PROVISION TO ACCEPT UPTO 7 ADDLN FUTURE BAYS)
MICOMP746 NUMERICAL CENTRALISED LOW IMPEDANCE BUSBAR PROTECTION RELAY WITH
(3 BOX) MAIN & CHECK ZONE (MAIN-II 87BB1) SUITABLE FOR 18 BAYS (11 BAYS UNDER 1 SET
PRESENT SCOPE + PROVISION TO ACCEPT UPTO 7 ADDLN FUTURE BAYS)
MVAJM BUSBAR TRIPPING RELAY 11

ODS CONTROL SWITCH IN/OUT 2

MVAAM11 AUXILIARY RELAY FOR DC SUPERVISION 2

MPG TEST BLOCK 11

QTY/
ITEM TYPE DESIGNATION
CKT

220KV INCOMING FEEDER (AS PART OF BUS EXTN FROM EXISITNG


5
SYTEM) PROTECTION PANEL (MSDS-1)
SIMPLEX PANEL 1 SET

MICOM C264 BAY CONTROL UNIT 1

MICOMP14x NUMERICAL DIRECTIONAL OVERCURRENT & EARTH FAULT PROTECTION RELAY 1

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 8/18
Ref: OP1209387545
Date:16/09/2014

QTY/
ITEM TYPE DESIGNATION
CKT

67/67N,25

MICOMP14x NUMERICAL OVER / UNDER VOLTAGE PROTECTION RELAY


1
27/59/DR
50LBB CB FAILURE PROTECTION INBUILT IN MICOM P74x BUSBAR PERIPHERAL RELAY -

MVAXM31 TRIP CIRCUIT SUPERVISION RELAY (95) 6

MVAJM HIGH SPEED TRIPPING RELAY (86) 2

MVAJM14 VOLTAGE SELECTION RELAY 2

MVAAM AUXILIARY RELAY FOR CB TROUBLES 1 SET

ODS CIRCUIT BREAKER SELECTOR SWITCH 1

MVAAM11 AUXILIARY RELAY FOR DC SUPERVISION 2

MPG TEST BLOCK 2

B1. SCADA EQUIPMENT LIST MSDS-1


BAY COMPUTER UNITS AT MSDS-1:

SCOPE OF SUPPLY DESCRIPTION


ITEM DESCRIPTION
QTY
BAY CONTROL UNIT FOR
1- 4
LINE BAY
1-1. MICOM C264 EACH WITH SINGLE UNIT
4U, 19 RACK (80 TE) WITH FRONT PANEL DIGITAL
MIMIC , 220 VDC POWER SUPPLY , CPU WITH 2 LEGACY
1 BASE RACK 1
BUS LINKS TO CONNECT UP TO 16 PROTECTIONS AND
IEDS PER LINK
2 ADDITIONAL LEGACY BUS LINKS TO CONNECT UP TO
2 CPU200 ADD 1
16 PROTECTIONS AND IEDS PER LINK
3 DIU200 3 16 DI BOARD, 220VDC
4 DOU200 2 10 DO BOARD
4 I AND 5U DIRECT ACQUISITION BOARD FROM CT/VT
5 TMU220 1
PROVIDING FUNCTION ANSI 25 AND ANSI 90

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 9/18
Ref: OP1209387545
Date:16/09/2014

SCOPE OF SUPPLY DESCRIPTION


ITEM DESCRIPTION
QTY

BAY CONTROL UNIT FOR


2- 8
TRAFO BAY
2-1. MICOM C264 EACH WITH SINGLE UNIT
4U, 19 RACK (80 TE) WITH FRONT PANEL DIGITAL
MIMIC , 220 VDC POWER SUPPLY , CPU WITH 2 LEGACY
1 BASE RACK 1
BUS LINKS TO CONNECT UP TO 16 PROTECTIONS AND
IEDS PER LINK
2 ADDITIONAL LEGACY BUS LINKS TO CONNECT UP TO
2 CPU200 ADD 1
16 PROTECTIONS AND IEDS PER LINK
3 DIU200 4 16 DI BOARD, 220VDC
4 DOU200 3 10 DO BOARD
4 I AND 5U DIRECT ACQUISITION BOARD FROM CT/VT
5 TMU220 1
PROVIDING FUNCTION ANSI 25 AND ANSI 90
6 AIU210 1 8 AI BOARD IN CURRENT LOW LEVEL

BAY CONTROL UNIT FOR BC


3- 1
BAY
3-1. MICOM C264 EACH WITH SINGLE UNIT
4U, 19 RACK (80 TE) WITH FRONT PANEL DIGITAL
MIMIC , 220 VDC POWER SUPPLY , CPU WITH 2 LEGACY
1 BASE RACK 1
BUS LINKS TO CONNECT UP TO 16 PROTECTIONS AND
IEDS PER LINK
2 ADDITIONAL LEGACY BUS LINKS TO CONNECT UP TO
2 CPU200 ADD 1
16 PROTECTIONS AND IEDS PER LINK
3 DIU200 2 16 DI BOARD, 220VDC
4 DOU200 1 10 DO BOARD
4 I AND 5U DIRECT ACQUISITION BOARD FROM CT/VT
5 TMU220 1
PROVIDING FUNCTION ANSI 25 AND ANSI 90

STN. AUX. BAY CONTROL


4- 2 MSDS-1
UNIT
4-1. MICOM C264 EACH WITH SINGLE UNIT
4U, 19 RACK (80 TE) WITH FRONT PANEL DIGITAL
MIMIC , 220 VDC POWER SUPPLY , CPU WITH 2 LEGACY
1 BASE RACK 1
BUS LINKS TO CONNECT UP TO 16 PROTECTIONS AND
IEDS PER LINK

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 10/18
Ref: OP1209387545
Date:16/09/2014

SCOPE OF SUPPLY DESCRIPTION


ITEM DESCRIPTION
QTY
2 ADDITIONAL LEGACY BUS LINKS TO CONNECT UP TO
2 CPU200 ADD 1
16 PROTECTIONS AND IEDS PER LINK
3 DIU200 5 16 DI BOARD, 220VDC
4 AIU210 2 8 AI BOARD IN CURRENT LOW LEVEL

CENTRAL CONTROL ROOM EQUIPMENTS (SERVER / WORKSTATIONS / GATEWAYS) MSDS-1

ITEM DESCRIPTION QTY SCOPE OF SUPPLY DESCRIPTION


1- HMI MAIN & REDUNDANT 2 HMI MAIN & REDUNDANT
1-1. INDUSTRIAL PC
INDUSTRIAL PC, PENTIUM IV 3.2GHZ, 2GB DDRAM-400MHZ,
1 BASE ELEMENT HD 250GB, CD WRITER 52X IDE, AUXILIARY SUPPLY 90-
264VAC, ETHERNET 100MBS CONNECTION
2 KEYBOARD AND MOUSE QWERTY 102 KEYBOARD + OPTICAL MOUSE
3 SCREEN FLAT LCD DISPLAY 21"
4 DS AGILE LICENCE

2- EWS 3 EWS-1 & 2, METERING


2-1. INDUSTRIAL PC
INDUSTRIAL PC, PENTIUM IV 3.2GHZ, 2GB DDRAM-400MHZ,
1 BASE ELEMENT HD 250GB, CD WRITER 52X IDE, AUXILIARY SUPPLY 90-
264VAC, ETHERNET 100MBS CONNECTION
2 KEYBOARD AND MOUSE QWERTY 102 KEYBOARD + OPTICAL MOUSE
3 SCREEN FLAT LCD DISPLAY 21"
4 DS AGILE LICENCE

3- DATA CONCENTRATOR 1
3-1. C264 / DAP100 FOR MFM INTEGRATION FROM 220KV & 33KV METERS

GIS CONTROL BUILDING EQUIPMENTS (SERVER / WORKSTATIONS / GATEWAYS) MSDS-1

ITEM DESCRIPTION QTY SCOPE OF SUPPLY DESCRIPTION


1- OWS 1 OWS-1

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 11/18
Ref: OP1209387545
Date:16/09/2014

ITEM DESCRIPTION QTY SCOPE OF SUPPLY DESCRIPTION


1-1. INDUSTRIAL PC
INDUSTRIAL PC, PENTIUM IV 3.2GHZ, 2GB DDRAM-400MHZ,
1 BASE ELEMENT HD 250GB, CD WRITER 52X IDE, AUXILIARY SUPPLY 90-
264VAC, ETHERNET 100MBS CONNECTION
2 KEYBOARD AND MOUSE QWERTY 102 KEYBOARD + OPTICAL MOUSE
3 SCREEN FLAT LCD DISPLAY 21"
4 DS AGILE LICENCE

2- EWS 1 EWS-1
2-1. INDUSTRIAL PC
INDUSTRIAL PC, PENTIUM IV 3.2GHZ, 2GB DDRAM-400MHZ,
1 BASE ELEMENT HD 250GB, CD WRITER 52X IDE, AUXILIARY SUPPLY 90-
264VAC, ETHERNET 100MBS CONNECTION
2 KEYBOARD AND MOUSE QWERTY 102 KEYBOARD + OPTICAL MOUSE
3 SCREEN FLAT LCD DISPLAY 21"
4 DS AGILE LICENCE

3- GATEWAY 1 TO MSDS-1 EXISTING SAS INTEGRATION

ANCILARY EQUIPMENT

ITEM DESCRIPTION SCOPE OF SUPPLY


QUANTITY
DESCRIPTION
LAN SWITCH FOR BAY LEVEL FOR 220KV CRP, 33KV & RUGGEDCOM / RAD /
1 SET
1 11KV SWGR, UHF SENSORS HARSHMANN / EQVT

RUGGEDCOM / RAD /
LAN SWITCH FOR STATION LEVEL 1 SET
2 HARSHMANN / EQVT

3 LINE INTERFACE UNIT - 2 CABLE ENTRY, 24 PORTS 2 NOS. D LINK /EQVT

A3 COLOR LASER JET PRINTER (REPORT & DR PRINTING)


4 @ CENTRAL CONTROL ROOM 1 NO HP/CANON/EQVT

5 A4 COLOR LASER JET PRINTER @ GIS CONTROL ROOM 1 NO HP/CANON/EQVT

DOT MATRIX PRINTER (ALARM & EVENTS PRINTING) @


6 GIS CONTROL ROOM 1 NO HP/CANON/EQVT

7 FO CABLE FOR SAS INTERNAL NETWORKING 1 LOT REPUTED MAKE

8 FO PATCH CORD 1 LOT PRESTON / EQVT

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 12/18
Ref: OP1209387545
Date:16/09/2014

9 RS485 CABLE 1 LOT REPUTED MAKE

10 RJ45 CABLE - CAT6 UTP 1 LOT REPUTED MAKE

11 GPS WITH RECEIVER, ANTENNA, CO-AXIAL CABLE 1 NO. MASIBUS / EQVT

12 LAPTOP 1 NO. DELL / HP / EQVT

13 LVS 67 WITH 4 CUBES SINGLE LAMP 1 NO. DELTA / PLANNAR / EQVT

14 FURNITURE 1 SET. HARMONY / EQVT

B2. SCADA EQUIPMENT LIST MSDS-2

BAY COMPUTER UNITS AT MSDS-2:

SCOPE OF SUPPLY DESCRIPTION


ITEM DESCRIPTION
QTY
BAY CONTROL UNIT FOR
1- 2
LINE BAY
1-1. MICOM C264 EACH WITH SINGLE UNIT
4U, 19 RACK (80 TE) WITH FRONT PANEL DIGITAL
MIMIC , 220 VDC POWER SUPPLY , CPU WITH 2 LEGACY
1 BASE RACK 1
BUS LINKS TO CONNECT UP TO 16 PROTECTIONS AND
IEDS PER LINK
2 ADDITIONAL LEGACY BUS LINKS TO CONNECT UP TO
2 CPU200 ADD 1
16 PROTECTIONS AND IEDS PER LINK
3 DIU200 3 16 DI BOARD, 220VDC
4 DOU200 2 10 DO BOARD
4 I AND 5U DIRECT ACQUISITION BOARD FROM CT/VT
5 TMU220 1
PROVIDING FUNCTION ANSI 25 AND ANSI 90

BAY CONTROL UNIT FOR


2- 7
TRAFO BAY
2-1. MICOM C264 EACH WITH SINGLE UNIT
4U, 19 RACK (80 TE) WITH FRONT PANEL DIGITAL
MIMIC , 220 VDC POWER SUPPLY , CPU WITH 2 LEGACY
1 BASE RACK 1
BUS LINKS TO CONNECT UP TO 16 PROTECTIONS AND
IEDS PER LINK
2 ADDITIONAL LEGACY BUS LINKS TO CONNECT UP TO
2 CPU200 ADD 1
16 PROTECTIONS AND IEDS PER LINK
3 DIU200 4 16 DI BOARD, 220VDC
4 DOU200 3 10 DO BOARD
5 TMU220 1 4 I AND 5U DIRECT ACQUISITION BOARD FROM CT/VT

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 13/18
Ref: OP1209387545
Date:16/09/2014

SCOPE OF SUPPLY DESCRIPTION


ITEM DESCRIPTION
QTY
PROVIDING FUNCTION ANSI 25 AND ANSI 90
6 AIU210 1 8 AI BOARD IN CURRENT LOW LEVEL

BAY CONTROL UNIT FOR BC


3- 1
BAY
3-1. MICOM C264 EACH WITH SINGLE UNIT
4U, 19 RACK (80 TE) WITH FRONT PANEL DIGITAL
MIMIC , 220 VDC POWER SUPPLY , CPU WITH 2 LEGACY
1 BASE RACK 1
BUS LINKS TO CONNECT UP TO 16 PROTECTIONS AND
IEDS PER LINK
2 ADDITIONAL LEGACY BUS LINKS TO CONNECT UP TO
2 CPU200 ADD 1
16 PROTECTIONS AND IEDS PER LINK
3 DIU200 2 16 DI BOARD, 220VDC
4 DOU200 1 10 DO BOARD
4 I AND 5U DIRECT ACQUISITION BOARD FROM CT/VT
5 TMU220 1
PROVIDING FUNCTION ANSI 25 AND ANSI 90

STN. AUX. BAY CONTROL


4- 2 MSDS-2
UNIT
4-1. MICOM C264 EACH WITH SINGLE UNIT
4U, 19 RACK (80 TE) WITH FRONT PANEL DIGITAL
MIMIC , 220 VDC POWER SUPPLY , CPU WITH 2 LEGACY
1 BASE RACK 1
BUS LINKS TO CONNECT UP TO 16 PROTECTIONS AND
IEDS PER LINK
2 ADDITIONAL LEGACY BUS LINKS TO CONNECT UP TO
2 CPU200 ADD 1
16 PROTECTIONS AND IEDS PER LINK
3 DIU200 5 16 DI BOARD, 220VDC
4 AIU210 2 8 AI BOARD IN CURRENT LOW LEVEL

CENTRAL CONTROL EQUIPMENTS (SERVER / WORKSTATIONS / GATEWAYS) MSDS-2

ITEM DESCRIPTION QTY SCOPE OF SUPPLY DESCRIPTION


1- HMI MAIN & REDUNDANT 2 HMI MAIN & REDUNDANT
1-1. INDUSTRIAL PC
1 BASE ELEMENT INDUSTRIAL PC, PENTIUM IV 3.2GHZ, 2GB DDRAM-400MHZ,

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 14/18
Ref: OP1209387545
Date:16/09/2014

ITEM DESCRIPTION QTY SCOPE OF SUPPLY DESCRIPTION


HD 250GB, CD WRITER 52X IDE, AUXILIARY SUPPLY 90-
264VAC, ETHERNET 100MBS CONNECTION
2 KEYBOARD AND MOUSE QWERTY 102 KEYBOARD + OPTICAL MOUSE
3 SCREEN FLAT LCD DISPLAY 21"
4 DS AGILE LICENCE

2- EWS 3 EWS-1 & 2, METERING


2-1. INDUSTRIAL PC
INDUSTRIAL PC, PENTIUM IV 3.2GHZ, 2GB DDRAM-400MHZ,
1 BASE ELEMENT HD 250GB, CD WRITER 52X IDE, AUXILIARY SUPPLY 90-
264VAC, ETHERNET 100MBS CONNECTION
2 KEYBOARD AND MOUSE QWERTY 102 KEYBOARD + OPTICAL MOUSE
3 SCREEN FLAT LCD DISPLAY 21"
4 DS AGILE LICENCE

3- DATA CONCENTRATOR 1
3-1. C264 / DAP100 FOR MFM INTEGRATION FROM 220KV & 33KV METERS

4- GATEWAY 1 TO MSDS-1 SAS INTEGRATION

ANCILIARY EQUIPMENT

ITEM DESCRIPTION SCOPE OF SUPPLY


QUANTITY
DESCRIPTION
LAN SWITCH FOR BAY LEVEL FOR 220KV CRP, 33KV & RUGGEDCOM / RAD /
1 SET
1 11KV SWGR HARSHMANN / EQVT

RUGGEDCOM / RAD /
LAN SWITCH FOR STATION LEVEL 1 SET
2 HARSHMANN / EQVT

3 LINE INTERFACE UNIT - 2 CABLE ENTRY, 24 PORTS 2 NOS. D LINK /EQVT

4 A3 COLOR LASER JET PRINTER (REPORT & DR PRINTING) 1 NO HP/CANON/EQVT

5 FO CABLE FOR SAS INTERNAL NETWORKING 1 LOT REPUTED MAKE

6 FO PATCH CORD 1 LOT PRESTON / EQVT

7 RS485 CABLE 1 LOT REPUTED MAKE

8 RJ45 CABLE - CAT6 UTP 1 LOT REPUTED MAKE

9 LAPTOP 1 NO. DELL / HP / EQVT

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 15/18
Ref: OP1209387545
Date:16/09/2014

10 LVS 67 WITH 4 CUBES SINGLE LAMP 1 NO. DELTA / PLANNAR / EQVT

11 FURNITURE 1 SET. HARMONY / EQVT

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 16/18
Ref: OP1209387545
Date:16/09/2014

C. TRAINING

ITEM DESCRIPTION
QUANTITY SCOPE OF SUPPLY DESCRIPTION
BRIEF INTRODUCTION, HANDS ON
TRAINING FOR 4 ENGINEERS AT OUR FACTORY TRAINING ON OUR PRODUCTS OFFERED
1 PREMISES 5 MANDAYS FOR 5 MANDAYS

D. SPARES

QTY /
ITEM DESIGNATION MAKE SITE
MSDS

1 MANDATORY SPARES FOR 2 YEARS OPERATION

MVAJM HIGH SPEED TRIP RELAYS ALSTOM 1 NO.

MVAAM21 AUXILIARY RELAY ALSTOM 1 NO.

MVAAM11 - DC SUPPLY SUPERVISION RELAY ALSTOM 1 NO.

MVAXM31 TRIP CIRCUIT SUPERVISION RELAY ALSTOM 1 NO.

MPG TEST BLOCK ALSTOM 1 NO.

TTB TEST TERMINAL BLOCK IMP / EQVT 1 NO.

ODS SWITCH ALSTOM 1 NO.

RUGGEDCOM / 1 NO.
RAD /
ETHERNET SWITCH
HARSHMANN /
EQVT

FO PATCH CORD PRESTON / EQVT 2 NOS.

QTY /
ITEM DESIGNATION MAKE SITE
MSDS

2 RECOMMENDED SPARES FOR 2 YEARS OPERATION

MICOM P14x NUMERICAL FEEDER MANAGEMENT RELAY ALSTOM 1 NO.

MICOM P54x NUMERICAL LINE DIFFERENTIAL RELAY ALSTOM 1 NO.

ABB / EQVT NUMERICAL LINE DIFFERENTIAL RELAY ALSTOM 1 NO.

MICOM C264 NUMERICAL BAY CONTROL UNIT ALSTOM 1 NO.

MICOM P64x NUMERICAL TRANSFORMER DIFFERENTIAL RELAY ALSTOM 1 NO.

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 17/18
Ref: OP1209387545
Date:16/09/2014

QTY /
ITEM DESIGNATION MAKE SITE
MSDS

MICOM P14x NUMERICAL FEEDER MANAGEMENT RELAY ALSTOM 1 NO.

MICOM P14x NUMERICAL FEEDER MANAGEMENT RELAY ALSTOM 1 NO.

ABT ENERGY METER EDMI / EQVT 1 NO.

GATEWAY ALSTOM 1 NO.

INDUSTRIAL PC (EWS) ALSTOM 1 NO.

ALSTOM T&D AUTOMATION


This document is strictly confidential and its reproduction is restricted to the distribution list Page : 18/18

You might also like